Analyses and Tests of Interlamination Short-Circuits: Danilo MAKUC, Maks BERLEC, Damijan MILJAVEC
Analyses and Tests of Interlamination Short-Circuits: Danilo MAKUC, Maks BERLEC, Damijan MILJAVEC
Analyses and Tests of Interlamination Short-Circuits: Danilo MAKUC, Maks BERLEC, Damijan MILJAVEC
Introduction
A traditional method for detection of interlamination
faults is the High Flux Ring Test, often referred to as a
Thermal Loop Test. The rotor is removed from the machine
and the stator core is magnetically excited by a high voltage
high current temporary winding. Magnetic flux produced in
stator yoke should be near to that normally applied in
service. Hot spots are detected by a variety of means
including thermal cameras. Because of the required
dismantling of the machine, high voltage excitation winding,
high power source, that method is not very convenient.
One of contemporary methods is ELCID test [1], which
is nowadays often used for testing of interlamination
insulation in stator cores of large electrical generators and
motors. The main advantages of the ELCID method are that
the core is excited with just 4% of the rated flux and
detection of damaged areas is sometimes possible even
when the rotor of the machine is not removed. Positions
and strength of the faults are determined with a
measurement of leakage fluxes produced by the fault
currents.
Investigation of the test method on a real working
machine is difficult or almost impossible to perform,
moreover the faults cannot be generated on purpose. To
investigate the influence of the fault position and strength
on measurements we performed several simulations of
interlamination faults using FEM and compare them with
measurements on a laboratory test core which enables
measurements and analyses of intentional short-circuits in
the core.
Laboratory test core
To verify the results obtained using FEM and to test
different sensing coils we carry out measurements on a real
model of stator core (Fig. 1 and 2). All measurements were
performed without a rotor in a stator bore. Since the model
consists of separated sheets which are not welded together
or fasten with building bars, the interlamination faults can be
simulated using short-circuit turns.
In Fig. 3 an electrical scheme of the laboratory model is
shown. It is similar to short-circuit of a transformer but in
this case only a part of the ferromagnetic core is shortcircuited. Separated sheets and short-circuit turns enable
also the investigation of the fluxes in the core, since every
part of the core can be embraced with a test winding.
A length and position of the short-circuit turn can be
arbitrary chosen, while the value of the fault current can be
determined using an external resistor. Furthermore, the
Short-circuit
turn
Pick-up coil
Fig. 2. Short-circuit turn at the top of the tooth and a pick-up coil.
115
Excitation
Short-circuit turn
Ie
A
Rc
It
f
FEM model
Since the interlamination fault is a genuine 3D problem,
a 3D FEM model would be adequate for simulation. In spite
of that the investigation of ELCID core testing was
performed using a 2D FEM model. The geometry of the
model was simpler and the calculation of parametric
analyses was not time consuming. Before the FEM model is
introduced let us get familiar with the problem definition.
Figure 5 shows the structure, which has to be calculated
using FEM (figure does not include the excitation). Shortcircuit turn does not embrace the whole cross-section of the
core. Length of the core is lc, while lt is length of the shortcircuit turn. The total magnetic flux in the core can be
written as the sum of a turn flux t and remaining core flux
c. Since the excitation is sinusoidal, all mentioned
magnetic quantities are complex.
A=0
2nd branch
Short-circuit turn
return path
1st branch
0
t
Different positions
of short-circuit turn
lc
A = Bc h
Fig. 7. FEM model with boundary conditions and material
properties.
lt
It
116
U It
It
Fault position
A fault position can be recognized by analysing the
voltage induced in the pick-up coil, considering also results
from the neighbouring teeth. Since the pick-up coil is
actually a Rogowski coil [4] the measured voltage is
proportional to derivative of the fault current. In conditions
where the current is sinusoidal or almost sinusoidal and the
frequency is constant we can simplify that and just say that
the voltage is proportional to the current. Therefore, the
results obtained from measurements on the laboratory
model are simply presented as voltages, while the results
obtained using FEM are presented as integrals Hdl along
the defined lines between the stator teeth (Fig. 9, 10). We
just compared the models therefore the absolute values
were not so important.
In both measurements and calculations the induced
voltage due to excitation flux was deducted from the
obtained signal so we could analyse only a "clear" signal
caused by the fault current. The influence of the fault length
was not included in the investigation since the FEM model
was only a 2D model, while the faults on the laboratory
model were 40 mm long and much longer than the pick-up
coil dimensions. Therefore, the end effect was neglected.
Line 1-2
0,25
0,20
0,15
0,10
0,05
0,00
0,25
Line 2-3
where h is the height of the stator core (see Fig. 7). Using
such boundary condition it was assured that the flux
through the core is constant what is also the case in a real
core.
Interlamination short-circuits were modelled as shortcircuit turns at different positions and with different material
properties. The FEM model consists of 10 conductors at
different positions and one outer conductor as return path
outside the core. If we would like to simulate a real
interlamination fault the position of the short-circuit turn
should be at the edge but in the ferromagnetic core. Since
an insulated wire was used to make a short-circuit turn in
the laboratory model, same position and properties were
used also in FEM model.
Only one pair of conductors was included in every
calculation. The pair consists of one conductor at specific
position (1 to 10) and the outer conductor. Figure 8 shows
the positions and numbers of conductors and the defined
lines (1-2, 2-3, 3-4) along which the integrals Hdl were
calculated. Positions and labels of the defined lines were
used also for positions of pick-up coil during the
measurements on a test core.
3-4
0,20
0,15
0,10
0,05
0,00
0,25
Line 3-4
A Bc h
2-3
0,20
0,15
0,10
0,05
0,00
10
Fault position
U1-2 (V)
(2)
1-2
1,0
0,5
0,0
1,5
U2-3 (V)
3
4
5 3
6
7
8 9 10
1,0
0,5
0,0
1,5
U3-4 (V)
(1)
12
c c 1
l
t
1,0
0,5
0,0
10
Fault position
Fault strength
Using the FEM model the power losses of
interlamination faults during the ELCID test can be simply
calculated and investigated. The resistance of the short-
117
0,25
12
0,20
0,15
0,10
0,05
10
15
20
25
REFERENCES
0,00
30
Conclusion
Laboratory test core and FEM model offer a lot of
possibilities for investigation, evaluation and research in the
field of diagnostics of laminated stator cores. Tests and
calculations showed that the interlamination faults can be
recognized using ELCID testing, but the fault strength can
not be easily determined. There are possibilities to combine
ELCID with additional methods, such as described in [5], to
118
[1] J. Sutton, "EL Cid: an easier way to test stator cores", Electrical
Review, 207 (1980), No. 1, 33-37
[2] J. Stein, "Generator core investigation and the importance of
good lamination contact at the back of the core", Iris Rotating
Machine Conference, Santa Monica, 2003, (paper obtained
from 'http://www.irispower.com/techpapers').
[3] D. B. Paley, "Current Low Power Core Testing Using EL CID",
Adwel International Ltd., April 1999 (paper obtained from
'http://www.adwel.com/technical.html').
[4] D. A. Ward, J. La T. Exon, "Using Rogowski coils for transient
current measurement", Engineering science and education
journal, June 1993, 105-113
[5] G. B. Kliman, S. B. Lee, M. R.Shah, R. M. Lusted and N. K.
Nair, "A New Method for Synchronous Generator Core Quality
Evaluation", IEEE Transactions on Energy Conversion, 19
(2004), No. 3, 576-582
[6] Z. Posedel, "Inspection of Stator Cores in Large Machines with
a Low Yoke Induction Method - Measurement and Analysis of
Interlamination Short-Circuits", IEEE Transactions on Energy
Conversion, 16 (2001), No. 1, 81-86