SM45 55 Ai
SM45 55 Ai
SM45 55 Ai
SIL
2
IEC 61508:2010
SIL
2
IEC 61508:2010
Contents
1 INTRODUCTION
2 System Configuration
4.1 EMC
4.2 Environmental
5 Installation
6 Maintenance
7 Appendices
This manual supports the application of the products in functional-safety related loops. It must be used in
conjunction with other supporting documents to achieve correct installation, commissioning and operation.
Specifically, the data sheet, instruction manual and applicable certificates for the particular product should be
consulted, all of which are available on the MTL web site.
In the interest of further technical developments, we reserve the right to make design changes.
PAGE 2
www.mtl-inst.com
INTRODUCTION
1.1
SIL
The analogue input modules, MTLx541 (single channel) and MTLx544 (dual channel) are intrinsic safety isolators that
interface with process measurement transmitters located in a hazardous area of a process plant. They are also designed
and assessed according to IEC 61508 for use in safety instrumented systems up to SIL2.
Each module provides a fully-floating dc supply for energising conventional 2-wire or 3-wire process transmitters while
repeating the current flowing in the field loop into another floating circuit to drive the safe area load. The MTLx544D
repeats the current flowing in a single field loop into two isolated safe area loads. For smart 2-wire transmitters using
the HART protocol the units allow bi-directional communications superimposed on the 4/20mA signal current. There are
no configuration switches or operator controls to be set on the module.
These modules are members of the MTL4500 and MTL5500 Series of products.
1.2
Variant Description
Functionally the MTL4500 and MTL5500 Series modules are the same but differ in the following way:
- the MTL4500 modules are designed for backplane mounted applications
- the MTL5500 modules are designed for DIN-rail mounting.
In both models the hazardous area field-wiring connections (terminals 1-3, and 4-6) are made through the removable blue
connectors, but the safe area and power connections for the MTL454x modules are made through the connector on the
base, while the MTL554x uses the removable grey connectors on the top and side of the module.
Note that the safe-area connection terminal numbers differ between the backplane and the DIN-rail mounting models.
PAGE 3
All the analogue input modules have the same connectivity for the field signals, supporting two- and three-wire process transmitters,
as well as accepting signals from separately powered current sources. The connection of the repeated current signals into the
input measurement channels for the safety logic system follows the arrangement shown in the following diagram. When the input
channels of the SIS are providing power for the loop, the S variants of the isolator modules are used to sink the measuring
current. In the other cases the isolator modules source the measuring current that flows into a load resistor inside the SIS.
Field wiring
MTLx541
MTLx541S
(Current
source)
2-wire Transmitter
(Current
sink)
2
Load
0V
Current
limiter
24V
Load
Pwr
3-wire Transmitter
24V
Pwr 2
1
3
0V
4-wire Transmitter
or current source
1
3
24V
B
1
3
24V
B
0V
Pwr
Pwr
Pwr
0V
Pwr
0V
24V
0V
Pwr
Pwr
MTL4541/S: A = 8 B = 9
MTL5541/S: A = 11 B = 12
System Configuration
+vs
vs
2-wire
Ch1
3-wire
+ve
20 to 35V dc
14
13
3
8
Ch2
ve
+ve
PLC
(Safety
related)
12
6
11
I
4
POWER
SUPPLY
(Not safety
related)
PLC
(Safety
related)
ve
Figure 2.1 - Analogue Input module system configuration - see the Note in the text regarding use of dual channel modules.
SIL
2
IEC 61508:2010
PAGE 4
www.mtl-inst.com
The MTLx54x modules are designed to power process transmitters in the hazardous area and to repeat the current
flowing in the field loop to the safe-area load. The shaded area indicates the safety-related system connection,
while the power supply connections are not safety-related. For simplicity the term PLC has been used to denote
the safety system performing the monitoring function of the process loop variable.
SIL
Note: When using the MTLX544 dual-channel modules, it is not appropriate for both channels to be used in the
same loop, or the same safety function, as this creates concerns of common-cause failures. Consideration must
also be made of the effect of common-cause failures when both loops of a dual-channel module are used for
different safety functions. A similar concern applies to the MTLX544D where only one of the output channels can
be used in a safety loop, not both channels.
2.1
There are many parallels between the loop components that must be assessed for intrinsic safety as well as
functional safety. In both situations the contribution of each part is considered in relation to the whole.
The MTLx54x module is a component in the signal path between safety-related process transmitters and safetyrelated control systems.
The transmitter or other field device must be suitable for the process and have been assessed and verified for use
in functional safety applications.
The instrumentation or control equipment shall have a current input with a normal operating range of 4-20mA
but capable of working over the extended range of 3 to 22mA for under- and over-range. It shall have the ability
to detect and signal input currents higher than the threshold of 21mA and lower than the threshold of 3.6mA to
determine out-of-range conditions.
The transmission of HART data is not considered as part of the safety function and is excluded from this analysis.
However, for HART data communication to take place then the input impedance of the equipment must be at least
240ohms.
The output signal from the MTLx54x is within the operating range of 4-20mA under normal conditions.
If the field wiring to the transmitter or connection between the isolator and logic solver is open-circuit then the
loop current will fall to less than 3.6mA and close to zero. If the field wiring is short circuit then the loop current
will rise to a value greater than 21mA.
For the modules that source the current in the safe area circuit, i.e. MTLX541/44/44D, then if the connection
between the isolator and logic solver is shorted, the current seen by the logic solver will be less than 3.6mA and
close to zero. For the MTLX541S/44S modules that control the current supplied by the logic solver input, if the
connection between the isolator and logic solver is shorted, the current seen by the logic solver will rise to a value
greater than 21mA. In both cases, the fault condition should be detected by the logic solver. This includes power
supply failures which cause the output of the isolator to fall to zero mA.
Using a process transmitter and logic controller, as defined in section 2, with an MTLx54x then a system-loop can
be implemented that applies functional safety together with intrinsic safety to meet the requirements of protection
against explosion hazards. The transfer of HART communications through the isolator is not considered as part of
the safety function of the isolator.
It should be recognised that the systematic capability of the products limits their application to SIL2 loops.
PAGE 5
The design features and the techniques/measures used to avoid systematic faults permit the use of the MTLx54x modules in
instrument loops implementing safety functions up to SIL2 in a simplex architecture.
The hardware assessment shows that MTLx54x Repeater Power Supplies:
have a hardware fault tolerance of 0
are classified as Type A devices (non-complex component with well-defined failure modes)
there are no internal diagnostic elements of these products.
The definitions for product failure of the modules at an ambient temperature of 45C are as follows:Failure mode
MTLx541
MTLx541S
16
16
203
210
238
243
227
17
19
20
21
22
116
120
131
141
153
MTLx544D
(FITs means failures per 10 9 hours or failures per thousand million hours)
Reliability data for this analysis is taken from IEC TR 62380:2004 Reliability Data Handbook.
Failure mode distributions are taken principally from IEC 62061:2005 Safety of Machinery.
It is assumed that the module is powered from a nominal 24V dc supply and operating at a maximum ambient temperature of
45C.
Example of use in a safety function
In this example, the application context is assumed to be:
the safety function is to repeat current within 2%
the logic solver will diagnose currents above 21mA and below 3.6mA as faults and take appropriate action
The failure modes shown above can then be defined as:
Failure mode
Category
The failure rates of the MTLx541 for these categories are then (FITs):
Model
MTL4541 or MTL5541
lsd
lsu
ldd
ldu
116
210
17
SIL
2
IEC 61508:2010
PAGE 6
www.mtl-inst.com
4.1
EMC
The MTL4500 and MTL5500 modules are designed for operation in normal industrial electromagnetic environment
but, to support good practice, modules should be mounted without being subjected to undue conducted or radiated
interference, see Appendix A for applicable standards and levels.
4.2
SIL
Environmental
The MTL4500 and MTL5500 modules operate over the temperature range from -20C to +60C, and at up to
95% non-condensing relative humidity.
The modules are intended to be mounted in a normal industrial environment without excessive vibration, as
specified for the MTL4500 & MTL5500 product ranges. See Appendix A for applicable standards and levels.
Continued reliable operation will be assured if the exposure to temperature and vibration are within the values
given in the specification.
Installation
There are two particular aspects of safety that must be considered when installing the MTL4500 or MTL5500
modules and these are:
Functional safety
Intrinsic safety
Reference must be made to the relevant sections within the instruction manual for MTL4500 Series (INM4500)
or MTL5500 Series (INM5500) which contain basic guides for the installation of the interface equipment to meet
the requirements of intrinsic safety. In many countries there are specific codes of practice, together with industry
guidelines, which must also be adhered to.
Provided that these installation requirements are followed then there are no additional factors to meet the needs
of applying the products for functional safety use.
To guard against the effects of dust and water the modules should be mounted in an enclosure providing at
least IP54 protection degree, or the location of mounting should provide equivalent protection such as inside an
equipment cabinet.
In applications using MTL4500 Series, where the environment has a high humidity, the mounting backplanes
should be specified to include conformal coating.
Maintenance
To follow the guidelines pertaining to operation and maintenance of intrinsically safe equipment in a hazardous
area, yearly periodic audits of the installation are required by the various codes of practice.
In addition, proof-testing of the loop operation to conform with functional safety requirements should be carried
out at the intervals determined by safety case assessment.
Proof testing must be carried out according to the application requirements, but it is recommended that this be
carried out at least once every three years.
Refer to Appendix B for the proof testing procedure of the MTL4500 or MTL5500 modules.
Note that there may also be specific requirements laid down in the E/E/PE operational maintenance procedure for
the complete installation.
If an MTL4500 or MTL5500 module is found to be faulty during commissioning or during the normal lifetime of
the product then such failures should be reported to MTL. When appropriate, a Customer Incident Report (CIR) will
be notified to enable the return of the unit to the factory for analysis. If the unit is within the warranty period then
a replacement unit will be sent.
Consideration should be made of the normal lifetime for a device of this type which would be in the region of ten years.
PAGE 7
Appendices
7.1
This annex lists all standards referred to in the previous sections of this document:
IEC 61508:2010
EN 61131-2:2003
EN 61326-1:2006
IEC 61326-3-1:2008
NE21 : 2007
EN 60068-2-27
SIL
2
IEC 61508:2010
PAGE 8
www.mtl-inst.com
7.2
Confirmation, through testing, that a safety function will operate as designed, is a necessary periodic activity to
ensure that the probability of failure upon demand (PFDavg) is maintained.
SIL
In many safety applications, where practical, the user may well prefer that these proof tests are conducted on the
instrument loop as a whole, without dismantling or disconnecting the parts. This will help to ensure the integrity of
the installation is continued after commissioning, but the disturbance to plant operations may not be acceptable.
The tests given in this section of the manual will enable only the function of the isolator component of the safety
loop to be proved. Proof tests of the other components of the loop must be conducted at the requisite intervals to
maintain availability of the safety function. Alternative proof tests may be devised and applied provided they give
a similar level of test that is appropriate to the safety function.
The tests described here - see Figure 7.1 - compare the output current with the input current (A1) over the required
range of operation, and measure the error current i.e. the difference between the two - as indicated on A2.
The tests should be employed per channel, as appropriate.
Figure 7.1
Basic test
arrangement
Ammeter A2 must be capable of handling either polarity of signal. If it is not an auto-ranging instrument, set it to
a high range before switch on, then adjust sensitivity to obtain the required reading.
Proof Test Procedure
Test sequence:
1. System Normal operation test
2. Input/Output characteristic functional safety test.
3. System - Normal operation test
1. System - Normal operation test
Make sure that the module to be tested is operating normally in the target system, without errors and in energised
mode. If the module is in a faulty or de-energised loop, restore normal fault free and energised operation before
testing.
2. Input/Output characteristic functional safety test
Observe normal anti-static precautions when handling equipment during device testing.
Remove the unit from the target system and connect it, as appropriate, in the manner shown in Figure 7.2. Please
note, that it is also acceptable to leave the unit in the target system but only after ensuring that the terminals 1, 2,
3, 8 and 9 or 11 and 12 are disconnected from the system and available for test. Alternatively, for the backplane
mounted MTL4500 series modules, a separate backplane can be used to facilitate access to the power and output
connections.
During testing, the power supply, Vs - nominal 24.0V, min/max. range 20.0 to 35.0V - should be connected
between terminals 13 and 14 (+ve to terminal 14).
PAGE 9
10kR
RV1
V1
A1
+
250R
Ch2
o/p
MTL554x
14(+)
V1
250R
A2
+
24V dc
1 2 3 4 5 6
Ch1
o/p
13()
A1
RV1
7 8 9 10 11 12
Ch2
i/p
10kR
24V dc
A2
1 2 3 4 5 6
Ch1
i/p
Ch1
i/p
VS
MTL5501-SR
MTL454x
13(-)
14(+)
Power
supply
VS
Ch2
i/p
Ch1
o/p
Ch2
o/p
14 13 12 11 1 0 9 8 7
+
Figure 7.2- Connections for testing the MTL554x and MTL454x modules
Measurements
Note: do not connect the voltmeter (V1 in Figure 7.2) across the module input terminals until requested in step 6 below, otherwise
the current measurements may be affected.
Make the following measurements and, it is recommended, record the results in a table such as that shown on the next page.
1.
2.
3.
4.
5.
6.
7.
Adjust resistor RV1 to vary the current (A1) through the range 4 to 20mA. (Tests 1 - 5 in table)
The measured current imbalance (A2) over this range should not exceed 50A.
Adjust RV1 to vary the current (A1) to 3.5mA and then 21.5mA. (Tests 6 & 7 in table)
The measured current imbalance (A2) at these currents should not exceed 200A
Adjust RV1 for a 20mA current reading on A1. (Test 8 in table)
The voltage V1 measured across the channel input should typically be 16.5V.
Record the supply voltage Vs.
SIL
2
IEC 61508:2010
PAGE 10
www.mtl-inst.com
Date: _____/_____/__________
Channel 1
Test #: Description
Actual
SIL
Target
<50A
<50A
<50A
<50A
<50A
<200A
<200A
~16.5V
Channel 2
Test #: Description
Actual
Target
<50A
<50A
<50A
<50A
<50A
<200A
<200A
~16.5V
PAGE 11
GLOBAL LOCATIONS
ITALY
MTL Italia srl, Via A. Meucci 10
I - 20094 Corsico MI, Italy
Tel: + 39 (0)2 61802011 Fax: + 39 (0)2 61294560
E-mail: [email protected]
SINGAPORE
Cooper Crouse-Hinds Pte Ltd
No 2 Serangoon North Avenue 5, #06-01 Fu Yu Building
Singapore 554911
Tel: + 65 6 645 9888 Fax: + 65 6 487 7997
E-mail: [email protected]
CHINA
Cooper Electric (Shanghai) Co. Ltd. Room 2001, China Life Tower,
16 Chao Yang Men Wai Street,
Chao Yang District, Beijing, China 100020
JAPAN
Cooper Crouse-Hinds Japan KK,
MT Building 3F
2-7-5 Shiba Daimon, Minato-ku,
Tokyo, Japan 105-0012
FRANCE
MTL Instruments sarl,
7 rue des Rosiristes, 69410 Champagne au Mont dOr
France
SOUTH KOREA
Cooper Crouse-Hinds Korea
12F, Vision Tower
707-2 Yeoksam-Dong Gangnam-Gu,
Seoul 135-080, South Korea.
UNITED KINGDOM
Measurement Technology Limited,
Great Marlings, Butterfield, Luton
Beds LU2 8DL
GERMANY
MTL Instruments GmbH, An der Gmpgesbrcke 17
D-41564 Kaarst, Germany
NETHERLANDS
MTL Instruments BV
Terheijdenseweg 465, 4825 BK Breda
The Netherlands
INDIA
MTL India, No.36, Nehru Street
Off Old Mahabalipuram Road
Sholinganallur, Chennai - 600 119, India
Tel: + 91 (0) 44 24501660 /24501857 Fax: + 91 (0) 44 24501463
E-mail: [email protected]
www.mtl-inst.com
ZL-B-SM45-55-AI-EN-0213
AUSTRALIA
MTL Instruments Pty Ltd, 205-209 Woodpark Road,
Smithfield, New South Wales 2164
Australia