Isa-12.01.01. Def. Electr. Areas Clasificadas
Isa-12.01.01. Def. Electr. Areas Clasificadas
Isa-12.01.01. Def. Electr. Areas Clasificadas
ANSI/ISA12.01.011999
Formerly ISAS12.01.011999
NOTICE OF COPYRIGHT
This is a copyrighted document and may not be copied or distributed in any
form or manner without the permission of ISA. This copy of the document was
made for the sole use of the person to whom ISA provided it and is subject to
the restrictions stated in ISAs license to that person. It may not be provided to
any other person in print, electronic, or any other form. Violations of ISAs
copyright will be prosecuted to the fullest extent of the law and may result in
substantial civil and criminal penalties.
ISAThe Instrumentation,
Systems, and
Automation Society
ANSI/ISA-12.01.01-1999
Definitions and Information Pertaining to Electrical Apparatus in Hazardous (Classified) Locations
ISBN: 1-55617-696-1
Copyright 1999 by the Instrument Society of America. All rights reserved. Printed in the United
States of America. No part of this publication may be reproduced, stored in a retrieval system, or
transmitted, in any form or by any means (electronic, mechanical, photocopying, recording, or
otherwise), without the prior written permission of the Publisher.
ISA
67 Alexander Drive
P.O. Box 12277
Research Triangle Park, North Carolina 27709
ANSI/ISA12.01.011999
PREFACE
This preface, as well as all footnotes and annexes, is included for information purposes and is not part of
ANSI/ ISA-12.01.01-1999.
This Standard has been prepared as part of the service of ISA, the international society for measurement
and control, toward a goal of uniformity in the field of instrumentation. To be of real value, this document
should not be static but should be subject to periodic review. Toward this end, the Society welcomes all
comments and criticisms and asks that they be addressed to the Secretary, Standards and Practices
Board; ISA; 67 Alexander Drive; P. O. Box 12277; Research Triangle Park, NC 27709; Telephone (919)
990-9227; Fax (919) 549-8288; E-mail: [email protected].
The ISA Standards and Practices Department is aware of the growing need for attention to the metric
system of units in general, and the International System of Units (SI) in particular, in the preparation of
instrumentation standards. The Department is further aware of the benefits to USA users of ISA standards
of incorporating suitable references to the SI (and the metric system) in their business and professional
dealings with other countries. Toward this end, this Department will endeavor to introduce SI-acceptable
metric units in all new and revised standards, recommended practices, and technical reports to the
greatest extent possible. Standard for Use of the International System of Units (SI): The Modern Metric
System, published by the American Society for Testing & Materials as IEEE/ASTM SI 10-97, and future
revisions, will be the reference guide for definitions, symbols, abbreviations, and conversion factors.
It is the policy of ISA to encourage and welcome the participation of all concerned individuals and interests
in the development of ISA standards, recommended practices, and technical reports. Participation in the
ISA standards-making process by an individual in no way constitutes endorsement by the employer of that
individual, of ISA, or of any of the standards, recommended practices, and technical reports that ISA
develops.
CAUTIONISA ADHERES TO THE POLICY OF THE AMERICAN NATIONAL STANDARDS
INSTITUTE WITH REGARD TO PATENTS. IF ISA IS INFORMED OF AN EXISTING PATENT THAT IS
REQUIRED FOR USE OF THE STANDARD, IT WILL REQUIRE THE OWNER OF THE PATENT TO
EITHER GRANT A ROYALTY-FREE LICENSE FOR USE OF THE PATENT BY USERS COMPLYING
WITH THE STANDARD OR A LICENSE ON REASONABLE TERMS AND CONDITIONS THAT ARE
FREE FROM UNFAIR DISCRIMINATION.
EVEN IF ISA IS UNAWARE OF ANY PATENT COVERING THIS STANDARD, THE USER IS
CAUTIONED THAT IMPLEMENTATION OF THE STANDARD MAY REQUIRE USE OF TECHNIQUES,
PROCESSES, OR MATERIALS COVERED BY PATENT RIGHTS. ISA TAKES NO POSITION ON THE
EXISTENCE OR VALIDITY OF ANY PATENT RIGHTS THAT MAY BE INVOLVED IN IMPLEMENTING
THE STANDARD. ISA IS NOT RESPONSIBLE FOR IDENTIFYING ALL PATENTS THAT MAY
REQUIRE A LICENSE BEFORE IMPLEMENTATION OF THE STANDARD OR FOR INVESTIGATING
THE VALIDITY OR SCOPE OF ANY PATENTS BROUGHT TO ITS ATTENTION. THE USER SHOULD
CAREFULLY INVESTIGATE RELEVANT PATENTS BEFORE USING THE STANDARD FOR THE
USERS INTENDED APPLICATION.
HOWEVER, ISA ASKS THAT ANYONE REVIEWING THIS STANDARD WHO IS AWARE OF ANY
PATENTS THAT MAY IMPACT IMPLEMENTATION OF THE STANDARD NOTIFY THE ISA
STANDARDS AND PRACTICES DEPARTMENT OF THE PATENT AND ITS OWNER.
ANSI/ISA12.01.011999
COMPANY
J. Cospolich, Chairman
D. Bishop, Managing Director
D. Ankele
A. Ballard
R. Brodin
U. Dugar
W. Fisk
D. Jagger
J. Kuczka
W. Lawrence*
F. McGowan*
W. Mostia, Jr.
J. Oudar
J. Propst
W. Seaforth
The following members of ISA Committee SP12 contributed to the development of this document:
NAME
COMPANY
F. McGowan, Chairman*
D. Bishop, Managing Director
N. Abbatiello*
D. Ankele*
B. Apel
A. Ballard*
G. Bentinck
K. Boegli
R. Brodin
M. Buettner
R. Buschart
R. Cardinal
C. Casso
M. Coppler
J. Cospolich
______
* One vote per company.
J. Costello
S. Czaniecki
T. Dubaniewicz
U. Dugar
A. Engler
T. Feindel
W. Fiske
G. Garcha
E. Geissler
E. Henning
D. Hohenstein
D. Jagger
J. Kuczka
B. Larson
E. Magison
R. Masek
K. McManama*
A. Mobley*
S. Nguyen
E. Olson*
A. Page III
J. Propst
T. Schnaare
W. Shao
J. Thomason
D. Wechsler
ANSI/ISA12.01.011999
Henkel Corp.
Intrinsic Safety Concepts
NIOSH
Mobil Chemical Company
EGS Electrical Group
R. Stahl, Inc.
Intertek Testing Services
PCS Engineering
Bartec US Corp.
Bailey, Fischer & Porter
Pepperl + Fuchs Inc.
Hawke America
Killark
Turck Inc.
Consultant
Bailey Controls Company
Underwriters Laboratories
3M Company
Milltronics
3M Company
MSHA Certification Center
Shell Development Company
Rosemount, Inc.
Canadian Standards Assoc.
OMNI Industrial Systems, Inc.
Union Carbide Corp.
This standard was approved for publication by the ISA Standards and Practices Board on
28 February 1999.
NAME
COMPANY
H. Dammeyer
H. Baumann
D. Bishop
P. Brett
M. Cohen
M. Coppler
W. Holland
A. Iverson
R. Jones
V. Maggioli
T. McAvinew
A. McCauley, Jr.
R. McFarland
R. Reimer
J. Rennie
R. Webb
W. Weidman
______
* One vote per company.
ANSI/ISA12.01.011999
J. Weiss
J. Whetstone
M. Widmeyer
R. Wiegle
C. Williams
G. Wood
M. Zielinski
EPRI
National Institute of Standards & Technology
Consultant
CANUS Corp.
Eastman Kodak Co.
Graeme Wood Consulting
Fisher-Rosemount Systems, Inc.
ANSI/ISA12.01.011999
CONTENTS
1 Purpose ............................................................................................................................................ 9
2 Scope ............................................................................................................................................... 9
3 Definitions....................................................................................................................................... 10
4 Area (location) classification........................................................................................................... 23
4.1 North American methods ...................................................................................................... 23
4.2 Additional background information........................................................................................ 25
5 Protection techniques for electrical apparatus in hazardous (classified) locations......................... 29
5.1 Explosion confinement and flame quenching........................................................................ 29
5.2 Isolation from flammable atmospheres ................................................................................. 30
5.3 Energy release limitation....................................................................................................... 32
5.4 Other methods of protection.................................................................................................. 33
5.5 Summary of Types of Protection........................................................................................... 33
6 Wiring methods............................................................................................................................... 35
6.1 Conduit system ..................................................................................................................... 40
6.2 Cable systems....................................................................................................................... 40
6.3 Conduit and cable seals........................................................................................................ 40
6.4 Comparison of the installation systems................................................................................. 43
6.5 Comparisons of wiring methods [see Tables 4a and 4b] ...................................................... 49
7 Grounding and bonding practices................................................................................................... 49
8 Maintenance practices.................................................................................................................... 51
Annex A Acronyms ......................................................................................................................... 53
Annex B References ....................................................................................................................... 57
Annex C Listing of worldwide-codes, guides, and standards.......................................................... 67
Annex D Listing of worldwide installation requirements.................................................................. 77
ANSI/ISA12.01.011999
ANSI/ISA12.01.011999
Purpose
This Standard provides definitions and information pertaining to protection techniques, terminology, and
the installation of electrical apparatus in hazardous (classified) locations and provides an introduction and
basic background to the ISA-SP12, Electrical Safety, series of publications and committee activities. It
replaces ISA-S12.1, Definitions and Information Pertaining to Electrical Instruments in Hazardous
Atmospheres, published in 1991.
This document provides a general review of applicable codes and standards, and it should not be used in
lieu of those codes and standards for equipment design, manufacture, installation, maintenance and test
criteria.
Scope
2.1
This Standard provides general guidance for safe design, installation, and maintenance of electrical
apparatus in hazardous (classified) locations using appropriate means to prevent ignition of flammable gases
and vapors, flammable liquids, combustible dusts, or ignitable fibers or flyings.
2.2
This Standard covers only locations made hazardous, or potentially hazardous, due to the presence
of flammable gases or vapors, flammable liquids, combustible dusts, or ignitable fibers or flyings. The
Standard is not necessarily relevant to the hazards posed by pyrophoric materials such as explosives or
propellants containing their own oxidizers.
2.3
This Standard is concerned only with design, manufacture, installation, maintenance, and test criteria
related to arcs, sparks, or hot surfaces produced by electrical apparatus that may cause ignition of flammable
gas or vapor-in-air mixtures, clouds or blankets of combustible dust, or easily ignitable fibers or flyings.
Apparatus should also comply with the applicable ordinary location requirements (e.g., ISA-S82.01 and ISAS82.03).
2.4
This Standard does not cover mechanisms of ignition from external sources, such as static electricity
or lightning. Some apparatus may produce static electricity. The materials of construction of parts in such
apparatus will be an important consideration for application in hazardous locations. The extra precautions
necessary for this are beyond the scope of this Standard.
2.5
This Standard does not consider the effects of installation in corrosive atmospheres and the resulting
deleterious conditions to the original design integrity of the apparatus. The additional precautions necessary
for these conditions are outside the scope of this document.
2.6
This Standard is not an instruction manual for untrained persons. However, it is intended to provide
guidance to those involved with the design, manufacture, installation, and maintenance of apparatus used
in hazardous (classified) locations. It is also intended to promote uniformity of practice among those skilled
in the art. Nothing contained in this Standard is to be construed as a fixed rule without regard to sound
engineering judgment.
2.7
ANSI/ISA12.01.011999
10
2.8
Specialized industries such as, but not limited to, mining and shipping may be regulated by the specific
authority having jurisdiction. This Standard does not include specific requirements or the rules and
regulations unique to any specific industry.
2.9
Various organizations have developed codes, guides, and standards that have substantial acceptance
by industry and governmental bodies. Codes, guides, and standards useful in the design and installation
of electrical instruments in hazardous (classified) locations are listed in Annex C. These are not considered
to be a part of this Standard except for those specific sections of documents referenced elsewhere in this
Standard.
2.10 Due to the purpose of this Standard, an attempt was made to avoid originality in principles whenever
possible, but rather to utilize definitions, explanations, etc., from accepted publications. As a result, much
of the material, except for minor changes, is directly as published by others. While specific credit is not given
for each reference, all references are included in Annex B.
Definitions
The list is not intended to be all inclusive. Throughout this Standard, reference is made to areas, spaces,
locations, and zones. These terms should be considered interchangeable terms designating a threedimensional space.
3.1
accessible surface:
a surface to which a flammable or combustible mixture has access.
3.2
adequately ventilated area:
an adequately ventilated area is an area that has a ventilation system (natural or artificial) that, as a
minimum, prevents the accumulation of gases or vapors to an explosive level. Most standards and
recommended practices recommend preventing levels in excess of 25 percent of the Lower Flammable
(Explosive) Limit, LFL (LEL).
NOTE Adequate ventilation of an area alone is not an effective means for the prevention of dust explosions.
3.3
AEx:
required marking prefix for apparatus meeting one or more types of protection in Section 505-2(c) for
installation in accordance with Article 505 of the National Electrical Code, NFPA 70: 1999.
3.4
approved:
acceptable to the authority having jurisdiction.
NOTE 1 See AUTHORITY HAVING JURISDICTION.
NOTE 2 In determining the acceptability of installations or procedures, equipment, or material, the AUTHORITY HAVING JURISDICTION
may base acceptance on compliance with appropriate standards. In the absence of such standards, said authority may require
evidence of proper installation, procedure, or use. The AUTHORITY HAVING JURISDICTION may also refer to the listing or labeling
practices of product-testing organizations. These organizations are in a position to determine compliance with appropriate standards
for the current production of listed or labeled items.
11
ANSI/ISA12.01.011999
3.5
arcing device:
an electrical make/break component, that is generally interpreted as capable of producing an arc with
energy sufficient to cause ignition of a specific ignitable mixture.
3.6
associated apparatus:
apparatus in which the circuits are not intrinsically safe themselves but affect the energy in the intrinsically
safe circuits and are relied upon to maintain intrinsic safety. Associated electrical apparatus may be either
a) electrical apparatus that has an alternative type of protection for use in the appropriate hazardous
(classified) location, or
b) electrical apparatus not so protected that shall not be used within a hazardous (classified) location.
See also INTRINSIC SAFETY.
3.7
authority having jurisdiction:
the organization, office, or individual that has the responsibility and authority for approving equipment,
installations, or procedures.
NOTE The term AUTHORITY HAVING JURISDICTION is used in a broad manner since jurisdiction and approval agencies vary, as do
their responsibilities. Where public safety is primary, the authority having jurisdiction may be a federal, state/provincial, local, other
regional department, or an individual such as an inspector from a labor or health department, electrical inspector, or others having
statutory authority. An insurance inspection agency, rating bureau, or other insurance company representative may be the authority
having jurisdiction. An owner or his designated agent may also assume the role. At government-owned installations, the
commanding officer, departmental official, or designated agent may be the authority having jurisdiction.
3.8
automatic:
self-acting, operating by its own mechanism when actuated by some impersonal influence, as for example,
a change in current strength, pressure, temperature, or mechanical configuration.
3.9
bonding:
the permanent joining of metallic parts to form an electrically conductive path that will ensure electrical
continuity and the capacity to conduct safely any current likely to be imposed.
3.10 cable entry (cable gland):
a device permitting the introduction of an electric cable into an electrical apparatus.
3.11 certified:
generic term referring to apparatus that has been evaluated by a recognized testing agency and confirmed
to be in compliance with the applicable standard(s).
NOTE Some agencies use the terms approved, listed, or labeled apparatus to indicate compliance with the applicable standard.
ANSI/ISA12.01.011999
12
13
ANSI/ISA12.01.011999
ANSI/ISA12.01.011999
14
3.33 encapsulation:
a type of protection in which the parts that could ignite an explosive atmosphere by either sparking or
heating are enclosed in an encapsulant in such a way that this explosive atmosphere cannot be ignited.
This type of protection is referred to as m.
3.34 energized:
electrically connected to a source of potential difference.
3.35 entity concept:
a concept that allows interconnection of intrinsically safe apparatus to associated apparatus not
specifically examined in such a combination. The criteria for interconnection is that the voltage (Vmax)
and current (Imax) which intrinsically safe apparatus can receive and remain intrinsically safe, considering
faults, must be equal to or greater than the voltage (Voc or Vt) and current (Isc or It) levels which can be
delivered by the associated apparatus, considering faults and applicable factors. In addition, the maximum
unprotected capacitance (Ci) and inductance (Li) of the intrinsically safe apparatus, including
interconnecting wiring, must be equal to or less than the capacitance (Ca) and inductance (La) that can
safely be connected to the associated apparatus. If these criteria are met, then the combination may be
connected without compromising intrinsic safety. For additional information refer to ISA RP12.6.
3.36 entry, direct:
a method of connection of an electrical apparatus to the external circuits by means of the connecting
facilities inside the main enclosure or in a terminal compartment having a free opening to the main
enclosure. (IEV 426-04-07)
3.37 entry, indirect:
a method of connection of an electrical apparatus to the electrical circuits by means of a terminal box or a
plug and socket connection which is external to the main enclosure. (IEV 426-04-08)
3.38 Ex:
designation of explosion-protected electrical apparatus
3.39 Ex component:
part of electrical apparatus for explosive atmospheres which is not to be used alone in such atmospheres
and which requires additional evaluation of any electrical apparatus with which it is used.
3.40 Ex Scheme:
an international system of certification for explosion-protected electrical apparatus administered by the
IECEE and described by IECEE-04. The eventual goal of this scheme is that a manufacturer of hazardous
location electrical apparatus would be able to obtain a single Ex Certificate of Conformity from one
Certification Laboratory and provide that product in any participating country without legal or technical
obstacle and without the need to get it recertified locally.
3.41 explosionproof:
a term used to describe an enclosure that is capable of withstanding an explosion of a specified gas or
vapor that may occur within it and of preventing the ignition of a specified gas or vapor surrounding the
enclosure by sparks, flashes, or explosion of the gas or vapor within, and that operates at such an external
temperature that a surrounding flammable atmosphere will not be ignited thereby. (NEC)
NOTE See also FLAMEPROOF ENCLOSURE.
15
ANSI/ISA12.01.011999
3.50 ground:
a conducting connection, whether intentional or accidental, between an electrical circuit or apparatus and
the earth, or to some conducting body that serves in place of the earth.
ANSI/ISA12.01.011999
16
17
ANSI/ISA12.01.011999
ANSI/ISA12.01.011999
18
3.69 listed:
equipment or materials included in a list published by an organization acceptable to the authority having
jurisdiction and concerned with product evaluation, that maintains periodic inspection of production of
listed equipment or materials, and whose listing states either that the equipment or material meets
appropriate designated standards or has been tested and found suitable for use in a specified manner.
NOTE The means for identifying listed equipment may vary for each organization concerned with product evaluation, some of
which do not recognize equipment as listed unless it is also labeled. The authority having jurisdiction should utilize the system
employed by the listing organization to identify a listed product.
19
ANSI/ISA12.01.011999
3.82 nonautomatic:
non-self-acting requiring personal intervention for control. As applied to an electric controller,
nonautomatic control does not necessarily imply a manual controller, but only that personal intervention is
necessary.
3.83 nonhazardous (unclassified) location:
a location in which fire or explosion hazards are not expected to exist specifically due to the presence of
flammable gases or vapors, flammable liquids, combustible dusts, or ignitable fibers or flyings. Such a
location may also be referred to as a safe area.
3.84 nonincendive circuit:
a circuit, other than field wiring, in which any arc or thermal effect produced, under intended operating
conditions of the equipment, is not capable, under specified test conditions, of igniting the flammable
gas-, vapor-, or dust-air mixture. See also 3.87, NONINCENDIVE FIELD WIRING.
3.85 nonincendive component:
a component having contacts for making or breaking an ignition-capable circuit and in which the contacting
mechanism is constructed so that the component is incapable of igniting the specified explosive
atmosphere. The housing of a nonincendive component is not intended to (1) exclude the flammable
atmosphere or (2) contain an explosion. This type of protection is referred to as nC.
3.86 nonincendive equipment:
equipment having electrical/electronic circuitry and components that are incapable, under normal
conditions, of causing ignition of the flammable gas-, vapor-, or dust-air mixture due to arcing or thermal
effect. This type of protection is referred to as nA, nC, or nR.
3.87 nonincendive field wiring:
wiring that enters or leaves an equipment enclosure and, under normal operating conditions of the
equipment, is not capable, due to arcing or thermal effects, of igniting the flammable gas-, vapor-, or dustair mixture. Normal operation includes opening, shorting, or grounding the field wiring. See also 3.84,
NONINCENDIVE CIRCUIT.
3.88 normal conditions:
equipment is generally considered to be under normal conditions when it conforms electrically and
mechanically with its design specifications and is used within the limits specified by the manufacturer.
3.89 oil-immersion:
type of protection in which the electrical apparatus or parts of the electrical apparatus are immersed in a
protective liquid in such a way that an explosive atmosphere which may be above the liquid or outside the
enclosure cannot be ignited. This type of protection is referred to as o.
ANSI/ISA12.01.011999
20
3.91 pressurization:
the technique of guarding against the ingress of the external atmosphere into an enclosure by maintaining
a PROTECTIVE GAS therein at a pressure above that of the external atmosphere. This type of protection is
referred to as p.
3.92 pressurization, Type X:
a method of reducing the classification within an enclosure from Division 1/Zone 1 to nonhazardous
(unclassified). See 5.2.1.
3.93 pressurization, Type Y:
a method of reducing the classification within an enclosure from Division 1/Zone 1 to Division 2/Zone 2.
See 5.2.1.
3.94 pressurization, Type Z:
a method of reducing the classification within an enclosure from Division 2/Zone 2 to nonhazardous
(unclassified). See 5.2.1.
3.95 protection, type of:
the specific measures applied to electrical apparatus to avoid ignition of a surrounding explosive
atmosphere. Examples are e and n.
3.96 protective component (as applied to intrinsic safety):
a component that is so unlikely to become defective in a manner that will lower the intrinsic safety of the
circuit that it may be considered not subject to fault when analyses or tests for intrinsic safety are made.
3.97 protective gas:
the gas used for pressurization or for the dilution of flammable gases to a level well below their lower
explosive limit, usually below 25 percent LFL/LEL. The protective gas may be air, nitrogen, other
nonflammable gas, or a mixture of such gases.
3.98 purging:
in a pressurized enclosure, the operation of passing a quantity of PROTECTIVE GAS through the enclosure
and ducts, so that the concentration of the explosive gas atmosphere is brought to a safe level.
3.99 qualified person:
one familiar with the construction and operation of the equipment and the hazards involved.
3.100 restricted breathing:
a protection technique in which the tightness of an enclosure is assured so that short-term presence of a
flammable gas or vapor cloud around the enclosure will not cause the concentration inside the enclosure
to reach the LFL/LEL because of breathing or diffusion. This type of protection is referred to as nR.
3.101 safe area:
refer to NONHAZARDOUS (UNCLASSIFIED) LOCATION.
21
ANSI/ISA12.01.011999
ANSI/ISA12.01.011999
22
23
ANSI/ISA12.01.011999
emptying points and areas where dust layers occur and are likely in normal operation to give rise to an
explosible concentration of combustible dust in mixture with air. (IEC 1241-3 - 2.12)
3.123 Zone 22 (IEC):
an area not classified as Zone 21 in which combustible dust, as a cloud, can occur infrequently, and persist
only for a short period, or in which accumulations or layers of combustible dust can give rise to an
explosive concentration of combustible dust in mixture with air. This zone can include, among others,
areas in the vicinity of equipment containing dust, and in which dust can escape from leaks and form
deposits (e.g. milling rooms in which dust can escape from the mills and then settle). (IEC 1241-3 - 2.13)
Area classification schemes should specify the kind of flammable material that may be present and the
probability that it will be present in ignitable concentrations. Area classification schemes and systems of
material classification have been developed to provide a succinct description of the hazard so that
appropriate safeguards may be selected. The type of protection technique selected and the level of
protection it must provide depend upon the potential hazard caused by using electrical apparatus in a
location in which a combustible, flammable, or ignitable substance may be present.
4.1
In the United States, the area classification definitions are stated in Articles 500 and 505 of the National
Electrical Code, (NEC) NFPA 70. In Canada, similar definitions are given in the Canadian Electrical Code
(CEC), Part 1, Section 18 and Annex J18 (CSA C22.1).
Various organizations have developed numerous guides and standards that have substantial acceptance
by industry and governmental bodies for area classification. Refer to Annex C.
Area classification definitions used in the United States and Canada include the following:
a) CLASS the generic form of the flammable materials in the atmosphere, which may include gas or
vapor, dusts, or easily ignitable fibers or flyings (see Clause 3 for detailed definitions);
b) DIVISION (or ZONE) an indication of the probability of the presence of the flammable material in
ignitable concentration (see Clause 3 for detailed definitions); and
c) GROUP the exact nature of the flammable material (see 4.1.1 & 4.1.2).
4.1.1
The United States and Canadian Electrical Codes recognize seven groups: Groups A, B, C, D, E, F, and G.
Groups A, B, C, and D apply to Class I locations; Groups E, F, and G apply to Class II Locations. In NEC
these groups are defined as:
Group A - Acetylene
Group B - Flammable gas, flammable liquid-produced vapor, or combustible liquid-produced vapor mixed
with air that may burn or explode, having either a MAXIMUM EXPERIMENTAL SAFE GAP (MESG) less than or
equal to 0.45 mm or a MINIMUM IGNITING CURRENT RATIO (MIC RATIO) less than 0.4.
NOTE A typical Class I, Group B material is hydrogen.
Group C - Flammable gas, flammable liquid-produced vapor, or combustible liquid-produced vapor mixed
with air that may burn or explode, having either MAXIMUM EXPERIMENTAL SAFE GAP (MESG) values greater
ANSI/ISA12.01.011999
24
than 0.45 mm and less than or equal to 0.75 mm or a MINIMUM IGNITING CURRENT RATIO (MIC RATIO) greater
than or equal to 0.4 and less than or equal to 0.80.
NOTE A typical Class I, Group C material is ethylene.
Group D - Flammable gas, flammable liquid-produced vapor, or combustible liquid-produced vapor mixed
with air that may burn or explode, having a MAXIMUM EXPERIMENTAL SAFE GAP (MESG) greater than 0.75
mm or a MINIMUM IGNITING CURRENT RATIO (MIC RATIO) greater than 0.80, or gases or vapors of equivalent
hazard.
NOTE A typical Class I, Group D material is propane.
Additional information on group classification can be found in NFPA 497, Classification of Flammable
Liquids, Gases or Vapors and of Hazardous (Classified) Locations for Electrical Installations in Chemical
Process Areas.
Group E Atmospheres containing combustible metal dusts, including aluminum, magnesium, and their
commercial alloys, or other combustible dusts whose particle size, abrasiveness, and conductivity present
similar hazards in the use of electrical equipment.
Group F Atmospheres containing combustible carbonaceous dusts that have more than 8 percent total
entrapped volatiles (see ASTM D3175-89 for coal and coke dusts) or that have been sensitized by other
materials so that they present an explosion hazard. Coal, carbon black, charcoal, and coke dusts are
examples of carbonaceous dusts.
Group G Atmospheres containing other combustible dusts, including flour, grain, wood flour, plastic, and
chemicals.
Additional information on Group Classification can be found in NFPA 499 Classification of Combustible
Dusts and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas.
4.1.2
Group IIB - Flammable gas, flammable liquid-produced vapor, or combustible liquid-produced vapor mixed
with air that may burn or explode, having either MAXIMUM EXPERIMENTAL SAFE GAP (MESG) values greater
than 0.5 mm and less than or equal to 0.9 mm or MINIMUM IGNITING CURRENT RATIO (MIC RATIO) greater
than or equal to 0.45 and less than or equal to 0.80, or gases or vapors of equivalent hazard.
NOTE 1 This group is similar to Group C as described in 4.1.1, although the MESG and MIC RATIO numbers are slightly different.
NOTE 2 Typical gases include ethylene and gases or vapors of equivalent hazard.
25
ANSI/ISA12.01.011999
Group IIA - Flammable gas, flammable liquid-produced vapor, or combustible liquid-produced vapor mixed
with air that may burn or explode, having MAXIMUM EXPERIMENTAL SAFE GAP(MESG) greater than 0.9 mm or
MINIMUM IGNITING CURRENT RATIO (MIC RATIO) greater than 0.80, or gases or vapors of equivalent hazard.
NOTE 1 This group is similar to Group D as described in 4.1.1, although the MESG number is slightly different.
NOTE 2 Typical gases include propane and gases or vapors of equivalent hazard.
Additional information on group classification can be found in IEC 60079-12 & IEC 60079-20.
4.2
4.2.1
Historically, the topic of Hazardous (Classified) Locations first appeared in the National Electrical Code
(NEC) in 1923, when a new article entitled Extra-Hazardous Locations was accepted. This article
addressed rooms or compartments in which highly flammable gases, liquids, mixtures or other substances
were manufactured, used, or stored. In 1931, Classifications consisting of Class I, Class II, etc., for the
hazardous locations were defined. However it was not until 1935 that Groups were introduced into the
NEC. (Note: Divisions were introduced into the NEC in 1947.) The four gas Groups, A, B, C, and D,
complemented the design of electrical equipment used in hazardous (classified) locations and were
defined based on the level of hazard associated with explosion pressures of specific atmospheres and the
likelihood that the effects of that explosion could be transmitted outside the enclosure. Group A was
defined as atmospheres containing acetylene. Group B was defined as atmospheres containing hydrogen
or gas or vapors of equivalent hazard. Group C was defined as atmospheres containing ethyl ether vapor;
and Group D was defined as atmospheres containing gasoline, petroleum, naphtha, alcohols, acetone,
lacquers solvent vapors, and natural gas.
Despite the fact that the introduction of these Groups was done without standardized testing and without
the advantage of todays technological advances or equipment, these definitions have changed little since
that time. The first major testing, in fact, was only conducted in the late 1950s, when engineers at
Underwriters Laboratories developed a test apparatus that provided a means to determine how various
materials behaved with respect to explosion pressures and transmission, when the specific combustible
material was ignited in the test vessel. This apparatus, called the Westerberg Explosion Test Vessel,
provided standardized documentation of a factor called the Maximum Experimental Safe Gap (MESG) and
permitted other materials to be classified by test into one of the four gas groups. The results of these
tests are contained in Underwriter Laboratories (UL) Bulletin Nos. 58 and 58A (reissued in July, 1993, as
UL Technical Report No. 58). In 1971, the International Electrotechnical Commission (IEC) published IEC
79-1A defining a different type of apparatus for obtaining MESG results. While the two MESG test
apparatus are physically different in both size and shape, the results are statistically comparative, although
in some cases differences have been observed. A sample of values is shown in the following table:
Material
Westerberg apparatus
MESG in mm
IEC apparatus
MESG in mm
Propane
0.92
0.94
Ethylene
0.69
0.65
Butadiene
0.79
0.79
Diethyl ether
0.30( 0.60)
0.87
Hydrogen
0.08 ( 0.23)
0.29
ANSI/ISA12.01.011999
26
Additional testing on the Westerberg Apparatus has demonstrated that this theory was true, and the MESG value for
diethyl ether more than doubled. Further, Westerberg apparatus testing has also shown that the hydrogen MESG value
is 0.23 mm.
Papers have been written to attempt to explain the reasons for these differences in the test data. One, by
H. Phillips, entitled Differences Between Determinations of Maximum Experimental Safe Gaps in Europe
and U.S.A., appeared in a 1981 edition of the Journal of Hazardous Materials and cited a condition of
spontaneous combustion in one portion of the Westerberg Apparatus, which was reflected in materials,
like diethyl ether, having low ignition temperatures.
While acetylene remains segregated in Group A because of the high explosion pressure, which results
from its very fast flame speed, newer test methodologies have defined other types of protection methods
that now consider acetylene and hydrogen to be of equivalent hazard. One such method examines the
MINIMUM IGNITION CURRENT required to ignite a specific combustible material. This testing produced more
variability when the results of specific combustible materials were compared. However, it was found that
the minimum ignition currents of one test could be favorably compared with those of other tests if a ratio
value based on methane was applied. This testing has resulted in the generation of MIC Ratio data.
Other testing has been performed when it was incorrectly assumed that factors called minimum ignition
energy (MIE) and autoignition temperature (AIT) were related and could be used to place materials into
Groups. The fact that these were independent factors resulted in deletion of AITS as a basis for Group
determination in the 1971 NEC.
MIEs have been found to exhibit theoretical results, which do not translate into practical designs that can
be applied to actual electrical devices with their associated energy levels.
Since the primary concern is to have electrical devices that can safely operate when used in locations
classified by Class, Group, and Division, the delineations for the gas groups have been defined on the
basis of MESG and MIC RATIO.
Further details may be found in NFPA 497.
4.2.2
Division 2 concept
The concept of Division 2, a location in which flammable material will be present only occasionally, was
initiated in North America. It was recognized that if the probability of the presence of flammable material is
low, the protective measures necessary to prevent an explosion can be less restrictive (and normally also
much less expensive) than those required in Division 1 locations. In Division 1 locations the probability
that the flammable material is present is much higher than in Division 2 locations because in the former,
the flammable atmosphere is present frequently during normal operations. Although many international
corporations, particularly oil and chemical companies, used the North American nomenclature and
practice, it was not until the 1960s that Division 2 began to be accepted outside North America. At the
present time the concept of Division 2 area classification is recognized universally. The relaxation of
protective measures in Division 2 has not yet reached the same level of acceptance, however. In Japan,
for example, the less onerous levels of protection permitted in Division 2 by the National Electrical Code
and the Canadian Electrical Code are not yet recognized.
4.2.3
Zone concept
In the 1960s Europe made its own contribution to the practice of area classification by introducing the
concept of Zone 0. The intent of defining Zone 0 was to define those locations in which the flammable
material is present such a high percentage of the time that extraordinary measures should be taken to
protect against ignition by electrical apparatus. The objective of defining Zone 0 and Zone 1 was to allow
a less restrictive practice in the remainder of locations formerly classified within Division 1. IEC has
recognized three levels of probability that a flammable concentration is present. In IEC terminology, these
27
ANSI/ISA12.01.011999
three levels are Zones 0, 1, and 2. North American Division 1 includes both Zone 0 and Zone 1, and North
American Division 2 is basically equivalent to Zone 2. Though the definitions of zones are similar in almost
all standards, the application of the words to specific industrial situations is different.
4.2.4
Temperature classification
Prior to 1971 the autogenous ignition (or autoignition) temperature, AIT, was a criterion for group
classification. Inclusion of the AIT as one of the classification criteria caused problems for those trying to
classify new materials that had not been tested, because other flammability and combustion parameters of
flammable gases and vapors are not correlated to AIT. For example, the AIT of diethyl ether is 160C
(320F). Hydrogen has an AIT of approximately 520 C (968 F). Methane has an AIT of approximately
630 C (1166 F). Yet hydrogen is much more easily ignited by an arc than diethyl ether. Methane is much
less easily ignited. Hydrogen requires very close-fitting flanges to prevent transmission of an explosion,
but the flanges for an enclosure to protect against transmission of an explosion in diethyl ether may be
much more widely separated, i.e., the MESG of diethyl ether is several times that of hydrogen.
When the 1971 National Electrical Code and the Canadian Electrical Code removed AIT as one of the
criteria for material classification, the practice of temperature marking was introduced. Table 1 lists the
temperature codes recognized in the NEC. Enclosures containing heat-producing devices must be
marked by a temperature code or with the maximum surface temperature of the enclosure based on 40C
(104F) ambient. Those that do not have an alphabetical suffix, i.e., T1-T6, are recognized internationally
by the International Electrotechnical Commission (IEC), by CENELEC, and by many national standards
bodies. In the United States and Canada, equipment of the nonheat-producing type (such as junction
boxes, conduit, and fittings) and equipment of the heat-producing type (such as industrial process
transmitters and transducers) having a maximum temperature not more than 100 C (212 F) need not be
marked. The temperature classification marking also applies to surfaces other than those of the
enclosures in the case of intrinsically safe and nonincendive equipment.
ANSI/ISA12.01.011999
28
4.2.5
Degrees C
Degrees F
Identification Number
450
842
T1
300
572
T2
280
536
T2A
260
500
T2B
230
446
T2C
215
419
T2D
200
392
T3
180
356
T3A
165
329
T3B
160
320
T3C
135
275
T4
120
248
T4A
100
212
T5
85
185
T6
Grouping of materials
4.2.5.1 A hazard grouping of materials is always relative to a stated property, i.e., to a particular ignition
mechanism or a means of hazard reduction. Materials that are very much alike relative to ignition by
electrical arcs or materials that have similar MESG may behave quite differently with respect to ignition by
a hot surface.
4.2.5.2 Table 2 compares several countries/organizations designations of gas groups. At the present
time most national standards use the IEC group designations, where II indicates an above-ground facility
and I indicates a hazard due to methane in the below-ground works of a mine. The comparisons of
Table 2 are approximate. For example, North American Group C is approximately the same list of
materials as IEC Group IIB. Grouping is an arbitrary designation of dividing lines in a continuous series of
values of a particular parameter.
29
ANSI/ISA12.01.011999
IEC
(60079-12)
UK
(BS4683)*
UK
(BS229:
1957)*
Germany
(VDE0171) *
USA National
Electrical
Code
Group
Typical gases
and vapors
IIA
IIA
II
IIB
IIB
III
IIC
IIC
IV
3a
3n
3b
3c
Class I
Acetylene
Ethyl nitrate
* Prior to CENELEC
The most basic protection technique is to avoid placing electrical equipment in a hazardous (classified)
location. Facility planning should take this factor into account, leaving only those situations where there is
no alternative.
Three basic methods of protection are:
a) explosion confinement;
b) isolation of the ignition source; and
c) energy release limitation.
Within each basic method, one (or more) specific technique necessitates specialized design in order to
minimize the potential risk of operating electrical apparatus in hazardous (classified) locations.
5.1
5.1.1
Explosionproof, applicable to Class I areas only, is a specific protection technique in which the ignition
source, fuel, and oxygen may coexist and ignition may occur. However, any ignition that does occur is
confined within an enclosure strong enough to withstand any explosion pressure associated with the gas
groups for which it is designated. Also, all joints have close enough values and tolerances so that flame,
sparks, or escaping hot gases are cooled sufficiently to prevent the external atmosphere from being
ignited. Additionally, all external surfaces must be kept below the autoignition temperature for the specific
ANSI/ISA12.01.011999
30
gases or vapors involved. The explosionproof technique is gas-group dependent i.e., an enclosure
designed and tested for Class I Group C would not be suitable for use in a Group B atmosphere.
5.1.2
Powder filling
Powder filling is a technique whereby the electrical components are immersed in a powder to a depth
sufficient to ensure that any arcing below the powder cannot ignite the flammable atmosphere surrounding
the apparatus.
The concept was developed in France and generally referred to sand, quartz, or solid glass particles used
as filling materials. At the present time, however, only quartz is permitted. Refer to ISA S12.25.01 (IEC
60079-5 Mod).
5.2
Isolation of the ignition source from the flammable atmosphere may be accomplished by several
techniques. Some of the most common techniques include pressurization, purging, continuous dilution,
and inerting.
5.2.1
Pressurization
Pressurization reduces the concentration of any flammable gas or vapor initially present to an acceptably
safe level and isolates electrical components from the external atmosphere by maintaining a pressure
within the equipment enclosure higher than that of the external atmosphere. Thus, the external
atmosphere is prevented from entering the enclosure. Unlike explosionproofing, the purging technique is
not gas-group dependent with the following exceptions:
a) For Type Y, a nonincendive component and nonincendive circuits must be gas-group related.
b) For Type X, door interlock and purge fail power cutoff must be rated for the location.
In the case of enclosures in which flammable materials are intentionally introduced within the enclosure
(such as with gas analyzers), a different technique, commonly referred to as continuous dilution, is
required. Refer to NFPA 496, although this standard does not use the term CONTINUOUS DILUTION. Also
refer to 5.2.2.
5.2.1.1 In North America the pressurization technique is used for reducing the classification within the
enclosure to a lower level, such as from Division 1 to Division 2 or nonhazardous (unclassified) or from
Division 2 to nonhazardous (unclassified). The European and North American requirements agree in
principle, but the bases for the respective requirements are equipment construction criteria. The end result
is essentially the same. Reference IEC 60079-2 and 60079-13.
A discussion of three different sets of requirements dependent upon the area classification and the nature
of the enclosed apparatus follows.
United States and Canada
Type X Pressurization. In the United States and Canada, Type X pressurization is a method of reducing
the classification within an enclosure from Division 1 to nonhazardous (unclassified). Type X purging
requires that the enclosure pressure be monitored and that the electrical power be mechanically
disconnected upon loss of positive pressure.
Type Y Pressurization. In the United States and Canada, Type Y pressurization is a method of reducing
the classification within an enclosure from Division 1 to Division 2. Devices that employ Type Y
31
ANSI/ISA12.01.011999
pressurization must be suitable for use in Division 2 locations without pressurization. A visual or audible
warning is required for loss of positive pressure.
Type Z Pressurization. In the United States and Canada, Type Z pressurization is a method of reducing
the classification within an enclosure from Division 2 to nonhazardous (unclassified). A visual or audible
warning is required for loss of positive pressure.
International
Types X, Y, and Z pressurization are not currently recognized outside the United States and Canada,
although the concept of Type X, Y, and Z is proposed in the 1997 draft revisions to IEC 60079-2. The IEC
currently uses the designation first case for Type X and Type Y pressurization and second case for
Type Z pressurization. International requirements for visual and/or audible alarms for loss of enclosure
pressure, when the pressurization technique is used, vary from country to country. Loss of pressure may
also require power disconnection.
5.2.1.2
Pressurization for Class II is the technique of supplying an enclosure with clean air or an inert gas, with or
without continuous flow, at sufficient pressure to prevent the entrance of combustible dusts.
5.2.2
Continuous dilution
Continuous dilution is a derivation of the purging technique and is intended for electrical equipment
enclosures in which a flammable material is deliberately introduced. Such equipment may include gas
analyzers, chromatographs, and similar instruments. The principle involved is to introduce sufficient flow
of protective gas to dilute any flammable gas present during normal operating conditions or failure
conditions to a level well below the lower explosive limit (normally, 25 percent of LFL/LEL). An example of
a failure condition would be a broken tube transporting flammable gas. As with purging, there are three
types of protection, depending upon the conditions of release within the enclosure. The safeguards
include (1) monitoring the presence of the protective gas, (2) removing electrical power, and (3) alarming
depending on the conditions of internal release and the nature of the enclosed electrical components.
Safeguards depend upon whether or not the electrical parts are normally a source of ignition or meet the
requirements for operation in a Division 2 hazardous (classified) location. A continuous dilution system
may also be used as a purging or pressurization system to prevent any external flammable gas or vapor or
combustible dusts from entering the enclosure.
5.2.3
Oil Immersion
While oil immersion is not a common protection technique for instruments, it is an acceptable isolation
method. The most common application is for electrical equipment such as switches, relays, and
transformers. All electrical parts are submersed in either nonflammable or low-flammability oil, which
prevents the external atmosphere from contacting the electrical components. The oil often serves also as
a coolant. Refer to ISA S12.26.01 (IEC 60079-6 Mod).
5.2.4
Sealing is a technique primarily applicable to Division 2 classified areas. The basic principle provides for
the isolation of electrical components within an enclosure by sealing the enclosure well enough to prevent
the casual entrance of any external flammable atmosphere. Sealing may be accomplished by several
means, from simple gasketing to a glass-to-metal hermetic seal. Reference ISA-S12.12, IEC 60079-15,
and CEC 22.2, No. 213, for further information.
ANSI/ISA12.01.011999
32
A hermetic seal is considered effective enough to be insensitive to gas group, but a gasketed enclosure is
sensitive to particular gases/vapors (based on their diffusion constants and on the effectiveness of the
gasket seal). For example, hydrogen, with its small molecular structure, will diffuse much more easily than
the heavier hydrocarbons.
The sealing technique has been applied in Europe to a variety of process control equipment. In North
America, hermetically sealed components such as relays, push button contacts, and limit, level, and
pressure switches are commonly used.
The following are two levels of protection provided by sealing: (1) the enclosure is sealed, and (2)
application is restricted to areas that become hazardous only upon equipment or process failure (Division
2).
5.2.5
Encapsulation
Potting or casting are both isolating techniques in which the electrical parts are encapsulated in a solidified
electrically insulating material, preventing the flammable atmosphere from contacting the electrical
components. Most encapsulation has been for the purpose of isolating hot components from the
atmosphere in order to obtain a lower temperature rating or to permit reduced creepage distances
because the spacings are shielded from conductive contamination. Reference ISA-S12.23.01 (IEC 6007918 Mod).
5.2.6
Inert gas filling is a technique of filling the interior of an enclosure with an inert gas. It typically is used in
conjunction with sealed or pressurized enclosures. Refer to 5.2.4.
5.3
5.3.1
The application of intrinsic safety is limited to equipment and circuits in which the available energy required
for operation is inherently low. Intrinsic safety involves the limitation of the available energy in a circuit to a
level at which any spark or thermal effect is incapable of causing ignition of a flammable atmosphere under
test conditions that include the application of circuit and component faults. As a result, the technique is
widely used in the instrument industry, e.g., 4 to 20 mA signal circuits; temperature, flow, pressure, and
level measurement instruments; portable battery-operated instruments (radios, combustible gas
detectors). Certain fault conditions need to be considered in the design and evaluation. For installation
information, refer to ISA-RP12.6 and NEC Article 504.
5.3.2 Nonincendive equipment (internationally referred to as energy limited apparatus and
circuits)
The nonincendive approach is similar to the intrinsic safety approach in basic principle but differs greatly in
detail. There are two major differences. First, nonincendive circuits are evaluated under normal conditions
only (i.e., no fault conditions need to be considered). Equipment meeting the nonincendive criteria is
suitable for use only in Division 2 areas in which the atmosphere is normally nonflammable and requires a
breakdown in the process or the process equipment to make it flammable.
Second, relative to the components used, few detailed requirements must be met other than those
applicable to nonhazardous (unclassified) location use as related to personnel shock and fire hazard. A
typical analysis involves itemizing all parts that could potentially interrupt a circuit such as switches, relays,
connectors, and potentiometers. These components are then analyzed or tested to see if they can ignite
the specified flammable atmosphere.
33
5.4
5.4.1
ANSI/ISA12.01.011999
Restricted breathing is a technique developed by the Swiss. It can be considered to be a modified form of
sealing. In the Swiss utilization of the technique, fairly large enclosures of relays and other ignitioncapable apparatus are gasketed so they are tightly sealed. The protection principle employed is that the
enclosure is sufficiently tight to make it highly unlikely that a flammable cloud of gas would surround the
enclosure for the length of time necessary for enough flammable material to enter the enclosure that a
flammable concentration would exist in the enclosure. This technique is applicable only to Zone 2
locations. Refer to IEC 60079-15 and ISA S12.12.01.
5.4.2
Increased safety
Increased safety is a technique developed in Germany. It has been used for equipment such as terminals,
motors, and lighting fixtures. The motors are specially designed to remain below the autoignition
temperature, even under certain locked rotor conditions, and have special connection facilities designed to
prevent loosening even under severe vibration. Refer to IEC 60079-7 and ISA S12.16.01.
5.4.3
Dust-ignitionproof
Dust-ignitionproof enclosures are essentially sealed enclosures that prevent the entrance of dusts.
Additionally, the outer enclosure temperature must be maintained below specific limits. For additional
information, refer to UL 1203.
5.5
Table 3 provides a summary of various Types of Protection and locations in which they are permissible.
ANSI/ISA12.01.011999
34
Designation
Technique
Zone *
Flameproof enclosure
Increased safety
ia
Intrinsic safety
ib
Intrinsic safety
[ia]
Non-hazardous
[ib]
Non-hazardous
Encapsulation
nA
Non-sparking equipment
nC
nR
Oil immersion
1 or 2
Powder-filled
For protection techniques (Types of Protection) applicable to Classes I, II, and III; Division 1 and 2, refer to
Article 500-4(a) of the NEC.
5.5.1 A special protection category, Type s, is a technique other than those that have been
standardized. When an area is classified Zone 0, it is common in some countries to provide two or more
protection techniques, such as pressurizing a flameproof enclosure. Ex s has also been applied for Zone
1, where, for example, a transmitting device partly satisfies the increased safety requirements and also
partly satisfies the intrinsic safety requirements. The combination results in a device that is safe for use in
a hazardous (classified) location but does not satisfy a specific set of requirements for a single protection
technique.
5.5.2 The intrinsic safety column indicates that there are two sets of requirements ia and ib; ia is
intended for Zone 0 applications while ib is for Zone 1 applications. The difference in requirements is that
ia considers two simultaneous faults while ib considers only one. The approach of the United States and
Canada (in the Division system) uses the two-fault criteria for all intrinsic safety applications since a
Division 1 area classification includes both the Zone 0 and Zone 1, and equipment must be rated to the
most stringent (Zone 0) requirements.
35
ANSI/ISA12.01.011999
Wiring methods
For the installation of electrical apparatus, three basic installation systems are allowed:
a) Conduit systems (Reference Figures 11, 13, and 15 and Tables 4a and 4b)
b) Cable systems with indirect entry (Reference Figures 5, 6, 12, 14, and 15 and Tables 4a and 4b)
c) Cable systems with direct entry (Reference Figure 7, 8, 9, 12, 14 and 15 and Tables 4a and 4b)
NOTE INTRINSICALLY SAFE ELECTRICAL APPARATUS and NONINCENDIVE FIELD WIRING can be installed with less restrictive wiring
methods. See NEC Section 504-20 or 501-4(b) Exception, respectively.
In the United States, NEC Article 501-4 allows only 1) a conduit system, 2) mineral-insulated (Type MI)
cables, or 3) in industrial establishments with restricted public access where the conditions of maintenance
and supervision ensure that only qualified persons will service the installation, Type MC cable, listed for
use in Class I, Division 1 locations, with a gas/vaportight continuous corrugated aluminum sheath, an
overall jacket of suitable polymeric material, separate grounding conductors in accordance with Section
250 and provided with termination fittings listed for the application.
NEC Article 501-4(b) allows for the use of certain other types of cables in Division 2 areas.
The European harmonized standards, EN 50014 through EN 50039 permit apparatus to be designed that
can be installed using one or more of the three installation approaches. The installation requirements,
however, are different from country to country.
NOTE All figures referred to in this section are shown below.
ANSI/ISA12.01.011999
36
37
ANSI/ISA12.01.011999
ANSI/ISA12.01.011999
38
39
ANSI/ISA12.01.011999
ANSI/ISA12.01.011999
6.1
6.1.1
40
Conduit system
General
With conduit systems in Class I, Division 1, locations in the United States, the electrical wiring is installed
inside closed threaded metal pipes (rigid steel or intermediate metal conduit) approved for the purpose.
The pipes, in turn, are screwed into entrances in the enclosures, which contain electrical equipment. The
entire conduit system, including all fittings, is required to be explosionproof and frequently requires an
explosionproof seal between the connected enclosure and the pipe. In Class I, Division 2, locations, the
conduit system need be explosionproof only between any explosionproof enclosure and the required
sealing fittings.
In Class I, Division l, locations in Canada, one difference is that threaded intermediate metal conduit is not
acceptable.
In this section all references to seal and sealing refer to an approved conduit or cable seal that is filled with
suitable compound, is designed to contain an explosion in the enclosure to which it is attached, and is
approved for use in Class I locations [Figures 1, 2, 3, and 4] (see Article 501 of the NEC).
6.2
Cable systems
In the United States, in Class I, Division 1, locations, the NEC will allow 1) mineral-insulated Type MI cable,
2) Type MC or Type ITC cable listed for use in Class I, Division 1, locations, with a gas/vaportight
continuous corrugated aluminum sheath, an overall jacket of suitable polymeric material, separate
grounding conductor in accordance with Section 250, and provided with termination fittings listed for the
application (Figure 3), and 3) cables used in intrinsically safe systems as permitted by Article 504 of the
NEC. For Class I, Division 2 locations, certain cable constructions are allowed. Refer to Table 4a.
Internationally, openly installed cable systems are common, using heavy-duty sheathed cables (i.e., with
an outer sheath of rubber, plastic, or metal). Armored or braided cable is often required in Zone 1 or in
areas where damage might occur to unprotected cable. The metal braid or armor is covered by an outer
sheath of rubber, plastic, or other synthetics, and the braid or armor is grounded.
Different technologies have been developed in various countries regarding the entry of cables into
explosionproof (flameproof) enclosures. In the course of harmonizing the standards, all these entry
possibilities were included in the CENELEC standards.
6.2.1 Indirect Entry - In Germany, and in many other countries influenced by German technology, only
indirect entry (via a terminal chamber that provided increased safety protection) and factory potted and
installed flameproof cable entries were allowed.
Cables enter the terminal chambers via cable glands and connect to increased safety terminals (Figures 5
& 6). Then the single conductors enter into the flameproof chamber via post-type bushings or conductor
bushings. The installer needs only to open the terminal chamber of increased safety for connection, not
the flameproof chamber. Flameproof cable glands are not required.
6.2.2 Direct Entry - Cables enter the flameproof chamber directly. For cable entry, suitable flameproof
cable glands must be used. (Figures 7 & 8)
6.3
Seals are installed in conduit and cable systems (except for Type MI cable systems with approved
explosionproof terminations) to
41
ANSI/ISA12.01.011999
a) confine an explosion occurring in an enclosure or a conduit system to only that enclosure or that
portion of the conduit system;
b) minimize the passage of gases, vapors, or liquids and prevent the passage of flames through the
conduit or cable system from a classified to an unclassified area, or from one enclosure to another;
c) prevent pressure piling the buildup of pressure inside conduit systems (ahead of an explosions
flame front) caused by precompression as the explosion travels through the system. Exploding
precompressed gases may reach pressures that would exceed the design pressure of the enclosures.
6.3.1
6.3.1.1
Seal requirements
Enclosure entries
In Division 1 and Division 2 locations, a seal must be installed in every conduit or cable system (reference
NEC Article 501-5 for requirements) that enters an enclosure containing arcing, sparking or high
temperature apparatus in which the enclosure is required to be explosionproof.
Multiconductor cables should be sealed in an approved fitting only after removing the jacket and any other
coverings so the sealing compound will surround each individual insulated conductor and the outer jacket
of the cable. The multiconductor cable may be treated as a single conductor if the cable end is sealed by
an approved means within the enclosure.
The conduit system between an enclosure and the required seal must be explosionproof, even in Division
2 locations, since the conduit system must be able to withstand the same internal explosion as the
enclosure to which it is attached. In Division 1 and Division 2 locations, approved explosionproof unions,
couplings, elbows, reducers, and conduit bodies similar to L, T, or Cross types are the only fittings
allowed between the sealing fitting and the enclosure. The conduit body cannot be larger than the trade
size of its associated conduit.
In addition to the above, in Division 1 areas only, explosionproof seals must be installed in each two-inch or
larger conduit run entering an enclosure that contains splices, taps, or terminals. All seals must be
installed within 18 inches (457 mm) from the enclosures to which they are attached.
6.3.1.2
Process Instruments
Seals and drains shall be installed in each conduit or cable connection to devices installed on process
lines that contain flammable fluids and depend upon a single compression seal, diaphragm, or tube (such
as a Bourdon tube) as a barrier between the process fluid and the conduit or cable. This is to prevent
flammable process fluids from entering conduit or cable systems and being transmitted to unclassified
areas or to electrical arcing or high temperature devices in other portions of the system if the process seal
fails. The additional seal and the interconnecting enclosure or conduit or cable system shall meet the
temperature and pressure conditions to which they will be subjected upon failure of the compression seal.
Ordinary conduit or cable seals typically may not meet this criterion due to their leakage rate. Typical
examples of such devices are solenoid valves and pressure, temperature, and flow switches or
transmitters. This requirement applies even in unclassified areas. Draining provisions must be such that
process-line leaks past the process seal will be obvious.
6.3.1.3
Wherever a conduit run passes from a Division 1 to a Division 2 area, from a Division 2 to an unclassified
area, or any other combination thereof, a seal must be placed in the conduit run at the boundary, on either
side. The conduit system must not contain any union, coupling, box, or other fitting between the sealing
fitting and the point at which the conduit leaves the Division 1 or Division 2 area. An exception to the
ANSI/ISA12.01.011999
42
above is that an unbroken rigid metal conduit that passes completely through a Division 1 or a Division 2
area is not required to be sealed if the termination points of the unbroken conduit are in unclassified
locations and the conduit has no fitting less than 12 inches (305 mm) beyond each boundary.
If drain seals are used at an area classification boundary, care must be exercised in the placement of such
seals to ensure that gases or vapor cannot be communicated across the boundary through the conduit
system by way of the seals drain passage. Reference Figure 10.
Cables with an impervious continuous sheath do not have to follow the same sealing requirements as
conduit systems when crossing Division 2 unclassified area classification boundaries. Such cables are not
required to be sealed unless the cable is attached to process equipment or devices that may cause a
pressure in excess of 6 inches of water (1.5 kPa) to be exerted at a cable end. In this case, a seal or other
means shall be provided to minimize migration of flammables into an unclassified area or to arcing or high
temperature devices in other portions of the system, in accordance with NEC Article 501. No seal is then
required at the boundary location. Cables with an unbroken, impervious, continuous sheath are permitted
to pass through a Division 2 unclassified area classification boundary without seals.
43
6.3.1.4
ANSI/ISA12.01.011999
Installation
In addition to being placed in proper locations, the following practices should be observed when installing
sealing fittings:
a) Sealing fittings must be accessible.
b) Sealing fittings must be mounted only in the positions for which they were designed. Some seals are
designed only to be installed vertically; some can be installed either vertically or horizontally; a third
type can be installed in any position.
c) Pouring hubs must be properly oriented. The hub through which the sealing compound is to be poured
must be installed above the sealing cavity to properly pour the seal.
d) Only a sealing compound and fiber approved for a particular sealing fitting should be used, and the
manufacturers instructions should be followed for the preparation of dams (if applicable) and the
preparation and installation of the sealing compound. Particular attention should be paid to
temperature limitations of the sealing compound during installation.
e) No splices or taps are allowed in sealing fittings. Sealing compounds may not be insulation materials
and may absorb moisture, causing grounding of the circuit conductors.
f)
Sealing fittings with drain provisions should be installed at the low points of a conduit system to allow
drainage of conduit where water or fluids may accumulate in the conduit/system.
g) Factory-sealed devices such as toggle switches, push buttons, lighting panels, and lighting fixtures
eliminate the need for externally sealing those particular devices.
6.4
ANSI/ISA12.01.011999
44
Figure 11 depicts a typical international Group II, Zone 1 conduit system installation.
45
ANSI/ISA12.01.011999
Figure 12 depicts a typical international Group II, Zone 1 cable system for a similar installation.
ANSI/ISA12.01.011999
46
Figure 13 depicts a typical United States and Canadian Class I, Division 1 conduit system installation.
Figure 13 Typical United States and Canadian Class I, Division 1 conduit system
installation (Reference API RP 14F, Figure 1, Recommended Practice for Design
and Installation of Electrical Systems for Fixed and Floating Offshore Petroleum
Facilities for Unclassified and Class I, Division 1 and Division 2 Locations)
47
ANSI/ISA12.01.011999
Figure 14 depicts a typical United States and Canadian Class I, Division 1 cable system installation.
Figure 14 Typical United States and Canadian Class I, Division 1 cable system
installation (Reference API RP 14F, Figure 2, Recommended Practice for Design
and Installation of Electrical Systems for Fixed and Floating Offshore Petroleum
Facilities for Unclassified and Class I,
Division 1 and Division 2 Locations)
ANSI/ISA12.01.011999
48
Figure 15 depicts a typical United States and Canadian Class I, Division 2 conduit/cable system
installation.
49
6.5
ANSI/ISA12.01.011999
6.5.1
Metallic conduit systems have been widely used in the United States and Canada to provide physical and
environmental protection to conductors for both hazardous and nonhazardous locations. Conduit systems
also prevent the transmission of an internally generated cable or conductor insulation fire within one
conduit from spreading to an adjacent conduit, thus offering superior fire resistance. Ferrous metallic
conduit can provide substantial magnetic shielding on sensitive circuits. Because conduit systems provide
a closed system for the transmission of gases from one area to another, they must rely on properly located
and properly installed conduit seals to provide explosionproof system integrity. Conduit systems are
subject to internal condensation and resulting corrosion, which, if unchecked, can compromise explosion
protection, especially with regard to offshore or shoreline locations. Also, under certain conditions, conduit
systems can provide a passageway for liquids and gases, possibly transmitting corrosive or toxic
substances to control rooms and electrical equipment buildings. In some countries, conduit systems are
not recognized or accepted.
In many instances, cable systems offer an attractive alternative to conduit systems and are used
worldwide. Cable systems may be less labor intensive during the initial installation and in follow-up
maintenance. Certain types of cable construction and termination methods offer greater corrosion
protection than conduit systems and offer an overall increase in system integrity due to reduced long-term
corrosion effects. Cable systems provide the benefit that they are visible, which allows for ongoing
inspection and simplifies the task of tracing circuits. There are numerous types of cables that are
permitted in hazardous areas.
6.5.2
A comparison between cable systems with direct and indirect entry shows some advantages to the indirect
method, the system with terminal chambers that uses the INCREASED SAFETY type of protection. The
installer can connect the indirect-entry type without opening the flameproof equipment chamber. With the
cable system that uses direct entry, the flameproof protection completion can be achieved only during
installation (on site).
Direct entry technology requires that the wiring connections be accomplished in the flameproof chamber.
When using indirect entry, the connection is to terminals made in a separate terminal chamber that may be
type of protection INCREASED SAFETY or FLAMEPROOF.
7.1
In the United States and Canada, grounding and bonding practices in hazardous (classified) locations
must follow the same standards as grounding and bonding practices in nonhazardous (unclassified)
locations. In addition, the following special precautions must be followed:
a) Locknut bushings and double-locknut bushings must not be used as the only bonding method but must
be paralleled with bonding jumpers. Reference NEC 501-16(a).
b) Flexible-metal conduit or liquid-tight flexible-metal conduit must not be used as the only grounding path
but must be paralleled with internal or external bonding jumpers. Reference NEC 501-16(b).
c) All conduit must be threaded (NPT standard threads with 3/4 inch taper per foot) and made wrenchtight to prevent sparking when fault current flows through the conduit system. Reference NEC 500-2.
d) When required by the control drawing, intrinsically safe systems must be provided with a dedicated
grounding conductor separate from the power system so that ground currents will not normally flow.
ANSI/ISA12.01.011999
50
The systems must be reliably connected to a ground electrode in accordance with NEC Article 250 or
CEC Part 1, Section 10. (Reference ISA-RP12.6)
7.2
Internationally, the term EARTHED is used instead of GROUNDED, but the same basic practices are
followed.
Zone 0
Division 1 / Zone 1
Division 2 / Zone 2
Wiring system
IS
NIS
IS
NIS
IS or
Nonincendive
NIS
Threaded steel
intermediate metal conduit
Flexible metal
explosionproof fitting
Adg
Ac,f
Ac,f
Flexible cord
Note 1
Ac,e
Note 1 or 2
a Abbreviations: IS = intrinsically safe; NIS = not intrinsically safe; A = acceptable; X = not acceptable.
b See the NEC for description and use of wiring systems.
c Acceptable only where flexibility is needed.
d Acceptable only with termination fittings approved for Class I, Division 1 locations of the proper groups.
e Extra-hard usage type with a grounding conductor only acceptable.
f Special bonding/grounding methods are required.
g Type MC or Type ITC cable approved for Division 1 permitted in industrial establishments, see NEC 501-4 (a) Exception 2 or 3.
NOTE 1 Acceptable on approved portable equipment where provisions are made for cord replacement, per NEC 501-11.
NOTE 2 Acceptable on process control instruments to facilitate replacements, per NEC 501-3(b) (6).
51
ANSI/ISA12.01.011999
Division 1
Wiring system
Division 2
IS
NIS
IS or Nonincendive
NIS
Ac
Ac
Type MI cable
Ad
Ae
Type MC cable
Ad
Xi
Ad
Af
Ad
Ad
Ac,d,g
Ac,d,g
Flexible cord
Ad
Ac,d,h
Ac,d,h
Ad
Ad
a Abbreviations: IS = intrinsically safe; NIS = not intrinsically safe; A = acceptable; X = not acceptable.
b See the NEC for description and use of wiring systems.
c Acceptable only where flexibility is needed.
d Acceptable only with dust-tight seals at both ends when electrically conductive dusts will be present.
e Acceptable only with termination fittings approved for Class I, Division 1 locations of the proper groups.
f Acceptable in ventilated channel-type cable trays in a single layer for a space not less than the larger
cable diameter between adjacent cables.
g Special bonding methods are required.
h Only extra-hard usage type with a grounding conductor acceptable.
i Type MC cable approved for Division 1 permitted in industrial establishments, see NEC 501-4 (a) Exception 2.
Maintenance practices
Special attention must be focused on hazardous location equipment maintenance procedures in order to
maintain the integrity of the original installation. The following are pertinent maintenance practices.
8.1
Hazardous location equipment can be repaired only in accordance with the manufacturers
instructions. Some codes of practice require the recording of repairs and the inspection of the completed
repair by a second competent person.
8.2
Maintenance personnel should ensure that all explosionproof enclosures are properly closed and
furnished with the proper number and type of fasteners. Care should be exercised to assure that all machinefinished flanges are protected from damage during maintenance to ensure surface integrity.
8.3
Maintenance personnel should ensure that all grounding conductors are properly terminated.
ANSI/ISA12.01.011999
8.4
52
Any physical abnormalities noted should be corrected or reported to the next level of supervision.
8.5
All threaded connections (including flame paths) should be regularly coated with a lubricant approved
for the purpose.
8.6
Defective circuit protection devices (primarily fuses) must be replaced with functional equivalent
devices (proper amperage, voltage, characteristics, etc.).
8.7
Periodic inspections should be made to ensure that intrinsically safe circuits are isolated from nonintrinsically safe circuits.
8.8
Periodic inspections should be made to ensure that the equipment is suitable for the current area
classification.
8.9
Special care must be taken to ensure that different intrinsically safe circuits do not become shorted
together during calibration and maintenance.
53
ANSI/ISA12.01.011999
Annex A Acronyms
Throughout the text, many acronyms or abbreviations are used. The following list of acronyms provides a
ready reference.
AIT
Autoignition Temperature
ANCE
ANSI
API
AS
Australian Standard
ASTM
AWG
BASEEFA
BS
British Standard
BSI
BVFA
BvS
CANMET
CEC
CEN
CENELEC
CEPEL
CERCHAR
CESI
CSA
CSIR
DEMKO
DIN
ANSI/ISA12.01.011999
54
DIP
Dust-ignitionproof
DNV
DMT
EECS
EMR
EN
EP
Explosionproof
ERA
FM
GOST
HSE
IEC
IECEE
IEEE
IEV
INIEX
INERIS
INSEMEX
IP
IP
ISA
ISSeP
ISO
ITS
JIS
KEMA
LCIE
55
ANSI/ISA12.01.011999
LEL
LFL
LOM
LOSC
MECS
MESG
MIC
MIE
MMS
MSHA
NAMUR
NAS
NEC
NEMA
NEMKO
NEPSI
National Supervision and Inspection Centre for Explosion Protection and Safety of
Instrumentation (China)
NFPA
NRC
NRTL
NMX
NOM
OSHA
PTB
RIIS
SAA
SABS
ANSI/ISA12.01.011999
56
SCS
SEV
SIMTARS
SIPAI
SNZ
SMRE
SP
TIIS
TUV-A
UEL
UFL
UK
United Kingdom
UL
ULC
USA
USCG
USBM
VTT
57
ANSI/ISA12.01.011999
Annex B References
AMERICAN GAS ASSOCIATION
AGA XF0277
Available from:
AGA
Tel: 703-841-8564
Voltage Ratings for Electrical Power Systems and Equipment (60 Hz)
Available from:
ANSI
Recommended Practice for Design and Installation of Electrical Systems for Fixed and
Floating Offshore Production Facilities for Unclassified and Class I, Division 1 and
Division 2 Locations
RP 14FZ
Recommended Practice for Design and Installation of Electrical Systems for Fixed and
Floating Offshore Production Facilities for Unclassified and Class I, Zone 0, Zone 1, and
Zone 2 Locations
RP 500
RP 505
Available from:
API
ANSI/ISA12.01.011999
58
General Requirements
EN 50 015,
Oil Immersion o
EN 50 016,
Pressurized Apparatus p
EN 50 017,
Powder Filling q
EN 50 018,
Flameproof Enclosure d
EN 50 019,
Increased Safety e
EN 50 020,
Intrinsic Safety i
prEN 50 021,
EN 50 028,
Encapsulation m
EN 50 039,
EN 50 054,
055, 056,
057, and 058;
Available from:
ANSI
Tel.: 44-181-996-7000
Fax: 44-181-996-7001
or
BSI
or
59
CENELEC
ANSI/ISA12.01.011999
C22.2, No. 25
C22.2, No. 30
ISBN 0-921347-39-1
Available from:
CSA
Approval Standard
Class No. 3610
Approval Standard
Class No. 3611
Approval Standard
Class No. 3615
Approval Standard
Class No. 3620
Approval Standard
Combustible Gas Detectors
Class Nos. 6310-6330
ANSI/ISA12.01.011999
60
Available from:
FMRC
Std. 142
Available from:
IEEE
Model Code of Safe Practice in the Petroleum Industry, Part 15: Area
Classification Code for Petroleum Installations
Available from:
IP
Institute of Petroleum
61 New Cavendish Street
London, UK W1M 8AR
ISA
ISA-S5.1
ISA-S7.3
ISA-S12.0.01
(IEC 79-0 Mod)
ISA-S12.01.01
ISA-dS12.2.01
(IEC 79-11 Mod)
ISA-RP12.2.02
ISA-RP12.4
Pressurized Enclosures
ISA-RP12.6
61
ANSI/ISA12.01.011999
ISA-S12.10
ISA-S12.11
ISA-S12.12
ISA-dS12.12.01
(IEC 79-15 Mod)
ISA-S12.13,
Part I
ISA-S12.13,
Part II
ISA-S12.15, Part I
ISA-RP12.15, Part II
ISA-S12.16.01
(IEC 79-7 Mod)
ISA-S12.22.01
(IEC 79-1 Mod)
ISA-S12.23.01
(IEC 79-18 Mod)
ISA-RP12.24.01
(IEC 79-10 Mod)
ISA-S12.25.01
(IEC 79-5 Mod)
ISA-S12.26.01
(IEC 79-6 Mod)
ISA-S51.1
ISA-S71.01
ISA-S82.01
Safety Standard for Electrical and Electronic Test, Measuring, Controlling, and
Related Equipment General Requirements
ISA-S82.02
Safety Standard for Electrical and Electronic Test, Measuring, Controlling, and
Related Equipment Electrical and Electronic Test and Measuring Equipment
ISA-S82.03
Safety Standard for Electrical and Electronic Test, Measuring, Controlling, and
Related Equipment Electrical and Electronic Process Measurement and
Control Equipment
ANSI/ISA12.01.011999
62
Calder, W. and Magison, E.C., Electrical Safety in Hazardous Locations, ISA, 1983.
Magison, E.C., Electrical Instruments in Hazardous Locations, ISA, 4th Edition - 1998.
Available from:
ISA
ISA
67 Alexander Drive, P.O. Box 12277
Research Triangle Park, NC 27709
60079-0
60079-1
60079-1A
60079-2
60079-3
60079-4
60079-4A
60079-5
60079-6
60079-7
60079-10
60079-11
60079-12
60079-13
60079-14
60079-15
60079-16
63
ANSI/ISA12.01.011999
60079-17
60079-18
60079-19
Repair and overhaul for apparatus used in explosive atmospheres (other than mines or
explosives)
60079-20
Data for flammable gases and vapours relating to the use of electrical apparatus
60529
60654-1
61241
61241-1-1
61241-1-2
61241-2-1
Part 2: Test methods Section 1: Methods for determining the minimum ignition
temperatures of dust
61241-2-2
Part 2: Test methods Section 2: Method for determining the electrical resistivity of dust
in layers
61241-2-3
Part 2: Test methods Section 3: Method for determining minimum ignition energy of
dust/air mixtures
61241-3
61892-7
Available from:
ANSI
Tel: 41-22-734-01-50
Tel: 41-22-734-01-50
Fax:41-22-733-38-43
http://www.iec.ch
or
IEC
ANSI/ISA12.01.011999
64
MISCELLANEOUS
Hilado, C.J., "A Method for Estimating Limits of Flammability," Journal Fire Flammability, Vol. 6, pp. 130139 (April 1975).
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ICS 6
No. 250
Available from:
NEMA
No. 37
No. 45
No. 70
No. 77
No. 90A
No. 91
Installation of Blower and Exhaust Systems for Dust, Stock, and Vapor Removal or
Conveying
No. 325
Guide to Fire Hazard Properties of Flammable Liquids, Gases, and Volatile Solids
No. 496
No. 497
No. 499
Available from:
NFPA
65
ANSI/ISA12.01.011999
UL 674
Standard for Electric Motors and Generators for Use in Hazardous (Classified) Locations,
Class I, Groups C and D, and Class II, Groups E, F, and G
UL 698
Standard for Industrial Control Equipment for Use in Hazardous (Classified) Locations
UL 781
Standard for Portable Electric Lighting Units for Use in Hazardous (Classified) Locations
UL 783
Standard for Electric Flashlights and Lanterns for Use in Hazardous (Classified)
Locations
UL 823
UL 844
Standard for Electric Lighting Fixtures for Use in Hazardous (Classified) Locations
UL 877
Standard for Circuit Breakers and Circuit-Breaker Enclosures for Use in Hazardous
(Classified) Locations, Class I, Groups A, B, C, and D, and Class II, Groups E, F, and G
UL 886
Standard for Outlet Boxes and Fittings for Use in Hazardous (Classified) Locations
UL 894
UL 913
Standard for Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II,
and III, Division 1, Hazardous (Classified) Locations
UL 1002
Standard for Electrically Operated Valves for Use in Hazardous (Classified) Locations,
Class I, Groups A, B, C, and D, Class II, Groups E, F, and G
UL 1010
UL 1067
Standard for Electrically Conductive Equipment and Materials for Use in Flammable
Anesthetizing Locations
UL 1203
UL 1207
UL 1604
Electrical Equipment for Use in Hazardous (Classified) Locations, Class I and II, Division
2, and Class III, Divisions 1 and 2 Hazardous (Classified) Locations
UL 2225
Standard for Metal-Clad Cables and Cable-Sealing Fittings for Use in Hazardous
(Classified) Locations
ANSI/ISA12.01.011999
66
Available from:
Global Engineering Documents
15 Inverness Way East
Englewood, CO 80112
Tel.:(847) 272-8800
Fax: (847) 272-8125
http://www.ul.com
or
Global Engineering Documents
A Division of Information Handling Services
15 Inverness Way East
Englewood, CO 80112
67
ANSI/ISA12.01.011999
Tel: 919-549-8411
Fax: 919-549-8288
[email protected]
Australia
Austria*
Belgium*
Canada
Standards
SAA
ETVA
ISSeP
CSA
General Requirements
AS 2380.1
AS 2381
AS 3000 Section 9
Oil Immersion/Type o
Pressurization/Type p
AS 2380.4
Powder Filling/Type q
CENELEC
NBN C23-001
EN 50 014
CEC 22.1
CSA E79-0
OVE-EX EN 50 015
NBN C23-104
EN 50 015
CSA E79-6
OVE-EX EN 50 016
NBN C23-105
EN 50 016
NFPA 496
CSA E79-2
IEC 60079-5
NBN C23-106
EN 50 017
CSA E79-5
AS 2380.2
OVE-EX EN 50 018
NBN C23-103
EN 50 018
C22.2 No. 30
CSA E79-1
Increased Safety/Type e
AS 2380.6
OVE-EX EN 50 019
NBN C23-102
EN 50 019
CSA E79-7
Intrinsic Safety/Type i
AS 2380.7
OVE-EX EN 50 020
NBN C23-101
EN 50 020
Type n
AS 2380.9
prEN 50 021
Encapsulation/Type m
AS 2431
CSA E79-18
EN 50 028
AS 2380.7
CEC Annex F
EN 50 039
AS 2430 Part 1
NBN C23-001
EN 50 014
CEC Section 18
EN 60 079-10
NBN C23-001
EN 50 014
CEC Annex B
IEC 60079-18
OVE-EX65
EX-RL Guidelines No. 11
AS 2380.4
IEC E79-13
AS 2430 Part 2
CEC Section 18
prEN 6 1241-3
AS 2236
C22.2 No. 25
prEN 6 1241-1-1
OVE A50
68
Explosionproof/Flameproof/Type d
ANSI/ISA12.01.011999
Country
Country
Denmark*
Standards
DEMKO
Finland*
France*
Germany*
UTE
VDE
Afsnit 7A
Afsnit 50
EN 50 014
SFS 4094
EN 50 014
NF C23-514
NF EN 50 014
Oil Immersion/Type o
Afsnit 50-1
EN 50 015
SFS 4095
EN 50 015
NF C23-515
NF EN 50 015
Pressurization/Type p
Afsnit 50-2
EN 50 016
SFS 4096
EN 50 016
NF C23-516
NF EN 50 016
Powder Filling/Type q
Afsnit 50-3
EN 50 017
SFS 4097
EN 50 017
NF C23-517
NF EN 50 017
Explosionproof/Flameproof/Type d
Afsnit 50-4
EN 50 018
SFS 4098
EN 50 018
NF C23-518
NF EN 50 018
Increased Safety/Type e
Afsnit 50-5
EN 50 019
SFS 4099
EN 50 019
NF C23-519
NF EN 50 019
Intrinsic Safety/Type i
Afsnit 50-6
EN 50 020
SFS 4100
EN 50 020
NF C23-520
NF EN 50 020
Type n
prEN 50 021
Encapsulation/Type m
NF C23-528
NF EN 50 028
NF C23-539
NF EN 50 039
Afsnit 7A
Afsnit 7A
Section 41
VDE 0165
DIN EN 60 079-10
VDE 0165
VDE 0171
Afsnit 7A
SFS 2972
NF C20-010
DIN 40050
ANSI/ISA12.01.011999
69
General Requirements
Greece*
Hungary
IEC
Irish Republic*
Italy*
Standards
CEI
IEC 60079-0
IEC 60079-0
IEC 60079-0
IS 231
CEI 31-8
CEI 64-2
EN 50 014
Oil Immersion/Type o
IEC 60079-6
IEC 60079-6
IEC 60079-6
IS 232
CEI 31-5
EN 50 015
Pressurization/Type p
IEC 60079-2
IEC 60079-2
IEC 60079-2
IS 233
CEI 31-2
EN 50 016
Powder Filling/Type q
IEC 60079-5
IEC 60079-5
IEC 60079-5
IS 234
CEI 31-6
EN 50 017
Explosionproof/Flameproof/Type d
IEC 60079-1
MS2 4814
IEC 60079-1
IEC 60079-1
IS 235
CEI 31-1
EN 50 018
Increased Safety/Type e
IEC 60079-7
IEC 60079-7
IEC 60079-7
IS 236
CEI 31-7
EN 50 019
Intrinsic Safety/Type i
IEC 60079-11
IEC 60079-11
IEC 60079-11
IS 237
CEI 31-9
EN 50 020
Type n
IEC 60079-15
IEC 60079-15
IEC 60079-15
CEI 31-11
Encapsulation/Type m
IEC 60079-18
IEC 60079-18
IEC 60079-18
CEI 31-13
EN 50 028
IEC 60079-10
IEC 60079-10
IEC 60079-10
CEI 64-2
IEC 60079-12
IEC 60079-12
IEC 60079-12
IEC 60079-13
IEC 60079-13
IEC 60079-13
IEC 61241-3
70
General Requirements
ANSI/ISA12.01.011999
Country
Country
Japan
Netherlands*
Norway*
Standards
JIS
NEN
NE
General Requirements
JIS C0903
Oil Immersion/Type o
Pressurization/Type p
JIS C0903
JIS C0904
Powder Filling/Type q
NEN-EN 50 014
NEN-110
NVE Communication 1/77
NEK-EN 50 014
NEN-EN 50 015
NEN-111
NEK-EN 50 015
NEN-EN 50 016
NEN-112
NEK-EN 50 015
NEN-EN 50 017
NEN-113
NEK-EN 50 017
JIS C903
JIS C904
NEN-EN 50 018
NEN-114
NEK-EN 50 018
Increased Safety/Type e
JIS C903
JIS C904
JIS C905
NEN-EN 50 019
NEN-115
NEK-EN 50 019
Intrinsic Safety/Type i
JIS C903
JIS C904
NEN-EN 50 020
NEN-116
NEK-EN 50 020
Type n
NEN-3125
Encapsulation/Type m
NEN-EN 50 028
NEK-EN 50 028
Directorate-General of
Labor Report No. 2E
NEN-1010
Portugal*
PN 721E
71
Explosionproof/Flameproof/Type d
Poland
VDE 0171
VDE 0165
Labour Ordinance
No. 16 RIIS
ANSI/ISA12.01.011999
Russia
S. Africa
Spain*
Sweden*
Switzerland*
Standards
GOST
SABS
SIEV/SAT
UNE
SEV
SABS 086
SABS 087
SABS 808
SABS IEC 60079-0
SS EN 50 014
SEN 421 0819
Instruccion MI.BT
UNE
20318
SS EN 50 014
SEV 1068
SS EN 50 014
Oil Immersion/Type o
SS EN 50 015
UNE 20326
UNE 21815
SS EN 50 015
SEV 1069
SS EN 50 015
Pressurization/Type p
SABS 0119
SABS IEC 60079-2
SS EN 50 016
UNE 20319
UNE 21816
SS EN 50 016
SEV 1070
SS EN 50 016
Powder Filling/Type q
SS EN 50 017
UNE 20321
UNE 21817
SS EN 50 017
SEV 1071
SS EN 50 017
Explosionproof/Flameproof/Type d
SABS 314
SABS IEC 60079-1
SS EN 50 018
UNE 20320
UNE 21818
SS EN 50 018
SEV 1072
SS EN 50 018
Increased Safety/Type e
SABS 1031
SABS IEC 60079-7
SS EN 50 019
UNE 20327
UNE 20328
SS EN 50 019
SEV 1073
SS EN 50 019
Intrinsic Safety/Type i
SABS 549
SABS IEC 60079-11
SS EN 50 020
SEN 421 0879
UNE 20327
UNE 21820
SS EN 50 020
SEV 1074
SS EN 50 020
Type n
SABS 970
Encapsulation/Type m
Intrinsically Safe Electrical Systems
Classification of Hazardous Gas & Vapor
Locations
EN 50 039
SABS 089 Part II
SABS 0108
SAI SIND-FS
SS 421 0820
SS 421 0821
SEV 3538
MI.BT 009
MI.BT 026
UNE 20322
SEV 3307-1
UNE 20320
SABS 969
SEN 2121
SS IEC 529
SEV 1000
72
General Requirements
ANSI/ISA12.01.011999
Country
Country
U.K.*
U.S.A
U.S.A.
U.S.A
U.S.A.
Standards
BS
API
FM
IEEE
ISA
ISA-S12.0.01 (Zones)
Oil Immersion/Type o
BS 5501 Part 2
EN 50 015
BS EN 50 015
IEC 60079-6
ISA-S12.26.01
Pressurization/Type p
BS 5501 Part 3
EN 50 016
BS EN 50 016
IEC 60079-2
ISA-RP12.4
Powder Filling/Type q
BS 5501 Part 4
EN 50 017
BS EN 50 01
IEC 60079-5
ISA-S12.25.01
Explosionproof/Flameproof/Type d
BS 5501 Part 5
EN 50 018
BS EN 50 018
IEC 60079-1
ISA-S12.22.01
Increased Safety/Type e
BS 5501 Part 6
EN 50 019
BS EN 50 019
IEC 60079-7
ISA-S12.16.01
Intrinsic Safety/Type i
BS 5501 Part 7
EN 50 020
BS EN 50 020
IEC 60079-11
ISA-RP12.6
Type n
BS 4533
BS 5000
BS 6941
IEC 60079-15
BS/prEN 50 021
ISA-S12.12.01
ANSI/ISA12.01.011999
BS 5501 Part 1
EN 50 014
BS EN 50 014
IEC 60079-0
73
General Requirements
ISA-S12.23.01
ANSI/ISA12.01.011999
ISA-S12.10
74
Country
U.K.*
U.S.A
U.S.A.
U.S.A
U.S.A.
Standards
BS
API
FM
IEEE
ISA
Encapsulation/Type m
BS 5501 Part 8
EN 50 028
BS EN 50 028
IEC 60079-18
BS 5501 Part 9
EN 50 039
BS EN 50 039
BS EN 60 079-10
BS 5345 Part 1
BS 5501 Part 1
BS EN 50 014
BS/EN 60079-12
BS 5345 Part 5
BS 6467 Part 2
BS 6467 Part 1
ANSI/API RP 500
ANSI/API RP 505
ISA-S12.11
Country
U.S.A
U.S.A.
Croatia
Standards
NFPA
UL
DZNM/S-Commission
General Requirements
Oil Immersion/Type o
Pressurization/Type p
UL 2279 Part 2
Powder Filling/Type q
P.R. of China
GB3836.1
GB3836.6
GB3836.5
GB3836.7
GB3836.2
Increased Safety/Type e
UL 2279 Part 7
GB3836.3
Intrinsic Safety/Type i
GB3836.4
Type n
GB3836.8
Encapsulation/Type m
UL 2279 Part 18
HRN-EN 50 028
GB3836.9
UL 913
HRN-EN 50 039
NFPA 497
NFPA 497
NFPA 496
NFPA 499
GB3836.12
GB12476.1
ANSI/ISA12.01.011999
75
Explosionproof/Flameproof/Type d
77
ANSI/ISA12.01.011999
Tel: 919-549-8411
Fax: 919-549-8288
[email protected]
Repair and
Overhaul
Selection of
Instrumentation,
Repair, and
Maintenance for
Dust
Atmospheres
Combustible
Gas Detectors
AS 3000
OVE
EX 65
Belgium
China
NBN C23-201
EN 50 039
RGIE
RGIE Article
251
Electrical
Safety
Regulations
for Explosive
Atmospheres
of Peoples
Republic of
China
Canada
CEC
Denmark
Finland
France
Germany
Greece
Italy
Japan
Heavy
Current
Regulations
Electrical
Safety
Regulations
NF C23539
EN 50 039
EX-RL
Guidelines
No. 11
Elexv ZHI/
227
Elexv ZHI/
200
Elexv ZHI/
309
VDE 0107
VDE 0166
PCC
Regulations
for interior
electrical
installation Chapter X
Presidential decree
DPR 546
Chapter X
CEI 64-2
JISHA Recommended
Practice for
ExplosionProtected
Electrical
Installations in
General
Industries.
JISHA Recommended
Practice for
Electrical
Equipment for
use in Explosive
Dust
Atmospheres in
General
Industries.
78
Inspection &
Maintenance
Austria
ANSI/ISA12.01.011999
Code of
Practice for
selection,
installation and
maintenance
basic
requirements
Australia
Netherlands
Code of Practice
for selection,
installation and
maintenance
basic
requirements
NEN 1010
Norway
NVE
Communications
No. 1/77
Portugal
S. Africa
Decree No.
740/74
Decree No.
517/80
Decree No.
36270
SABS 086
SABS 0119
Spain
Sweden
Instruccion
MI.BT 026
SIEV-FS
Safety
Regulations
SIND-FS
Classification
Regulations
Switzerland
SEV 1000
SEV 3538
U.K.
BS/EN
60079-14
U.S.A.
IEC
NEC/NFPA
70
API RP 14F
API RP 14FZ
(draft)
API RP 540
IEC 60079-14
BS 5345
BS/EN
60079-17
IEC 60079-17
Repair and
Overhaul
BS/EN
60079-19
IEC 60079-19
Selection of
Instrumentation
Repair and
Maintenance for
Dust
Atmospheres
BS 6467
Part 2
BS/EN
61241-1-2
IEC 61241-12
Combustible
Gas Detectors
BS 6959
BS/EN
60079-14
ISA RP 12.13
Part II
API RP 500
API RP 505
IEC 60079-14
79
Inspection &
Maintenance
ANSI/ISA12.01.011999
Developing and promulgating technically sound consensus standards, recommended practices, and
technical reports is one of ISAs primary goals. To achieve this goal, the Standards and Practices
Department relies on the technical expertise and efforts of volunteer committee members, chairmen,
and reviewers.
ISA is an American National Standards Institute (ANSI) accredited organization. ISA administers
United States Technical Advisory Groups (USTAGs) and provides secretariat support for
International Electrotechnical Commission (IEC) and International Organization for Standardization
(ISO) committees that develop process measurement and control standards. To obtain additional
information on the Societys standards program, please write:
ISA
Attn: Standards Department
67 Alexander Drive
P.O. Box 12277
Research Triangle Park, NC 27709
ISBN 1-55617-696-1