WALL MOUNT STROBES

FS-340 SERIES
Features

UL and C-UL listed

12 VDC with 15, 35 or 60 cd settings

24 VDC with 15, 35, 60, 75, 95 or 110 cd settings

6 distinct candela settings

Candela selection view window

15/75 ADA compliant on 60 cd setting

Pre-wire back plate

Universal back plate mounting (single gang, double


gang, octagon, or 4 square)

Single screw mounting

For indoor applications

Description
The FS-340 Strobe Series provides a wide range of
candela light output options in a single device. The
candela settings include a 12 or 24 volt DC operation
for the 15, 35 and 60 (75 on axis) candela settings and
24 volt DC operation for the 15, 35, 60, 75, 95 and
110 candela settings. The candela setting is displayed
through the front window and is selectable using a
drum wheel.
The voltage input can be either regulated DC or full
wave rectified (FWR) 12 volt or 24 volt operation with
an operating range from 8 to 33 V DC. The strobes can
be synchronized using a control panel with the Mircom
(Amseco) sync protocol or an SDM-240 sync module.
The FS-340 utilizes a universal mounting plate that
will mount on a single gang, double gang, octagon
and 4 square electrical boxes. The back plate allows
the installer to mount the plate and connect the wire
connections. The strobe attaches in a hinge fashion
from the top and is secured by a single mounting screw.
The strobe completely covers the mounting back plate,
therefore it can be mounted before other trades work is
completed and not affect the final look.

The strobes can be synchronized using a control panel


with the Mircom sync protocol or the SDM-240 sync
module. The strobe shall utilize a mounting plate that
allows the installer to pre-wire the mounting plate.
The mounting plate shall be universal and mount on
a single gang, double gang, octagon or 4 inch square
box. The mounting plate shall be completely covered
by the strobe and shall be secured by a single screw.
The strobe shall be UL listed to standard 1638, General
Signaling, and standard 1971, Signaling Devices for
the Hearing Impaired. In addition, the strobes shall be
C-UL listed to CAN-ULC S526.

Wiring Diagram
FS-340

Engineering Specifications
The installer shall provide and install the FS-340
selectable strobe. The strobe shall have six (6) candela
settings. The candela settings shall be selectable using
a drum roller and shall display the candela setting on
the front of the device. The strobe shall operate at 12
or 24 VDC regulated or full wave rectified. The strobe
shall have an operating range between 8 and 33 VDC.
NOT TO BE USED FOR INSTALLATION PURPOSES.

S5375

CATALOG NUMBER

5268

Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.

Installation

Dimensions
Inches (mm)

6 5/64 (154.4)

A jumper plug is provided to test


for correct wiring in the supervisory
mode only. Do not pass alarm current
through the jumper.

5 (127)

2 5/16 (59)

Selector Switch

Note: Installation must comply in accordance with applicable standards.

High voltage may be present inside the light assembly even though
power is not connected. If access to the component board is required
(removal or replacement), the capacitor must be discharged by
touching a wire to both ends of the flash tube.
DO NOT attempt to touch or move the assembly until the capacitor
has been discharged.

Light Output
Light output in precentage when measured from the following directions per
UL 1971.

Specifications
Strobe Current
Light
Output

Max. RMS Operating Current (mA RMS)


Reg. 12
VDC

Reg. 12
FWR

Reg. 24
VDC

Reg. 24
FWR

15cd

116

152

62

99

35cd

209

267

102

152

60/75cd

254

258

131

190

75cd

NA

NA

146

208

95cd

NA

NA

177

243

110cd

NA

NA

196

268

Voltage

12/24V

UL Designation

Regulated 12 DC/ Regulated 24 DC/


FWR
FWR

Operating Voltage
Range

8 - 17.5V

Flash Rate

60 times/min.

Sync Module (SDM-240)


Operating
Temperature Range

16 - 33V

N/A

Available

32F to 120F (0C to 49C)

Ordering Information
Model Number

Description

FS-340R

Wall Mount Strobe, Red

FS-340W

Wall Mount Strobe, White


NOT TO BE USED FOR INSTALLATION PURPOSES.

Distributed by:

Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: (905) 660-4655
Fax: (905) 660-4113
Web page: http://www.mircom.com

U.S.A.
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Toll Free: (888) 660-4655
Fax Toll Free: (888) 660-4113
Email: [email protected]

CAT. 5268

Rev. 0

You might also like