Mircom FS340R Data Sheet
Mircom FS340R Data Sheet
FS-340 SERIES
Features
Description
The FS-340 Strobe Series provides a wide range of
candela light output options in a single device. The
candela settings include a 12 or 24 volt DC operation
for the 15, 35 and 60 (75 on axis) candela settings and
24 volt DC operation for the 15, 35, 60, 75, 95 and
110 candela settings. The candela setting is displayed
through the front window and is selectable using a
drum wheel.
The voltage input can be either regulated DC or full
wave rectified (FWR) 12 volt or 24 volt operation with
an operating range from 8 to 33 V DC. The strobes can
be synchronized using a control panel with the Mircom
(Amseco) sync protocol or an SDM-240 sync module.
The FS-340 utilizes a universal mounting plate that
will mount on a single gang, double gang, octagon
and 4 square electrical boxes. The back plate allows
the installer to mount the plate and connect the wire
connections. The strobe attaches in a hinge fashion
from the top and is secured by a single mounting screw.
The strobe completely covers the mounting back plate,
therefore it can be mounted before other trades work is
completed and not affect the final look.
Wiring Diagram
FS-340
Engineering Specifications
The installer shall provide and install the FS-340
selectable strobe. The strobe shall have six (6) candela
settings. The candela settings shall be selectable using
a drum roller and shall display the candela setting on
the front of the device. The strobe shall operate at 12
or 24 VDC regulated or full wave rectified. The strobe
shall have an operating range between 8 and 33 VDC.
NOT TO BE USED FOR INSTALLATION PURPOSES.
S5375
CATALOG NUMBER
5268
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.
Installation
Dimensions
Inches (mm)
6 5/64 (154.4)
5 (127)
2 5/16 (59)
Selector Switch
High voltage may be present inside the light assembly even though
power is not connected. If access to the component board is required
(removal or replacement), the capacitor must be discharged by
touching a wire to both ends of the flash tube.
DO NOT attempt to touch or move the assembly until the capacitor
has been discharged.
Light Output
Light output in precentage when measured from the following directions per
UL 1971.
Specifications
Strobe Current
Light
Output
Reg. 12
FWR
Reg. 24
VDC
Reg. 24
FWR
15cd
116
152
62
99
35cd
209
267
102
152
60/75cd
254
258
131
190
75cd
NA
NA
146
208
95cd
NA
NA
177
243
110cd
NA
NA
196
268
Voltage
12/24V
UL Designation
Operating Voltage
Range
8 - 17.5V
Flash Rate
60 times/min.
16 - 33V
N/A
Available
Ordering Information
Model Number
Description
FS-340R
FS-340W
Distributed by:
Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: (905) 660-4655