(2011-01-21) Daikin BACnet Interface Programming Guide PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 69
At a glance
Powered by AI
The presentation discusses Daikin VRV heat pump and heat recovery systems, their components like outdoor units, indoor units and control networks, as well as control concepts like individual zone control and scheduling.

VRV systems use variable refrigerant volume to meet varying heating and cooling loads in different zones. They have outdoor units, indoor units connected via refrigerant piping, and use DIII-NET for communication between components. They can simultaneously heat and cool different zones for efficiency.

VRV systems allow individual indoor units or groups of units to control temperature in different zones to individual setpoints. They use control concepts like PID control, adaptive control technology and zoning to efficiently meet varying loads in different areas.

Daikin BACnet Interface DMS502B71

Programming Guide
Rev 2.0
1/21/2011
Daikin AC - Controls Engineering Dept

2006 Daikin AC

Contents
VRV system overview for BMS
integrator
VRV system
Configuration and
Mechanism
DIII-net system and Group
address
Changeover master
Indoor unit
Room temperature
Skyair & Mini-split

BACnet Object format and list


Basic to Optional
Programming functions
Setpoint Range
Auto Changeover
Setback
Notes to program
Others
Q&A
Links Online documentation

Presentation
Title
: Presenter
: Date Programming Guide
Daikin
BACnet
Interface
Name
DMS502B71

Slide 2

2005 Daikin AC

VRV Overview

Great for comfort zoning efficient to meet load time by time


Quiet operation
Multi-split with one refrigerant network
Scalable
Heat Pump, Heat Recovery system
Air cooled, Water cooled
208/230, 460V 3phase; 208/230 1phase
Simple communication network DIII-NET
Light Commercial office, school, hotel etc.
Residential
VRV III
VRV III-S
Heat Pump

Heat Pump / Heat Recovery

VRV-WIII
Water cooled
Heat Pump / Heat Recovery

VRV
Condensing
Units

3 and 4 Ton
208-230V/60Hz/1Ph

6 to 20 Ton
208-230V/60Hz/3Ph &
460V/60Hz/3ph

Presentation
Title
: Presenter
: Date Programming Guide
Daikin
BACnet
Interface
Name
DMS502B71

5 to 21 Ton
208-230V/60Hz/3Ph

Slide 3

2005 Daikin AC

VRV - How does it work


Heat Pump System

Heat Recovery System

Presentation
Title
: Presenter
: Date Programming Guide
Daikin
BACnet
Interface
Name
DMS502B71

Slide 4

2005 Daikin AC

VRV Control Concepts VRV System


Variable Refrigerant Volume Application Flexibility
Variable loads meet variable capacity Individual setpoints
Staggered occupancy and space utilization
Simultaneously heat and cool for ultimate efficiency
The keyword zoning drives Daikin control philosophy
PID Adaptive control technology optimizes efficiency
Automatic device addressing at start-up
Rethinking traditional means of air conditioning control
DIII-Net (F1-F2)

Presentation
Title
: Presenter
: Date Programming Guide
Daikin
BACnet
Interface
Name
DMS502B71

Slide 5

2005 Daikin AC

Individual Zone Controls


Heat pump system applications Remote control groups

Heat Pump
Private Office

Open / Common Areas

Benefits
One setpoint for multiple indoor units allows effective zoning
Individual indoor units in a group control to their respective setpoints
independent of the load on that unit or the system
Give occupants the freedom to control their own environment
Control groups reduce material and labor costs
Presentation
Title
: Presenter
: Date Programming Guide
Daikin
BACnet
Interface
Name
DMS502B71

Slide 6

2005 Daikin AC

Individual Zone Controls


Heat recovery system applications Zoning principals

BS Box

BS ox
BS Box

BS Box

BS Box

Heat Recovery

Heat Recovery
South
Exposures

North Exposures

Office Application Controls accommodating exposure affected loads

Hotel application Individual control is satisfied

Benefits
Exploits efficiency potential of the heat recovery technology
Individual control is maintained where expected
Control groups reduce cost and complexity
Up to 16 indoor units on a single controller
Presentation
Title
: Presenter
: Date Programming Guide
Daikin
BACnet
Interface
Name
DMS502B71

Slide 7

2005 Daikin AC

Indoor Unit has information and a control logic


Daikin individual zone controllers serve as a sort of

browser into the current settings residing in the indoor


unit PCB (on/off, temperature set-point, mode, etc.)
Information is stored within the indoor units PCB
Changes are initiated by the user at the controller and
pushed to the indoor unit PCB

Exceptions include navigation / programmable

controllers where some functions schedule, auto


changeover, etc. occur in the controller, however
once a multi zone controller such like BACnet
Interface and I-Touch Controller is connected, these
functions would be disabled. *
* They can be enabled back with a field setting

Presentation
Title
: Presenter
: Date Programming Guide
Daikin
BACnet
Interface
Name
DMS502B71

Slide 8

2005 Daikin AC

VRV Controls Concepts Controllers


Daikin Controls Matrix What are your choices?
Individual Zone Controllers

Multi-zone Controllers

Open Protocol Interfaces

Adapter PCBs

Presentation
Title
: Presenter
: Date Programming Guide
Daikin
BACnet
Interface
Name
DMS502B71

Slide 9

2005 Daikin AC

Typical BACnet project Configuration


BMS controls / monitors each indoor unit in VRV systems through the
BACnet and DIII-Net communications with BACnet Interface which is
a gateway between BACnet and DIII-Net.
DIII-Net

DIII-Net

BACnet

BS Box
DMS502B71
BACnet Interface

BS Box

BS Box

DCS601C71
Intelligent Touch
Controller

REYQ
VRVIII
Heat Recovery

FXMQ

FXFQ

Concealed Ceiling

Ceiling Cassette

BRC1E71

FXAQ

Navigation
Remote Controller

Wall Mounted

DIII-Net

Building Automation
System
VRV III-S
Heat Pump

BACnet Interface
and I-Touch Controller (Optional)

FHQ
Ceiling
Suspended
Unit

BRC2A71

BRC2A71
REYMQ

BMS

FXMQ
Concealed Ceiling

Simplified
Remote Controller

RZQ
SkyAir
Heat Pump

Simplified
Remote Controller

VRV System

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 10

2005 Daikin AC

Case Study
New ASHRAE Headquarters in Atlanta, GA
Two Daikin 14-Ton VRVIII heat recovery systems for

optimum efficiency
One 4-Ton VRV-S and Two 3-Ton SkyAir systems
25 indoor units
BACnet integration to Automated Logics WebCTRL
automation system
Includes Daikins Intelligent Touch Controller for backup
operation
Internet access via web portal and email notification of
system alarms
Daikin simplified remote controller for local control where
required
BS Box
DMS502B71
BACnet Interface

BS Box

BS Box

DCS601C71
Intelligent Touch
Controller

FXAQ

REYQ
VRVIII W/ Heat
Recovery

Automated Logic
WebCTRL
Third Party
Automation System

FXMQ
Concealed Ceiling
Unit (Medium Static)

FXSQ
Concealed Ceiling Unit

FXMQ

FHQ

Concealed Ceiling
Unit (Medium Static)

Ceiling
Suspended
Unit

VRV-S

Simplified
Remote Controller

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Simplified
Remote Controller

BRC2A71

BRC2A71
REYQ

BRC2A71

Wall
Mounted
Unit

RZQ
SkyAir

Simplified
Remote Controller

Slide 11

2005 Daikin AC

Mechanism Overview
Available a set of 26 BACnet objects for each indoor unit which is

connected to the DIII-Net system


Daikin BACnet Interface is a gateway between BACnet and DIII-Net
BMS

VRV System Indoor unit

Application
Graphics
Schedule
Trend etc.
Categorized
by Object type

DIII-Net
Communication

BACnet Interface

Application Interface

BACnet

Set of 26
Objects for
each indoor
unit

TCP(UDP)/IP
Ethernet
Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 12

2005 Daikin AC

DIII-Net system and Group address


You can recognize the specific indoor unit with the DIII-Net system number and

the indoor unit group address. BACnet Interface can handle up to 4 DIII-Net
systems. (2 in 4 as option)
DIII-Net system
Up to 10 VRV condensing units (Daisy chained)
Up to 64 Indoor unit Groups = 64 remote controllers, up to 128 indoor units
Group address
Unique address in the DIII-Net system, configured manually in VRV
commissioning
1-00 to 1-15, 2-00 to 2-15, 3-00 to 3-15, 4-00 to 4-15 (64 addresses at maximum)
DIII-Net system #1

DIII-Net system #2

Daisy Chained

Daisy Chained
1-00

1-01

1-02

1-03

1-04

1-00

1-01

1-05

1-06

1-07

1-08

1-09

2-00

2-01

1-10

1-11

1-12

1-13

1-14

VRV
Condensing
Unit

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Remote
Controller

Indoor
Unit

1-02

Group
Address

Slide 13

2005 Daikin AC

Remote Control Group and Group Address


Assign a group address
to an indoor unit
F1F2*

F1F2*

1-00

Unit #0
P1P2**

Assign a group address to a R/C group

No R/C
Group

Can monitor
and control
the indoor
unit through
F1F2

* F1F2 = DIII-Net
** P1P2 = R/C line

Unit #0

BMS can control the indoor


unit which is Unit #0 in a R/C
group

Unit #1

P1P2**

Up to 16
indoor units

Unit #16

Can monitor one indoor unit (unit #0) through F1F2


Can control one indoor unit (unit #0) through F1F2
and other indoor units will follow the unit #0 though
P1P2 line

Assign a group address to each indoor unit in a R/C group


F1F2*

BMS can monitor the indoor


unit which the group address
is assigned

1-00

1-00
Unit #0

1-15

1-01
Unit #1

P1P2**

Up to 16
indoor units

Unit #16

Can monitor each indoor unit through F1F2


Can control one indoor unit (unit #0) through F1F2
and other indoor units will follow the unit #0 though
P1P2 line

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 14

2005 Daikin AC

Remote Controller-less System


Assign group address to each indoor unit

1-00

1-01

1-02

1-03

1-04

1-05

1-06

1-07

1-08

1-09

All indoor unit would be the Unit #0, so that


you can monitor and control each indoor
unit.

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 15

2005 Daikin AC

Changeover master unit


Heat Pump System
You can change the operation mode to Cool or Heat on only a changeover master unit.
Other units under the same condensing unit will follow the operation mode of the
changeover master unit.
Heat Recovery System
You can change the operation mode to Cool or Heat on only a changeover master unit
under a BS unit.
Other units under the same BS unit will follow the operation mode of the changeover
master unit.
In case of only one indoor unit connected a BS unit, you can change to Cool or Heat on
individual indoor unit.
Heat Pump System

Heat Recovery System


DIII-Net

DIII-Net

BS Box

BS Box

Changeover
Master
There is one Changeover master unit
under Heat pump condensing unit or Heat
recovery BS Box even in case of remote
controller-less system.

Changeover
Master

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Changeover
Master

Slide 16

2005 Daikin AC

Changeover Master and Followers

Auto mode is not recommended to set because of a potential wide room temperature swing range. (See slide 20)
I-TC V6.02 or higher overrides Auto mode with Cool or Heat mode once Auto mode in an indoor unit is detected.

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 17

2005 Daikin AC

Indoor unit
Indoor unit has a control logic to maintain a room temperature adjusting
a refrigerant flow and has the following data points
Unit On/Off On/Off
Operation mode Cool/Dry/Heat/Fan (Auto would not work well)
Setpoint (16C to 32C, 0.1C basis)
Room temperature (read only)
Fan Speed (H/L or H/M/L depends of the indoor unit type)
Air flow direction (if an indoor unit has a louver)
Alarm status (read only)
Malfunction code (read only) etc.

BMS can change them or get the latest ones to control / monitor the

indoor unit through BACnet Interface.


There are no data points for the condensing unit except for the
Compressor status.
Since VRV is a packaged system, you dont have to worry about the
condensing unit. If something wrong in the system, Alarm status and
Malfunction code will show you.
Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 18

2005 Daikin AC

Daikin Indoor unit Sequence of Operation


Cooling & Heating
Unit Turned On

Cooling Mode

Thermo-on
Call for Cooling)

Thermo-Off

Fan in Cooling Thermo-Off


period can be OFF with the
field setting (this setting is
available depends on the
indoor unit type *). However
when an indoor unit receives
outside air, the fan should not
be OFF.

Thermo-on
Call for Cooling)

74
73

Set-point 72
71
70

Fan

Fan ON while
the unit is ON

H or L
Off

Heating Mode

Thermo-on
Call for Heating)

Thermo-Off

Fan in Heating Thermo-Off period


can be ON (H or L) or completely
OFF with the field setting. (this
setting is available depends on the
indoor unit type *). However when
an indoor unit receives outside air,
the fan should not be OFF.

Thermo-on
Call for Heating)

74
73

Set-point 72
71
70

Fan

H or L
Off

Similar to
Fan Auto

LL
To sense the suction air temperature correctly

* Field setting: see slide 56, 57 for details.

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 19

2005 Daikin AC

Daikin Indoor unit Sequence of Operation


Auto mode in H/R
In the cooling mode, thermo on and off is working with +/- 1F(speaking precisely, 0.9F [0.5C]) basis around a cooling set-point.
When a room temperature comes down 3.6F below the cooling set-point, it goes into the heating mode with a heating set-point
that is the cooling set-point minus the differential (0F). As the chart shows, it goes into the heating thermo-on mode, not thermo
off mode, because the room temperature is below heating set-point minus 1F at the changeover point.
In the heating mode, thermo on and off is working with +/- 1F basis around a heating set-point.
When a room temperature comes up 5.4F above the heating set-point, it goes into the cooling mode with the cooling set-point
that is the heating set-point plus the differential (0F). As the chart shows, it goes into the cooling thermo-on mode, not thermo off
mode, because the room temperature is above cooling set-point plus 1F at the changeover point.
To Heating Changeover point
68.4F (= Cooling set-point (0F / 2 +3.6F [2C]))

To Cool
at Setpoint + 5.4F

Cooling Set-point 72F

Temp swing
9F

Cooling Thermo ON
Cooling
Thermo
OFF

To Heat
at Setpoint 3.6F

Heating Thermo OFF

Heating Thermo ON
67

68

Heating Set-point
72F (= Cooling set-point 0F)

69

70

71

72

73

74

75

76

77

78

79

To Cooling Changeover point


77.4F (= Heating set-point + 5.4F [3C])

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 20

2005 Daikin AC

Daikin Indoor unit Sequence of Operation


Dry Mode
Dry mode is only selectable at the remote controller
Dry mode cannot be scheduled from a multi-zone controller or through a Interface
Set-point is determined based on the room temperature internally when the Dry
mode is set, so as to not further cool down the room temperature
Set-point RETURN AIR (in case of RETURN AIR <= 75)
Set-point RETURN AIR 1F (in case of RETURN AIR > 76)
The set-point is not displayed on the remote controller when Dry mode is engaged
Unit Turned On

Cool mode

Dry mode
Thermo-On
(Call for Cooing)

Thermo-Off

Thermo-On
(Call for Cooing)

76
75

Only allow an end user to


select it from a remote
controller in a zone, because
an internal cooling setpoint is
set based on a room
temperature when Dry mode is
selected.

(Set point) 74
73
72

H or L
L
Fan
Off

Do not set Dry mode from a


BMS side.

6 min
(For not returning moisture on a coil)

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 21

2005 Daikin AC

Room Temperature
Room Temperature is either
Indoor unit Return air sensor,
Remote sensor (alternative of Return air sensor), or
Sensor in the BRC1E71 (Remote controller)
It depends on the VRV indoor unit configuration (Field Setting *).
An indoor unit works with one of them. BMS can not provide the room
temperature to the indoor unit.

Return Air Sensor


implemented in the unit

Remote Sensor should be


installed when Return Air
Sensor cannot sense room
temperature correctly

BRC1E71 has a sensor


(BRC2A71 doesnt)

(Remote sensor physically


replace the Return Air
Sensor )
* Field setting: see slide 58 for details.

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 22

2005 Daikin AC

Skyair and Mini-split


Skyair* is connected to DIII-Net system directly
Recognized as VRV III-S system which has only one
indoor unit.
All objects are available.

Mini-split is connected to the DIII-Net system with an

optional adapter, KRP928BB2S


KRP928BB2S is connected to the indoor unit
If it is a multi system, each indoor unit has to have
KRP928BB2S.
Basic objects are available.
DIII-Net (Daisy Chained)
KRP928B2S
DIIInet Adapter

* Except for RXS30/36HVJU + FTXS30/36HVJU


which requires KRP928BB2S as same as Mini-split.
Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

FTXS/RX
RA System

Slide 23

2005 Daikin AC

Status LED

DIII-net #1
10 outdoor units
64 groups
128 indoor units

DIII-net #2
10 outdoor units
64 groups
128 indoor units

Option Board Slot


(DAM411B51)
for additional
two DIII-net lines

Ethernet
LED

DIII-net #1 & #2
Communication
LED

24 Volt
Power Supply
24v Com Gd

Not Used

* LED are good for


troubleshooting.
See slide 54, 55
for details.

VRV malfunction (Optional)

goes to Outdoor unit

Forced Off for


each DIII-net line
(Optional)

BACnet Interface Malfunction


(Optional)

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 24

2005 Daikin AC

Battery
backup
Turn ON

Alternative
Configuration
(Backup for
Ethernet)
Presentation Title : Presenter
Name : Date

Ethernet for BACnet


connection and
configuration

Daikin BACnet Interface DMS502B71 Programming Guide

Slide 25

2005 Daikin AC

Daikin BACnet Object List

One indoor unit has the following 26 objects

#15, 18
Celsius Only

Reserved
#17, 21
Available for each
DIII-Net system
#19
Accumulated Power
is not supported

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 26

2005 Daikin AC

Object ID Format
One indoor unit has the following 26 objects, highlighted
Object Type

0 - 5, 13, 14

Instance Number

0 - 255

Mapped with
DIII-Net system
and Group Address

1 - 14, 16, 17, 20 - 31


26 objects
per indoor unit

(See the previous page)

(See the next page)

Specify Indoor unit

Specify Object

Example
Setpoint of DIII-Net system 2 and Group address 1-2
Object type AV Object Number: 2
DIII-Net 2 & 1-2 A/C number: 66
Setpoint Member number: 10
Instance Number = 16,906 (0x420A) = (66 * 2^8) + (10)
Object ID = 8,405,514 (0x80420A) = (2 * 2^22) + Instance Number
Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 27

2005 Daikin AC

Air conditioner number


Air conditioner (Indoor unit) number (0 to 255) is mapped with the DIII-Net
System number (1 to 4) and Group Address (1-00 to 4-15)
Group
Addr.

A/C
Num.

DIIINet
System

Group
Addr.

A/C
Num.

1-00

1-00

64

128

192

1-01

65

1-01

129

1-00

1-00

1-01

1-01

193

(Port 2)

(Port 3)

(Port 4)

2-00

16

2-00

80

2-00

144

2-00

208

2-01

17

2-01

81

2-01

145

2-01

209
223

3-00

32

3-00

96

3-00

160

3-00

224

3-01

33

3-01

97

3-01

161

3-01

225

3-15

239

4-00

48

4-00

112

4-00

176

4-00

240

4-01

49

4-01

113

4-01

177

4-01

241

4-15

63

4-15

127

4-15

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

191

175

3-15

111

3-15

47

3-15

2-15

159

2-15

95

2-15

31

2-15

207

1-15

143

1-15

79

1-15

15

1-15

(Port 1)

DIIINet
System

A/C
Num.

Group
Addr.

DIIINet
System

A/C
Num.

Group
Addr.

DIIINet
System

4-15

255

Slide 28

2005 Daikin AC

Auto-discovery
Object list can be created with the Point List creation tool. See BACnet
Interface Design Guide. (See Slide 53)

The BMS will get all available objects from the Daikin BACnet interface by
reading the object list property in the Device object.

Cimetrics BACnet Explorer

Wireshark Network Analyzer

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 29

2005 Daikin AC

BACnet Control Points

(per DIII-net)

(per DIII-net)

* Increase internal setpoint +2C in cooling, and decrease -2C in


heating in an indoor unit. Actual setpoint is not changed.

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 30

2005 Daikin AC

BACnet Monitoring Points

Note: Monitor unit status by StartStopStatus_XXX not StartStopCommand_XXX.


Commands will not always match input status.

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 31

2005 Daikin AC

Typical Objects for Indoor Unit


Although a set of 26 objects for each indoor unit is available, you will use only some of them.
Object
type

Member
Number

StartStopCommmand_XXX

BO

StartStopStatus_XXX

BI

AirConModeCommand_XXX

MO

AirConModeStatus_XXX

MI

Room Temperature

RoomTemp_XXX

AI

Setpoint

TempAdjust_XXX

AV

10

AirFlowRateCommand_XXX

MO

AirFlowRateStatus_XXX

MI

AirDirectionCommand_XXX

AV

22

Item

Monitor
Status
(Read)

Control
(Write)
X

Unit On/Off
X

Operation mode

Fan Speed
X

Air Flow Direction

Object Name
(_XXX means A/C number)

(When indoor unit has a louver)

AirDirectionStatus_XXX

AI

23

Alarm Status

Alarm_XXX

BI

Malfunction Code

MalfunctionCode_XXX

MI

R/C On/Off button prohibit

RemoteControlStart_XXX

BV

13

R/C Ope. mode button prohibit

RemoteControlAirConModeSet_XXX

BV

14

R/C SP adjust button prohibit

X
X
RemoteControlTempAdjust_XXX
Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

BV

16
2005 Daikin AC
Slide 32

Malfunction Code
Decode Present value of Malfunction code to Daikin Error code
VRV Service manual provide
troubleshooting flow chart for each
Error code.
Example: Present Value 149 = U4 error

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 33

2005 Daikin AC

Optional Objects for Indoor Unit

The following objects are also available


Item

Air Filter Sign

Monitor
Status
(Read)

Control
(Write)

Air Filter Sign Reset

Object
type

Member
Number

FilterSign_XXX

BV

11

FilterSignReset_XXX

BV

12

Object Name
(_XXX means A/C number)

Communication Status

CommunicationStatus_XXX

BI

20

Call for Cool/Heat Status


(Thermo-on Status)

ThermoStatus_XXX

BI

28

Compressor Status

CompressorStatus_XXX

BI

29

Indoor Fan Status

IndoorFanStatus_XXX

BI

30

Heater Status

HeaterStatus_XXX

BI

31

ForcedThermoOFFCommand_XXX

BO

24

ForcedThermoOFFStatus_XXX

BI

25

EnergyEfficiencyCommand_XXX

BO

26

EnergyEfficiencyStatus_XXX

BI

27

Forced disable Call for


Coo/Heat (Forced
Thermo-off)

X
X

Energy Saving

X
X

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 34

2005 Daikin AC

Optional Objects for DIII-Net


The following objects are for the DIII-net system.
Assigned at Group address 1-00 on each DIII-Net
system. Therefore air conditioner numbers are 0, 64, 128
and 192.
Monitor
Status
(Read)

Control
(Write)

Central Control

Forced System Stop

Item

Object
type

Member
Number

CL_Rejection_XXX

BV

17

SystemForcedOff_XXX

BV

21

Object Name
(_XXX means A/C number)

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 35

2005 Daikin AC

Limitation of KRP928BB2S for Mini-split


11 essential objects are available for mini-split

Fan, Auto mode are not


available

Not available for On/Off


button prohibit
When Mode or Setpoint
button prohibit through
KRP928, On/Off button
will not be available on the
remote controller

#17, 21
Available for each DIII-Net
system

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 36

2005 Daikin AC

Available Objects Comparison


Member
Numer
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31

Point Name
ON/OFF (setting)
ON/OFF (status)
Alarm Sign
Error Code
Operation Mode (setting)
Operation Mode (status)
Airflow Rate (setting)
Airflow Rate (status)
Measured Room Temperature
Set Room Temperature
Filer Limit Sign
Filter Limit Sign Reset
Remote Control Operation (ON/OFF)
Remote Control Operation (Operation Mode)
Blank
Remote Control Operation (Set Temperature)
Central Control (lower Central Contoll disable)
Blank
Accumulated Power
Communication Status
System Forced OFF
Air Direction (setting)
Air Direction (status)
Forced Thermostat OFF (setting)
Forced Thermostat OFF (status)
Energy Efficiency Command (setting)
Energy Efficiency Command (status)
Thermostat Status
Compressor Status
Indoor Fan Status
Heater Operation Status

VRV, Skyair
indoor unit

Mini-Split through
KRP928BBS2

StartStopCommand_xxx
StartStopStatus_xxx
Alarm_xxx
MalfunctionCode_xxx
AirConModeCommand_xxx
AirConModeStatus_xxx
AirFlowRateCommand_xxx
AirFlowRateStatus_xxx
RoomTemp_xxx
TempAdjust_xxx
FilterSign_xxx
FilterSignReset_xxx
RemoteControlStart_xxx
RemoteControlAirConModeSet_xxx

X
X
X
X
X
X
X
X
X
X
X
X
X
X

X
X
X
X
X (Cool, Heat only)
X (Cool, Heat only)

RemoteControlTempAdjust_xxx
CL_Rejection_xxx

Object Name

ElecTotalPower_XXX
CommunicationStatus_xxx
SystemForcedOff_xxx
AirDirectionCommand_xxx
AirDirectionStatus_xxx
ForcedThermoOFFCommand_xxx
ForcedThermoOFFStatus_xxx
EnergyEfficiencyCommand_xxx
EnergyEfficiencyStatus_xxx
ThermoStatus_xxx
CompressorStatus_xxx
IndoorFanStatus_xxx
HeaterStatus_xxx

For DIII-Net

X
X

X
X

X
X
X
X
x
x
x
X
x
X

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 37

2005 Daikin AC

BMS just to Monitor or Control


VRV system would work with Remote Controllers. Not necessary to have additional
controller.
I-Touch Controller is beneficial as a centralized controller and gives some functions
such like setback schedule, auto changeover, setpoint range limitation, etc.
You may put BMS just monitor the VRV system. A

You may put BMS control the VRV system to satisfy control requirements, I-Touch
Controller might be installed as a backup controller in case that BMS and/or
network is in a trouble. B
Control function on I-Touch Controller might conflict the control from BMS, so
that it is recommended not to enable any I-TC control functions.

BACnet

DIII-Net

DIII-Net
BS Box

DMS502B71
BACnet Interface

BS Box

DCS601C71
Intelligent Touch
Controller

REYQ
VRVIII
Heat Recovery

Building Automation
System

BS Box

Which
controls the
VRV
system?

FXMQ

FXFQ

Concealed Ceiling

Ceiling Cassette

BMS

I-Touch Control

Monitor

Control VRV

Control VRV

Back up

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

FXAQ
Wall Mounted

BRC1E71
Navigation
Remote Controller

Slide 38

2005 Daikin AC

CL Rejection and DIII-Net for a Backup


Controller
When CL Rejection is enabled for a DIII-Net line, a lower

classified multi zone controller such like I-TC on the same


line is completely disabled.
Manual operations are no longer available
Any functions on I-TC would be disabled

I-TC would be resumed once CL Rejection is disabled, or

5 minutes after BACnet Interface is disconnected (or


powered off).
If BMS is disconnected keeping CL Rejection enabled,
M8 error would occur on I-TC in 5 minutes, and it is the
time when I-TC is resumed.

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 39

2005 Daikin AC

BMS to Satisfy Control Requirements


Setpoint Range Limitation on Remote Controller
Monitor and override setpoint when out of range.
Prohibit Remote Controller if necessary.
Limit Setpoint Range by iTouch or Navigation Controller. Cannot be adjusted through
BMS.

Auto Changeover
Indoor unit auto changes to cooling at 5.4F above the setpoint, and to heating at 3.6F
below the setpoint. Total 9F room temperature swing would occur theoretically.
BMS should control changeover when tighter control is necessary.
Mode change must be sent to changeover master. See the slide 16.

Setback Schedule
BMS should turn off the unit to enable setback.
BMS should turn the unit on when setback setpoints have been reached and turn the
unit off when room temperature has recovered.
Changing of occupied setpoints is not necessary.

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 40

2005 Daikin AC

BMS Setpoint Range Limit


80
79
78
77
76
75

Cool Setpoint Range

Cool Setpoint 74
73
72

Heat Setpoint 71
70

Heat Setpoint Range

69
68
67
66
65

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 41

2005 Daikin AC

BMS Setpoint Range Limit


Sequence of Operation
Points Used TempAdjust_XXX
Control Logic
BMS shall monitor temperature setpoint. When BMS detects point
out of range, it shall override the setpoint to acceptable value.
To detect setpoint change by a end user in a timely fashion, COV
would be considered. (COV is disabled at factory default)

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 42

2005 Daikin AC

BMS Autochangeover - Dual Setpoint


Unit Turned On (Occ)

Unit Turned Off (Unocc)

80
79
78
77

HeatCool 76
Changeover Point 75
Cool Setpoint 74
73
72

Heat Setpoint 71
CoolHeat 70
Changeover Point 69
68
67
66
65

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 43

2005 Daikin AC

BMS Autochangeover - Dual Setpoint


Sequence of Operation
Points Used RoomTemp_XXX, AirConMode_XXX, TempAdjust_XXX
Control Logic
BMS shall monitor space temperature and temperature setpoint.
When space temperature rises to 1oF (adj.) above cooling setpoint, BMS
shall command the unit into cooling and command a new setpoint.
When space temperature drops to 1oF (adj.) below heating setpoint, BMS
shall command the unit into heating and command a new setpoint.
* When using independent cooling and heating setpoints, the new setpoint
must be communicated with every mode change as both heating and
cooling setpoint memory locations are simultaneously overwritten when
TempAdjust_XXX command is used. A 1 hour guard timer is recommended
with this sequence to prevent excessive mode changeovers.

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 44

2005 Daikin AC

BMS Autochangeover Single Setpoint


Unit Turned On (Occ)

Unit Turned Off (Unocc)

80
79
78
77
76

Changeover - Immediate 75
Changeover - 30 min delay (adj.)
Setpoint

74
73
72
71

Changeover - 30 min delay (adj.) 70


Changeover - Immediate 69
68
67
66
65

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 45

2005 Daikin AC

BMS Autochangeover Single Setpoint


Sequence of Operation
Points Used RoomTemp_XXX, AirConMode_XXX, TempAdjust_XXX
Control Logic
BMS shall monitor space temperature and temperature setpoint.
When space temperature rises to 2oF (adj.) above cooling setpoint and
maintains for 30 min, BMS shall command the unit into cooling. When space
temperature rises to 3oF (adj.) above setpoint, BMS shall command the unit
into cooling.
When space temperature drops to 2oF (adj.) below heating setpoint and
maintains for 30 min, BMS shall command the unit into heating. When space
temperature drops to 3oF (adj.) below setpoint, BMS shall command the unit
into heating.
* Commanding of new setpoints is not necessary. A 1 hour guard timer is
recommended with this sequence to prevent excessive mode changeovers.
Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 46

2005 Daikin AC

BMS Setback
Unit Turned On (Occ)

Unit Turned Off


(Unocc)

80
79
78
77

Setback

BMS turn on
the unit when
necessary

HeatCool 76
Changeover Point 75
Cool Setpoint 74
73
72

Heat Setpoint 71
CoolHeat 70
Changeover Point 69
68
67
66
65

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Setback

Slide 47

2005 Daikin AC

BMS Setback
Sequence of Operation
Points Used RoomTemp_XXX, StartStopCommand_XXX
Control Logic
BMS shall energize the unit once setback setpoints have been
reached. Unit shall try and control to occupied setpoints.
BMS shall de-energize the unit once temperature has dropped
(when cooling) or risen (when heating) the set differential which is
adjustable.

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 48

2005 Daikin AC

Notes to program
C/F conversion
Since Daikin BACnet Interface supports Celsius only, so that you may
have to make conversion program if BMS doesnt support it natively.

EEPROM
Every change you made will be transferred to an Indoor unit.
The Indoor unit stores the latest setting in EEPROM which has the

maximum writable number of 100,000 times. With this, the indoor unit will
resume with the previous setting from power failure.
Do not change anything frequently and you will be ok. Keep below 19
average per day.

Priority Array
An object in the BACnet Interface has a priority array, so that the highest
priority value would be transferred to the indoor unit.
The indoor unit doesnt have priority. The last change would be valid in
the indoor unit either from BACnet Interface or Remote Controller.
Releasing BMS value by sending a NULL command will revert point to
default settings stored in the gateway of 25oC (77oF).

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 49

2005 Daikin AC

Foreign Device
When BACnet Interface is in a different subnet from BMS,
a BBMD is required and should register BACnet Interface
as a Foreign Device.

BACnet Interface should also be configured as a Foreign


Device and set BBMD IP address and port No.

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 50

2005 Daikin AC

ITC V6
When you install ITC V6 as a backup controller, disable all controls
such as schedule, setpoint range limitation, and auto changeover.
Also configure it as a Single Setpoint Mode
Set Min. C/H setpoint differential to 0* (single setpoint mode)
Otherwise when BMS change the mode, ITC would change the
setpoint because ITC manages individual C/H setpoints.

Or enable CL Rejection, and ITC control is disabled.


Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 51

2005 Daikin AC

Q&A
Q. What changes can be globally applied vs. individually applied?
A. SystemForcedOff_XXX and CL_Rejection_XXX can be applied globally.
Q. Can the BACnet gateway be configured to report temperature values in oF?
A. No. The BACnet interface can only handle values in oC.
Q. What ASHRAE std. does the BACnet gateway comply with? Is the gateway BTL certified?
A. The Daikin BACnet Interface was designed per ASHRAE std. 135-2004 and BTL certified in 2007.
Q. How to execute Gateway self-discovery? Capability of this function? Limitations?
A. The BMS will get all available objects from the Daikin BACnet interface by reading the object list
property in the Device object. Allows for less potential for error as manual command which can require
matching up Port Number, Object ID, and Instance Number for each point. No limitations that Im aware of.
Q. Most efficient way to address indoor units?
A. Units must be addressed individually at the remote controller. There is currently no auto-addressing
capability.
Q. Must mode changes be done unit by unit or can they be done globally?
A. Unit by unit (or units in remote control group).
Q. Can the BACnet gateway be set up as a BACnet Broadcast Management Device (BBMD)?
A. No, however it can be setup as a foreign device to communicate directly with a BBMD on a different
subnet.
Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 52

2005 Daikin AC

BACnet Interface DMS502B71- Online Documentation


Installation Manual
http://www.daikinac.com/DOC/BACnet%20Gateway%20DMS502B71%20

-%20Installation%20Manual%20-%20Daikin.pdf
Design Guide
http://www.daikinac.com/DOC/BACnet%20Gateway%20DMS502B71%20
-%20%20Design%20Guide%20-%20ED72-749A%20-%20Daikin.pdf
Protocol Implementation Conformance Statement (PICS)
http://www.daikinac.com/commercial/documents/BACnet%20gateway%2
0PICS%20statement%20Ver%206.20%20-%20Daikin.pdf
Submittal Data Sheet
http://www.daikinac.com/commercial/documents/sds/SDS%20DMS502B7
1.pdf
BTL Product Listing
http://www.bacnetinternational.net/btl/index.php?m=29

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 53

2005 Daikin AC

Extracted from
BACnet Interface
Design Guide

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 54

2005 Daikin AC

Extracted from
BACnet Interface
Design Guide

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 55

2005 Daikin AC

For Indoor unit


Fan Control

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 56

2005 Daikin AC

For Indoor unit


Fan Control

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 57

2005 Daikin AC

BRC1E71 sensor Only - Field Settings


To use only BRC1E71 sensor, set field settings as 10-2-03, 10-5-02 & 1C-1-02
To use Return air sensor or Remote sensor, set as 10-2-02, 10-5-01 & 1C-1-01
10-2-03, 10-5-02 availability
FXMQ_P, FXTQ_P, FTQ_P: always available
All _M series (except FXFQ, FXHQ, FCQ, FHQ)
Manufactured after 9/1/2009: always available
Manufactured before 9/1/2009: confirm if 10-2-03, 10-5-02 are available.
FXFQ, FXHQ, FCQ, FHQ: never available
Set 10-2-01 and use Remote sensor (or Return air sensor) only
Which single sensor
is used?

For indoor unit control


(Cool/Dry/Heat VRV and
thermo-on/off control)

For BRC1E71 control


(Auto changeover and
setback control)

(Which sensor temperature is sent


to Mulizone Controller such as
BACnet Interface and I-TC)

BRC1E71 sensor

10-2-03

1C-1-02 (default)

10-5-02

Remote sensor
(or Return air sensor)

10-2-02
(it is always available)

1C-1-01

10-5-01 (default)

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

For Multizone Control

Slide 58

2005 Daikin AC

Appendix

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 59

2005 Daikin AC

Functionality
BMS vs. iTouch / BRC1E71

Autochangeover
Setback
Setpoint Range Limit
Scheduling
Button Prohibit

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 60

2005 Daikin AC

iTouch / BRC1E71
Autochangeover, Setback, and Setpoint Range Limit
Unit Turned On (Occ)

Unit Turned Off (Unocc)

80

Setback

79
78
77

HeatCool 76
Changeover Point 75
Cool Set-point 74
73
72

Heat Set-point 71
CoolHeat 70
Changeover Point 69
68
67
66
65

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Setback

Slide 61

2005 Daikin AC

iTouch / BRC1E71
Sequence of Operation
Auto Changeover (BRC1E71) When in heating mode, changeover to cooling
mode shall occur at cooling setpoint + 1oF. When in cooling mode,
changeover to heating mode shall occur at heating setpoint 1oF.
Setback When the unit is off during the unoccupied period, it shall energize
once setback setpoints have been reached and de-energize once
temperature has dropped (when cooling) or risen (when heating) the set
differential which is adjustable.
Setpoint Range Limit Individual cooling and heating setpoints can be bound
by setpoint range limit between 60oF and 90oF.

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 62

2005 Daikin AC

iTouch / BRC1E71 Scheduling


Three weekly schedule pattern options are available: 7-Day, 5+2 (Weekday +
Weekend), and 5+1+1 (Weekday + Saturday + Sunday).
BRC1E71: Supports up to 5 On/Off operations per day, 1 Schedule
iTouch: Supports up to 8 On/Off operations per day, 8 Schedules, 4 Exception
Schedules

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 63

2005 Daikin AC

Open Protocol Solutions


Gateways to Open Protocol Networks
Vendor neutral control for Daikin air conditioning products
DMS502B71

DMS504C71

BACnet Interface

LonWorks Interface

Communications

BACnet IP Data Link Layer (Annex J)

LonTalk Protocol

Connectivity (Network)

FT-X1 (78Kbps Free Topology)

VRV outdoor unit quantity

10/100 BASE-T Ethernet


DIII-Net x 2 channels
Another 2 channels with DAM411B51
Option
20 40 with DAM411B51 Option

VRV indoor unit quantity

128 256 with DAM411B51 Option

64

Monitor & control VRV indoor units


24 VAC 50/60Hz

Monitor & control VRV indoor units


24VAC 50/60Hz

VRV (All Unit Types and Sizes)


SkyAir
Single Split Systems*
Multi Split Systems*

VRV (All Unit Types and Sizes)


SkyAir
Single Split Systems*
Multi Split Systems*

Connectivity (Daikin)

Control points
Power supply
Applicable Daikin products
*KRP928B2S DIII-net adapter required.

DIII-Net x 1 channel
10

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 64

2005 Daikin AC

Status LED

Service Switch

F1 F2 goes to outdoor unit

24V + ground

T1 T2 Forced system shut down


Presentation
Title
: Presenter
Name : DateTwisted
pair to LonGuide
connection
Daikin
BACnet
Interface
DMS502B71
Programming

Slide 65

2005 Daikin AC

Battery Backup
Switch

Cable connection for


commissioning

Cable provided by
commissioning agent
DLS-CABLE-9PIN

Terminal Resistance
No resistance (factory default),
52.5, or 105 ohms

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 66

2005 Daikin AC

LonWorks SNVT List

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 67

2005 Daikin AC

Network Variables

Presentation
Title
: Presenter
Name : Date Programming Guide
Daikin
BACnet
Interface
DMS502B71

Slide 68

2005 Daikin AC

Thank You .