HVDC For Beginners PDF
HVDC For Beginners PDF
HVDC For Beginners PDF
Stafford
UK
France
USA
Germany
1962
1968
1989
English
Electric
GEC
GEC Alsthom
1996
1998
2004
Alstom AREVA
CGEE - Alsthom
GE
HVDC for beginners and beyond (C) Copyright AREVA T&D UK Limited, September 2009
PREFACE
This booklets contents is intended to fill a gap in the available
literature between the very basic introductory material generally
available from suppliers and the more academic analysis of HVDC
presented in text books. This booklet is therefore aimed at those who
wish to gain a better understanding of the complex systems which
are now forming an integral part of power transmission in the world
today, a trend which will only increase.
In recent years the technology of HVDC transmission using power
transistors known as Voltage Source Converter (VSC) has been
introduced into the market. Whilst sharing some commonality with Line
Commutated Converter (LCC) HVDC in terms of the asynchronous nature
of the interconnection and the benefits it can bring to the AC system the
technology differs in several ways. In order to avoid any confusion with
VSC technology this booklet focuses on LCC HVDC only.
The first three chapters of the booklet provide an introductory
overview of the subject of LCC HVDC, covering usage, configurations
and basic operating principles. Chapter 4 contains more detailed
examination of the main equipment of a HVDC converter station
and chapter 5 discusses the layout of this equipment within the
converter station. Chapters 6 and 7 review the operation of a HVDC
converter and its control. Chapter 8 provides an introduction to static
characteristics and introduces the concept of superposition of AC
quantities onto the characteristics.
An important design consideration of an LCC HVDC scheme relates
to the reactive power loading that a HVDC converter station imposes
on the network to which it is connected and this is reviewed in
chapters 9 through to 13.
Chapter Title
INTRODUCTION TO HVDC
HVDC CONFIGURATIONS
WHAT IS HVDC?
Page
6
7
10
13
STATION LAYOUT
19
23
28
STATIC CHARACTERISTICS
30
33
10
34
36
12
37
13
38
39
15
40
16
41
17
42
18
DC HARMONICS
45
19
46
20
48
52
22
55
23
57
24
61
25
63
65
67
28
68
29
69
30 REFERENCES
83
84
6 HVDC
for beginners and beyond
1 INTRODUCTION TO hvdc
Electrical power is generated as an alternating current (AC). It is also transmitted and distributed as
AC and, apart from certain traction and industrial drives and processes, it is consumed as AC.
In many circumstances, however, it is economically and technically advantageous to introduce direct
current (DC) links into the electrical supply system. In particular situations, it may be the only feasible
method of power transmission. When two AC systems cannot be synchronized or when the distance
by land or cable is too long for stable and/or economic AC transmission, DC transmission is used. At
one converter station the AC is converted to DC, which is then transmitted to a second converter
station, converted back to AC, and fed into another electrical network. In back-to-back HVDC
schemes the two converter stations are brought under the same roof, reducing the DC transmission
length to zero.
HVDC transmission applications fall into four broad categories and any scheme usually involves a
combination of two or more of these. The categories are:
i) Transmission of bulk power where AC would be uneconomical, impracticable or subject to
environmental restrictions.
ii) Interconnection between systems which operate at different frequencies, or between nonsynchronized or isolated systems which, although they have the same nominal frequency, cannot
be operated reliably in synchronism.
iii) Addition of power infeed without significantly increasing the short circuit level of the receiving
AC system.
iv) Improvement of AC system performance by the fast and accurate control of HVDC power.
7 HVDC
for beginners and beyond
2 HVDC CONFIGURATIONS
2.1
8 HVDC
for beginners and beyond
This is a very common arrangement with the following
operational capabilities:
During
2.3
Figure 2.4: Bipolar System with
Monopolar Metallic Return for Pole
Outage
9 HVDC
for beginners and beyond
converter unit, and the valves for both converters may
be located in one valve hall. The control system, cooling
equipment and auxiliary system may be integrated into
configurations common to the two converters. DC filters
are not required, nor are electrodes or electrode lines, the
neutral connection being made within the valve hall. It is
important to note that AREVA T&D has developed a solution
for a back-to-back HVDC link which does not require a
smoothing reactor, hence, there is no external DC insulation
[3]. Figure 2.5 shows two different circuit configurations
used by AREVA T&D for back-to-back HVDC links.
10 HVDC
for beginners and beyond
3 WHAT IS HVDC?
A simple representation of a HVDC interconnection is
shown in Figure 3.1. AC power is fed to a converter operating
as a rectifier. The output of this rectifier is DC power, which
is independent of the AC supply frequency and phase. The
DC power is transmitted through a conduction medium;
be it an overhead line, a cable or a short length of busbar
and applied to the DC terminals of a second converter.
This second converter is operated as a line-commutated
inverter and allows the DC power to flow into the receiving
AC network.
11 HVDC
for beginners and beyond
12 HVDC
for beginners and beyond
AC Harmonic Filter
(Double frequency)
DC
Reactor
DC Voltage
Measurement
DC Harmonic
Filter
DC Pole 1
HV Line
Connection
Valve
Converter Pole
Breaker
HF Filter
Quadri
-valve
H
F
AC
System
DC Current
Measurement
G.R.T.S
N.B.S
N.B.G.S
Electrode
Connection
AC
System
M.R.T.B
H
F
DC Pole 2
HV Line
Connection
13 HVDC
for beginners and beyond
AC
System
Converter
Filter
Filter
Converter
Converter
AC
System
Filter
Filter
AC Switchyard
14 HVDC
for beginners and beyond
Converter
Converter
AC
System
Filter
4.2
Filter
AC Harmonic Filters
15 HVDC
for beginners and beyond
the converter bus and the converter in order to limit the interference that can
propagate into the AC system.
Converter
As with the AC harmonic filter, the HF filter comprises a high voltage connected
capacitor bank, an air-core air-insulated reactor and an additional low voltage
circuit composed of capacitors, reactors and resistors which are referred to as
a tuning pack.
4.4
Converter Transformer
Converter
AC
System
Filter
Filter
The converter transformer is the interface between the AC system and the
thyristor valves. Typically the HVDC converter transformer is subjected to a DC
voltage insulation stress as well as the AC voltage stress normally experienced
by a power transformer. These AC and DC stresses are fundamentally different.
The AC voltage stress is predominantly in the insulating oil and defined by the
geometry and permittivity of the materials, whilst the DC stress is governed
by the resistivity of the insulating materials which, in turn, vary with operating
conditions. In addition, it is important that the converter transformer be thermally
designed to take into consideration both the fundamental frequency load and
the AC harmonic currents that will flow from the converter through the converter
transformer to the AC harmonic filters.
Typically, the converter transformer is arranged as an earthed star-line winding
and a floating-star and delta secondary windings. There is normally an on-load
tapchanger on the line winding.
4.5
Converter
16 HVDC
for beginners and beyond
4.6
DC Smoothing Reactor
Filter
Filter
Converter
DC Filter
DC Switchgear
17 HVDC
for beginners and beyond
Interruption of fault events is done by the controlled action of the converter and therefore, with the
exception of the NBS, does not require switchgear with current interruption capability.
Where more than one HVDC Pole share a common transmission conductor (typically the neutral)
it is advantageous to be able to commutate the DC current between transmission paths without
interrupting the DC power flow. Figure 4.1 shows a typical Single Line Diagram (SLD) for a HVDC
transmission scheme utilizing DC side switchgear to transfer the DC current between different paths
whilst on load. The following switches can be identified from Figure 4.1.
NBGS - Neutral Bus Ground Switch
This switch is normally open but when closed it solidly connects the converter neutral to the
station earth mat. Operation with this switch can normally be maintained if the converter
can be operated in a bipole mode with balanced currents between the poles, that is, the
DC current to earth is very small. The switch is also able to open, commutating a small DC
unbalance current out of the switch and into the DC circuit.
A NBS is in series with the neutral connection of each pole. In the event of an earth fault on
one pole, that pole will be blocked. However, the pole remaining in service will continue to
feed DC current into the fault via the common neutral connection. The NBS is used to divert
the DC current away from the blocked pole to ground.
The connection between the HVDC conductor and the neutral point includes both a high
voltage disconnector and a GRTS and is used as part of the switching operation to configure
the HVDC scheme as either a ground return monopole or a metallic return monopole. The
disconnector is maintained open if the HV conductor is energized in order to isolate the
medium voltage GRTS from the high voltage. The GRTS is closed, following the closing of
the disconnector in order to put the HV conductor in parallel with the earth path. The GRTS
is also used to commutate the load current from the HV conductor transferring the path to
the earth (or ground return) path. Once current flow through the HV conductor is detected
as having stopped, the disconnector can be opened, allowing the HV conductor to be reenergized at high voltage.
18 HVDC
for beginners and beyond
MRTB - Metallic Return Transfer Breaker
The MRTB is used in conjunction with the GRTS to commutate the DC load current between
the earth (ground return) and a parallel, otherwise unused, HV conductor (metallic return).
The MRTB closes in order to put the low impedance earth return path in parallel with the
metallic return path. The MRTB must also be able to open, causing current flowing through
the earth return to commutate into the much higher impedance metallic return path.
4.9
DC Transducers
DC connected transducers fall into two types, those measuring the DC voltage of the scheme and
those measuring the DC current.
DC voltage measurement is made by either a resistive DC voltage divider or an optical voltage divider.
The resistive voltage divider comprises a series of connected resistors and a voltage measurement
can be taken across a low voltage end resistor which will be proportional to the DC voltage applied
across the whole resistive divider assembly. Optical voltage transducers detect the strength of the
electric field around a busbar with the use of Pockel cells.
DC current measurement for both control and protection requires an electronic processing system.
Measurement can be achieved by generating a magnetic field within a measuring head which is
sufficient to cancel the magnetic field around a busbar through the measuring head. The current
required to generate the magnetic field in the measuring head is then proportional to the actual
current flowing through the busbar. Devices using this method are commonly known as Zero Flux
Current Transducer (ZFCT).
Optical current measurement makes use of, amongst others, the Faraday effect in which the phase
of an optical signal in a fibre optic cable is influenced by the magnetic field of a busbar around which
the cable is wound. By measuring the phase change between the generated signal and the signal
reflected back from the busbar, the magnitude of the current can be found.
19 HVDC
for beginners and beyond
5 STATION LAYOUT
The converter station is normally split into two areas:
AC Switchyard
Converter Island
In modern HVDC converter stations, the thyristor valves are almost always located indoors in a
purpose built enclosure known as a valve hall. This enclosure provides a clean, controlled environment
in which the thyristor valves can safely operate without the risk of exposure to pollution or outdoor
conditions.
20 HVDC
for beginners and beyond
Figure 5.1: Lindome, Sweden,
Converter Station Layout; Part of
the 380 MW KontiSkan HVDC
Interconnection
420 kV AC busbars
285 kV DC lines
Converter Transformers
AC filters
DC filters
Outdoor Valve
Cooling System
Thyristor Valves
Valve Cooling System
Control Building
Converter Transformers
Smoothing Reactor
AC Filters
21 HVDC
for beginners and beyond
Within the valve hall, the thyristor valves are typically suspended from the roof of the building with
the low voltage being closest to the roof and the high voltage being at the lowest point on the
valve. An air gap between the bottom of the valve and the valve hall floor provides the high voltage
insulation.
The valve hall has an internal metal screen covering all walls, the roof and the floor. This screen creates
a Faraday cage in order to contain the electromagnetic interference generated by the thyristor valve
operation. The integrity of this screen is typically maintained by having the valve connection side
converter transformer bushings protruding into the valve hall and connecting the bushing turrets to
the building screen.
The DC switchyard varies widely in complexity and physical arrangement between projects. For
outdoor DC areas, the majority of the equipment (disconnectors, earth switches, transducers, etc.)
is typically mounted on structures to create a walk-around area with only the DC filter, if present,
ground mounted within a fenced-off area. However, where sound shielding is required around the
DC reactor, this may be ground mounted with the sound shielding in the form of separate walls or an
enclosure, also forming the safety barrier. When the DC area is located indoors, it is more common
to have the majority of the equipment mounted at ground level in order to avoid an excessive height
requirement for the building. In such circumstances, access to the whole, or parts of, the DC area is
controlled by a fenced-off enclosure.
The control and services building is also located on the converter island. This building generally
contains equipment rooms such as:
ontrol room
C
Cooling plant room
Auxiliary supplies distribution
Batteries
Workshop
Offices
5.3
Acoustic Noise
Invariably there are requirements resulting from local environmental rules related to the acoustic
noise any substation (or other industrial site) can generate at either its boundary or at the nearest
property. Much of the equipment in an HVDC converter station generates acoustic noise when
operating and therefore careful consideration is required in terms of equipment layout in order to
minimize the acoustic noise at the point of measurement.
22 HVDC
for beginners and beyond
Typical acoustic noise sources within a converter station (measured as sound power (P)) are:
As an approximation, the acoustic noise sound pressure (L(A)) from any individual point source,
at a distance from the component is calculated as follows:
L() = P - 20 x Log10 - 8
where,
L() = the sound pressure at a distance (in metres).
P = the acoustic sound power of the point source (dB(A)).
= the distance from the point source at which the sound pressure is to be calculated
(in metres).
In order to meet the boundary, or nearest residence, acoustic noise limit, it may be necessary to
add acoustic noise barriers or to modify the equipment itself. The barriers may take the form of
walls or enclosures.
23 HVDC
for beginners and beyond
Ld
La
D1
Ia
Lb
D3
D5
Ib
Lc
6.1
Id
Vd
Ic
D4
D6
Vc
Va
Vd
Vb
2
D2
Id
Commutation
24 HVDC
for beginners and beyond
2.EL(RMS)
+/6
Vdio = 1
/3
-/6
+/6
-/6
-/6
6.3
wt
+/6
Vc
Va
Vd
Vb
2
25 HVDC
for beginners and beyond
Ld
La
Lb
Lc
T1
Ia
T3
Id
T5
= 180 - -
Ib
Vd
Lc
T4
T2
T6
Id
6.5
Vc
Direct
Voltage
Va
Vd
Vb
2
26 HVDC
for beginners and beyond
1
3
C
Vd = 0
A
- Vd
3
1
27 HVDC
for beginners and beyond
Single Phase
Three-winding
Transformers
B
AC
Switchyard
28 HVDC
for beginners and beyond
Id = V Rectifier - V Inverter
Rd
Under normal, steady-state operation, the inverter control
system is normally arranged to maintain the DC voltage at a
certain point on the HVDC link (known as the compounding
point) at a target value. This target value is typically 1.0 pu
for a transmission scheme but for back-to-back schemes,
where the DC transmission losses can be ignored, this
value can be varied to provide a further degree of reactive
power control. The compounding point is usually at the
rectifier DC terminal and hence the inverter must calculate
this voltage based on the DC voltage at the inverter
terminals, the DC current and the known resistance of the
transmission circuit (this latter quantity being measurable
by the HVDC controller if telecommunications between the
rectifier and the inverter are available). The rectifier normally
controls the DC current flowing in the circuit and does this
by adjusting its output DC voltage to give a current flow as
described by the above equation.
There are a number of ways that a six-pulse converter can
be controlled in a HVDC link.
29 HVDC
for beginners and beyond
For a rectifier the control options are:
onstant valve winding voltage control With this method of control, the converter transformer
C
tapchanger is used to maintain the voltage applied to the AC terminals of each six-pulse bridge
to a constant target value. Control of the current is then achieved by variation in converter
operating angle.
Constant firing angle range control With constant valve winding voltage control, the firing
angle at lower power transmission levels can be large. To reduce the range over which the firing
angle can operate in the steady state, the converter transformer tapchanger can be used to vary
the applied AC voltage to the six-pulse bridge and hence limit the range over which the firing
angle operates.
onstant valve winding voltage control This is the same as the equivalent rectifier control.
C
Constant gamma angle range control This is similar to the rectifier constant firing angle range
control but acts on the inverter extinction angle instead of the firing angle.
Constant extinction angle control (CEA) With this method of control, the inverter DC voltage
is allowed to vary in order to achieve a constant extinction angle with varying DC current. The
inverter converter transformer tapchanger is used to adjust the applied AC terminal voltage in
order to maintain the DC voltage to within a fixed, steady-state, range.
30 HVDC
for beginners and beyond
8 STATIC CHARACTERISTICS
Id
3 x x Lc
Vd
Vdio x cos()
Vd = Vdio x cos() - 3 x x Lc Id
However, with these static characteristics, as can be seen in Figure 8.4, if the
AC voltage applied to the rectifier falls then there are multiple crossover points
between the rectifier and the inverter. Hence, the operating point cannot be
determined. To overcome this, the basic converter characteristics are modified
in order to control the way that the converters respond during transient events.
An example of a practical characteristic is shown in Figure 8.5. Note that in
Figure 8.5 the constant current characteristic of the inverter is at a lower DC
current than the constant current characteristic of the rectifier. Under normal
operation, the inverter controls the DC voltage and the rectifier controls the
31 HVDC
for beginners and beyond
= Constant
= Constant
= Constant
= Constant
Rectifier
= Constant
1.0
= Constant
Inverter
Imargin
1.0
Id
DC current. However, if the AC terminal voltage at the rectifier falls such that
the rectifier characteristic shown in Figure 8.5 crosses the inverter constant
current characteristic, then the inverter will maintain the DC current at this level
with the DC voltage being dictated by where the rectifier characteristic crosses
the inverter constant current characteristic. The margin between the rectifier
constant current characteristic and the inverter constant current characteristic
is known as the current margin.
Some dynamic characteristics can be superimposed on the static characteristic
as shown in Figure 8.6. For example, a curve of constant real power can be
superimposed indicating the required DC current for a given change in DC
voltage to maintain the rectifier DC terminal power. Another characteristic that
can be superimposed is one of constant reactive power. If the operating point
were to be maintained along the reactive power curve, then at any point the
reactive power absorbed by the converter would remain constant. Consequently,
if there is a reduction in, for example, the rectifier AC system, then, by following
an approximately constant reactive power curve, the change in reactive power
at the inverter terminal is minimized, even though there is a change in real
power. Consequently, the converter bus voltage at the inverter would remain
approximately constant.
32 HVDC
for beginners and beyond
= Constant
= Constant
33 HVDC
for beginners and beyond
9 REACTIVE POWER IN AC
SYSTEMS
Reactive power is inherent within all AC power systems. It is a quantity that results from the stray
capacitance and inductance within all elements of the power system. Its effect is to shift, in phase,
the current AC waveform with respect to the voltage AC waveform hence reducing the instantaneous
value of voltage multiplied by current. In order to assess the effect of this phase shift, the AC power
is considered as two components; the Real power which results from the in-phase component of
voltage and current and the out-of-phase component of voltage and current which is referred to as
Reactive power.
Reactive power can either be leading, that is the current waveform is phase advanced with respect
to the voltage waveform, or lagging, that is the current waveform is phase delayed with respect to
the voltage waveform. In HVDC systems, it is conventional to consider leading reactive power as
a source or generator of reactive power and lagging reactive power as a load or absorber
reactive power. Hence, reactive power resulting from capacitance is generated and reactive power
resulting from inductance and from the converter is absorbed.
An AC network is composed of generators, VAr compensators, transmission lines and various
inductive and capacitive loads. Reactive power flow through the AC system results in voltage variation
between busbars. When any additional reactive power source or load is connected to a busbar within
the AC system, the variation in voltage at both that busbar and interconnected busbars should still
be maintained within the steady-state limits. Therefore, there is always a limit to the reactive power
that can be connected to a busbar.
34 HVDC
for beginners and beyond
Converters are a reactive power load as they operate with a delay firing angle which leads to a
situation where the current lags the voltage. In addition, the converter transformer impedance (plus
the small valve impedance) introduces an additional lag in the current which is observed as the
overlap angle.
The converter operating overlap angle is a function of the operating current and the converter
transformer leakage reactance:
-1
= cos
cos() - Id x p -
Id0
cos = x [cos()+cos(+)]
Hence the reactive power absorption is approximately:
Where,
Qdc0 = the reactive power absorption of the converter at rated DC current (pu).
35 HVDC
for beginners and beyond
Vc
Vb
Converter Line Current
-30
30
60
90
120
150
180
210
Ia
Va
Fundamental Component
Converter Line Current
= 16
Va
Ia
( + ) = 68
Va
Ia
( + ) = 90
Va
Ia
( + ) = 165
Va
Ia
36 HVDC
for beginners and beyond
11 REACTIVE POWER
SOURCES WITHIN A
CONVERTER STATION
C1
C2
L1
R1
L2
R2
The main sources of capacitive (positive) reactive power in a HVDC station are the AC harmonic
filters. Harmonic filters have two purposes: reducing the harmonics injected into the AC system and
generating reactive power. An AC filter is composed of capacitances, inductances and resistances
but at fundamental frequency the HV-connected capacitor is the main contributor to the reactive
power generated.
Q filter = f (C, V)
Figure 11.1: The Single Line Diagram
of a typical AC Harmonic Filter
Lindome AC Filters
37 HVDC
for beginners and beyond
12 CONTROLLING CONVERTER
REACTIVE POWER
Control action on the converter can be used to modify the reactive power
exchange with the AC system. In a HVDC scheme, the DC power is defined as:
DC Power = DC Voltage x DC Current
Filter switching
P
100
DC Power (%)
100
Hence, for a given DC power level the voltage can be reduced and the current
proportionately increased at the expense of additional IR transmission
losses. Therefore, if the number of filters energized to meet AC harmonic
filter performance exceeds the reactive power exchange limits, the converter
operating conditions can be changed to increase the reactive power absorbed
by the converter in order to achieve the desired exchange target between the
converter station and the AC system.
The change in DC conditions is achieved by lowering the DC voltage which
requires the firing delay angle to be increased and with an increase in DC
current, to maintain the DC power constant, the overlap angle increases, hence
the reactive power absorbed by the converter increases. It must be noted that,
as the DC side of the converter is common to the rectifier and inverter, changing
the DC conditions will reduce, or increase, the reactive power load at both
rectifier and inverter together. Figure 12.2 shows a typical operating range for
the DC voltage on a back-to-back HVDC converter.
In Figure 12.2 the upper limit is defined by the minimum allowable operating
angles of the converter whilst the lower limit is defined by the maximum voltage
transient that can be applied to the converter resulting from the firing voltage of
a rectifier or recovery voltage of an inverter.
38 HVDC
for beginners and beyond
Where:
V
= the change in AC voltage (p.u.)
SCLmin = the minimum Short Circuit Level of the AC system in which the switching operation is
to take place (MVA)
QSWITCH = the reactive power step to be imposed on the AC system (MVAr)
QTOTAL = the total reactive power connected to the converter bus including the reactive power to
be switched (MVAr)
Where the step change in AC voltage exceeds a defined limit, it is possible to increase the effective
limit by imposing an opposite change in reactive power at the converter busbar. This opposite
change can be achieved through converter action by applying a fast change to the DC voltage whilst
maintaining the DC power as discussed in Section 12 above. As an example, consider switching in
a filter onto an AC system that has a fundamental frequency var rating, which would exceed the AC
voltage step change limit. By increasing the DC converter absorption at the same instant as the filter
bank circuit breaker closes, the net reactive power exchanged with the AC system can be controlled
and hence the step change in AC voltage.
39 HVDC
for beginners and beyond
14 EFFECTS OF HARMONICS
IN AC POWER SYSTEMS
40 HVDC
for beginners and beyond
15 SOURCES OF HARMONICS
IN AC POWER SYSTEMS
All equipment that includes a non-linear element and is connected to a power system can result
in the generation of harmonics as a consequence of either its design or its operation. Examples of
harmonics sources within a Power System are:
Planning Limit
Harmonic Distortion %
27/06/2004
00:00
28/06/2004
00:00
29/06/2004
00:00
30/06/2004
00:00
01/07/2004
00:00
02/07/2004
00:00
03/07/2004
00:00
04/07/2004
00:00
05/07/2004
00:00
41 HVDC
for beginners and beyond
42 HVDC
for beginners and beyond
The main components of a typical HVDC converter terminal are shown in Figure
17.1. The action of the thyristor sequential switching results in current waveforms
in the line side of the transformer which consists of blocks of current as shown
in Figure 17.2.
If a Fourier analysis is performed on the idealized waveforms shown in Figure
17.2, the following results are obtained:
1)
Y/Y
It can be seen from equations (1) and (2) that each six-pulse bridge generates
harmonic orders 6n 1, n = 1, 2, 3 ..., there are no triplen harmonics (3rd, 6th,
9th...) present and that for n = 1, 3, etc., the harmonics are phase shifted by 180.
The idealized magnitudes of the six-pulse harmonics are shown in Table 17.
By combining two six-pulse bridges with a 30 phase shift between them, i.e.
by using Y/Y and Y/ transformers as shown in Figure 17.1 and summating
equations (1) and (2), a twelve-pulse bridge is obtained. The idealized magnitudes
of the twelve-pulse harmonics are shown in Table 17.2.
The current waveforms shown in Figure 17.3 appear in the common connection
to the transformers shown in Figure 17.1.
If a Fourier analysis is performed on this idealized waveform, the following result
is obtained:
3)
43 HVDC
for beginners and beyond
Thus, in a twelve-pulse bridge, the harmonic orders 6n 1, n = 1, 3, 5 ... are
effectively cancelled in the common supply leaving only the characteristic
twelve-pulse harmonics
i.e.
12n 1, n = 1, 2, 3, ...
COMBINED
The usual published formulae and graphs for these currents give magnitudes
only. For special purposes (e.g. net harmonic contribution from two or more
bridges of slightly different firing angles or reactances) both magnitude and
phase (i.e. vector solutions) are required.
44 HVDC
for beginners and beyond
Fundamental
(50 Hz)
Fundamental
(50 Hz)
5th
(250 Hz)
0.2
5th
(250 Hz)
7th
(350 Hz)
0.14
7th
(350 Hz)
11th
(550 Hz)
0.09
11th
(550 Hz)
0.09
13th
(650 Hz)
0.08
13th
(650 Hz)
0.08
17th
(850 Hz)
0.06
17th
(850 Hz)
19th
(950 Hz)
0.05
19th
(950 Hz)
23rd
(1150 Hz)
0.04
23rd
(1150 Hz)
0.04
25th
(1250 Hz)
0.04
25th
(1250 Hz)
0.04
(n x 50 Hz)
1/n
(n x 50 Hz)
1/n
45 HVDC
for beginners and beyond
18 DC HARMONICS
The idealized voltage across an unloaded six-pulse converter is shown in Figure 18.1, and the
idealized voltage across a twelve-pulse converter is shown in Figure 18.2. The voltage is a mix of a
direct voltage and harmonics. Table 18.1 shows the harmonics on the DC side produced by a sixpulse converter.
No-Load DC (Vd0)
(DC)
1.0000
6th
(300 Hz)
0.0404
12th
(600 Hz)
0.0099
18th
(900 Hz)
0.0044
24th
(1200 Hz)
0.0025
0.8
0.8
DC Voltage (p.u.)
DC Voltage (p.u.)
0.6
0.4
0.6
0.4
0.2
0.2
0
0
100
200
300
Electrical Degrees
100
200
300
Electrical Degrees
46 HVDC
for beginners and beyond
19 CHARACTERISTIC AND
NON-CHARACTERISTIC
HARMONICS
The harmonic currents derived from the examination of the ideal converter, as described in Section
17, are known as the characteristic harmonics of a converter. However, a practical converter can
cause other harmonic currents to be generated which result from non-ideal operating conditions.
These harmonics are referred to as non-characteristic harmonics. Non-characteristic harmonics
can result from several sources; unbalance or negative phase sequence in the supply AC system
will result in the generation of 2nd harmonic voltage on the DC side by the converter; a harmonic not
predicted by the 6n or 12n analysis described previously will give rise to 3rd harmonic current being
injected back into the AC system by the converter. Unbalance between the converter transformer
leakage reactances for the Y and bridges will result in a small amount of each of the classical
harmonics which should have been completely cancelled still being present in the AC side
current. Stray capacitance which is inherent in, for example, the converter transformer valve winding
bushings will provide a stray path within the converter for harmonic currents to flow leading to the
generation of triplen harmonics such as, 3rd, 9th and 15th on the DC side and 1 of these harmonic
numbers on the AC side. Also, minor control inaccuracies within the converter controller resulting
in the firing instance between valves of a bridge not being perfectly symmetrical (the error is much
less than 0.1 electrical) will cause the generation of harmonics at all multiples of n on both the AC
and DC side of the converter.
19.1
Cross-Modulation Harmonics
47 HVDC
for beginners and beyond
distortion caused by one converter will be applied to the DC terminals of the other converter and vice
versa. These harmonic voltage distortions will cause a distortion in the circulating DC current which
will cause harmonics to be generated in each converter that are a multiple of the other converters
AC system frequency and not of its own. For example, the 60 Hz converter will have AC current
harmonics corresponding to 11th and 13th harmonic at 660 Hz and 780 Hz respectively and a
corresponding DC side harmonic at 720 Hz. However, this 720 Hz distortion will result in 660 Hz
and 780 Hz components in the AC current harmonics of the 50 Hz connected converter. Neither of
these frequencies are an integer multiple of 50 Hz and, as a consequence, non-integer harmonics
are produced.
48 HVDC
for beginners and beyond
The AC side current waveform of a HVDC converter, as already discussed previously, is highly nonsinusoidal, and, if allowed to flow in the connected AC network, might produce unacceptable levels
of distortion. AC side filters are therefore required as part of the total HVDC converter station in
order to reduce the harmonic distortion of the AC side current and voltage to acceptably low levels.
C1
HVDC converters also consume substantial reactive power, a large proportion of which must normally
be supplied locally within the converter station. Shunt-connected AC filters appear as capacitive
sources of reactive power at fundamental frequency, and normally in conventional HVDC schemes
the AC filters are used to compensate most or all of the reactive consumption of the converter.
Additional shunt capacitors and reactors and occasionally Static VAr Compensators (SVCs), Static
Compensators. (STATCOMs) or synchronous compensators, may also be used to ensure that the
desired reactive balance is maintained within specified limits under defined operational conditions.
L1
R1
The design of the AC filters, therefore, normally has to satisfy these two requirements of harmonic
filtering and reactive power compensation, for various operational states and load levels.
20.1
1.0E+04
45
1.0E+03
0
1.0E+02
-45
1.0E+01
1.0E+00
-90
0
12 16 20 24 28 32 36 40 44 48
Harmonic Number
Phase
Magnitude
90
1.0E+05
49 HVDC
for beginners and beyond
The choice of the optimum filter solution is the responsibility of the contractor and will differ from
project to project. The design will be influenced by a number of factors that may be specified by the
customer:
s pecified harmonic limits (voltage distortion, telephone interference factors, current injection),
AC system conditions (supply voltage variation, frequency variation, negative phase sequence
voltage, system harmonic impedance),
switched filter size (dictated by voltage step limit, reactive power balance, self-excitation limit of
nearby synchronous machines, etc.),
environmental effects (ambient temperature range),
converter control strategy (voltage and overvoltage control, reactive power control),
site area (limited switch bays),
loss evaluation criteria,
availability and reliability requirements.
Different filter configurations will possess certain advantages and disadvantages when considering
the above factors. As only the filter design and performance aspects are considered, additional
equipment such as surge arresters, current transformers and voltage transformers are omitted from
the circuits shown. In HV and EHV applications, surge arresters are normally used within the filters
to grade the insulation levels of the equipment.
20.2
the tuned filter or band-pass filter which is sharply tuned to one or several harmonic
frequencies.
These are filters tuned to a specific frequency, or frequencies. They are characterized by a relatively
high q (quality) factor, i.e. they have low damping. The resistance of the filter may be in series with the
capacitor and inductor (more often it is simply the loss of the inductor), or in parallel with the inductor,
in which case the resistor is of high value. Examples of tuned filters include single (e.g. 11th) double
(e.g. 11/13th) and triple (e.g. 3/11/13th) tuned types
the damped filter or high-pass filter offering a low impedance over a broad band of
frequencies.
These are filters designed to damp more than one harmonic, for example a filter tuned at 24th harmonic
will give low impedance for both 23rd and 25th harmonic, and even for most of the higher harmonics.
Damped filters always include a resistor in parallel with the inductor which produces a damped
characteristic at frequencies above the tuning frequency. Examples of damped filters include singletuned damped high-pass (e.g. HP12) and double-frequency damped high-pass (e.g. HP 12/24).
50 HVDC
for beginners and beyond
The distinction between these two filter types may sometimes be almost lost depending on the
choice of q-value for different filter frequencies.
C1
C2
L1
R1
L2
R2
For a HVDC scheme with a twelve-pulse converter, the largest characteristic harmonics will be
the following: 11th, 13th, 23rd, 25th, 35th, 37th, 47th, and 49th. As the level of the 11th and 13th
harmonic are generally twice as high as for the rest of the harmonics, a common practice is to provide
band-pass filters for the 11th and 13th harmonic and high-pass filters for the higher harmonics.
Due consideration also has to be taken concerning the possible low-order resonance between the
AC network and the filters and shunt banks. When a big HVDC scheme is to be installed in a weak
AC system, a low-order harmonic filter (most often tuned to 3rd harmonic) may be also needed.
90
1.0E+05
1.0E+04
Advantages:
45
1.0E+03
0
1.0E+02
-45
1.0E+01
1.0E+00
-90
0
Phase
Magnitude
Disadvantages:
12 16 20 24 28 32 36 40 44 48
Harmonic Number
20.4
51 HVDC
for beginners and beyond
The advantages and the disadvantages of a double-tuned band-pass filter are as follows:
C1
Advantages:
L1
R1
C2
L2
R2
C3
L3
R3
Disadvantages:
90
1.0E+05
1.0E+04
45
1.0E+03
0
1.0E+02
-45
1.0E+01
1.0E+00
-90
0
12 16 20 24 28 32 36 40 44 48
Harmonic Number
Phase
Magnitude
20.5
This type of filter is electrically equivalent to three parallelconnected tuned filters, but is implemented as a single
combined filter. Figure 20.5 shows the circuit arrangement
and Figure 20.6 the impedance/frequency response for a
typical triple-tuned filter.
The use of triple-tuned filters could improve the operational
requirements for reactive power control. This would be
of particular importance at low-load conditions if a 3rd
harmonic filter is needed in the circuit from the beginning.
As they are similar in nature to double-tuned filters their
merits and drawbacks are as described in section 20.2
above.
For each of the above arrangements, sensitivity to detuning
has been identified as a disadvantage. However, with the
addition of resistors (and hence additional losses) to make
the filter arrangement damped as discussed in section
20.2, this detuning can be mitigated.
52 HVDC
for beginners and beyond
21 AC HARMONIC
PERFORMANCE AND
RATING CALCULATIONS
In
Ifn
Isn
FILTER
Zfn
SYSTEM
Zsn
Isn =
Zfn
x In
Z fn + Zsn
5)
Vn = Zfn x Zsn x In
Zfn + Zsn
In order to calculate harmonic performance and design the filters (i.e. Zfn), it
is essential that detailed information be available on the harmonic currents
generated by the HVDC converter (In) and the harmonic impedance of the
supply system (Zsn).
21.1
53 HVDC
for beginners and beyond
There are several methods of modelling the system impedance:
X
1
21.1.2
r
2r
R
Z plane
54 HVDC
for beginners and beyond
21.1.3
+jX
Polygon Method
This method gives a realistic assessment of the system impedances, and avoids
any problems of over-designing the filter.
-jX
55 HVDC
for beginners and beyond
22 DC HARMONIC
PERFORMANCE AND
RATING CALCULATIONS
Impedance (ohms)
104
103
102
101
100
10-1
0
1000
2000
3000
Frequency (Hz)
4000
5000
When operating in balanced bipole mode, the harmonic currents will flow through
the DC lines in such a way that at any point along the line, the instantaneous
harmonic currents in one poles DC conductor will be equal and opposite to that
in the other (assuming that both poles are operating identically, that is, at the
same DC voltage, DC current, measurement errors, tolerances, etc). Therefore,
the currents induced in a parallel conductor will be reduced. Hence, typically, the
worst-case DC harmonic performance and the case which defines the DC filter
rating, is monopole operation.
56 HVDC
for beginners and beyond
An important consideration in the design of a DC filter, as opposed to an AC filter, is the main capacitor
bank as, on the DC side, this will be subject to the applied DC voltage and hence the sharing of
the DC voltage as well as the AC voltage must be controlled. This means that the resistive voltage
distribution needs to be controlled in DC capacitors (Figure 22.3). For this reason it is common for
DC filter capacitor banks to be constructed as one single tall bank as opposed to any form of split
bank where the split banks would have post insulators between the capacitor racks and disturb the
voltage distribution due to leakage currents across them.
57 HVDC
for beginners and beyond
23 CONTROL FACILITIES
PROVIDED BY HVDC
SCHEMES
The basic control parameter of a HVDC converter is the DC current which circulates between the
rectifier and inverter assuming that the DC voltage is maintained at a constant value (which is
typically true for DC power transmission schemes but not always true for back-to-back schemes).
However, the HVDC controller can adjust the DC current flow in response to other operator-settable
parameters or measured quantities providing an extremely flexible and fast part of a power systems
transmission infrastructure. Typical control features provided or available as an additional feature are
described below:
23.1 Power Control
The power transferred between the sending and receiving end of the HVDC link is controlled to
meet an operator-set value at the point in the circuit where the DC power is defined, known as the
compounding point. Typically the compounding point is at the rectifier DC terminal but it can also
be at the inverter DC terminal, the mid-point of the DC transmission conductors (e.g., at the border
between two countries), the inverter AC terminal or the rectifier AC terminal.
If the power demand is changed then the power order will ramp to the new power transfer level at a
rate of change (known as the ramp rate) pre-selected by the operator. Typically the maximum power
limit is defined by an overload controller which is continuously calculating the thermal capability of
the converter station equipment.
58 HVDC
for beginners and beyond
23.2 Frequency Control
A HVDC scheme can control the AC frequency of an AC system by automatically adjusting the
power being delivered into that AC system in order to balance the load with the supply. The fast
power control by the HVDC reduces the under-frequency or over-frequency which can result from a
changing load in a small power system such as an island load.
Frequency control can also be applied as limits to the power control function. For example, the
sending end can be arranged so that it will continue to supply power via the HVDC link to the
receiving end as so long as the sending end AC system frequency is above some threshold value. In
this way the sending end can be protected from a severe system disturbance as a consequence of a
disturbance in the receiving end AC system. The controllability of a HVDC scheme is very important
and is sometimes referred to as providing a firewall. With a power system consisting of islands
of AC interconnected with DC, this firewall property of HVDC will mitigate the risk of cascading
black-outs across multiple interconnected AC systems [5].
Other frequency limits can be applied, for example the receiving end AC system could have an
upper frequency limit to automatically stop further increases in the power being delivered by the
HVDC scheme. Equally, the receiving AC system can have a lower frequency limit which, if reached,
automatically increases the power being delivered into the receiving AC system, though this can
normally be overridden by the sending end minimum frequency limit described above, that is, the
sending end system will help out the receiving end AC system as much as possible without risking
a cascade failure.
59 HVDC
for beginners and beyond
23.3 Power Modulation Control
The power being transferred through a HVDC link can be automatically modulated to provide
damping to low-frequency power oscillations within either, or both, interconnected AC systems as
determined by studies during the design phase of the HVDC scheme.
60 HVDC
for beginners and beyond
23.5 DC Protection
A detailed description of the protections used within a HVDC station is beyond the scope of this
document. However, it is worth noting that within a HVDC converter station the types of protection
utilized fall into two categories:
AC connected equipment such as converter transformers and AC harmonic filter components, along
with feeders and busbars, are protected using conventional AC protection relays. The converter,
along with the DC circuit, is protected using hardware and software specifically purpose designed
by AREVA T&D. Typical DC specific protections include:
AC > DC
AC Overcurrent
DC Differential
DC Overcurrent
DC > AC
AC Overvoltage
Asymmetry
AC Undervoltage
Abnormal firing angle
Low DC current
DC Undervoltage
61 HVDC
for beginners and beyond
Thyristors used for HVDC valves are amongst the largest semiconductors of any type produced for
any industry. Figure 24.2 shows an 8.5 kV thyristor with an active silicon diameter of 115 mm (which
starts life as a silicon ingot of 125 mm diameter, hence such thyristors are often referred to as
125 mm thyristors).
Such components are expensive and there may be many thousand such components in a HVDC
station. Moreover, they are quite delicate and require a great many additional components to control
and protect them. In fact, although it is the most obvious component of a thyristor valve, the thyristors
account for a surprisingly low percentage of the total valve cost.
Modern thyristor valves are relatively standardized, that is to say that the bulk of the real design
work is carried out during the product development phase, hence, applying the valves to a particular
project is a relatively straightforward matter. At its simplest, the work involved for a particular project
62 HVDC
for beginners and beyond
may just involve adapting the number of series-connected
thyristors according to the voltage rating requirements
imposed by the overall system design.
DC Neutral
AC
(Delta)
Module
Module
Module
Module
Module
DC Midpoint
AC
(Star)
Module
Module
Module
Module
Module
HVDC
63 HVDC
for beginners and beyond
25 THYRISTOR VALVE
COOLING CIRCUIT
Aluminum Heatsink
PEX Hose
Stainless Steel Electrode
O Ring
Nylon nut
Water cooling is always provided for the thyristors and damping resistors, and usually also for the
di/dt reactor and DC grading resistor.
The water coolant is distributed in parallel to every thyristor level in the valve via insulating plastic
pipes, and the waste heat is rejected to outdoor-mounted coolers.
The design of the water cooling circuit is an important engineering task in order to ensure that the
system has adequate flow rates in all critical areas and avoids excessively high flow rates that could
cause erosion, or low flow rates that lead to accumulation of gas pockets.
Even though the water conductivity in a HVDC valve is normally extremely low, it is never zero,
and hence, its potential for causing undesired electrochemical effects has been widely recognized.
Ultra-pure deionized water can have a very low conductivity, less than 0.1 S/cm. However, no
matter how sophisticated the deionization equipment, it is not possible to reduce the conductivity
completely to zero, because water always dissociates into H+ and OH- ions, to an extent governed
mainly by temperature. As a consequence, any water pipe spanning two points at different electrical
potentials will inevitably carry a small leakage current. When the applied voltage is only AC, the
consequences of this are not particularly serious, but when the applied voltage has a DC component,
certain electrochemical reactions inevitably take place at the anode and cathode electrodes.
Aluminum, which is widely used as a heatsink material because of its excellent thermal conductivity,
is very vulnerable to corrosion in the event that leakage currents flowing in the water are allowed
to impinge directly on the aluminum. In order to prevent damage to the aluminum, it is necessary to
ensure that the leakage currents flowing in the water do not flow directly from water to aluminum
but instead pass via some inert electrode material. In this way (shown on Figure 25.1) the vulnerable
aluminum is protected from damage.
64 HVDC
for beginners and beyond
AREVA T&Ds first water-cooled HVDC valves have now been in service since
1989 [6] and those of the Nelson River project have been in service since
1992, see Figure 25.2. AREVA has maintained the same design principles used
on those projects, up to the present day, on all its HVDC valves and most of
its FACTS converters. AREAVA T&D has in excess of 70,000 small-diameter
(15 mm) and 8,000 larger-diameter (50-75 mm) cooling connections installed
in such converters around the world. Even with such a large installed base,
there have been no reported problems caused by electrochemical erosion or
deposition in any of AREVAs HVDC valves.
Figure 25.2: A valve hall from Valve Group VG13 of the Nelson River
project in Canada, showing the large developed length used for the
coolant pipework to span the distance between earth and the base of
the valve stack at 330 kVDC.
Cooling plant
65 HVDC
for beginners and beyond
26 HVDC CONVERTER
TRANSFORMERS AND
THEIR CONFIGURATIONS
66 HVDC
for beginners and beyond
3x 1 phase/3 windings
The converter transformer is the largest plant item to be shipped to site for
an HVDC project. Hence transport restrictions such as weight or height, if the
transformer has to go over or under a bridge for example, can have a major impact
on the selected converter transformer arrangement. Figure 26.2 illustrates the
commonly recognized transformer arrangements in HVDC schemes.
Lowest cost can normally be achieved by minimizing the number of elements
the converter transformer is broken down into, hence the lowest cost is
typically a 3-phase, 3-winding transformer. However, due to shipping limits,
such a transformer may not be practical so another arrangement should be
considered. Where a spare converter transformer is deemed necessary, based
on an availability analysis of the scheme, then it is more cost-effective to use a
1-phase, 3-winding transformer arrangement, as one spare unit can replace any
of the in-service units, whilst 2-winding arrangements require two spare units
to be supplied.
6x 1 phase/2 windings
67 HVDC
for beginners and beyond
27 RELIABILITY AND
AVAILABILITY OF
An HVDC CONVERTER
Reliability and availability assessment is the recognized way of assessing the performance of an
HVDC converter scheme [7]. CIGRE collects reliability and availability of existing HVDC schemes
from around the world and publishes a bi-annual report indicating what performance is being
achieved for those schemes that provide data for the report.
27.1
Reliability
Reliability is a measure of the capability of the HVDC link to transmit power above some minimum
defined value at any point in time under normal operating conditions. Reliability is normally expressed
as the number of times in one year the scheme is incapable of transmitting power above a minimum
defined value. This inability to transmit above a defined power level is termed Forced Outage Rate
(F.O.R.).
27.2
Availability
Availability is not commercially significant, for example, if the scheme is unavailable during times of
zero loading, the unavailability of the scheme will have no impact. For HVDC schemes, the term is,
therefore, used to represent energy availability. Energy availability is the ability of a HVDC scheme
to transmit, at any time, power up to the rated power. Hence, a converter scheme which can transmit
1.0 pu power for 100% of the time would have an energy availability of 100%. Any outage of the
HVDC scheme or, for example, the outage of one pole in a bipole, will impact the energy availability,
reducing the figure to less than 100%.
68 HVDC
for beginners and beyond
28 LOSSES IN A CONVERTER
STATION
An important commercial consideration of any power interconnection is the electrical losses within
the connection, that is, the amount of power lost in the process of transmitting the power from one
location to another. Losses within a line commutated converter scheme are carefully considered
during the design phase in order to ensure that the relationship between capital equipment cost
and the effective cost of losses can be optimized. In calculating the effective cost of the losses, the
purchaser must consider the duration of the financial plan for the HVDC link, the expected cost of
electricity during this period and the expected interest rate during this period. By taking these values,
the net present value of the losses can be calculated, that is, a figure which represents a cost to
the owner of using the equipment within the network. The loss evaluation is normally assessed by
multiplying a cost/kW figure by the HVDC suppliers guaranteed losses. Figures of 4,000 USD/kW
to 5,000 USD/kW are common today.
Figure 28.1 shows the typical split between equipment within a HVDC transmission scheme whilst
Figure 28.2 shows the split between equipment for a back-to-back HVDC scheme.
8%
Converter Transformer
Converter Valves
1%
0% 5% 1% 5%
4%
3%
5%
2%
35%
25%
DC Smoothing Reactor
50%
56%
AC Harmonic Flters
HF Filter
Auxiliaries
Figure 28.1: Typical Split of Losses
Within an HVDC Transmission
Scheme
69 HVDC
for beginners and beyond
AREVA has the capability to undertake a wide variety of power system and environmental studies
in order to assist a purchaser in developing a HVDC scheme. Presented below is a description
of recommended studies performed during the contract phase of a HVDC converter scheme
construction.
70 HVDC
for beginners and beyond
Typical Contract Reports
Title
Objective
To define the range of operating conditions of the HVDC scheme and the major component
ratings.
Consistent operating data for the HVDC scheme under different operating conditions, the number
of thyristor valve levels and the converter transformer rating.
Equipment Affected
Thyristor valves, converter transformers and reactive power banks (AC harmonic filters).
Methodology
The steady-state operating parameters of the HVDC scheme across its operating power range are
calculated for coherent operating conditions.
The various operating parameters, equipment tolerances and measurement errors that are applicable
to the scheme are varied between studies in order to explore the boundaries of the HVDC schemes
operation.
71 HVDC
for beginners and beyond
Typical Contract Reports
Title
Reactive Power
Objective
To establish the necessary sub-bank rating and switching sequence to meet the reactive power
control requirements of the scheme.
Reactive power bank/AC harmonic filter bank MVAr rating, switching sequence of banks under
different operating conditions and converter reactive power absorption capability utilization.
Equipment Affected
Methodology
The HVDC converter absorption under all extremes of operating condition tolerances, measurement
errors and operating DC voltage are established as part of the Main Scheme Parameters reports.
From this converter absorption, the total reactive power required, allowing for the appropriate
tolerance conditions, is established. Using the reactive power exchange limits, established switch
points will be calculated which keep the net reactive power interchange of the converter plus AC
reactive power banks with the AC systems within the established limits.
72 HVDC
for beginners and beyond
Typical Contract Reports
Title
Harmonic Filter
Objective
To evaluate the AC side harmonic currents generated by the converters as a function of DC power
and to establish an AC harmonic filter solution which meets the harmonic limits of the project.
Equipment Affected
AC harmonic filters.
Methodology
The analysis performed by AREVA establishes the combinations of the AC system and converter
conditions, such as frequency, temperature, transformer impedance, etc; which would give rise to the
maximum levels of harmonic distortion at the terminals of the HVDC station.
The harmonic currents generated by the rectifier and inverter of the HVDC converter are evaluated
using a digital computer program called JESSICA. The JESSICA program calculates the magnitude
of the individual harmonic currents from a mathematical analysis of the frequency domain behaviour
of the converter.
The performance of the AC harmonic filters and their operational losses are calculated using the
network harmonic penetration program HARP. The program models the filters and the injected
currents from the converters.
A standard mathematical maximization technique is used to search each harmonic impedance area
to find the impedance which produces the maximum value of voltage at a chosen node, or of current
in a chosen branch. This system impedance is inserted into the impedance matrix of the circuit being
analyzed for the harmonic current penetration study. The program then solves Ohms law, using
standard matrix mathematics techniques. This procedure is repeated for each harmonic of interest.
73 HVDC
for beginners and beyond
Typical Contract Reports
Title
Objective
To evaluate the high-frequency interference generated by the converters and to establish a PLC
filter and RF screening solution which meets the limits for the project.
Equipment Affected
Methodology
The components of the converter station will be modelled in the appropriate frequency range to
the necessary level of detail. Of most importance will be the converter transformers, the converters
and the PLC filters.
The PLC frequency noise will be calculated at the relevant busbars with a range of transmission
line impedances over the range of PLC frequencies of interest.
The radiated interference at 15 m from the substation fence will be calculated taking into account
practical levels of RF screening applied to the valve halls.
74 HVDC
for beginners and beyond
Typical Contract Reports
Title
Insulation Coordination
Objective
To establish the appropriate protective levels of station surge arresters and hence BIL, clearance
and creepage of station equipment.
The study will yield protective levels of station surge arresters, equipment BIL and creepages and
clearances on the DC side of the converter transformer.
Equipment Affected
All insulation.
Methodology
From the maximum valve winding and DC voltage along with the specified maximum AC system
operating voltage, the appropriate surge arrester protective levels are calculated based on
historical data. From this data, the insulation levels of primary equipment are calculated as well
as the insulation levels of insulators. The calculated insulation level for insulators is corrected to
provide an insulator which will provide the necessary withstand flashover probability for the DC
side equipment.
Clearances between equipment on the DC side of the converter transformer are also calculated.
75 HVDC
for beginners and beyond
Typical Contract Reports
Title
Objective
The objective of this study is to determine the transient overvoltage and current stresses on major
converter station equipment including surge arresters, which form a basis for their insulation
coordination. Surge arrester energy absorption requirements will also be determined.
Transient overvoltage levels. Surge arrester protection levels and energy absorption.
Equipment Affected
Methodology
76 HVDC
for beginners and beyond
Typical Contract Reports
Title
Objective
The objective of this study is to optimize the control parameters to provide stable operation and good
dynamic performance of the HVDC scheme. This study will be primarily carried out using physical
controls and AREVAs Real Time Digital Simulator (RTDS).
Static characteristics, control system functions and parameters, verification of stability, response
times and fault recovery.
Equipment Affected
Control equipment
Methodology
High voltage equipment in the respective converter stations (e.g. converter transformers, AC/DC
filters and DC filters) as well as relevant generators and step-up transformers will be represented in
the simulator model. Derived equivalent AC system network models will be used to represent the
AC systems.
This Dynamic Performance Study will be used to achieve the following objectives:
77 HVDC
for beginners and beyond
78 HVDC
for beginners and beyond
Typical Contract Reports
Title
Audible Noise
Objective
Confirmation that the equipment design meets the maximum acoustic noise limits at the boundary.
Equipment Affected
Methodology
Individual equipment suppliers information giving the acoustic noise predicted for individual items
will be modelled in a graphical representation of the site layout. The predictor software performs the
acoustic noise calculations using the methodology set out in the following standards.
ISO 9613-1: Attenuation of sound during propagation outdoors, Part 1: Calculation of sound by
the atmosphere (first edition 1993-06-01).
ISO 9613-2: Attenuation of sound during propagation outdoors, Part 2: General method of
calculation (first edition 1996-12-15).
VDI 2571: Schallabstrahlung von industriebauten (Sound emission from industrial buildings).
79 HVDC
for beginners and beyond
80 HVDC
for beginners and beyond
Typical Contract Reports
Title
Objective
The objective of this study is to assess the performance of the DC interconnection, its controls and
compensating equipment and the overvoltage limiting feature in response to large load rejection
disturbances in the equivalent AC/DC system, in order to determine the resulting temporary
overvoltages.
Equipment Affected
Methodology
For specified base cases of the system, equivalent network (and load) transient type studies (for a
short period of a few cycles) will be made for a partial and a full load rejection conditions. AC system
outage condition situations are studied similarly. The appropriate study cases will be repeated with
and without the reactive power absorption mode (TCR mode) of control for voltage limiting actions
in order to determine its effects, characteristics and ratings.
The study requires all the usual load flow and transient stability type data/models of the network
impedances, loads, generators/controls and operating levels/features. The study does not
necessitate a very large, full AC network to be modelled in order to achieve its objectives of converter
station design/assessment.
The maximum fundamental frequency TOVs occur when there is loss of power transmission in the
HVDC link, which can occur due to:
a) B
locking of the link. This causes the converter transformer circuit breakers to open thereby
isolating the converter station. Any delay in tripping the filters will cause high overvoltages due
to the prior rejection of the HVDC link reactive power demand which affects both ends of the
link.
b) Three-phase solid faults close in to the converter HV busbars which can also cause loss of
DC transmission, although the converter transformers remain connected for this scenario.
Following clearance of the fault, TOVs can be high in the period before full power transfer is reestablished.
81 HVDC
for beginners and beyond
Typical Contract Reports
Title
Objective
To define the overall reliability and availability of the converter station equipment, confirm the
equipment design and the recommended spares to meet the specified requirement.
The energy availability and the Forced Outage Rate associated with different scheme
configurations.
Equipment Affected
Methodology
A reliability study model is built by grouping together smaller models, known as subsystems. A
subsystem is a collection of components (or smaller subsystems) whose individual reliabilities can
be combined together on the basis of their inter-relationships (dependencies) to provide an overall
measure of subsystem reliability. The subsystem is then treated as a single component with its
own failure and repair characteristics. In this way, a reliability study model can be simplified by
consideration of its reliability in modular fashion into a smaller quantity of representative subsystem
modules. There are no fixed rules regarding the way in which components are combined together
to form subsystems; the choice is based on the nature of the plant and the experience of existing
installations.
Examples of subsystems are:
a) C
onverter valve, comprizing; thyristors, gate units, monitoring units, ground-level electronics,
cooling components, etc.
b) Harmonic filter, comprizing: inductors, capacitors, resistors, CTs, isolators, AC circuit breakers, etc.
A reliability study model of a complete system is built up by relating together all the subsystems
which it contains in terms of the effect of their failures on the other subsystems.
82 HVDC
for beginners and beyond
Typical Contract Reports
Title
Losses
Objective
Equipment Affected
None.
Methodology
The converter station losses for operation under nominal AC system voltage and frequency conditions
and with nominal equipment parameters at an outdoor ambient temperature of typically 20 C will
be presented. The study will compile results from equipment factory tests along with the proposed
nominal operating conditions and present the total converter station losses in accordance with the
formulae defined in IEC 61803 or, if prefered by the client, IEEE Std 1158.
83 HVDC
for beginners and beyond
30 References
[1]
PL Sorensen, B Franzn, JD Wheeler, RE Bonchang, CD Barker, RM Preedy, MH Baker,
Konti-Skan 1 HVDC pole replacement, CIGR session 2004, B4-207.
[2]
JL Haddock, FG Goodrich, Se Il Kim, Design aspects of Korean mainland to Cheju
island HVDC transmission, Power Technology International, 1993, Sterling Publication Ltd
p.125.
[3]
BT Barrett, NM MacLeod, S Sud, AI Al- Mohaisen, RS Al-Nasser, Planning and design
of the AL Fadhili 1800MW HVDC Interconnector in Saudi Arabia, CIGR Session 2008, B4114.
[4]
RP Burgess, JD Ainsworth, HL Thanawala, M Jain, RS Burton, Voltage/var control at
McNeill Back-to-Back HVDC convertor station, CIGR Sesson 1990, p.14-104.
[5]
NM MacLeod, DR Critchley, RE Bonchang, Enhancing the control of large Integrated
AC Transmission Systems using HVDC technology, Powergrid Europe conference, Madrid,
Spain, May 2007.
[6]
DM Hodgson, Qualification of XLPE tube systems for cooling high-voltage high-power
electrical equipment, Power Engineering Journal, November 1991.
[7]
CD Barker, AM Sykes, Designing HVDC Schemes for Defined Availability, IEE
Colloquium (Digest), n 202, (1998), p.4/14/11
84 HVDC
for beginners and beyond
31 APPENDIX
1.1
A B
A B
A B
A
A
Voltage
nominal
maximum continuous
minimum continuous
maximum short time and duration
minimum short time and duration
1.2 Frequency
A B
nominal
A B
maximum continuous
A B
minimum continuous
A
maximum short time and duration
A
minimum short time and duration
A B
1.3
Short circuit levels, maximum and minimum, for each stage of the development
A B
1.4
Insulation levels
1.5
1.6
Harmonic impedance
85 HVDC
for beginners and beyond
A
1.7 Distortion and/or TIF limits for AC system. Which harmonics are to be
assessed?
A
1.8
A
1.9
A
1.10 Give details of undervoltages and durations for AC system faults, both during the
faults and during the fault clearance period for both main and back-up protection,
for single phase and three phase faults if they are different.
A B
1.11 Give results of AC system disturbance studies including transient voltage and
frequency variations, and details of any limits on acceptable VAr generation/
absorption and switching during and after the disturbance.
A B
1.12 a) What is maximum permitted step voltage change arising from filter
switching?
b) What is the maximum permitted ramped voltage change and over what time
duration?
A B
1.13 What is maximum temporary (<1 sec) overvoltage that existing equipment can
withstand? Are there any other significant limits on permissible temporary
overvoltage?
A B
1.14 How much reactive compensation is required (i.e. what power factor is to be
achieved) at the AC terminals at various transferred power levels up to full load?
A
A
1.16 Give negative sequence voltage on each converter station AC busbar, and existing
harmonic voltages.
2. DC System
A B
2.1
A B
2.2
86 HVDC
for beginners and beyond
A B
2.3
Is an overload capability required? If so how much and for how long and under
what conditions of ambient temperatures?
A B
2.4
A B
2.5
What are the permitted limits for harmonic current injection into the DC line?
A B
2.6
A B
2.7
A B
A
2.9
A
2.12 What are the capitalized costs for fixed and variable losses and at what power
loading do they apply?
A
2.13
In order that the quantities of spares required may be determined, give details
of the energy availability and station reliability targets, preferred maintenance
intervals and design criteria to be adopted (information to include cost of loss of
service for availability and reliability optimization).
87 HVDC
for beginners and beyond
3.
A B
3.1
MVA
Voltage (including harmonic content)
Power factor
Reactances, both transient and sub-transient direct axis.
A B
3.2
MVA
Voltage ratings
Percentage reactance
Connection
3.3
3.4
A B
3.5
A
3.6
A
4.1
A
Give details of preferred voltages and frequencies to be used for the auxiliary
power system and sources of auxiliary power supply, i.e. will supply be provided
from a generating station or will contractor have to supply auxiliary power
transformers connected to the AC busbars?
88 HVDC
for beginners and beyond
A
4.3
5.
A
5.2
A
5.3 Any operation requirements to be defined, i.e. power and/or current control, rate
of change of power, etc.
C
5.4 Define the performance required during and after disturbances in either AC
system
C
5.5 Define any restrictions on the recovery from DC disturbances arising from the
requirements of the AC system
C
5.6 Define the disturbances liable to occur in either AC system and the control
objectives required of the DC system in such circumstances such as supplementary
control signals in response to AC frequency or voltage at one or more terminals.
C
5.7 Control desk or panel requirements )
)
A B
5.8 Protection requirements
) (a) what are
) the particular
A
5.9 Requirements for line fault protection ) requirements?
)
A
5.10 Requirements for line fault location
) (b) What are
) the system
A
5.11 Requirements for alarm annunciation ) practices
) which should
A
5.12 Requirements for sequential event
) be followed
recording
) for operational
A
5.13 Requirements for disturbance recording) convenience?
)
A
5.14 Supervisory system requirements
)
A
5.15 Is an HVDC power line carrier (or fibre optic cable communications) system to
be provided by the contractor and, if so, what information will be carried on it?
89 HVDC
for beginners and beyond
A
5.16 Details of any interface between power line carrier (or fibre optic cable
communications) and any other telecommunication system(s).
A
5.17 Arrangements for communication during the construction/commissioning stage,
between sites and from each site to national and international circuits for
telephone, printer, fax, etc.
A
5.18 Requirements for permanent facilities to be provided by the contractor for
telephone, telex, fax, etc., circuits.
A
5.19 Map of route of DC line (if applicable) showing sites, and respective distances,
for power line carrier repeater stations, indication of any suitable auxiliary power
supplies that may be available at these sites.
A
6.1
A
6.2
A B
Site conditions:
6.3
(i)
(ii)
(iii)
(iv)
nominal
maximum
minimum
maximum wet bulb and coincident dry bulb
(b) Altitude
(c) Maximum wind speed
(d) Maximum depth of snow
(e) Rainfall
(f) Isokeraunic levels
(g) Range of relative humidity
(h) Incidence of air pollution (salt or industrial)
6.4
What are the RFI limits and where are they to apply?
6.5
90 HVDC
for beginners and beyond
A
6.6
What are the audible noise limits and where are they to apply?
A B
6.7 Are the sites in an earthquake zone; if so what forces do structures and building
have to be designed to withstand?
A
6.8 Local structural/building codes, defining what factors have to be applied to
forces due to wind and/or snow, when designing buildings and structures.
A B
6.9
What are the maximum loading gauges and weight restrictions at the ports and
on the routes to each site?
A
6.10 Maps of the areas of the sites showing the areas available for the converter
station and those available for ground or sea-shore electrodes.
A
6.11 Site surveys including soil analysis especially in the areas of the ground
electrodes if these are required.
A
6.12 Maps showing the location of the outgoing AC lines and DC lines from the
converter stations.
A
6.13 Details of auxiliary supplies that will be available, during construction and
installation.
A
6.14 Details of water supplies, available at the sites, including flow rates and chemical
analysis.
A
A
6.16 Details of any preferred materials that will utilize local resources, e.g. copper or
aluminum, brick or concrete.
A
6.17 Standards and specifications to be used, stating the order of precedence.
This list should also include specific standards relating to items of equipment
including Busbars, Transformers, Switchgear, Cabling and Wiring, Insulation Oil,
Civil Works and Structures, Equipment Finishes, Painting, Drawings and Drawing
Symbols.
C
A
If the customer has any standard specification for control and protection circuits,
e.g. control circuits for circuit breakers, then copies of these should be provided.
91 HVDC
for beginners and beyond
A
6.19 Define what office and workshop facilities are to be provided, e.g. should
workshops be capable of handling major items such as converter transformers?
A
Systems-L4-HVDC Basics -2165-V1-EN AREVA - 2009. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks
of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. 389191982 RCS PARIS. Printed at Lecaux.
All over the world, AREVA provides its customers with solutions for
carbon-free power generation and electricity transmission. With its
knowledge and expertise in these fields, the group has a leading role
to play in meeting the worlds energy needs.