Chapter 9 - Strength and Serviceability Requirements: Commentary
Chapter 9 - Strength and Serviceability Requirements: Commentary
318-115
COMMENTARY
9.1 General
R9.1 General
9.1.2 Members also shall meet all other requirements of this Code to ensure adequate performance at
service load levels.
9.1.3 Design of structures and structural members
using the load factor combinations and strength reduction factors of Appendix C shall be permitted. Use of
load factor combinations from this chapter in conjunction
with strength reduction factors of Appendix C shall not
be permitted.
U = 1.4(D + F )
(9-1)
U = 1.2(D + F + T) + 1.6(L + H)
(9-2)
+ 0.5(Lr or S or R)
U = 1.2D + 1.6(Lr or S or R) + (1.0L or 0.8W) (9-3)
U = 1.2D + 1.6W + 1.0L + 0.5(Lr or S or R)
(9-4)
--``,`,,,```,``,`,,`,,`,`,`,-`-`,,`,,`,`,,`---
318-116
CODE
COMMENTARY
(9-5)
(9-6)
(9-7)
except as follows:
(a) The load factor on the live load L in Eq. (9-3) to
(9-5) shall be permitted to be reduced to 0.5 except for
garages, areas occupied as places of public assembly,
and all areas where L is greater than 100 lb/ft2.
(b) Where wind load W has not been reduced by a
directionality factor, it shall be permitted to use 1.3W
in place of 1.6W in Eq. (9-4) and (9-6).
(c) Where E, the load effects of earthquake, is based
on service-level seismic forces, 1.4E shall be used in
place of 1.0E in Eq. (9-5) and (9-7).
--``,`,,,```,``,`,,`,,`,`,`,-`-`,,`,,`,`,,`---
CODE
318-117
COMMENTARY
elevator shafts, etc., impact effects should be considered. In all
equations, substitute (L + impact) for L when impact should
be considered.
--``,`,,,```,``,`,,`,,`,`,`,-`-`,,`,,`,`,,`---