REB 670 Application

Download as pdf or txt
Download as pdf or txt
You are on page 1of 22

ABB Ltd.

Bangalore, 2007

Substation Automation
Products Training

Substation Automation Products 2007-09-11


1

REB 670
Busbar Protection IED

ABB LtdBangalore., 2007

REB 670 Training

Substation Automation Products 2007-09-11


2

Application Areas for REB 670

Centralized Busbar
Protection from 4 up to 24
CT inputs

Differential, BFP & Non-Dir


OC Protection for:
Busbars
Meshed corners,

ABB LtdBangalore., 2007

Substation Automation Products 2007-09-11


3

T-protection

Three-Phase Terminal; 4/8 Bays- Double Zone

REB 670; 3Ph


2 Zones (A & B);
8 Bays

Application Areas:
Smaller Buses (up to 8 CTs per zone)
Single Busbar Stations (with Transfer Bus)
1 Breaker Stations
Double Busbar Stations (with Transfer Bus)
Zone Interconnection included in the design

ABB LtdBangalore., 2007

No switching in CT secondary circuits

Substation Automation Products 2007-09-11


4

REB 670 3- Ph; BBP, BFP & EnFP for single buses

ZA

ZB

ZA

Single Bus with bus tie CB


up to 3/7 feeder bays on each side

Single Busbar
up to 4/8 feeder bays

ZA
ZA

ZB

ZB

ABB LtdBangalore., 2007

H type station with bus-section CB


or sectionalizing disconnector
Alternative CT Location

Substation Automation Products 2007-09-11


5

T connections

REB 670 3- Ph, BBP, BFP, EnFP for 1 CB stations


ZA

ZB

1 Breaker Stations
up to 4 diameters

ZA

.. .
ZB

ABB LtdBangalore., 2007

1 Breaker Stations
up to 8 diameters

Substation Automation Products 2007-09-11


6

REB 670 3- Ph; BBP, BFP & EnFP for Double CB stations

ZA

.. .
ZB

Double Breaker Station


up to 8 feeders

ABB LtdBangalore., 2007

Alternative CT Location

Substation Automation Products 2007-09-11


7

REB 670 3- Ph; BBP, BFP & EnFP for double buses
ZA

.. .

ZB

Double Bus with bus-coupler CB


and up to 6/7 feeder bays
ZA

.. .
ZB

.. .

Transfer Bay

Transfer Bus

ABB LtdBangalore., 2007

.. .

Isolator replica in REB 670*1.0


by CAP 531 Configuration

Double Busbars with bus coupler CB and Transfer Bus


up to 6/7 feeder bays
Substation Automation Products 2007-09-11
8

Optional Measuring Point

Scheme Layout for Double Busbar; 2 Zones/7 feeders


700

ABB

EQUIPMENT INCLUDED in the PANEL:

ABB LtdBangalore., 2007

1 pcs 3 phase, Busbar protection terminal REB 670*1.0


- two differential zones
- check zone
- eight BFP relays
- eight OC feeder backup protection (EnFP)
- internal disconnector replica logic
- internal individual bay tripping logic
- disconnector status supervision

Substation Automation Products 2007-09-11


9

Single-Phase Terminal; 12/24 Bays- Double Zone


REB 670; Ph-L1
2 Zones (A & B);
24 Bays

REB 670; Ph-L2


2 Zones (A & B);
24 Bays

REB 670; Ph-L3

ABB LtdBangalore., 2007

2 Zones (A & B);


24 Bays

Substation Automation Products 2007-09-11


10

Application Areas:
Bigger Buses (up to 12/24 bays per zone)
Single Busbar Stations (with Transfer Bus)
1 Breaker Stations
Double Busbar Stations (with Transfer Bus)
Load Transfer is included into the design
3 Terminals required for complete scheme
LDCM available to share binary IO

No switching in CT secondary circuits

REB 670 1- Ph; BBP, BFP & EnFP for single buses

ZA

.. .

ZA

Single Bus
up to 12/24 feeder bays

ABB LtdBangalore., 2007

ZA

.. .

.. .

11

.. .

Single Bus with bus-section disconnector


up to 12/24 feeder bays (i.e. 12+12; 16+8 etc.)

ZB

Single Bus with bus-section CB, up to


11/23 feeder bays (i.e. 12+11; 10+13 etc.)

Substation Automation Products 2007-09-11

.. .

ZB

ZA

.. .

.. .

ZB

Single Bus with bus-section CB


up to 11/23 feeder bays on each side

REB 670 1- Ph; BBP applications for 1 CB stations

ZA

ZA

.. .
ZB

ABB LtdBangalore., 2007

1 Breaker Stations
up to 6 / 12 diameters

Substation Automation Products 2007-09-11


12

.. .
ZB

1 Breaker Stations
up to 12 / 24 diameters

REB 670 1- Ph, Complete BBP, BFP & EnFP for 1 CB Stations!

ZA

.. .
ZB

ABB LtdBangalore., 2007

Bus Diff, CB Fail & EnFP


1 Breaker Stations
up to 4/8 diameters

Substation Automation Products 2007-09-11


13

REB 670 1- Ph; BBP, BFP & EnFP for Double CB stations

ZA

ZA

.. .

.. .

ZB

ZB

Double Breaker Station


up to 6 / 12 feeders

Double Breaker Station


up to 12 / 24 feeders

ABB LtdBangalore., 2007

Alternative CT Location

Substation Automation Products 2007-09-11


14

REB 670 1- Ph; BBP, BFP & EnFP for double buses

ZA

.. .

ZB

Double Bus with bus-coupler CB


up to 22/23 feeder bays

ABB LtdBangalore., 2007

Isolator replica in REB 670*1.0


by CAP 531 Configuration

Substation Automation Products 2007-09-11


15

Optional Measuring Point

REB 670 1- Ph; BBP, BFP & EnFP for double bus & transfer
ZA

.. .
ZB

.. .

Transfer Bus

.. .
Combined Bus-Coupler
& Transfer Bay

ZA

.. .
ZB

.. .

Bus-Coupler Bay
Transfer Bay

Transfer Bus

.. .

ABB LtdBangalore., 2007

Isolator replica in REB 670*1.0


by CAP 531 Configuration

Double Busbars with Transfer Bus


up to 22/23 feeder bays
Substation Automation Products 2007-09-11
16

Scheme Layout for Double Busbar; 2 Zones/22 feeders


700

ABB

EQUIPMENT INCLUDED in the PANEL:

ABB LtdBangalore., 2007

3 pcs 1 phase, Busbar protection terminal REB 670*1.0


- two differential zones
- check zone
- 24 BFP relays
- 24 OC feeder backup protection (EnFP)
- internal disconnector replica logic
- internal individual bay tripping logic
- disconnector status supervision

Substation Automation Products 2007-09-11


17

REB 670 1- Ph; BBP, BFP & EnFP for double buses
Main 2

Main 1

.. .
Reserve 1

.. .
Reserve 2

Four Zone Double Bus with two bus-coupler CBs and two
bus-section CBs and up to 20/21 feeder bays on each station side

Main 1

.. .

ABB LtdBangalore., 2007

Reserve 1

Main 2

.. .
Reserve 2

Four Zone Double Bus with two BC-CBs one BS-CB and one sectionalizing
disconnector with up to 18-20 feeder bays in the whole station
Substation Automation Products 2007-09-11
18

Optional Measuring Point

REB 670*1.0; 1-ph version Summation Principle

REB 670; 1 Ph
2 Zones (A & B);
24 Bays

+ N times

ABB LtdBangalore., 2007

N 8
Substation Automation Products 2007-09-11
19

Buses up to 24 bays per zone


Single Busbar
1 Breaker Systems
Double Busbar
Same applications possible as for 1Ph solution
Software Driven Zone Selection
Cost effective Solution

UserFriendliness

Pre-configured REB670 ready to use

ABB LtdBangalore., 2007

Substation Automation Products 2007-09-11


20

Single zone applications


Two zone applications without
need for any zone selection
(e.g. 1 CB stations)
Double busbar stations with zone
selection using busbar
disconnectors a & b aux contacts
Double busbar stations with zone
selection using only busbar
disconnectors b aux contact
Direct replacement for RED 521

ABB LtdBangalore., 2007

Available Configurations X01, X02 & X03

X01 = Just BBP for simple stations layouts (i.e. 1 CB, Double
Breaker, Single Breaker, or for double busbar-single breaker
stations where Zone Selection is done by using just b contacts).
Available for all five versions A20, A31, B20, B21 & B31.
Direct replacement for RED 521

X02 = Just BBP for double busbar-single breaker stations where


Zone Selection is done by using a&b contacts from disconnectors
and breakers. Available for versions A31, B21 & B31

X03 = BBP with BFP, EnFP & OCP for double busbar-single
breaker stations where Zone Selection is done by using a&b
contacts from disconnectors and breakers. Available for versions
A31, B21 & B31

For other station layouts or functionality CAP 531 configuration shall


be arranged by the end user.

Make country/end-customer specific solution

Substation Automation Products 2007-09-11


21

You might also like