m10 BW

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

.

M10-BW
Semi-welded plate heat exchanger

Applications
Heating and cooling of aggressive media. Duties in
refrigeration installations.
Standard design
The plate heat exchanger consists of a pack of corrugated
metal plates with portholes for the passage of the two fluids
between which heat transfer will take place.
The plate pack is assembled between a fix frame plate and
a movable pressure plate and compressed by tightening
bolts. The semi-welded plates combine the flexibility and
serviceability of the gasketed heat exchangers with the
assurance against leakage of the welded heat exchangers.
In the plate arrangement, every other channel is welded,
and every other channel is gasketed. The number of plates
is determined by the flow rate, physical properties of the
fluids, pressure drop and temperature program. The plate
corrugations promote fluid turbulence and support the plates
against differential pressure.
The semi-welded plate heat exchanger is provided with
gaskets specifically designed to resist aggressive media.
The non-aggressive med ia flows in the gasketed channels.
This construction means that it can easily be dismantled, for
example for exchanging gaskets or for inspection and cleaning
. the gasketed channels.
of

M10-BW

Corrosion-resistant plate materials, the absence of pressure


retaining welds, double gasket seals, and a flexible yet
vibration resistant design - to assure long life and trouble free
operation.
The frame plate and the pressure plate are suspended from an
upper carrying bar and located by a lower guiding bar, both of
which are fixed to a support column. Connections are located
in the frame plate or, if either or both fluids make more than a
single pass within the unit, in the frame and pressure plates.
Typical capacities
Liquid flow rate
Up to 50 kg/s (800 gpm), depending on media, permitted
pressure drop and temperature program.
Refrigeration duties
50-250 RT / 175-875 kW
Plate types
M10-BW
Frame types
FG, FD, FT, REF and FX

Cross section of a semi-welded plate heat exchanger

Dimensions

STANDARD MATERIALS
Frame plate
Mild steel, Epoxy painted

W
225 (8.9") or
231(9.1")

Nozzles
Metal lined: Stainless steel, Titanium, SMO, Alloy C276
H
719 (28.3")

Plates
Stainless steel: Alloy 304, Alloy 316, Titanium, Alloy 254
(SMO), Alloy C276
Gaskets
Field gaskets:

Nitrile, EPDM, Chloroprene, Viton,


FEPMAL
Ring gaskets:
Nitrile, EPDM, Chloroprene, Viton,
FEPMAL
Other grades and material available on request.
For refrigeration: Gasket design temperature range
-45C to 150C

695-2400 (27-95")

Measurements mm (inch)
Type
M10-FG
M10-FD
M10-FD ASME
M10-REF
M10-FT
M10-FX

TECHNICAL DATA
Pressure vessel codes, PED, ASME, pvcALS
Mechanical design pressure (g) / temperature
FG
FG
FG
FD
FD
FD
FDR
FT
FT
REF
FX

pvcALS
PED
ASME
pvcALS
PED
ASME
PED
PED
ASME
PED
PED

1.6 MPa / -50 to 180C


1.6 MPa / -10 to 180C
150 psig / -54F to 482F
2.5 MPa / -50 to 180C
2.5 MPa / -50 to 180C
300 psig / -54F to 482F
2.5MPa / -50 to 160C
4.0 MPa / -50 to 180C
600 psig / -54F to 482F
2.5 MPa / -50 to 150C
5.5 MPa / -50 to 150C

pvcALS
PED
ASME
pvcALS
PED
ASME
PED
ASME
PED
PED

100
100
4
100
100
4
100
4
100
100

DIN PN16, ASME CI. 150, JIS 16K


DIN PN 16, ASME CI. 150
ASME CI. 150
DIN PN25, ASME CI. 150, JIS 20K
DIN PN25, ASME CI. 150
ASME CI. 300
DIN PN40, ASME CI. 300
RLF
DIN PN25
DIN PN 16, PN25, PN63

mm
mm
mm
mm
mm
mm
mm

470
470
470
470
470
470

W
(18.5")
(18.5")
(18.5")
(18.5")
(18.5")
(18.5")

215
131
215
163
215
215

The number of tightening bolts may vary depending on pressure rating.

Maximum heat transfer surface


100m (825 sq. ft)
Particulars required for quotation
- Flow rates or heat load
- Temperature program
- Physical properties of liquids in question (if not water)
- Desired working pressure
- Maximum permitted pressure drop
- Available steam pressure

Connections
FG
FG
FG
FD
FD
FD
FT
FT
REF
FX

H
1084 (42.7")
981 (38.6")
1084 (42.7")
1110 (43.7")
1084 (42.7")
1133 (44.6")

RLF in pressure plate: M10-FG, M10-FD, M10-FT/PED, M10-FX/PED


RLF = Rectangular loose flange

Working principle
Channels are formed between the plates and the corner ports
are arranged so that the two media flow through alternate
channels. The heat is transferred through the plate between
the channels, and complete counter-current flow is created
for highest possible efficiency. The corrugation of the plates
provides the passage between the plates, supports each
plate against the adjacent one and enhances the turbulence,
resulting in efficient heat transfer.

Flow principle of a plate heat exchanger


.

PCT00134EN 1306

How to contact Alfa Laval


Up-to-date AlfaLaval contact details for
all countries are always available on our
website on www.alfalaval.com

Alfa Laval reserves the right to change specifications without prior notification.

h
(8.5")
(5.2")
(8.5")
(6.4")
(8.5")
(8.5")