Sandc Recloser
Sandc Recloser
Sandc Recloser
Specifications
Conditions of Sale
STANDARD: Sellers standard conditions of sale set
forth in Price Sheets 150 and 181 apply, except as modified
by the SPECIAL WARRANTY PROVISIONS and
WARRANTY QUALIFICATIONS on pages 6 and 7.
Synchronization check,
IntelliRupter Fault Interrupter is available in the uprightcrossarm and compact-crossarm mounting configuration,
with or without integral, hookstick-operated disconnect
for visible air-gap isolation of switched-open circuits.
The disconnect is interlocked with the interrupters to
ensure that pole-units are open prior to opening or closing
the disconnect; a status point for remote monitoring
of disconnect position is included. Interrupters may be
operated with the disconnect in the open position.
Control Groups
IntelliRupter Fault Interrupter is available with a variety
of control groups. Each features easy configuration and
operationand examination of waveforms and events
using secure wireless communication to a nearby laptop
computer.
The control group includes a base-mounted, hookstickremovable protection and control module, and communication module. This flexible, low-maintenance arrangement
offers excellent immunity to surges and noise induced
by normal power line events such as faults and lightning
strikes, and minimizes pole clutter. IntelliRupter Fault
Interrupter is powered from the distribution line, through
the integral power module(s) or the external power supply,
if furnished.
The protection and control module provides point-onwave closing to minimize asymmetric fault current and
inrush current. It features a complete set of protection and
control functions, including:
Simultaneous independent directional phase, ground,
negative-sequence, and sensitive-earth time-overcurrent,
instantaneous-overcurrent, and definite-time elements,
Directional blocking of overcurrent elements,
Over/under voltage elements,
Over/under frequency elements,
Phase unbalance detection,
Services-Only Packages
Equipment/Services Packages
Complete equipment/services packages are available
for three- through twelve-member IntelliRupter Fault
Interrupter teams, as listed in the table on page14. Each
team member includes the IntelliTeam SG Automatic
Restoration System and a SpeedNet Radio or IntelliCom DA
IntelliTeam SG Training
IntelliTeamSG training is conducted on-site and ensures
that users personnel fully understand IntelliTeam SG
functioning. Both operations and engineering sessions are
provided.
Checking each IntelliRupter Fault Interrupter for conformance with installation recommendations.
Verification that each team is capable of achieving
READY status. (Upon user request, the teams will be
disabled after verification.)
Designing and installing the communication infrastructure linking IntelliTeamSG with the users LAN.
IntelliTeam SG Monitoring
Range, kV, at 50 Hz
9 through 19.2
18.81 through 27
20 through 24
23.8 through 38
29.7 through 38
How to Order
1. Obtain the catalog number of the desired IntelliRupter
Fault Interrupter from the tables on pages 8 and9.
2. Add the suffix of the desired control power source option
from the table on page10.
3. Add the suffix of the desired control group option from
the table on page11.
4. Add the suffix(s) of desired optional features and
special optional features from the tables on page12.
5. If wide-area network capability is desired for the Standard Control Group, Standard Control Group with
Battery Backup, or Universal Control Group, add the suffix
of the desired communication device from the table on
page13.
6. If a mounting pedestal is desired for a substation application, obtain the catalog numbers of the desired mounting
pedestal and anchor bolts from the table on page 14.
Four anchor bolts are required per mounting pedestal.
7. Obtain the catalog number of the desired connectors
from the table on page14. Six connectors are required
per IntelliRupter Fault Interrupter.
8. Obtain the catalog numbers of desired accessories from
the table on page15.
Ratings
Standard
Mounting/
Operating
Arrangement
Max
BIL
15.5
110
27
125
ED-856
38
170
ED-855
15.5
110
ED-855
27
125
kV
Amperes, RMS
Cont.
Interr.
Catalog
Number
Upright-Crossarm
630
16 000
248112
12 500
248113
12 500
248114
16 000
248612
12 500
248613
Compact-Crossarm
630
-P350.
Ratings
Standard
Mounting/
Operating
Arrangement
Max
BIL
15.5
110
27
125
38
170
kV
Amperes, RMS
Cont.
Interr.
Catalog
Number
Upright-Crossarm
ED-857
630
16 000
248122
12 500
248123
12 500
248124
Voltage Range, kV LL
Suffix to be Added
to Catalog Number
11.4315.5
-P162
18.8127
-P163
23.838.0
-P165
11.4315.5
-P362
18.8127
-P363
23.838.0
-P365
11.4315.5
-P262
18.8127
-P263
23.838.0
-P265
11.4315.5
-P462
18.8127
-P463
23.838.0
-P465
-P300
912
-P151
1419.2
-P152
2024
-P153
23.033.0
-P154
912
-P351
1419.2
-P352
2024
-P353
23.033.0
-P354
912
-P251
1419.2
-P252
2024
-P253
23.033.0
-P254
912
-P451
1419.2
-P452
2024
-P453
23.033.0
-P454
-P350
Item
Standard Control GroupFor IntelliTeamSG Automatic Restoration, automatic source transfer, automatic loop restoration,
SCADA, and stand-alone (non-communicating) applications. Includes IntelliTeamSG Bronze Level Software. Optional
IntelliTeamSG Silver Level Software provides suitability for basic closed-loop applications. Optional IntelliTeamSG Gold Level
Software provides suitability for basic closed-loop applications and applications on systems with three or more sources.
No batteries are required for stand-alone applications and application with operating times of 30 seconds or less; ac line
voltage must be available on the side of the IntelliRupter Fault Interrupter with the integral power module or control power must
be available from the external power supply, if furnished.
-C0
Specify communication device, if required for the application, from Communication Devices for IntelliTeamSG, IntelliTeamII,
Automatic Source Transfer, and SCADA Applications table on page13. All team devices must be furnished with the same type
of communication device.
IntelliTeam Designer Configuration and License Management Software is required to activate IntelliTeamSG Software
Standard Control Group with Battery BackupIdentical to the Standard Control Group but additionally includes batteries
that support operation for a minimum of four hours after loss of ac line voltage on both sides of IntelliRupter Fault Interrupter,
permitting extended dead-line switching.
Specify communication device, if required for the application, from Communication Devices for IntelliTeamSG, IntelliTeamII,
Automatic Source Transfer, and SCADA Applications table on page 13. All team devices must be furnished with the same type
of communication device.
-C1
IntelliTeam Designer Configuration and License Management Software is required to activate IntelliTeam SG Software
Universal Control GroupIdentical to the Standard Control Group with Battery Backup. Includes either IntelliTeam SG Gold
Level Software and IntelliTeam Designer Configuration and License Management Software or IntelliTeam II Software License,
as specified.
For IntelliTeam SG Automatic Restoration System specify one IntelliTeam Design Slot part number 008-007006-01 and one
IntelliRupter PulseCloser Fault Interrupter Gold License part number 008-007101-01. This license requires an IntelliTeam SG
qualified communication device from the communication device options listed on page 13.
For IntelliTeam II Automatic Restoration System specify one IntelliTeam Design Slot part number 008-007006-03 and
one IntelliRupter PulseCloser Fault Interrupter IntelliTeam II License part number 008-007106-01. This license requires an
IntelliTeam II qualified communication device from the communication device options listed on page 13.
-C7
When ordering enter the selected licenses as separate line items as included in the above and specify communication device,
if required for the application, from Communication Devices for IntelliTeam SG, IntelliTeam II, Automatic Source Transfer, and
SCADA Applications table on page 12. All team devices must be furnished with the same type of communication device
Item
-B1
Includes 900-MHz, 9-dBd gain, directional Yagi antenna with female N-Type
connector, coax cable, and mounting hardware
-B2
-B3
-B12
-B13
-B14
Includes PA-50-21, 4.9- to 5.8-GHz, 23-dBi Gain, Panel Antenna (21-dBi Gain
at 4.9 to 5.1 GHz), with Azimuth/Elevation Adjustable Mount
-B16
-B17
International CratingWood products used in packaging are either hardwood or certified by the wood supplier
as being heat treated (kiln dried) to a core temperature of 133F (56C) for a minimum of 30 minutes
-M9
-M10
-M1
-M2
-M3
-M4
-M5
-M6
-M7
-M8
-N9
-N10
-N1
-N2
-N3
-N4
-N5
-N6
-N7
-N8
-N11
-N12
Ten-Year IntelliRupter Fault Interrupter WarrantyIn lieu of standard two-year warranty. Matches standard ten-year warranty
for control groups
Wildlife Protection
-L71
-T1
-W1
-W2
15.5-kV IntelliRupter Fault Interrupter furnished with interrupters tested and certified to meet 27 kV
A whip antenna is not provided when this option is specified. If a whip
-Z3
Reversed Colors for Interrupter Open/Closed Indicators and Open/Close/Ready Lever (green for closed, red for open)
Suffix to be Added
to Catalog Number
-F2
Item
Communication Devices Suitable for IntelliTeam SG, IntelliTeam II, Automatic Source Transfer, and SCADA Applications
Factory-Installed and Wired S&C SpeedNet Radio, providing high-speed network communication via DNP 3.0 protocol, and
900-MHz, 5-dBi gain antenna with male N-Type connector
-R80
-R201
-R139
-R140
Communication Device Suitable for IntelliTeam II, Automatic Source Transfer, and SCADA Applications Only
Factory-Installed and Wired UtiliNet Series IV IWR Radio, providing communication via DNP 3.0 protocol, and 900-MHz, 5-dBi
gain antenna with male N-Type connector
-R67
Communication Devices Suitable for Automatic Source Transfer and SCADA Applications Only
Factory-Installed and Wired Single-Mode Dymec 5843SHRT Fiber-Optic Modem
-R44
-R45
-R42
-R43
Factory-Installed and Wired MDS TransNET 900 Transceiver and 900-MHz, 5-dBi gain antenna with male N-Type
connector
-R18
Factory-Installed and Wired MDS TransNET 900 Transceiver with Diagnostics and 900-MHz, 5-dBi gain antenna with male
N-Type connector
-R19
These are the only wide-area network communication devices
approved for use with IntelliRupter Fault Interrupter. For other communication devices, refer to the nearest S&C Sales Office.
A Multi-Mode Mating Connector and Termination Kit or a Multi-
band range and application for the radio, from the following table. For
example, for a 928- to 960-MHz MDS SD9 Radio for Ethernet and serial
application, specify Catalog Number Suffix -R216CL.
Frequency Band Range, MHz
Application
Suffix to be Added
to Catalog Number
820 to 870
-R216AK
928 to 960
-R216CK
-R216DK
880 to 915
880 to 915, 50-kHz Channel
-R216EK
Serial
-R216FK
-R216GK
-R216HK
Application
Suffix to be Added
to Catalog Number
820 to 870
-R216AL
928 to 960
-R216CL
-R216DL
880 to 915
880 to 915, 50-kHz Channel
Ethernet
and Serial
-R216EL
-R216FL
-R216GL
-R216HL
820 to 870
-R216AM
928 to 960
-R216CM
-R216DM
880 to 915
880 to 915, 50-kHz Channel
9710
Emulation
-R216EM
-R216FM
-R216GM
-R216HM
Catalog Number
Single-Mode Mating Connector and Termination KitIncludes connector hood, inserts, and fiber termination components
SD-6607
Multi-Mode Mating Connector and Termination KitIncludes connector hood, inserts, and fiber termination components
SD-6608
48-Foot Single-Mode Liquid-Tight Cable AssemblyIncludes pre-terminated mating connector on one end and ST connector
on other end
SD-6609
48-Foot Multi-Mode Liquid-Tight Cable AssemblyIncludes pre-terminated mating connector on one end and ST connector
on other end
SD-6610
Custom-length cable assemblies can be furnished. Refer to the
Catalog Number
SDA-4813-1
SDA-4813-2
S-81365-1
Anchor Bolt138 (25 mm1118 mm). Four required per mounting pedestal
Galvanized steel. Furnished with two hex nuts and two flat washers to
Connectors
Illustration
Description
Accommodating Conductor
Catalog Number
4740R1
4741R2
Provision only for compression connectors. Includes two 132 Galvanized Steel Bolts
4581
Catalog Number
Battery Charger Output HarnessFor connecting battery pack to an 800-mA, current-limited 12-Vdc lead-acid
battery charger
007-001551-01
Module Handling FittingFor field installation and removal of protection and control module, and communication module,
in IntelliRupter Fault Interrupter base. Attaches to hookstick with universal fitting. Includes prong for operating IntelliRupter
Fault Interrupter levers
4450
Module Stub HandleFor installation and removal of protection and control module, and communication module, in
IntelliRupter Fault Interrupter basein users service center or lab. When permitted by utility operating practice, this handle
can be used by a gloved individual to install and remove modules in the field
4435
Pre-Configured Laptop Computer14-inch Dell computer with 2-MB RAM, 80-GB hard drive, and factory-loaded IntelliLink
Setup Software
7031-986
WiFi Tester. Simulates connection to communication module. Confirms users laptop computer is properly configured to
establish secure WiFi connection to IntelliRupter Fault Interrupter. Also demonstrates use of WiFi security keys. For indoor use
only, in users service center or lab
908-000961-01
Detailed Instruction ManualBinder containing printed copies of all IntelliRupter Fault Interrupter instruction sheets, erection
drawings, and reference drawings (detailing, for example, installation of optional features such as surge arresters and bracketmounted antennas)
RD-6949
SDA-4540
SDA-4554-1
SDA-4605
SEL AutoRANGER Model AR8-OH Faulted Circuit Indicators, Set of ThreeDetects and provides visible indication
of fault current passage. User-installed on each phase conductor. Eight-hour reset time
SDA-4625
Docking StationPowers protection and control module, and communication module, removed from IntelliRupter Fault
Interrupter base. Permits uploading and downloading of configuration settings, plus programming of radio and charging of radio
batteries, as applicable, in users service center or lab
SDA-4650R2
Indoor Power SupplyAttaches to external power supply connector in base. Powers protection and control module, and
communication module, for pre-installation uploading and downloading of configuration settings, plus radio programming
and battery charging, as applicable. For indoor use only, in users service center or lab. Input voltage range is 88264 Vac,
50/60 Hz
TA-3221
External Power SupplyFor use with a pedestal-mounted IntelliRupter Fault Interrupter in a substation. Enables use of
preferred and alternate control power sources, and can be installed in combination with integral power modules. Preferred
source input voltage range is 90159 Vac, 50/60 Hz, alternate source input voltage range is 90159 Vac, 50/60 Hz, 1960 Vdc,
or 100360 Vdc
SDA-4910
904-000071-00
904-002216-01
Three-Member Team
Four-Member Team
Five-Member Team
15.5-kV IntelliRupter PulseCloser Fault Interrupter/Services Packages
Each package includes Non-Disconnect Style IntelliRupter PulseCloser Fault Interrupters Catalog Number
248112P262C1N4R80W1 or 248112P262C1N4R201W1. Each IntelliRupter Fault Interrupter includes two Integral
Power Modules for use on 11.43kV to 15.5kV, 60Hz systems, Standard Control Group with Battery Backup, with
SpeedNet Radio or IntelliCom DA Mesh Radio, six 15kV Surge Arresters, and Wildlife Protection. One SpeedNet
Extension-Arm-Mounted Repeater Radio or IntelliCom WAN Mesh Radio is also included. Services furnished
include communication site survey, IntelliTeamSG factory acceptance testing, IntelliRupter Fault Interrupter training,
IntelliTeamSG training, and IntelliTeam SG commissioning
Six-Member Team
Seven-Member Team
Eight-Member Team
Nine-Member Team
Ten-Member Team
Eleven-Member Team
Twelve-Member Team
Three-Member Team
Four-Member Team
Five-Member Team
Six-Member Team
Seven-Member Team
Eight-Member Team
Nine-Member Team
Ten-Member Team
Eleven-Member Team
Twelve-Member Team
Three-Member Team
Four-Member Team
Five-Member Team
Six-Member Team
Seven-Member Team
Eight-Member Team
Nine-Member Team
Ten-Member Team
Eleven-Member Team
Twelve-Member Team
Catalog Number
Communication Site Survey. Field testing to confirm that user-proposed IntelliRupter Fault Interrupter locations will provide
acceptable communication between team members and head-end SCADA radio, if applicable. User should make available their
engineer/technician responsible for the project
AS100
IntelliTeam SG Training. On-site training on functioning of IntelliTeam SG. Includes operations and engineering training sessions
AS101
IntelliTeam SG Commissioning. Ensures that IntelliRupter Fault Interrupters have been set up correctly and IntelliTeamSG is
ready to be put into service
AS102
IntelliTeam SG SCADA Integration. Includes review of users SCADA system, development of DNP points lists, coordination with
the users SCADA supplier, and review of SCADA database
AS103
IntelliTeam SG Factory Acceptance Testing. Factory testing ensures that all information required for successful IntelliTeamSG
implementation is gathered and understood prior to commissioning. Provides insight on how IntelliTeamSG will work on the
users system. User must travel to Chicago to witness the testing
AS104
IntelliTeam SG Monitoring. Ongoing remote monitoring ensures that IntelliTeamSG operation meets agreed-upon service levels.
Minimum monitoring period is six months
AS105
IntelliRupter Fault Interrupter Maintenance. Includes inspection, testing, and battery replacement on a three-year interval
AS106
IntelliRupter Fault Interrupter Project and Construction Management. Includes IntelliRupter Fault Interrupter installation,
construction oversight, and EPC projects
AS107
Overcurrent Protective Device Coordination Study. Determination of appropriately rated protective devices and their settings,
including those of IntelliRupter Fault Interrupters. Proper coordination minimizes the impact of short-circuits, by isolating faults as
quickly as possible, while maintaining power to the rest of the system
AS108
IntelliTeam SG Device Settings Determination. Determination of these settings is essential to the successful implementation of
IntelliTeamSG, and must be documented prior to factory acceptance testing and commissioning
AS109
Loop Restoration Training. Covers setup, configuration, and operation of IntelliRupter Fault Interrupters in a loop application
comprised of normally-closed IntelliRupter Fault Interrupters or conventional reclosers, with a normally-open IntelliRupter Fault
Interrupter switching point
AS110
IntelliRupter Fault Interrupter Training. Covers IntelliLink Setup Software; configuring IntelliRupter Fault Interrupter for use in an
IntelliTeamSG, source-transfer, or loop restoration system, as appropriate; use of security keys; and operation
AS111
IntelliRupter Fault Interrupter Secondary Injection Testing. Validates settings, functions, and logic of IntelliRupter Fault
Interrupter protection and control module using Omicron testing equipment
AS112
Voltage Rating
15.5
27
38
110
125
170
50
60
70
45
50
60
Current Ratings
IntelliRupter Fault Interrupter Maximum Voltage Rating, kV
Current Rating
15.5
27
38
630
630
630
800
800
800
16 000
12 500
12 500
31 000
31 000
31 000
21 600
21 600
21 600
2 400
2 400
2 400
10
25
40
Number of Operations
IntelliRupter Fault Interrupter Maximum Voltage Rating, kV
Operations Rating
15.5
27
38
1520
44
44
44
4555
56
56
56
90100
16
16
16
10
10
10
20
20
20
20
20
20
10 000
10 000
10 000
Rating
15.5
27
38
-40 to +40
-40 to +40
-40 to +40
0.5
0.5
0.5
0.5
0.5
0.5
2.0
2.0
2.0
.75 (19)
.75 (19)
.75 (19)
IntelliRupter Fault Interrupter Certified Test Abstracts and Engineering Test Reports
Description
Description
Standard
CERT-696
Temperature Rise
CERT-697
CERT-698
CERT-699
CERT-700
CERT-701
CERT-705
CERT-706
IEEE C37.60-2003
CERT-719
CERT-722
IEEE C37.60-2003
CERT-766
CERT-772
CERT-896
CERT-897
CERT-898
Dielectric Ratings, 38 kV
CERT-900
TR 13737-A1
IEEE C37.60-2003
TR 14893
IEEE 1247-2005
8
(213)
(16) TYP.
1 (38) TYP.
1 (44) TYP.
1
(44)
(6)
3
(76)
(16)
1
(44)
20
(530)
(16)
3
(76)
1
(44)
15
(387)
(19)
(16)
1 (38)
2 (51)
1 (44)
1 (44)
16
(406)
15
(381)
12
(305)
22
(581)
11
(298)
49
(1254)
11
(298)
16
(410)
4 (102) TYP.
TOP VIEW
24
(610)
6116
(154)
24
(610)
32
(813)
8
(210)
8
(210)
2 (51) TYP.
FRONT VIEW
Ratings
kV
Max
15.5
Amperes, RMS
BIL
Continuous
Catalog Number
Interrupting
110
16 000
248112
12 500
248113
630
27
Net Wt.,
Assembled,
Lbs. (kg)
835 (378)
125
(6)
(6)
21
(543)
12
(308)
42
(1080)
29
(749)
SIDE VIEW
2
(51)
.250
(6)
(6)
15
15
(381)
(381)
10
10
(254)
10
(254)
8
8
(203)
(203)
6116
(154)
9
(229)
24
(610)
TOP VIEW
32
(813)
48
(1219)
2
(51)
9
(229)
(6)
5
(127)
FRONT VIEW
24S&C Specification Bulletin 766-31
2
(51)
Ratings
kV
Max
38
Amperes, RMS
BIL
Continuous
Interrupting
170
630
12 500
Catalog Number
Net Wt.,
Assembled,
Lbs. (kg)
248114
890 (403)
3
(76)
1
(44)
(16)
21
(533)
(16)
36
(914)
3
(76)
1
(44)
13
(330)
SIDE VIEW
PEDESTAL
TOP VIEW
51
(1314)
18
(457)
18
(457)
7
(200)
4716
(113)
2 (70)
FRONT VIEW
Ratings
kV
Max
Amperes, RMS
BIL
15.5
Continuous
Catalog Number
Interrupting
110
16 000
248612
12 500
248613
630
27
Net Wt.,
Assembled,
Lbs. (kg)
700 (317)
125
49
(1257)
221516
(582)
20
(520)
6
(156)
15
(387)
1
(29)
19
(482)
1
(44)
9
(248)
1
(35)
401316
(1036)
43
(1104)
14
(355)
531516
(1369)
20
(508)
SIDE VIEW
22
(581)
11
(298)
66
(1689)
33
(841)
7 (191)
4 (102) TYP.
TOP VIEW
9
(251)
24
(610)
24
(610)
32
(813)
8
(210)
8
(210)
2 (51) TYP.
FRONT VIEW
Ratings
kV
Max
15.5
Amperes, RMS
BIL
Continuous
110
Catalog Number
Interrupting
16 000
248122
12 500
248123
630
27
Net Wt.,
Assembled,
Lbs. (kg)
1033 (467)
125
316 (5)
(6)
43
(1111)
12
(308)
20
(521)
29
(749)
SIDE VIEW
2
(51)
(6)
10
(254)
12
(305)
27
(686)
14
(356)
2
(51)
(102)
TOP VIEW
48
24
6116
(154)
32
(813)
(1219)
(610)
(229)
(51)
18
(457)
FRONT VIEW
30S&C Specification Bulletin 766-31
Ratings
kV
Max
38
Amperes, RMS
BIL
Continuous
Interrupting
170
630
12 500
Catalog Number
Net Wt.,
Assembled,
Lbs. (kg)
248124
1063 (482)
15
(381)
1
(44)
4
(76)
(16)
7
(178)
(16)
1
(44)
3
(76)
1 (44)
16
(406)
1
(44)
15
(381)
12
(305)
SIDE VIEW
10
(257)
(22)
2 DIA. (51)
25
(641)
22
(568)
1316 (21)
Dimension
Description
Dry Arcing
Distance, inches
(mm)
Leakage Distance,
inches (mm)
Leakage at 15 kV,
mm/kV
Leakage at 27 kV,
mm/kV
14 (359)
34 (864)
57
32
Interrupter
11 (292)
38 (965)
64
35
Insulator
18 (457)
37 (940)
62
34
Push Rod
15516 (389)
31 (795)
53
29
Dry arcing distance is the shortest distance between the metal sur-
A 18
(457)
Dimension
16
(406)
Description
12
(305)
15
D
(381)
Dry Arcing
Distance, inches (mm)
Leakage Distance,
inches (mm)
Leakage at 38 kV,
mm/kV
18 (457)
46 (1178)
31
Interrupter
12 (305)
46 (1178)
31
Insulator
16 (406)
46 (1178)
30
Push Rod
18 (457)
47 (1207)
31
Dry arcing distance is the shortest distance between the metal
13
(337)
14
(356)
2364
(52)
132764
(341)
6
(152)
6
(171)
11
(292)