Doc. No.
: FEI/AE/C002
Date/Rev.: 26.11.13/0
BBL PMSM Machine
D. Basic Parameter List to run the PMSM:
No
Establishment item
Default value
Set Value
F03
Maximum Speed
1800
Motor Data
F04
Rated Speed
1500
Motor Data
F05
Rated Voltage
380
Motor Data
F07
Acceleration/Deceleration Time 1
F08
Acceleration/Deceleration Time 2
2.5
As per site
requirement
F42
Control Mode Selection
For PMSM
E01
Terminal [X1] Function
E02
Terminal [X2] Function
E03
Terminal [X3] Function
E24
Terminal [Y5A/C] Function
74
12
MC Control
E27
Terminal [30A/B/C] Function
99
57
Brake Control
C05
Run Speed
As per
requirement
As per connection
C06
Maintenance speed
20.0
P01
Motor 1 (Num. of poles)
Motor Data
P02
Motor 1 (Rated capacity)
P03
Motor 1 (Rated current)
L01
Pulse encoder
As per drives
rating
As per drives
rating
0
Motor Data
Motor data
Digital I/P for
Speed as per
controller logic
As per connection
Motor Data
Motor Data
As per PG
card
As per
encoder
L02
Resolution
1024
L36
P constant at High speed
40.0
2.0
L31
Elevator speed (m/min)
60
As per
requirement
L38
P constant at low speed
40.0
2.0
Encoder data
motor data
Note: Parameters marked in yellow are sufficient to run the motor in Local mode through keypad.
Page 9 of 10
BBL PMSM Machine
Doc. No.: FEI/AE/C002
Date/Rev.: 26.11.13/0
E. Encoder Pole tuning procedure:
To perform the described procedure the enable (EN) input must be active.
1. Connect the motor and encoder properly.
2. Apply power to the inverter.
3. The functions mentioned in the table above must be set.
4. Set function L03 to 1 and press FUNC/DATA key.
5. Give RUN command to the inverter from the lift controller (normally in Local or
INSPECTION mode). The main contactors will be closed and current will flow through the
motor producing some acoustic noise. This procedure will take some seconds. After the
procedure was finished correctly the offset value is saved and shown in function L04.
Write down the displayed value.
If Er7 is displayed check the motor and encoder cabling and repeat steps 5 and 6 or connect
motor directly to the drive.
6. If possible, open the brake and let the cabin move some centimeters.
7. Perform steps 5 and 6 again. The result in function L04 between different measurements
must not differ more than 15.
F. Motor Auto Tuning Procedure:
1. Connect the motor.
2. Turn on the mains supply.
3. Put the controller in inspection mode.
4. Set P04 to 1 (Auto tuning mode 1), press FUN/DATA button on the keypad.
5. Press Inspection switch to give run command to the Drive or give the run command to the
drive in local mode & keep pressing it; the O/p Contactor will become ON.
6. The current flowing through the motor winding will generate sound.
7. The auto tuning takes few seconds.
8. After completion of auto tuning, the O/p Contactor will drop automatically; it means the auto
tuning procedure has been finished.
Now, Motor is ready to run.