Modbus Intro
Modbus Intro
If you have a software application program that uses Modbus, you can skip to the Modbus
Register listing in this document for the address information your program will need. The rest of
this section provides the information you will need to write your own software application using
Modbus RTU.
Modbus RTU
Messages are coded in eight-bit bytes, with one start bit and one stop bit, no parity bit is used
(8,N,1). Negative values are written in twos compliment format. Parameters are read from, or
written to, 16 bit registers (two-byte) using an absolute address.
Message packets are separated by a pause of at least 3 character times(30 bits). The packet must
be sent in a continuous stream with an inter-character interval of no greater than 1.5 character
times (15 bits). Messages that begin without a 30 bit silent interval or have an inter-character
interval greater than 15 bits are ignored.
Each message packet uses the following syntax.
The first byte is a 1 byte instrument address, Love Controls uses addresses 0x01 through 0xFF.
The second byte is the command, read status (0x01 or 0x02), read register (0x03 or 0x04), write
register (0x06 or 0x10), or loop back (0x08).
The next n bytes are the register address and / or data.
The last two bytes are for error checking and contain the CRC16 generated on the message
bytes.
Address
##
Command
##
Reg. / Data
####.......
CRC
####
##
##
High byte
Low byte
Register Data
##
Low byte
CRC
##
Low byte
CRC
##
High byte
CRC
##
High byte
CRC
Example:
Read the Process Value register (0x0001) from instrument at address 50 (0x32).
Sent:
32 03 00 01 00 01 D0 09
Received:
32 03 02 00 64 BD AB
Data:
100 (0x0064)
##
##
High byte Low byte
Register Data
##
Low byte
CRC
##
High byte
CRC
Example:
Write 257 (0xC8) to the SP1 register (0x0101) of instrument at address 50 (0x32).
Sent:
32 06 01 01 00 C8 DD A3
Received:
32 06 01 01 00 C8 DD A3
00
01
High byte Low byte
Number of registers
##
Low byte
CRC
##
H. byte
CRC
##
High byte
CRC
Example:
(0x32).
Sent:
32 10 01 01 00 01 02 00 AF B7 CC
Received:
32 10 01 01 00 01 54 36
00
01
High byte Low byte
Number of points
##
Single Byte
Register Data
##
Low byte
CRC
##
Low byte
CRC
##
High byte
CRC
##
High byte
CRC
The single byte of data returned contains the requested Status bit in the LSB (0000000#),
status is indicated as 1 = ON and 0 = OFF.
Example:
Sent:
32 02 00 03 00 01 4C 09
Received:
32 02 01 01 6F 0C
Data:
1 (0x01)
##
High byte
Data
##
Low byte
Data
##
Low byte
CRC
Example:
Sent:
32 08 12 34 82 29
Received:
32 08 12 34 82 29
##
High byte
CRC
Exception Codes
Commands that cannot be processed by an instrument will cause an exception code to be
returned. These messages are identified by the command byte returned having its high bit
set, i.e. +(0x80).
Exception codes supported by Love Controls instruments are as follows:
0x01 Illegal Command
0x02 Illegal Address
0x03 Illegal Data
Message returned by instrument:
##
##
Instrument
Command
Address
+ 0x80
##
Exception
Code
##
Low byte
CRC
##
High byte
CRC
Messages sent with the wrong CRC, format or timing are ignored by the instrument.
The broadcast command (write to instrument address 0x00) is not supported.
Example:
Sent:
32 02 01 07 00 01 0C 34
Received:
32 82 01 71 6F
Example:
Sent:
32 04 01 02 00 01 94 35
Received:
32 84 02 32 CE
Example:
Cannot write 10,000 (0x2710) to SP1 (0x0101), Illegal data value (Exception 03)
Sent:
32 06 01 01 27 10 C6 09
Received:
32 86 03 F2 6E
CRC Calculation
The last two bytes of all messages contain the CRC value. The CRC is calculated for the
message being transmitted and is appended to the message. The receiving device recalculates
a CRC for the message it receives. If the two CRC values do not match, the message is ignored
by the receiver.
The CRC is calculated by first loading a 16 bit register with all 1s (0xFFFF), this register
will hold the final CRC value. A second 16 bit register is loaded with a constant (0xA001).
Each eight bit character is then applied to the CRC register using the following procedure.
1. The eight bit character is Exclusive ORed with the CRC register.
2. The CRC register is then shifted one bit toward the LSB (least significant bit) and a zero
placed in the MSB (most significant bit).
3. The LSB from the result of the Exclusive OR between the CRC and the eight bit character is
then examined, if the LSB is a 1 then the CRC is Exclusive ORed with the constant, if the
LSB is a 0 no Exclusive OR is performed.
4. The eight bit character is then shifted one bit toward of the LSB and a zero is placed in the
MSB.
Steps 1 through 4 are repeated for all eight bits of the character, then the process is repeated for
the next character. Once all the message characters have been processed the CRC register will
contain the final CRC value. When the CRC is appended to the message, the byte order is
reversed. As an example, a CRC of 0x0A84 will be appended as 0x840A
A sample CRC calculation program written for QBASIC is supplied on the next page.
REM
CRC16.BAS
REM if message for crc is 010300000001 crc = 0A84 (0A high byte, 84 low byte)
REM if message for crc is 320301010001 crc = D1F5
crc = &HFFFF&
polynomial = &HA001&
msg$ = "320301010001"
ptr = 1
DO WHILE ptr < LEN(msg$)
num$ = "&h" + (MID$(msg$, ptr, 2))
num = VAL(num$)
ptr = ptr + 2
cnt = 8
DO WHILE cnt > 0
temp = num XOR crc
crc = INT(crc / 2)
IF (temp AND 1) THEN crc = crc XOR polynomial
num = INT(num / 2)
cnt = cnt - 1
LOOP
LOOP
PRINT "crc", HEX$(crc): REM The CRC is generated in high byte, low byte order
END:
REM but the order is reversed in the actual message.