Toshiba GRB150B
Toshiba GRB150B
Toshiba GRB150B
INSTRUCTION MANUAL
HIGH-IMPEDANCE DIFFERENTIAL RELAY
GRB150 - B
( Ver. 1.0)
6 F 2 S 0 7 9 0
Safety Precautions
Before using this product, please read this chapter carefully.
This chapter describes the safety precautions recommended when using the GRB150. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
DANGER
WARNING
CAUTION
CAUTION
6 F 2 S 0 7 9 0
DANGER
Current transformer circuit
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING
Exposed terminals
Do not touch the terminals of this equipment while the power is on, as the high voltage generated
is dangerous.
Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply.
It takes approximately 30 seconds for the voltage to discharge.
Fiber optic
When connecting this equipment via an optical fibre, do not look directly at the optical signal.
CAUTION
Earth
The earthing terminal of the equipment must be securely earthed.
CAUTION
Operating environment
The equipment must only used within the range of ambient temperature, humidity and dust
detailed in the specification and in an environment free of abnormal vibration.
Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that
they conform to the equipment ratings.
Printed circuit board
Do not attach and remove printed circuit boards when the DC power to the equipment is on, as
this may cause the equipment to malfunction.
External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
Connection cable
Carefully handle the connection cable without applying excessive force.
Modification
Do not modify this equipment, as this may cause the equipment to malfunction.
Disposal
When disposing of this equipment, do so in a safe manner according to local regulations.
6 F 2 S 0 7 9 0
Contents
Safety Precautions
1.
Introduction
2.
Application Notes
2.1
2.2
2.3
2.4
2.5
3.
7
8
8
8
10
10
11
11
12
12
12
13
13
Technical Description
14
3.1
3.2
14
19
19
20
21
21
21
22
23
23
24
24
25
26
26
3.3
3.4
3.5
4.
Application
High-impedance Differential Protection
2.2.1 Principle of operation
2.2.2 Through Fault Stability
2.2.3 Current Transformer Requirements
2.2.4 Fault Setting or Primary Operating Current
2.2.5 Peak Voltage Developed under Internal Fault Conditions
2.2.6 CT Supervision
Scheme Logic
2.3.1 High-impedance Differential Protection
2.3.2 Cold Load Protection
Setting
Tripping Output
Hardware Description
Input and Output Signals
3.2.1 Input Signals
3.2.2 Binary Output Signals
Automatic Supervision
3.3.1 Basic Concept of Supervision
3.3.2 Relay Monitoring
3.3.3 Failure Alarms
3.3.4 Trip Blocking
3.3.5 Setting
Recording Function
3.4.1 Fault Recording
3.4.2 Event Recording
3.4.3 Disturbance Recording
Metering Function
User Interface
27
4.1
27
27
29
30
30
32
4.2
6 F 2 S 0 7 9 0
4.3
4.4
4.5
4.6
5.
6.
35
38
41
42
54
57
57
58
58
Installation
59
5.1
5.2
5.3
5.4
5.5
Receipt of Relays
Relay Mounting
Electrostatic Discharge
Handling Precautions
External Connections
59
59
59
59
60
61
6.1
6.2
61
62
62
62
63
64
64
65
65
66
67
67
70
70
71
71
71
72
72
72
73
74
74
6.3
6.4
6.5
6.6
6.7
7.
75
6 F 2 S 0 7 9 0
Appendix A Block Diagram
77
79
81
Appendix D Details of Relay Menu and LCD & Button Operation Instruction
83
93
97
101
105
Appendix I
109
113
117
121
125
137
Appendix O Ordering
139
The data given in this manual are subject to change without notice. (Ver. 1.0)
6 F 2 S 0 7 9 0
1. Introduction
The GRB150 is a numerical high-impedance differential relay for busbar protection and restricted
earth fault protection.
The GRB150 is a member of the G-series numerical single-function relays which are built on
common hardware modules and equipped with the following functions:
Human interfaces on relay front panel, local and remote PCs
2 16 character LCD and keypad
RS232C and RS485 communication ports
Metering and recording of events, faults and disturbances
IRIG-B time synchronisation
Automatic supervision
User configurable binary output
6 F 2 S 0 7 9 0
2. Application Notes
2.1
Application
The GRB150 provides high-impedance differential protection scheme and is applied for the
following protections:
Restricted earth fault protection
Single or one-and-a-half busbar protection
T zone protection of one-and-a-half busbar arrangement
Short line cable protection
The high-impedance differential protection detects a fault even if the CT is saturated by fault current.
The GRB150 provides the following metering and recording functions.
Metering
Fault records
Event records
Disturbance records
The GRB150 provides the following human interfaces for issuing alarms, setting relay
parameters or viewing stored data.
Relay front panel: LCD, LED display and operation keys
Local PC
Remote PC
The relay can be integrated with a local PC or a remote PC through a communication port.
A local PC can be connected via the RS232C port on the front panel of the relay. A remote PC can
also be connected through the RS485 port on the rear panel of the relay.
IEC60870-5-103 protocol is provided for communication with substation control and automation
systems.
The GRB150 has two models, model 101 and model 201. The model 101 is used for single-phase
applications and for restricted earth fault protection. The model 201 is used for three-phase
applications and for three-phase busbar, T zone and short line cable protection.
6 F 2 S 0 7 9 0
2.2
Busbar
EB-101 or
Resistor
EB102
EB-101 or
Resistor
EB102
GRB150
Varistor
GRB150
Varistor
In the case of an internal fault the current transformer secondary currents will be in the same
direction and their sum will correspond to the total primary fault current. The corresponding
driving voltages will be in the same direction and a high voltage will be developed in the
differential circuit as it attempts to drive the secondary current through the burden presented by
the high-impedance relay. Dependent upon its setting the voltage relay will operate.
Note that in Figure 2.2.1 an external unit, either type EB-101 for single-phase protection or
EB-102 for three-phase protection has been shown. These include a varistor to limit the high
voltage developed in the differential circuit during internal faults and a series resistor to fix the
relay input impedance at 667ohms. Refer to Sections, 2.2.4 Fault Setting or Primary Operating
Current and 2.2.5 Peak Voltage Developed under Internal Fault Conditions.
6 F 2 S 0 7 9 0
Busbar
EB-101 or
EB102
Resistor
GRB150
Varistor
In this example an external fault is fed through a single circuit with the fault current being
supplied through all of the other circuits connected to the busbar. Since the total busbar current
has to be transformed by the current transformer on the faulted feeder there is a high probability
of this current transformer saturating whilst the current transformers on the other more lightly
loaded circuits remain unsaturated. Under these conditions a secondary current will flow in the
differential circuit that is equivalent to the primary fault current. The voltage drop caused by the
secondary current that flows in the differential circuit therefore determines the voltage input at the
relay.
In the equivalent circuit the shunt impedance for the fully saturated CT is negligible and the CT
will not produce an output, this is shown as a short circuit across the excitation impedance in
Figure 2.2.3.
Busbar
RS1
RL1
RL2
GRB150 +
ZR EB-101/
EB-102
CT1 ZE1
Figure 2.2.3
RS2
ZE2
CT2
The total voltage drop is therefore due to the secondary fault current through the secondary
winding resistance of the saturated CT together with the wiring connecting it to the relay circuit
terminals. Provided that the relay setting voltage exceeds the value of VR in Equation (1) the
scheme will remain stable.
6 F 2 S 0 7 9 0
VR K1 (RS2 + RL2) IFmax/N
(1)
where,
VR : maximum voltage developed across the relay circuit
K1 : safety factor for the GRB150, K1=1.2
RS : resistance of current transformer secondary winding
RL : resistance of secondary wiring for CT connecting lead loop
most onerous case
IFmax : maximum through fault current
N
: CT ratio
Factor K1 is associated with the design of the GRB150 relay and directly relates to its inherent
capability to block the unidirectional transient component of the fault current. This is based on
previous service experience and extensive laboratory tests.
In addition to K1 an inherent safety factor exists because the basic assumption of complete
saturation of one current transformer with no ratio error of the complementary one is an extreme
case of unbalance. In practice it is unlikely to occur as when one current transformer begins to
saturate its burden is transferred to the other current transformer(s) due to the fact that they are of
the same construction and experience the same secondary voltage.
All current transformers used in the scheme shall have the same turns ratio
All current transformers shall be of the low reactance type class X as specified in B.S.3938 in
terms of turns ratio, knee point voltage, secondary winding resistance and secondary exciting
current
Bushing or toroidal current transformers with fully distributed windings and low leakage flux
shall be used.
For an internal fault it is essential that the current transformer(s) produce sufficient output to
operate the relay. In order to achieve this, cater for any current transformer ratio errors and ensure
a high speed of operation the current transformers should have a VK of at least twice that of the
relay setting voltage as stated above.
A setting example is provided in Appendix L.
10
6 F 2 S 0 7 9 0
currents are not in-phase and hence the summation should be vectorial. However, an arithmetic
addition is acceptable resulting in the calculated setting being slightly higher than the actual
setting.
Imin = (n.Ie + Ir + I)N
(2)
where,
Imin : minimum primary operating current
n
Ie
Ir
: varistor current at GRB150 setting voltage, this is obtained from the varistor V-I
characteristic
: CT ratio
If the value calculated for Imin is too low the sensitivity can be reduced by the use of a shunt
resistor connected across the relay/varistor unit input.
A setting example is provided in Appendix L.
2.2.6 CT Supervision
The DIFSV element provides CT supervision to detect any unbalance in the CT secondary circuit
in the event of a fault in the wiring or the CT itself. The voltage setting of this element must be
greater than any erroneous voltage that can be developed under normal service conditions. The
two main sources of error are: CT turns ratio error
Differences in the respective lengths of the CT secondary connecting leads to the
paralleling point of the differential circuit
The setting of the DIFSV element is best illustrated with an example which is given in Appendix
L.
11
6 F 2 S 0 7 9 0
2.3
Scheme Logic
2.3.1
11, 12 , 13
DIF
28
Tripping
output relay
TP-1
&
0.2 s
(Trip1)
TP-2
0
14, 15, 16
DIFSV
t
&
TVDSV
t
0
(Trip2)
1
27
0 .01 s
VD ERR
(Alarm)
&
0.1 0 - 60 .0 0s
[VDCHK]
[SVCNT]
"A LM&BLK "
"ON"
2.3.2
TCLP
Function 1
BI1 COMMAND
&
Off
0.01100.00s
1 [CLPTST]
Function 2
1
[CLEN]
F1
F2
Off
&
TCLE
t 0
&
COLD LOAD
1
N-CL
CL
TCLR
0
0.00100.00s 0.00100.00s
12
&
6 F 2 S 0 7 9 0
Two separate operational functions are available and they depend on the status of binary input
BI1. (Refer to Appendix N.)
- Function 1: used when CB closing command is allocated to BI1 input.
- Function 2: used when CB contact is allocated to BI1 input.
These functions are selected by the scheme switch [CLEN].
When using the CB close command function, set [CLEN] to F1.
When using the CB contact, set [CLEN] to F2.
If the cold load protection is disabled, set [CLEN] to OFF.
The [CLPTST] switch is used for testing purposes please refer to Section 4.2.7.1.
The timing chart of cold load status judgment is shown in Appendix N.
If the cold protection is not to be used and BI1 is to be used for Indication Reset, then scheme
switch [IND. R] must be set to ON.
2.3.2.2
If cold load status has been determined, then the operation sensitivity of DIF is modified from
([DIF] setting value) to ([DIF] setting [DIFCC] setting value).
2.4
Setting
The following list shows the setting elements for the high-impedance differential protection and
their setting ranges.
Element
Range
Step
Default
Off / On
On
[CLEN]
Off / F1 / F2
Off
[IND. R]
Off / On
[SVCNT]
ALM&BLK / ALM
ALM&BLK
DIF
10 - 600V
1V
100 V
DIFSV
5 - 100V
1V
50 V
TVDSV
0.10 - 60.00s
0.01s
0.50 s
DIFCC
1.00 10.00
0.01
1.00
TCLP
0.01 100.00s
0.01s
0.01 s
TCLE
0.00 100.00s
0.01s
0.00 s
TCLR
0.00 100.00s
0.01s
0.00 s
[VDCHK]
2.5
On
Tripping Output
As shown in Figure 2.3.1, two high-speed tripping output relays TP-1 (Trip 1) and TP-2 (Trip 2)
are provided and each relay has one normally open contact.
The tripping output relays reset 200ms after the tripping signal disappears when the fault is
cleared. The tripping circuit must be broken using one of the circuit breaker auxiliary switch
contacts prior to the tripping relay being reset to prevent the tripping relay from directly
interrupting the tripping current of the circuit breaker.
13
6 F 2 S 0 7 9 0
3. Technical Description
3.1
Hardware Description
Case outlines of GRB150, EB-101 and EB-102 are shown in Appendix E.
The hardware structure of GRB150 is shown in Figure 3.1.1.
The GRB150 relay unit consists of the following hardware modules. These modules are fixed to
the front panel and cannot be taken off individually. The human machine interface module is
provided with the front panel.
Binary input and analogue input module (DI/AI)
Main processing module (MPU)
Binary output and communication module (DO/COM)
Human machine interface module (HMI)
The hardware block diagram of GRB150 is shown in Figure 3.1.2.
Frame
DI / AI
DO/COM
HMI
IN SERVICE VIEW
TRIP
ALARM
TESTING
MPU
(back of front
panel)
RESET
0V
CAN
CEL ENTER
END
14
6 F 2 S 0 7 9 0
DC
supply
DI/AI
MPU
DO/COM
DC/DC
converter
Auxiliary relay
(high speed)
2
Binary
input
Photocoupler
AC input
CT 1 or 3
External
clock
Analogu
e
filter
IRIG-B
port
Multiplexer
A/D
converter
Auxiliary relay
7
MPU
RAM
ROM
RS485
transceiver
Front panel
Binary output
Trip
command
Binary output
Alarm
Relay
setting and
monitoring
system
or
IEC60870-5
-103
Human machine
interface (HMI)
Liquid crystal display
16 characters 2 lines
LEDs
Local
personal
computer
RS232C
I/F
Operation keys
Monitoring
jacks
DI/AI Module
The DI/AI module insulates internal circuits from external circuits through auxiliary transformers
and transforms the magnitude of AC input signals to suit the electronic circuits. The AC input
signals are single-phase or three-phase current which is the output from the varistor units EB-101
or EB-102.
There are 1 or 3 auxiliary CTs depending on the relay model. (For the correspondence between
the relay model and terminal number AC input signals, see Table 3.2.1.)
This module incorporates a DC/DC converter, analogue filter, multiplexer, analogue to digital
(A/D) converter and a photo-coupler circuit for the binary input signal.
The input voltage rating of DC/DC converter is 48V, 110V/125V or 220/250V. The normal range
of input voltage is 20% to +20%.
The analogue filter performs low-pass filtering for the corresponding current signals.
The A/D converter has a resolution of 12 bits and samples input signals at sampling frequencies
of 2400 Hz (at 50 Hz) or 2880 Hz (at 60 Hz).
This module is also provided with an IRIG-B port. This port collects the serial IRIG-B format
data from the external clock for synchronisation of the relay calendar clock. The IRIG-B port is
insulated from the external circuit by a photo-coupler. A BNC connector is used as the input
connector.
15
6 F 2 S 0 7 9 0
MPU Module
The MPU module consists of main a processing unit (MPU), random access memory (RAM) and
a read only memory (ROM) and executes all kinds of processing such as protection,
measurement, recording and display.
The MPU implements two 60 MIPS (Million Instructions Per Second) RISC (Reduced
Instruction Set Computer) type 32-bit microprocessors.
DO/COM Module
The DO/COM module incorporates two auxiliary relays (TP-1 and TP-2) dedicated to the circuit
breaker tripping command, 7 auxiliary relays (BO1-BO6 and FAIL) for binary output signals and
an RS485 transceiver.
TP-1 and TP-2 are the high-speed operation type and have one normally open contact.
The auxiliary relay FAIL has one normally closed contact, and operates when a relay failure or
abnormality in the DC circuit is detected. BO1 to BO6 have one normally open contacts.
The RS485 transceiver is used for the link with the relay setting and monitoring (RSM) system.
The external signal is isolated from the relay internal signal.
Human Machine Interface (HMI) Module
The operator can access the GRB150 via the human machine interface (HMI). As shown in
Figure 3.1.3, the HMI panel has a liquid crystal display (LCD), light emitting diodes (LEDs),
view and reset keys, operation keys, monitoring jacks and an RS232C connector on the front
panel.
The LCD consists of 16 columns by 2 rows with a back-light and displays recording, status,
setting data, and testing switches.
There are a total of 6 LED indicators and their signal labels and LED colors are defined as
follows:
Label
Color
Remarks
IN SERVICE
Green
TRIP
Red
ALARM
Red
TESTING
Red
(LED1)
Red
User-configurable
(LED2)
Red
User-configurable
LED1 and LED2 are user-configurable. Each is driven via a logic gate which can be programmed
for OR gate or AND gate operation. Further, each LED has a programmable reset characteristic,
settable for instantaneous drop-off, or for latching operation. A configurable LED can be
programmed to indicate the OR combination of a maximum of 4 elements. For the setting, see
Section 4.2.6.10.
The VIEW key starts the LCD indication and switches between windows. The RESET key
clears the LCD indication and turns off the LCD back-light.
Once a trip command is issued, the TRIP LED remains lit even after the trip command disappears.
Pressing the RESET key resets it. The other LEDs operate as long as a signal is present. The
16
6 F 2 S 0 7 9 0
RESET key is ineffective for these LEDs.
The operation keys are used to display the record, status and setting data on the LCD, input or
change the settings.
The monitoring jacks and two pairs of LEDs, A and B, on top of the jacks can be used while the
test mode is selected in the LCD window. Signals can be displayed on LED A or LED B by
selecting a signal to be observed from the "Signal List" and setting it in the window. The signals
can be transmitted to an oscilloscope via the monitoring jacks. (For the "Signal List", see
Appendix B.)
The RS232C connector is a 9-way D-type connector for serial RS232C connection. This
connector is used for connection with a local personal computer.
Screw for cover
Liquid crystal
display
IN SERVICE
VIEW
TRIP
ALARM
TESTING
Light emitting
diodes (LED)
RESET
Light emitting
diodes (LED)
Monitoring Jacks
Type
GRB150
Model
201B-21-10
In
Vn
___
Fn
50Hz
Vdc
110/125Vdc
Made in Japan
RS232C connector
0V
Operation keys
CAN
CEL ENTER
END
To a local PC
Screw for cover
Varistor unit EB101 or 102 is connected in parallel to the GRB150 to prevent an overvoltage
generated at the differential circuit during a fault. Figure 3.1.4 shows an internal circuit of the
varistor unit.
The EB-101 is coupled with the GRB150 model 101 for single-phase protection, and the EB-102
is coupled with the GRB150 model 201 for three-phase protection.
17
6 F 2 S 0 7 9 0
2 k
TB1-1
2 k
TB1-4
2 k
11
Varistor
TB1-2
TB1-8
TB1-5
Earth
(a) EB-101
2 k
TB1-1
2 k
TB2-1
2 k
11
Varistor
TB1-2
A phase
TB22 k
TB1-3
2 k
TB2-3
2 k
11
TB2-
Varistor
TB1-4
B phase
2 k
2 k
TB1-5
TB2-5
2 k
11
Varistor
TB1-6
C phase
TB2-
TB1-8 Earth
(b) EB-102
Figure 3.1.4 Internal Circuit of Varistor Unit
18
6 F 2 S 0 7 9 0
3.2
Input Signals
AC input signals
Table 3.2.1 shows the AC input signals necessary for each of the GRB150 models and their
respective input terminal numbers.
Table 3.2.1 AC Input Signals
Terminal No. of TB1
GRB150-101
GRB150-201
1-2
3-4
5-6
Current
A phase current
B phase current
C phase current
Table 3.2.2 shows the binary input signal required by the GRB150, its driving contact conditions
and functions enabled.
The binary input circuit of the GRB150 is provided with a logic level inversion function as shown
in Figure 3.2.1. The input circuit has a binary switch BISW which can be used to select either
normal or inverted operation. This allows the inputs to be driven either by normally open or
normally closed contacts. Where the driving contact meets the contact conditions indicated in
Table 3.2.2 then the BISW can be set to N (normal). If not, then I (inverted) should be
selected.
The default setting of the BISW is "N" (normal).
If a signal is not required, the function concerned is disabled.
The operating voltage of binary input signal is typical 74V DC at 110V/125V DC rating and
138V DC at 220/250V DC. The minimum operating voltage is 70V DC at 110/125V DC rating
and 125V DC at 220/250V DC.
Table 3.2.2 Binary Input Signal
Signal Name
BI1 command
19
BISW
1
6 F 2 S 0 7 9 0
GRB150
(+) ()
[BISW1]
BI1
BI1 COMMAND
"N"
1
"I "
0V
3.2.2
Auxiliary relay
1
or
1 4 GATES
&
[RESET]
0.2s
"DEL"
&
S
F/F
"LATCH"
Reset button
REMOTE RESET
20
6 F 2 S 0 7 9 0
3.3
Automatic Supervision
3.3.1
3.3.2
Relay Monitoring
The relay is supervised with the following items.
Differential voltage monitoring
The supervisory element DIFSV is provided to check the health of CT circuits. The DIFSV
element detects the erroneous differential voltage that appears under a CT circuit failure.
A/D accuracy checking
The memories are monitored as follows depending on the type of memory, and checked that the
memory circuits are healthy:
Random access memory monitoring:
Writes/reads prescribed data and checks the storage function.
Program memory monitoring: Checks the checksum value of the written data.
Setting value monitoring:
Watchdog timer
A hardware timer which is cleared periodically by software is provided and it is checked that the
software is running normally.
21
6 F 2 S 0 7 9 0
DC Supply Monitoring
The secondary voltage level of the built-in DC/DC converter is monitored and checks that the DC
voltage is within a prescribed range.
3.3.3
Failure Alarms
When a failure is detected by the automatic supervision, it is followed with an LCD message,
ALARM LED indication, external alarm and event recording. Table 3.3.1 summarises the
supervision items and alarms.
The alarms are retained until the failure is recovered.
The alarms can be disabled collectively by setting the scheme switch [AMF] (Automatic
Monitoring Function) to OFF. The setting is used to block unnecessary alarms during
commissioning, testing or maintenance.
When the watchdog timer detects that the software is not running normally, the LCD display and
event recording of the failure may not function normally.
Table 3.3.1 Supervision Items and Alarms
Supervision Item
[SVCNT]
switch*
Differential voltage
monitoring
LCD
Message
LED
"IN SERVICE"
LED
"ALARM"
Off
On
On
On
(1)
Off
Watchdog Timer
----
DC supply monitoring
----
ALM
(1)
Ext. alarm
Event record
Message
(2)
Vd err
On
(3)
Relay fail
Off
On
(3)
----
Off
(4)
(3)
----
*: For [SVCNT] (supervision control) switch, see Appendix G and for its scheme logic, see
Appendix A.
(1) Diverse messages are provided as expressed with " Err:---" in the table in Section 6.7.2.
(2) The configurable signal VD ERR operates. (See Appendix B.)
(3) The binary output relay "FAIL" operates.
(4) Whether the LED is lit or not depends on the degree of the voltage drop.
22
6 F 2 S 0 7 9 0
3.3.4
Trip Blocking
When a failure is detected by the following supervision items, the trip function is blocked for as
long as the failure exists and is restored when the failure is removed.
Differential voltage monitoring (selectable)
A/D accuracy check
Memory monitoring
Watchdog Timer
DC supply monitoring
When a failure is detected by the differential voltage monitoring, the scheme switch [SVCNT]
setting can be used to determine if both tripping is blocked and an alarm is initiated, or, if only an
alarm is initiated. (For the setting, see Section 4.2.6.7)
3.3.5
Setting
The setting elements necessary for the automatic supervision and their setting range are shown in
the table below.
Element
Range
[SVCNT]
ALM&BLK/ALM
Step
Default
Remarks
ALM&BLK
23
6 F 2 S 0 7 9 0
3.4
Recording Function
The GRB150 is provided with the following recording functions:
Fault recording
Event recording
Disturbance recording
These records are displayed on the LCD of the relay front panel or on the local or remote PC.
3.4.1
Fault Recording
Fault recording is started by a tripping command of the GRB150 and the following items are
recorded for one fault:
Date and time of fault occurrence
Operating phase
Relevant events
Power system quantities
Up to 8 most-recent faults are stored as fault records. If a new fault occurs when 8 faults have
been stored, the record of the oldest fault is deleted and the latest fault one is then stored.
Date and time of fault occurrence
The differential voltages in pre-faults and post-faults are recorded. The following power system
quantities are not recorded during evolving faults.
- Magnitude of differential voltage (Vd) for model 101 or phase differential voltage (Vda,
Vdb, Vdc) for model 201
24
6 F 2 S 0 7 9 0
3.4.2
Event Recording
The events shown in Table 3.4.1 are recorded with a 1 ms resolution time-tag when the status
changes. The user can select the recording items and their status change mode to initiate a
recording.
Up to 96 event records can be stored. If an additional event occurs when 96 records have been
stored, the oldest event record is deleted and the latest one is then stored.
Table 3.4.1 Event Record Items
Event
LCD Indication
Trip
On or Off
Relay fail
On or Off
Vd err
On or Off
Ind. reset
On or Off
Cold load
On or Off
Note: A change of setting is classified into three events. The event "System setting changed"
corresponds to all the setting changes except setting changes in the sub-menu "Protection".
(See section 4.2.6 for changing the settings). The event "Relay setting changed" corresponds
to a setting change of the measuring elements and timers in the sub-menu "Protection". The
event "Group setting changed" corresponds to other setting changes in the sub-menu
"Protection".
Setting
Recording mode can be set for each event. One of the following four modes is selectable except
for a change of setting(s).
Not to record the event
To record the event when status changes to "operate".
To record the event when status changes to "reset".
To record the event when status changes both to "operate" and "reset".
For System setting changed, Relay setting changed and System setting changed, one of the
following modes is selectable.
Not to record the event
To record the event when status changes to "operate".
25
6 F 2 S 0 7 9 0
3.4.3
Disturbance Recording
Disturbance recording is started when the supervisory element DIFSV operates or a tripping
command is initiated. In Model 201, the records include three analogue signals (Vda, Vdb, Vdc :
phase differential voltage), eight binary signals listed below and the dates and times at which
recording started.
- DIF-A
- DIF-B
- DIF-C
- DIFSV-A
- DIFSV-B
- DIFSV-C
- Trip
- Cold load
In Model 101, the records include an analogue signal (Vd: differential voltage), four binary
signals (DIF, DIFSV, Trip, Cold load) and the dates and times.
The LCD display only shows the dates and times of the disturbance records stored. Details can be
displayed on a PC. For how to obtain disturbance records on the PC, see the Instruction Manual
PC Interface, RSM100.
The pre-fault recording time is fixed at 0.3s and post-fault recording time can be set between 0.1
and 3.0s.
The number of records stored depends on the post-fault recording time. The approximate
relationship between the post-fault recording time and the number of records stored is shown in
Table 3.4.2.
Note: If the recording time setting is changed, the records stored so far are deleted.
Table 3.4.2 Post Fault Recording Time and Number of Disturbance Records Stored
3.5
Recording time
0.1s
0.5s
1.0s
1.5s
2.0s
2.5s
3.0s
50Hz
49
25
15
11
60Hz
41
20
12
Metering Function
The GRB150 performs continuous measurement of the analogue input quantities. The
magnitudes of the phase differential voltage (Vda, Vdb, Vdc) or differential voltage (Vd) are
renewed every second and displayed on the LCD of the relay front panel or on the local or remote
PC. The model 101 series measures a single phase quantity only.
26
6 F 2 S 0 7 9 0
4. User Interface
4.1
4.1.1
Front Panel
As shown in Figure 3.1.3, the front panel is provided with a liquid crystal display (LCD), light
emitting diodes (LED), operation keys, VIEW and RESET keys, monitoring jacks and an
RS232C connector.
LCD
The LCD screen, with a 2-line, 16-character display and back-light, provides the user with
information of the relay interior such as records, statuses and settings. The LCD screen is
normally unlit, but pressing the VIEW key will display the digest screen and pressing any key
other than VIEW and RESET will display the menu screen.
These screens are turned off by pressing the RESET key or the END key. If any display is left
for 5 minutes or longer without operation, the back-light will go off.
LED
There are 6 LED displays. The signal labels and LED colors are defined as follows:
Label
Color
Remarks
IN SERVICE
TRIP
ALARM
TESTING
(LED1)
(LED2)
Green
Red
Red
Red
Red
Red
The operation keys are used to display records, statuses, and setting values on the LCD, as well as
27
6 F 2 S 0 7 9 0
to input or change setting values. The functions of each operation key are as follows:
c
and
are also
d CANCEL :
e END :
f ENTER :
Pressing VIEW key displays digest screens such as "Metering", "Latest fault" and
"Auto-supervision".
Pressing RESET key turns off the display.
Monitoring jacks
The two monitoring jacks A and B and their respective LEDs can be used when the test mode is
selected on the LCD screen. By selecting the signal to be observed from the "Signal List" (See
Appendix B) and setting it on the screen, the signal can be displayed on LED A or LED B, or by
using an oscilloscope via the monitoring jacks.
RS232C connector
The RS232C connector is a 9-way D-type connector for serial RS232C connection with a local
personal computer.
28
6 F 2 S 0 7 9 0
4.1.2
Communication Ports
The following three individual interfaces are mounted as communication ports:
RS232C port
RS485 port
IRIG-B port
RS232C port
This connector is a standard 9-way D-type connector for serial port RS232C transmission and is
mounted on the front panel. By connecting a personal computer using this connector or via
modems and a telephone line, setting operation and display functions can be performed on the
personal computer.
RS485 port
The RS485 port is used for the RSM (Remote Setting and Monitoring system) via the protocol
converter G1PR2 and IEC60870-5-103 communication via BCU/RTU (Bay Control Unit /
Remote Terminal Unit) to connect between relays and to construct a network communication
system. (See Figure 4.4.1 in Section 4.4.)
One or two (dual) RS485 ports (COM1 and COM2) are provided on the rear of the relay as shown
in Figure 4.1.1 and Appendix F.
IRIG-B port
The IRIG-B port collects serial IRIG-B format data from the external clock to synchronise the
relay calendar clock. The IRIG-B port is isolated from the external circuit by using a
photo-coupler. A BNC connector is used as the input connector.
This port is provided on the back of the relay and Figure 4.1.1 shows the location of this
connector. The rated voltage level of the signal is from 2 to 8 Vpeak (4 to 16 Vpeak-to-peak).
TB2
TB1
TB3
RS485
connection
terminal
CN1
E
IRIG BNC
connector
Rear view
Figure 4.1.1 Locations of RS485 Port and IRIG Port
29
6 F 2 S 0 7 9 0
4.2
4.2.1
When the GRB150 is operating normally, the green "IN SERVICE" LED is lit and the LCD is off.
Press the VIEW key when the LCD is off to display the "Metering", "Latest fault" and
"Auto-supervision" screens in turn. The last two screens are displayed only when there is some
data. The screen below are the digest screens and can be displayed without entering the menu
screens.
.
V d
D I F - A B C
T r i p
E r r
To clear the latched indications (latched LEDs, LCD screen of Latest fault), press RESET key
for 3 seconds or more.
For any display, the back-light is automatically turned off after five minutes.
Displays in tripping
If a fault occurs and a tripping command is output when the LCD is off, the red "TRIP" LED and
other configurable LED if signals assigned to trigger by tripping
Press the VIEW key to scroll the LCD screen to read the rest of messages.
Press the RESET key to turn off the LEDs and LCD display.
Notes:
1) When configurable LEDs (LED1 and LED2) are assigned to latch signals by trigger of tripping,
press the RESET key more than 3s until the LCD screens relight. Confirm turning off the
configurable LEDs. Refer to Table 4.2.1 Step 1.
2) Then, press the RESET key again on the "Latest fault" screen in short period, confirm turning
off the "TRIP" LED. Refer to Table 4.2.1 Step 2.
3) When only the "TRIP" LED is go off by pressing the RESET key in short period, press the
RESET key again to reset remained LEDs in the manner 1) on the "Latest fault" screen or
other digest screens. LED1 and LED2 will remain lit in case the assigned signals are still active
state.
30
6 F 2 S 0 7 9 0
Table 4.2.1 Turning off latch LED operation
LED lighting status
Operation
Step 1
"TRIP" LED
Step 2
Configurable LED
(LED1, LED2)
turn off
When any of the menu screens is displayed, the VIEW and RESET keys do not function.
To return from menu screen to the digest "Latest fault" screen, do the following:
Return to the top screen of the menu by repeatedly pressing the END key.
Press the END key to turn off the LCD.
Press the VIEW key to display the digest "Latest fault" screen.
Displays in automatic supervision operation
If the automatic supervision function detects a failure while the LCD is off, the
"Auto-supervision" screen is displayed automatically, showing the location of the failure, and the
"ALARM" LED lights.
Press the VIEW key to display other digest screens in turn including the "Metering" and "Latest
fault" screens.
Press the RESET key to turn off the LEDs and LCD display. However, if the failure continues,
the "ALARM" LED remains lit.
After recovery from a failure, the "ALARM" LED and "Auto-supervision" display turn off
automatically.
If a failure is detected while any of the screens is displayed, the current screen remains displayed
and the "ALARM" LED lights.
Notes:
1) When configurable LEDs (LED1 and LED2) are assigned to latch signals by issuing an alarm,
press the RESET key more than 3s until all LEDs reset except "IN SERVICE" LED.
2) When configurable LED is still lit by pressing RESET key in short period, press RESET
key again to reset remained LED in the above manner.
3) LED1 and LED2 will remain lit in case the assigned signals are still active state.
31
6 F 2 S 0 7 9 0
While any of the menu screens is displayed, the VIEW and RESET keys do not function. To
return to the digest "Auto-supervision" screen, do the following:
Return to the top screen of the menu by repeatedly pressing the END key.
Press the END key to turn off the LCD.
Press the VIEW key to display the digest screen.
Press the RESET key to turn off the LCD.
4.2.2
Relay Menu
Figure 4.2.1 shows the menu hierarchy in the GRB150. The menu has five sub-menus, "Record",
"Status", "Set. (view)", "Set. (change)", and "Test". For details of the menu hierarchy, see
Appendix D.
32
6 F 2 S 0 7 9 0
Menu
Record
F. record
E. record
D. record
Status
Metering
Binary I/O
Ry element
Time synch.
Clock adjust.
LCD contrast
Set. (view)
Version
Description
Comms
Record
Status
Protection
Binary I/P
Binary O/P
LED
Set. (change)
Password
Description
Comms
Record
Status
Protection (Protected by password)
Binary I/P
Binary O/P
LED
Test
Switch
Binary O/P
Logic circuit
33
6 F 2 S 0 7 9 0
Record
In the "Record" menu, the fault record, event record and disturbance record can be displayed or
erased.
Status
The "Status" menu displays the power system quantities, binary input and output status, relay
measuring element status, signal source for time synchronisation (IRIG-B, RSM or
IEC60870-5-103) and adjusts the clock and LCD contrast.
Set. (view)
The "Set. (view)" menu displays the relay version, description, relay address and baud rate in
RSM or IEC60870-5-103 communication, the current settings of record, status, protection, binary
inputs, configurable binary outputs and the configurable LEDs.
Set. (change)
The "Set. (change)" menu is used to change the settings of password, description, relay address
and baud rate in RSM or IEC60870-5-103 communication, record, status, protection, binary
inputs, configurable binary outputs and configurable LEDs.
Since this is an important menu and is used to change settings related to relay tripping, it has a
password security protection.
Test
The "Test" menu is used to set testing switches, to forcibly operate binary output relays and to
observe the binary signals in the logic circuit.
When the LCD is off, press any key other than the VIEW and RESET keys to display the top
"MENU" screen and then proceed to the relay menus.
R
S
S
S
T
e
t
e
e
e
M
c
a
t
t
s
E N U
o r d
t u s
.
( v i e w )
.
( c h a n g e )
t
To display the "MENU" screen when the digest screen is displayed, press the RESET key to
turn off the LCD, then press any key other than the VIEW and RESET keys.
Press the END key when the top screen is displayed to turn off the LCD.
An example of the sub-menu screen is shown below. The top line shows the hierarchical layer.
The last item is not displayed for all the screens. "/4" displayed on the far left means that the
screen is in the fourth hierarchical layer, while " " or " " displayed on the far right shows that
upper or lower lines exist.
To move the cursor downward or upward for setting or for viewing other lines not displayed on
the window, use
or
key.
34
6 F 2 S 0 7 9 0
/ 4
T
O
V
O
S c h e m e
s w
r i p
f f / O n
d
e r r
f f / O n
To return to the higher screen or move from the right side screen to the left side screen in
Appendix D, press the END key.
The CANCEL key can also be used to return to the higher screen but it must be used carefully
because it may cancel entries made so far.
To move between screens of the same hierarchical depth, first return to the higher screen and then
move to the lower screen.
4.2.3
Displaying Records
The sub-menu of "Record" is used to display fault records, event records and disturbance records.
4.2.3.1
1
R e
F . r e
E . r e
D . r e
c
c
c
c
o
o
o
o
d
r d
r d
r d
Select "Display" to display the dates and times of fault records stored in the relay from the
top in new-to-old sequence.
/ 3
F . r e c o r d
# 1
1
1
2
1
0
1
2
0
# 2
# 3
# 4
6
8
0
5
4
1
8
7
/
:
/
:
/
:
/
:
O
1
S
2
J
5
F
3
c
3
e
9
u
4
e
0
t
:
p
:
l
:
b
:
/
5
/
2
/
5
/
1
1
7
1
2
1
3
1
8
9
.
9
.
9
.
9
.
9
0
9
1
9
2
9
4
7
3
7
0
7
9
7
1
1
1
9
2
Move the cursor to the fault record line to be displayed using the
the ENTER key to display the details of the fault record.
35
and
6 F 2 S 0 7 9 0
/
1
1
D
T
P
V
V
V
F
V
V
V
3
6
8
I
r
r
d
d
d
a
d
d
d
/
:
F
i
e
a
b
c
u
a
b
c
F
O
1
p
f
.
c
3
A
r
t
:
B
l t
e c o r d
# 1
/ 1 9 9 7
5 7 . 0 3 1
C
t
.
.
.
a
.
.
.
v a l u e s
V
l u e s
V
The lines which are not displayed in the window can be displayed by pressing the
keys.
and
r e c o r d ?
C A N C E L = N
Press the END (= Y) key to clear all the fault records stored in non-volatile memory.
If all fault records have been cleared, the "Latest fault" screen of the digest screens is not
displayed.
4.2.3.2
Select "Display" to display the events with date from the top in new-to-old sequence.
/ 3
1
T
1
V
1
R
6
r
6
d
6
l
E . r e c o r d
/ O c
i p
/ O c
e r
/ O c
y .
t / 1 9 9 7
O n
t / 1 9 9 7
r
t / 1 9 9 7
c h a n g e
key.
36
O n
6 F 2 S 0 7 9 0
/ 3
1
T
1
V
1
R
Press the
8
r
8
d
8
l
E . r e c o r d
: 1 3
i p
: 1 3
e r
: 1 3
y .
: 5 8 . 2 5 5
O n
: 5 8 . 0 2 8
r
O n
: 5 8 . 5 2 8
c h a n g e
The lines which are not displayed in the window can be displayed by pressing the
and
keys.
r e c o r d ?
C A N C E L = N
Press the END (= Y) key to clear all the event records stored in non-volatile memory.
4.2.3.3
Details of disturbance records can be displayed on the PC screen only (*); the LCD displays only
the recorded date and time for all disturbances stored in the relay. They are displayed in the
following sequence.
(*) For the display on the PC screen, refer to the RSM100 manual.
Open the top "MENU" screen by pressing any keys other than the VIEW and RESET
keys.
Select "Record" to display the "Record" sub-menu.
Select "D. record" to display the "Disturbance record" screen.
/ 2
D . r e c o r d
D i s p l a y
C l e a r
Select "Display" to display the date and time of the disturbance records from the top in
new-to-old sequence.
/ 3
D . r e c o r d
# 1
1
1
2
1
0
1
2
0
# 2
# 3
# 4
6
8
0
5
4
1
8
7
/
:
/
:
/
:
/
:
O
1
S
2
J
5
F
3
c
3
e
9
u
4
e
0
t
:
p
:
l
:
b
:
/
5
/
2
/
5
/
1
1
7
1
2
1
3
1
8
9
.
9
.
9
.
9
.
9
4
9
3
9
4
9
8
7
0
7
8
7
4
7
7
1
8
4
6
The lines which are not displayed in the window can be displayed by pressing the
37
and
6 F 2 S 0 7 9 0
keys.
To clear disturbance records, do the following:
Open the "Record" sub-menu.
Select "D. record" to display the "Disturbance record" screen.
Select "Clear" to display the following confirmation screen.
C l e a r
E N D = Y
r e c o r d ?
C A N C E L = N
Press the END (= Y) key to clear all the disturbance records stored in non-volatile
memory.
4.2.4
1
M
B
R
T
C
L
e
i
e
i
l
C
S
t
n
l
m
o
D
t
e
a
a
e
c
a t u s
r i n g
r y
I /
y
e l e
s y n
k
a d j
c o n t r
O
m
c
u
a
e n t
.
s t .
s t
M e t e r i n g
V
.
(Model 101)
/ 2
M e
V d a
V d b
V d c
(Model 201)
4.2.4.2
r
.
.
.
i n g
V
38
6 F 2 S 0 7 9 0
Select "Status" on the top "MENU" screen to display the "Status" screen.
Select "Binary I/O" to display the binary inputs and outputs status.
/
I
O
O
2
B
P
[
P 1 [
P 2 [
i n a r y
I / O
0
0 0
0 0 0
0 0 0
0
]
]
]
Input (IP)
BI1
Output (OP1)
TP-1
TP-2
Output (OP2)
BO1
BO2
BO3
BO4
BO5
BO6
FAIL
Line 1 shows the binary input status. BI1 corresponds to a binary input signal. For the binary
input signal, see Appendix F. The status is expressed with logical level "1" or "0" at the
photo-coupler output circuit.
Lines 2 and 3 show the binary output statuses. TP-1 and TP-2 of line 2 correspond to the tripping
command outputs. FAIL of line 3 corresponds to the relay failure output. Other outputs expressed
with BO1 to BO6 are configurable. The status of these outputs is expressed with logical level "1"
or "0" at the input circuit of the output relay driver. That is, the output relay is energised when the
status is "1".
To display all the lines, press the
4.2.4.3
and
keys.
Model 101:
/ 2
R y
e l e m e n t
[ 0 0
R y
e l e m e n t
0 0 0
[ 0 0 0
Model 201:
/ 2
DIF, DIFSV
[
DIF
DIFSV
B
DIF
B
DIFSV
Model 201:
DIF, DIFSV
39
6 F 2 S 0 7 9 0
This shows the operation status of differential elements and the supervisory element.
The status of each element is expressed with logical level "1" or "0". Status "1" means the element
is in operation.
4.2.4.4
The internal clock of the GRB150 can be synchronised with external clocks such as the IRIG-B
time standard signal clock or RSM (relay setting and monitoring system) clock or
IEC60870-5-103. To display on the LCD whether these clocks are active (=Act.) or inactive
(=Inact.) and which clock the relay is synchronised with, do the following:
Select "Status" on the top "MENU" screen to display the "Status" screen.
Select "Time sync." to display the status of time synchronisation sources.
/ 2
I R
R S
I E
T
I
M
C
i m e
s y
G :
A c t
:
I n a
:
I n a
n c .
.
c t .
c t .
The asterisk on the far left shows that the internal clock is synchronised with the marked source
clock. If the marked source clock is inactive, the internal clock runs locally.
For details of the setting time synchronisation, see Section 4.2.6.6.
4.2.4.5
Clock Adjustment
To adjust the clock when the internal clock is running locally, do the following:
Select "Status" on the top "MENU" screen to display the "Status" screen.
Select "Clock adjust." to display the setting screen.
/ 2
Mi
H o
D a
M o
Y e
1 2 / N o v / 1 9 9 9
2 2 : 5 6 : 1 9
L o c
n u t e
5 6
_
u r
2 2
_
y
1 2
_
n t h
1 1
_
a r
1 9 9 9
Line 1 shows the current date, time and time synchronisation source with which the internal clock
is synchronised. The time can be adjusted only when Loc is indicated on the top line, showing
that the clock is running locally. When IRI(IRIG), RSM or IEC is indicated, the adjustment
is invalid.
Enter a numerical value for each item and press the ENTER key. For details to enter a
numerical value, see 4.2.6.1.
Press the END key to adjust the internal clock to the set hours without fractions and
return to the previous screen.
If a date which does not exist in the calendar is set and END key is pressed, "**** Error ****"
40
6 F 2 S 0 7 9 0
is displayed on the top line and the adjustment is discarded. Adjust again.
4.2.4.6
LCD Contrast
c o n t r a s t
Press the or key to adjust the contrast. The screen becomes dark by pressing the
key and light by pressing the key.
4.2.5
1
V
D
C
R
S
P
B
B
L
e
e
o
e
t
r
i
i
E
S
r
s
m
c
a
o
n
n
D
e
s
c
m
o
t
t
a
a
t
i
r
s
r
u
e
r
r
. ( v i e w )
o n
i p t i o n
d
s
c t i o n
y
I / P
y
O / P
41
6 F 2 S 0 7 9 0
N o .
S e r i a l
S o f t w a r e
Select "Relay type" to display the relay type form and model number.
G R B 1 5 0 - 2 0 1 B - 1 2
- 3 0
4.2.5.2 Description
Select "Description" to display the "Description" screen.
/ 2
D e s c r i p t i o n
n a m e
P l a n t
D e s c r i p t i o n
The "Comms", "Record", "Status", "Protection", "Binary I/O", "Binary O/P" and "LED" screens
display the current settings input using the "Set. (change)" sub-menu.
4.2.6
Setting Method
42
6 F 2 S 0 7 9 0
- Numerical values
A selected item
1
P
D
C
R
S
P
B
B
L
a
e
o
e
t
r
i
i
E
S
s
s
m
c
a
o
n
n
D
e
s
c
m
o
t
t
a
a
t
w
r
s
r
u
e
r
r
and
. ( c h a n g e)
o r d
i p t i o n
d
s
c t i o n
y
I / P
y
O / P
To select a character, use keys , , and to move the blinking cursor down, left, up and
right. "" and "" on each of lines 4, 8 and 10 indicate a space and backspace, respectively. A
maximum of 22 characters can be entered within the brackets.
A B C D E F G
H
O
V
a
h
o
v
0
7
(
}
>
I
P
W
b
i
p
w
1
8
)
!
:
L
Q
X
c
j
q
x
2
9
[
/
K
R
Y
d
k
r
y
3
]
+
#
,
L
S
Z
e
l
s
z
4
M N
T U
f g
m n
t u
5 6
@_ {
< =
$ %&
. `
Set the cursor position in the bracket by selecting "" or "" and pressing the ENTER
key.
Move the blinking cursor to a selecting character.
43
6 F 2 S 0 7 9 0
Press the ENTER key to enter the blinking character at the cursor position in the
brackets.
Press the END key to confirm the entry and return to the upper screen.
P r o t . e l e m e n t
D I F
D I F
T V D
0
D I F
1
T C L
0
T C L
0
T C L
0
V
1 0
S V
5
S V
. 5 0
C C
. 0 0
P
. 0 1
E
. 0 0
R
. 0 0
_
V
_
s
_
_
s
_
s
_
s
_
or
or
44
6 F 2 S 0 7 9 0
upper one.
After making entries on each setting screen by pressing the ENTER key, the new settings are
not yet used for operation, though stored in the memory. To validate the new settings, take the
following steps.
Press the END key to return to the upper screen. Repeat this until the confirmation screen
shown below is displayed. The confirmation screen is displayed just before returning to
the "Set. (change)" sub-menu.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N
When the screen is displayed, press the ENTER key to start operation using the new
settings, or press the CANCEL key to correct or cancel the entries. In the latter case, the
screen turns back to the setting screen to enable re-entries. Press the CANCEL key to
cancel entries made so far and to turn to the "Set. (change)" sub-menu.
4.2.6.2
Password
For the sake of security of setting changes, password protection can be set as follows:
Select "Set. (change)" on the main "MENU" screen to display the "Setting change" screen.
Select "Password" to display the "Password" screen.
Enter a 4-digit number within the brackets after "Input" and press the ENTER key.
I n p u t
[ _
0 1 2 3 4 5 6 7 8 9
For confirmation, enter the same 4-digit number in the brackets after "Retype".
R e t y p e
[ _
0 1 2 3 4 5 6 7 8 9
Press the END key to display the confirmation screen. If the retyped number is different
from that first entered, the following message is displayed on the bottom of the "Password"
screen before returning to the upper screen.
"Unmatch password!"
Re-entry is then requested.
Password trap
After the password has been set, the password must be entered in order to enter the setting change
screens.
If "Set. (change)" is entered on the top "MENU" screen, the password trap screen "Password" is
displayed. If the password is not entered correctly, it is not possible to move to the "Set. (change)"
sub-menu screens.
P a s s w o r d
[ _
0 1 2 3 4 5 6 7 8 9
45
6 F 2 S 0 7 9 0
Canceling or changing the password
To cancel the password protection, set "0000" as a password. The "Set. (change)" screen is then
displayed without having to enter a password.
The password can be changed by entering a new 4-digit number on the "Password" screen in the
same way as the first password setting.
If you forget the password
Press CANCEL and RESET keys together for one second on the top "MENU" screen. The
screen goes off, and the password protection of the GRB150 is canceled. Set the password again.
4.2.6.3
Description
To enter the plant name and other data, do the following. These data are attached to records.
Select "Set. (change)" on the main "MENU" screen to display the "Set. (change)" screen.
Select "Description" to display the "Description" screen.
/ 2
D e s c r i p t i o n
n a m e
P l a n t
D e s c r i p t i o n
To enter the plant name, select "Plant name" on the "Description" screen.
The plant name and special items entered are viewed with the "Set. (view)" sub-menu and
attached to disturbance records when they are displayed on a local or a remote PC.
4.2.6.4
Communication
If the relay is linked with RSM (relay setting and monitoring system) or IEC60870-5-103
communication, the relay address must be set. Do this as follows:
Note: The settings related to IEC60870-5-103 communication are available for the relay with dual
RS485 port.
Select "Set. (change)" on the main "MENU" screen to display the " Set. (change)" screen.
Select "Comms" to display the "Comms" screen.
/ 2
C o m m s
A d d r . / P a r a m .
S w i t c h
Select "Addr./Param." on the "Comms" screen to enter the relay address number.
/ 3
A d d r . / P a r a m .
H D L C
1
I E C
2
Enter the relay address number on "HDLC" line for RSM or "IEC" line for
IEC60870-5-103 and press the ENTER key.
46
6 F 2 S 0 7 9 0
CAUTION Do not overlap the relay address number.
Select "Switch" on the "Comms" screen to select the protocol and transmission speed
(baud rate), etc., of the RSM and IEC60870-5-103.
/ 3
I
9
I
N
E
.
E
o
S w i t c h
C
6
C
r
B
/
B
m
R
1
1 9 . 2
L K
0
a l / B l o c k e d
This line is to select the baud rate when the IEC60870-5-103 system is applied.
<IECBLK>
r
/
d
/
n
/
e
/
o
/
y
/
l
/
r
/
E . r e c o r d
i p
O / R
e r
O / R
d . r
O / R
l a y
O / R
l d
O / R
s . c
O
y . c
O
p . c
O
3 _
3 _
e t
3 _
a i l
3 _
n g e
1 _
h a n g e
1 _
h a n g e
1 _
/
r
/
e
/
/
l
/
h
B
B
s
B
f
B
o
B
a
a d
Enter 0 or 1 or 2 or 3 and press the ENTER key. Repeat this for all events.
47
6 F 2 S 0 7 9 0
Enter 0 (= N) not to record the event.
Enter 1 (= O) to record the event when the status changes to "operate".
Enter 2 (= R) to record the event when the status changes to "reset".
Enter 3 (= B) to record the event when the status changes both to "operate" and "reset".
Setting the disturbance recording
Select "D. record" to display the "Disturbance record" screen.
/ 3
D . r e c o r d
T i m e / s t a r t e r
s w
S c h e m e
T i m e / s t a r t e r
T i m e
2 . 0
s
_
S c h e m e
R I P
f f / O n
d
e r r
f f / O n
s w
1
Status
The calendar clock can run locally or be synchronised with the external IRIG-B time standard
signal, RSM clock, or by an IEC60870-5-103. This is selected by setting as follows.
Select "Time sync" to display the "Time synchronisation" screen.
/ 3
T i m e
T i m e
s y n c .
s y n c
48
6 F 2 S 0 7 9 0
O f f / I R I / R S M / I E C
When the calendar clock is synchronised with the IRIG-B time standard, it is possible to
transform GMT to the local time.
Select "Time zone" to display the "Time zone" screen.
/ 3
G M T
T i m e
z o n e
h r s
+ 9
Enter the difference between GMT and local time from 12 to +12 and press the ENTER
key.
4.2.6.7
Protection
The GRB150 can have 4 setting groups for protection in order to accommodate changes in the
operation of the power system, one setting group is assigned active. To set protection, do the
following:
Select "Protection" on the "Set. (change)" screen to display the "Protection" screen.
/
2
P r o t e
C h a n g e
C h a n g e
C o p y
g p
c t i o n
a c t . g p .
s e t
.
C h a n g e
a c t .
g p .
A c t i v e
g p .
1
_
All the setting items have default values that are set when the product was shipped except names
and descriptions specified by the user. For the default values, see Appendix C and G.
To change the settings, do the following:
49
6 F 2 S 0 7 9 0
Select "Change set." to display the "Change setting" screen.
/ 3
A c t
g p . =
G r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
Select the group number to change the settings and press the ENTER key.
/ 4
G r o u p
P a r a m e t e r
T r i p
D
f
V
L
N
f
L
f
S c h e m e
C
f
C
M
D
f
E
f
H
/
N
&
.
/
N
/
s w
K
1
O n
T
0
B L K / A L M
R
1
O n
0
F 1 / F 2
<VDCHK>
Enter 1 to perform the differential voltage supervision or enter 0 if you do not need to
perform it, and press the ENTER key.
50
6 F 2 S 0 7 9 0
<SVCNT>
Enter 0 (= ALM&BLK) to output an alarm and to block the trip function by the differential
voltage monitoring.
<IND.R>
Enter 1 (= On) to use BI1 for the indication reset.
Enter 0 (= Off) not to use BI1 for the indication reset.
<CLEN>
Enter 1 (= F1) to use BI1 for the function 1 of the cold load protection.
Enter 2 (= F2) to use BI1 for the function 2 of the cold load protection.
Enter 0 (= Off) not to use BI1 for the cold load protection.
Press the END key to return to the "Trip" screen.
Setting the protection elements
Select "Prot. element" to display the "Protection element" screen.
/ 6
P r o t . e l e m e n t
D I F
1 0
D I F S V
5
T V D S V
0 . 5 0
_
V
_
s
_
<DIF>
Enter the numerical value and press the ENTER key.
<DIFSV>
Enter the numerical value and press the ENTER key.
<TVDSV>
Enter the numerical value and press the ENTER key.
After setting, press the END key to return to the "Trip" screen.
Setting group copy
To copy the settings of one group and overwrite them to another group, do the following:
Select "Copy gp" on the "Protection" screen to display the "Copy A to B" screen.
/ 3
C o p y
A
B
t o
B
_
_
51
6 F 2 S 0 7 9 0
Enter the group number to be copied in line A and press the ENTER key.
Enter the group number to be overwritten by the copy in line B and press the ENTER
key.
4.2.6.8
Binary Input
The logic level of binary input signals can be inverted by setting before entering the scheme logic.
Inversion is used when the input contact cannot meet the requirement described in Table 3.2.2.
Select "Binary I/P" on the "Set. (change)" sub-menu to display the "Binary I/P" screen.
/ 2
B i n a r y
B I S W1
N o r m / I n v
I / P
1
Binary Output
All the binary outputs of the GRB150 except the tripping command, and relay failure signal are
user-configurable. It is possible to assign one signal or up to four ANDing or ORing signals to
one output relay. Available signals are listed in Appendix B.
It is also possible to attach Instantaneous or delayed or latched reset timing to these signals.
Appendix C shows the factory default settings.
To configure the binary output signals, do the following:
Selection of output relay
Select "Binary O/P" on the "Set. (change)" screen to display the "Binary O/P" screen.
/ 2
B O
B O
B O
B O
B O
B O
B i n a r y
1
O / P
2
3
4
5
6
Note: The setting is required for all the binary outputs. If any of the binary outputs are not used, enter
0 to logic gates #1 to #4 in assigning signals.
Enter the output relay number (BO number) and press the ENTER key to display the
"Set. (BO)" screen.
/ 3
S e t .
( B O )
L o g i c / R e s e t
F u n c t i o n s
L o g i c / R e s e t
52
6 F 2 S 0 7 9 0
L
O
R
I
o
R
e
n
g
/
s
s
i
A
e
t
c
0
_
N D
t
0
/ D e l / L a t c h
Enter 0 (= OR) or 1 (= AND) to use an OR gate or AND gate and press the ENTER key.
Enter 0 (= Instantaneous) or 1 (= Delayed) or 2 (=Latched) to select the reset timing and
press the ENTER key.
Press the END key to return to the "Set. (BO)" screen.
Note: To release the latch state, push the [RESET] key for more than 3 seconds.
Assigning signals
Select "Functions" on the "Set. (BO)" screen to display the "Functions" screen.
/ 4
F u n c t i o n s
I n
# 1
2 1
# 2
4
# 3
6 7
# 4
0
I n
I n
I n
_
_
_
_
Assign signals to gates (In #1 to #4) by entering the number corresponding to each signal
referring to Appendix B. Do not assign the signal numbers 120 to 125 (signal names: "BO1
OP" to "BO6 OP").
Note: If signals are not assigned to all the gates #1 to #4, enter 0 for the unassigned gate(s).
Two LEDs of the GRB150 are user-configurable. A configurable LED can be programmed to
indicate the OR/AND combination of a maximum of 4 elements. One of the signals listed in
Appendix B can be assigned to each LED as follows:
Select "LED" on the "Set. (change)" screen to display the "LED" screen.
/ 2
L E D
L E D 1
L E D 2
Note: The setting is required for all the LEDs. If any of the LEDs are not used, enter 0 to logic
gates #1 to #4 in assigning signals.
Select the LED number and press the ENTER key to display the "LED" screen.
/ 3
L E D
L o g i c / R e s e t
F u n c t i o n s
53
6 F 2 S 0 7 9 0
Setting the logic gate type and reset type
Select "Logic/Reset" to display the "Logic/Reset" screen.
/ 4
L
O
R
I
o
R
e
n
L o g i c / R e s e t
g
/
s
s
i
A
e
t
c
N D
t
/ L a t c h
Enter 0 (= OR) or 1 (= AND) to use an OR gate or AND gate and press the ENTER key.
Enter 0 (= Instantaneous) or 1(=Latched) to select the reset timing and press the ENTER
key.
Press the END key to return to the "LED" screen.
Note: To release the latch state, push the [RESET] key for more than 3 seconds.
Assigning signals
Select "Functions" on the "LED" screen to display the "Functions" screen.
/ 5
F u n c t i o n s
I n
# 1
2 1
# 2
1 1
# 3
2 4
# 4
0
I n
I n
I n
Assign signals to gates (In #1 to #4) by entering the number corresponding to each signal
referring to Appendix B.
Note: If signals are not assigned to all the gates #1 to #4, enter 0 for the unassigned gate(s).
4.2.7
Testing
The sub-menu "Test" provides such functions as disabling the automatic monitoring function,
forced operation of binary outputs, and logic signal observation.
4.2.7.1
Scheme switch
The automatic monitoring function (A.M.F.) can be disabled by setting the switch [A.M.F] to
"OFF".
Disabling the A.M.F. inhibits trip blocking even in the event of a failure in the items being
monitored by this function. It also prevents failures from being displayed on the "ALARM" LED
and LCD described in Section 4.2.1. No events related to A.M.F. are recorded, either.
Disabling the A.M.F. is useful for blocking the output of unnecessary alarms during testing.
54
6 F 2 S 0 7 9 0
Select "Test" on the top "MENU" screen to display the "Test" screen.
/
1
T e
S w i t
B i n a
L o g i
s t
c h
r y
O / P
c
c i r c u i t
.
f
L
f
E
f
S w i t c h
M
f
P
f
C
f
.
/
T
/
T
/
F
O
S
N
S
O
.
n
T
- C L / C L
T
n
Enter 0 or 1 to disable the A.M.F. or not and press the ENTER key for each switch.
Enter 0(=Off) to disable the cold load protection, or enter 1(=N-CL) forcibly to set to
No-cold load condition or enter 2(=CL) forcibly to set to Cold load condition. And
press the ENTER key.
Enter 1(=On) for IECTST to transmit test mode to the control system by
IEC60870-5-103 communication when testing the local relay, and press the ENTER key.
Press the END key to return to the "Test" screen.
4.2.7.2
It is possible to forcibly operate all binary output relays for checking connections with the
external devices. Forced operation can be performed on one or more binary outputs at a time.
Select "Binary O/P" on the "Test" screen to display the "Binary O/P" screen. Then the
LCD displays the name of the output relay.
/ 2
T
D
T
D
B
D
B
D
B
D
B
D
B
D
B
D
F
D
P
i
P
i
O
i
O
i
O
i
O
i
O
i
O
i
A
i
B i n a r y
s
s
1
s
2
s
3
s
4
s
5
s
6
s
I
s
O / P
1
0
a b l e / E n a b l
2
0
a b l e / E n a b l
0
a b l e / E n a b l
0
a b l e / E n a b l
0
a b l e / E n a b l
0
a b l e / E n a b l
0
a b l e / E n a b l
0
a b l e / E n a b l
L
0
a b l e / E n a b l
55
_
e
_
e
_
e
_
e
_
e
_
e
_
e
_
e
_
e
6 F 2 S 0 7 9 0
Enter 1 and press the ENTER key to operate the output relay(s) forcibly.
After completing the entries, press the END key. Then the LCD displays the screen
shown below.
O p e r a t e ?
E N T E R = Y
C A N C E L = N
Keep pressing the ENTER key to operate the assigned output relay(s).
Release pressing the ENTER key to reset the operation.
Press the CANCEL key to return to the upper "Binary O/P" screen.
4.2.7.3
Logic Circuit
It is possible to observe the binary signal level on the signals listed in Appendix B with
monitoring jacks A and B.
Select "Logic circuit" on the "Test" screen to display the "Logic circuit" screen.
/ 2
L o g i c
c i r c u i t
T e r m A
1
_
T e r m B
4 8
_
Enter a signal number to be observed at monitoring jack A and press the ENTER key.
Enter the other signal number to be observed at monitoring jack B and press the ENTER
key.
After completing the setting, the signals can be observed by the binary logic level at monitoring
jacks A and B or by the LEDs above the jacks.
On screens other than the above screen, observation with the monitoring jacks is disabled.
56
6 F 2 S 0 7 9 0
4.3
Harmonic analysis:
For the details, see the separate instruction manual "PC INTERFACE RSM100".
4.4
Twisted-pair
cable
57
6 F 2 S 0 7 9 0
4.5
differential voltage
The IEC60870-5-103 function in the relay can be customized with the original software IEC103
configurator. It runs on a personal computer (PC) connected to the relay, and can help setting of
Time-tagged messages, General command, Metering, etc. For details of the setting method, refer
to IEC103 configurator manual. For the default setting of IEC60870-5-103, see Appendix M.
The protocol can be used through the RS485 port on the relay rear panel and can be also used
through the optional fibre optical interface. The relay connection is similar to Figure 4.4.1.
The relay supports two baud-rates 9.6kbps and 19.2kbps.
The data transfer from the relay can be blocked by the setting.
For the settings, see the Section 4.2.6.4.
4.6
Clock Function
The clock function (Calendar clock) is used for time-tagging for the following purposes:
Event records
Disturbance records
Fault records
The calendar clock can run locally or be synchronised with the external IRIG-B time standard
signal, RSM or IEC clock. This can be selected by setting.
If it is necessary to synchronise with the IRIG-B time standard signal, it is possible to transform
GMT to the local time by setting.
When the relays are connected to the RSM system as shown in Figure 4.4.1, the calendar clock of
each relay is synchronised with the RSM clock. If the RSM clock is synchronised with the
external time standard (GPS clock etc.), then all the relay clocks are synchronised with the
external time standard.
58
6 F 2 S 0 7 9 0
5. Installation
5.1
Receipt of Relays
When relays are received, carry out the acceptance inspection immediately. In particular, check
for damage during transportation, and if any damage is found, contact the vendor.
Check that the following accessories are attached.
3 pins for the monitoring jack, packed in a plastic bag.
5.2
Relay Mounting
A flush mounting relay is delivered. Appendix E shows the case outlines.
For details of relay withdrawal and insertion, see Section 6.7.3.
5.3
Electrostatic Discharge
CAUTION
Do not take out the relay unit outside the relay case since electronic components on the modules
are very sensitive to electrostatic discharge. If it is absolutely essential to take the modules out of
the case, do not touch the electronic components and terminals with your bare hands.
Additionally, always put the module in a conductive anti-static bag when storing it.
5.4
Handling Precautions
A person's normal movements can easily generate electrostatic potentials of several thousand
volts. Discharge of these voltages into semiconductor devices when handling electronic circuits
can cause serious damage, which often may not be immediately apparent but the reliability of the
circuit will have been reduced.
The electronic circuits are completely safe from electrostatic discharge when housed in the case.
Do not expose them to risk of damage by withdrawing relay unit unnecessarily.
The relay unit incorporates the highest practicable protection for its semiconductor devices.
However, if it becomes necessary to withdraw the relay unit, the precautions should be taken to
preserve the high reliability and long life for which the equipment has been designed and
manufactured.
CAUTION
Before removing the relay unit, ensure that you are at the same electrostatic potential as the
equipment by touching the case.
Use the handle to draw out the relay unit. Avoid touching the electronic components,
printed circuit board or connectors.
Do not pass the relay unit to another person without first ensuring you are both at the same
electrostatic potential. Shaking hands achieves equipotential.
59
6 F 2 S 0 7 9 0
Place the relay unit on an anti-static surface, or on a conducting surface which is at the
same potential as yourself.
Do not place the relay unit in polystyrene trays.
5.5
External Connections
External connections for each relay model are shown in Appendix F.
60
6 F 2 S 0 7 9 0
These tests are performed for the following hardware to ensure that there is no hardware defect.
Defects of hardware circuits other than the following can be detected by monitoring which
circuits function when the DC power is supplied.
User interfaces
Binary input circuits and output circuits
AC input circuits
Function tests
These tests are performed for the following functions that are fully software-based.
Measuring elements
Metering and recording
Human interface
Conjunctive tests
The tests are performed after the relay is connected with the primary equipment and other external
equipment.
The following tests are included:
On load test: phase sequence check and polarity check
Tripping circuit test
61
6 F 2 S 0 7 9 0
6.2
Cautions
6.2.1
Safety Precautions
CAUTION
The relay rack is provided with an earthing terminal.
Before starting the work, always make sure the relay rack is earthed.
When connecting the cable to the back of the relay, firmly fix it to the terminal block and
attach the cover provided on top of it.
Before checking the interior of the relay, be sure to turn off the power.
Failure to observe any of the precautions above may cause electric shock or malfunction.
6.2.2
Cautions on Tests
CAUTION
When testing the relay, house it in the case and test it.
While the power is on, do not draw out/insert the relay unit.
Before turning on the power, check the followings:
- Make sure the polarity and voltage of the power supply are correct.
- Make sure the CT circuit is not open.
If dc power has not been supplied to the relay for two days or more, then it is recommended
that all fault records, event records and disturbance records be cleared soon after restoring
the power. This is because the back-up RAM may have discharged and may contain
uncertain data.
Be careful that the relay is not damaged due to an overcurrent or overvoltage.
If settings are changed for testing, remember to reset them to the original settings.
Failure to observe any of the precautions above may cause damage or malfunction of the relay.
62
6 F 2 S 0 7 9 0
6.3
Preparations
Test equipment
Before starting the tests, it must be specified whether the tests will use the users settings or the
default settings.
For the default settings, see the following appendixes:
Appendix C Binary Output Default Setting List
Appendix G Relay Setting Sheet
Visual inspection
After unpacking the product, check for any damage to the relay case. If there is any damage, the
internal module might also have been affected. Contact the vendor.
Relay ratings
Check that the items described on the nameplate on the front of the relay conform to the users
specification. The items are: relay type and model, AC voltage, current and frequency ratings, and
auxiliary DC supply voltage rating.
Local PC
When using a local PC, connect it with the relay via the RS232C port on the front of the relay.
RSM100 software is required to run the PC.
For the details, see the separate manual "PC INTERFACE RSM100".
63
6 F 2 S 0 7 9 0
6.4
Hardware Tests
The tests can be performed without external wiring, but a DC power supply and AC voltage
source are required.
6.4.1
User Interfaces
This test ensures that the LCD, LEDs and keys function correctly.
LCD display
Apply the rated DC voltage and check that the LCD is off.
Note: If there is a failure, the LCD will display the "Err: " screen when the DC voltage is applied.
Press the RESET key and check that black dots appear on the whole screen.
LED display
Apply the rated DC voltage and check that the "IN SERVICE" LED is lit in green.
Press the RESET key and check that remaining five LEDs are lit in red.
VIEW and RESET keys
Press the VIEW key when the LCD is off and check that the "Metering" screen is
displayed on the LCD.
Press the RESET key and check that the LCD turns off.
,
and
keys
Press any key when the LCD is off and check that the LCD displays the "MENU" screen.
Press the END key to turn off the LCD.
Repeat this for all keys.
64
6 F 2 S 0 7 9 0
6.4.2
TB3
-B3
BI1
-A4
DC
power
supply
TB3 -A5
-B5
E
2
B
P
[
P 1 [
P 2 [
i n a r y
I / O
0
0 0
0 0 0
0 0 0
]
]
]
Check that the status display corresponding to the input signal changes from 0 to 1. (For
the binary input status display, see Section 4.2.4.2.)
6.4.3
P
i
P
i
O
i
O
i
O
B i n a r y
s
s
1
s
2
s
3
O / P
1
0
a b l e / E n a b l
2
0
a b l e / E n a b l
0
a b l e / E n a b l
0
a b l e / E n a b l
0
_
e
_
e
_
e
_
e
_
65
6 F 2 S 0 7 9 0
After completing the entries, press the END key. The LCD will display the screen shown
below. If 1 is entered for all the output relays, the following forcible operation can be
performed collectively.
O p e r a t e ?
E N T E R = Y
C A N C E L = N
Keep pressing the ENTER key to operate the output relays forcibly.
Check that the output contacts operate at the terminal.
Stop pressing the ENTER key to reset the operation.
6.4.4
AC Input Circuits
This test can be performed by applying the checking voltages to the AC input circuits and
verifying that the values applied coincide with the values displayed on the LCD screen.
The testing circuit is shown in Figure 6.4.2. A single-phase voltage source is required.
GRB150
EB-10
V
Single-phase
voltage
source
TB1-1
-2
TB2-1
Va
-3
-4
-5
-6
Vb
Vc
-2
TB1 -1
-2
-3
-4
-5
-6
-3
-4
-5
-6
-8
DC
power
supply
Va
TB3 -A5
-B5
Vb
Vc
E
*(Note) EB-101: single-phase, EB-102: three-phase
66
6 F 2 S 0 7 9 0
6.5
Function Test
6.5.1
Measuring Element
Measuring element characteristics are realised by software, so it is possible to verify the overall
characteristics by checking representative points.
Operation of the element under test is observed by the binary output signal at monitoring jacks A
or B or by the LED indications above the jacks. In any case, the signal number corresponding to
each element output must be set on the "Logic circuit" screen of the "Test" sub-menu.
/ 2
L o g i c
c i r c u i t
T e r m A
1
_
T e r m B
4 8
_
When a signal number is entered for the Term A line, the signal is observed at monitoring jack A
and when entered for the Term B line, it is observed at monitoring jack B.
Note:
The voltage level at the monitoring jacks is +5V for logic level "1" and less than 0.1V for
logic level "0".
CAUTION
Use test equipment with more than 1 k of internal impedance when observing the output
signal at the monitoring jacks.
Do not apply an external voltage to the monitoring jacks.
Do not leave the A or B terminal shorted to 0V terminal for a long time.
In case of a three-phase element, it is sufficient to test for a representative phase. The A-phase
element is selected hereafter.
67
6 F 2 S 0 7 9 0
6.5.1.1
Figure 6.5.1 shows a testing circuit. The minimum operating voltage value is checked by
increasing the magnitude of the voltage applied.
GRB150
EB-10
TB1-1(TB1-1)
+
Single-phase
voltage
source
TB1-4(TB2-1)
TB1 -1
TB1-5(TB2-2)
-2
Va
TB1-2(TB1-2)
-3
-4
-5
-8
Monitoring
jack
A
0V
-6
DC
power
supply
TB3 -A5
-B5
E
DC
voltmeter
*(Note) EB-101: single-phase, EB-102: three-phase. The terminal No. shown in the parentheses are in the case of EB-102.
Signal number
DIF-A (DIF)
11
DIF-B
12
DIF-C
13
Remarks
Select "Logic circuit" on the "Test" sub-menu screen to display the "Logic circuit" screen.
Enter signal number 11 to observe the DIF-A operation at monitoring jack A and press the
ENTER key.
Apply a test voltage and change the magnitude of the voltage applied and measure the
value at which the element operates.
Check that the measured value is within 10% of the setting value.
68
6 F 2 S 0 7 9 0
Operating time
GRB150
EB-10
TB1-1
(TB1-1)
Single-phase
voltage
source
Va
TB1-2
(TB1-2)
TB1-4 TB1 -1
(TB2-1)
TB1-5
(TB2-2)
-2
Monitoring
jack
0V
-8
DC
power
supply
TB3 -A5
-B5
E
Start
Time
counter
Stop
0V
*(Note) EB-101: single-phase, EB-102: three-phase. The terminal No. shown in the parentheses are in the case of EB-102.
Figure 6.5.1 shows a testing circuit. The minimum operating voltage value is checked by
increasing the magnitude of the voltage applied.
The output signal numbers of the DIF elements are as follows:
Element
Signal number
DIFSV-A
14
DIFSV-B
15
DIFSV-C
16
Remarks
Select "Logic circuit" on the "Test" sub-menu screen to display the "Logic circuit" screen.
Enter signal number 14 to observe the DIFSV-A operation at monitoring jack A and press
69
6 F 2 S 0 7 9 0
the ENTER key.
Apply a test voltage and change the magnitude of the voltage applied and measure the
value at which the element operates.
Check that the measured value is within 10% of the setting value.
6.5.2
Protection Scheme
In the protection scheme tests, a dynamic test set is required to simulate power system pre-fault,
fault and post-fault conditions.
Tripping is observed with the tripping command output relays TP-1 and 2.
Differential tripping
The tripping should be checked for the voltage which is two times or larger than the minimum
operating voltage DIF. Operating time is measured by the operating time of the tripping
command output relay. It is usually 20ms.
Check that the indications and recordings are correct.
6.5.3
Some of the internal events can be checked in the protection scheme tests.
Disturbance recording can be checked while testing the protection schemes. The LCD display
only shows the date and time when a disturbance is recorded. Open the "Disturbance records"
screen and check that the descriptions are correct.
Details can be displayed on the PC with the RSM100 software. Check that the descriptions on the
PC are correct. For details on how to obtain disturbance records on the PC, see the RSM100
Manual.
70
6 F 2 S 0 7 9 0
6.6
Conjunctive Tests
6.6.1
On Load Test
With the relay connected to the line which is carrying a load current, it is possible to check the
polarity of the current transformer with the metering displays on the LCD screen.
Open the following "Metering" screen from the "Status" sub-menu.
/ 2
V d
M e t e r i n g
V
.
(Model 101)
/ 2
M e
V d a
V d b
V d c
(Model 201)
r
.
.
.
i n g
V
Check that the differential voltage Vd or Vda, Vdb and Vdc are sufficiently smaller than
the DIF and DIFSV setting values.
6.6.2
TP-1 and -2 are output relays with one normally open contact.
Enter 1 for TP-1 and press the ENTER key.
Press the END key. Then the LCD displays the screen shown below.
O p e r a t e ?
E N T E R = Y
C A N C E L = N
Keep pressing the ENTER key to operate the output relay TP-1 and check that the No.1
breaker is tripped.
Stop pressing the ENTER key to reset the operation.
Repeat the above for TP-2.
71
6 F 2 S 0 7 9 0
6.7
Maintenance
6.7.1
Regular Testing
The relay is almost completely self-supervised. The circuits that can not be supervised are binary
input and output circuits and human interfaces.
Therefore, regular testing is minimised to checking the unsupervised circuits. The test procedures
are the same as described in Sections 6.4.1, 6.4.2 and 6.4.3.
6.7.2
Failure location
Relay Unit
Err: Sum
Err: MEM
Err: RAM
Err: BRAM
Err: ROM
Err: A/D
Err: SP
Err: DI
Err: DO
Err: LCD
Err: Vd
EB-101 or -102
AC cable
(2)
(2)
(1)
72
6 F 2 S 0 7 9 0
If no message is shown on the LCD, this means that the failure location is either in the DC power
supply circuit or in the microprocessors.
When a failure is detected by automatic supervision or regular testing, replace the failed relay
unit.
Note: When a failure or an abnormality is detected during the regular test, confirm the following
first:
- Test circuit connections are correct.
- Relay unit is securely inserted in position.
- Correct DC power voltage with correct polarity is applied and connected to the correct
terminals.
- Correct AC inputs are applied and connected to the correct terminals.
- Test procedures comply with those stated in the manual.
6.7.3
CAUTION
WARNING Hazardous voltage may remain in the DC circuit just after switching off the
DC power supply. It takes approximately 30 seconds for the voltage to
discharge.
Keep the handle up when inserting the relay unit into the case.
Do not catch the handle when carrying the relay unit.
73
6 F 2 S 0 7 9 0
IN SERVICE VIEW
TRIP
ALARM
TESTING
IN SERVICE VIEW
TRIP
ALARM
TESTING
RESET
RESET
0V CAN ENTER
CEL
END
0V CAN ENTER
CEL
END
Handle
Pull up handle
Bind screw
6.7.4
Resumption of Service
After replacing the failed relay unit or repairing failed external circuits, take the following
procedures to put the relay into service.
Switch on the DC power supply and confirm that the "IN SERVICE" green LED is lit and
the "ALARM" red LED is not lit.
Supply the AC inputs and reconnect the trip outputs.
6.7.5
Storage
The spare relay should be stored in a dry and clean room. Based on IEC Standard 60255-6 the
storage temperature should be between 25C and +70C, but the temperature of 0C to +40C is
recommended for long-term storage.
74
6 F 2 S 0 7 9 0
In particular, when settings are changed temporarily for testing, be sure to restore them.
Clear any unnecessary records on faults, events and disturbances which are recorded
during the tests.
CAUTION:
If dc power has not been supplied to the relay for two days or more, then it is
recommended that all fault records, event records and disturbance records be
cleared soon after restoring the power. This is because the back-up RAM may
have discharged and may contain uncertain data.
Press the VIEW key and check that no failure message is displayed on the
"Auto-supervision" screen.
Check that the green "IN SERVICE" LED is lit and no other LEDs are lit on the front
panel.
75
6 F 2 S 0 7 9 0
76
6 F 2 S 0 7 9 0
Appendix A
Block Diagram
77
6 F 2 S 0 7 9 0
Tripping
output relay
DIF
&
TP-1
0.2s
(Trip1)
TP-2
t
&
DIFSV
&
0.01s
Alarm
(VD ERR)
0.5s
[VDCHK]
[SVCNT]
"ALM&BLK"
"ON"
Tripping
output relay
0
&
TP-1
0.2s
DIF
&
t
TP-2
0.2s
&
0
&
DIFSV
&
0.2s
&
0.01s
0
0.5s
Alarm
(VD ERR)
0
0.5s
&
0
0.5s
[VDCHK]
"ON"
[SVCNT]
"ALM&BLK"
78
6 F 2 S 0 7 9 0
Appendix B
Signal List
79
6 F 2 S 0 7 9 0
SIGNAL LIST
No .
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
CO NTENTS
0 (Zer o log ic)
BI1
CO L D LO AD
DIF-A
B
C
DIFSV-A
B
C
C OL D LO AD PRO TECTION
D IFFERENTIAL REL AY
d itto
d itto
D IFFERENTIAL RELAY FOR SV
d itto
d itto
TRIP-A
TRIP-B
TRIP-C
VD ERR -A
VD ERR -B
VD ERR -C
VD ERR -O R
TRIP
TRIP-H
A.M.F O FF
FALUT RECO R D IN ITIATIO N
IND.D AT TRIG
DIF-AT
DIF-BT
DIF-CT
SV BLO CK
TRIG O F FAUL T R ECO RD
d itto
FALL T REC O RD D ATA
d itto
d itto
No .
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
1 00
1 01
1 02
1 03
1 04
1 05
1 06
1 07
1 08
1 09
1 10
1 11
1 12
1 13
1 14
1 15
1 16
1 17
1 18
1 19
1 20
1 21
1 22
1 23
1 24
1 25
1 26
1 27
1 28
1 29
1 30
1 31
1 32
1 33
1 34
1 35
1 36
1 37
1 38
1 39
1 40
1 41
1 42
1 43
1 44
1 45
1 46
1 47
1 48
1 49
1 50
1 51
1 52
1 53
1 54
1 55
1 56
1 57
1 58
1 59
1 60
REL AY FAIL
REL AY BL O CK
TESTING
REL AY FAIL-A
C O NTENTS
RELAY FAIL
RELAY BLO C K
TEST SWITCH AC TIVATED
RELAY FAIL -A
BO 1 O P
BO 2 O P
BO 3 O P
BO 4 O P
BO 5 O P
BO 6 O P
Bina ry o utpu t1
Bina ry o utpu t2
Bina ry o utpu t3
Bina ry o utpu t4
Bina ry o utpu t5
Bina ry o utpu t6
IECBLK
IECTST
G RO UP1 AC TIVE
G RO UP2 AC TIVE
G RO UP3 AC TIVE
G RO UP4 AC TIVE
LO C AL OP ACT.
REMO TE OP ACT.
NO R MAL LED O N
ALAR M LED O N
TRIP L ED O N
TEST LED O N
LED R ESET
TR IP LED R ESET
PRO T CO M O N
PRG . L ED1 O N
PRG . L ED2 O N
80
No.
1 61
1 62
1 63
1 64
1 65
1 66
1 67
1 68
1 69
1 70
1 71
1 72
1 73
1 74
1 75
1 76
1 77
1 78
1 79
1 80
1 81
1 82
1 83
1 84
1 85
1 86
1 87
1 88
1 89
1 90
1 91
1 92
1 93
1 94
1 95
1 96
1 97
1 98
1 99
2 00
CO NTENTS
DI
D I C ON TAC T ER RO R
ER R
FAU LT RECO R D DO NE
FAU LT R ECO RD D O NE
PRO T C OM RC V
TPL ED RST RC V
PRG LED /D O R ST RC V
SET.G RO UP1
SET.G RO UP2
SET.G RO UP3
SET.G RO UP4
6 F 2 S 0 7 9 0
Appendix C
Binary Output Default Setting List
81
6 F 2 S 0 7 9 0
Signal Name
Contents
Model
Setting
LOGIC
(OR:0, AND:1)
Reset
(Inst:0, Del:1, Latch:2)
101
BO1
BO2
BO3
BO4
BO5
BO6
VD ERR
VD ERR
VD ERR
TRIP
TRIP
TRIP
24
24
24
21
21
21
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
BO1
BO2
BO3
BO4
BO5
BO6
VD ERR-A
VD ERR-B
VD ERR-C
TRIP-A
TRIP-B
TRIP-C
24
25
26
21
22
23
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
201
82
6 F 2 S 0 7 9 0
Appendix D
Details of Relay Menu and
LCD & Button Operation Instruction
83
6 F 2 S 0 7 9 0
MENU
xRecord
xStatus
xSet. (view)
xSet. (change)
xTest
/1 Record
xF. record
xE. record
xD. record
/2 F.record
xDisplay
/3 F.record
xClear
#1 16/Oct/1997
18:13:57.031
Refer to Section
4.2.3.1.
/4 F.record #1
16/Oct/1997
Clear records?
END=Y
CANCEL=N
/2 E.record
xDisplay
/3 E.record
xClear
16/Oct/1997
Ext. trip A
Refer to Section
4.2.3.2.
On
Clear records?
END=Y
CANCEL=N
/2 D.record
xDisplay
/3 D.record
xClear
#1 16/Oct/1997
18:13:57.401
Refer to Section
4.2.3.3.
Clear records?
END=Y
CANCEL=N
a-1
84
6 F 2 S 0 7 9 0
a-1
/1 Status
xMetering
xBinary I/O
xRelay element
xTime sync.
xClock adjust.
xLCD contrast
/2 Metering
Vda ***.* V
/2 Binary I/O
IP [0
/2 Ry element
[000 000
/2 Time sync.
*IRIG: Act
/2 12/Nov/1999
22:56:19 [L]
/2 LCD contrast
/1 Set. (view)
xVersion
xDescription
xComms
xRecord
xStatus
xProtection
xBinary I/P
xBinary O/P
xLED
/2 Version
xRelay type
xSerial No.
xSoftware
/2 Description
xPlant name
GRB150-201B-12
-30
GS1BP1-03-*
xDescription
/2 Comms
xAddr./Param.
/3 Addr./Param.
xSwitch
/3 Switch
a-1, b-1
85
6 F 2 S 0 7 9 0
a-1 b-1
/2 Record
xE.record
xD.record
/2 Status
xTime sync.
/3 E.record
/3 D.record
xTime/starter
/4 Time/starter
Time
2.0s
x Scheme sw
/4 Scheme sw
/3 Time sync.
xTime zone
/3 Time zone
GMT
+9hrs
/2 Act. gp. =*
xGroup1
xGroup2
xGroup3
xGroup4
/3 Group1
xParameter
xTrip
/4 Parameter
xLine name
/4 Trip
xScheme sw
/5 Scheme sw
xProt.element
/5 Prot.element
DIF
10V
/3 Group2
xParameter
/3 Group4
xParameter
a-1 b-1
86
6 F 2 S 0 7 9 0
a-1
b-1
/2 Binary I/P
BISW1
Norm/Inv
1 _
/2 Binary O/P
BO1 AND, D
( 1, 10, 29, 0)
BO6 AND, D
( 0, 0, 0, 0)
/2 LED
LED1
21
LED2
11
/1 Set.(change)
xPassword
xDescription
xComms
xRecord
xStatus
xProtection
xBinary I/O
xBinary O/P
xLED
Input
[_
1234567890
: Password trap
Password [_
1234567890
: Confirmation trap
Change settings?
ENTER=Y CANCEL=N
Retype
[_
1234567890
Refer to Section
4.2.6.2.
/2 Description
xPlant name
xDescription
Refer to Section
4.2.6.3.
a-1
_
ABCDEFG
_
ABCDEFG
b-2
87
6 F 2 S 0 7 9 0
a-1
b-2
/2 Comms
xAddr./Param.
xSwitch
Refer to Section
4.2.6.4.
/3 Addr./Param.
/3 Switch
/2 Record
xE.record
/3 E.record
xD.record
Trip
N/O/R/B
Refer to Section
4.2.6.5.
3 3 _
Grp. change 1 1 _
N/O
/3 D.record
xTime/Starter
xScheme sw
/2 Status
xTime sync.
xTime zone
/3 Time sync.
/3 Time zone
Refer to Section
4.2.6.6.
/2 Protection
xChange act. gp.
xChange set.
xCopy gp.
Refer to Section
4.2.6.7.
/3 Change act.
gp.
/3 Act gp.=1
xGroup1
xGroup2
xGroup3
xGroup4
a-1
b-2
c-1
d-1
88
/4 Time/Starter
/4 Scheme sw
6 F 2 S 0 7 9 0
a-1
b-2
c-1
d-1
/4 Group*
xParameter
xTrip
/5 Parameter
xLine name
/5 Trip
xScheme sw
xProt.element
/6 Scheme sw
ABCDEFG
VDCHK
Off/On
SVCNT
ALM&BLK/ALM
IND.R
Off/On
CLEN
Off/N-CL/CL
1 _
0 _
1 _
0 _
/6 Prot.element
DIF
V
10 _
DIFSV
/4 Group2
xParameter
5 _
/4 Group4
xParameter
/3 Copy A to B
A
B
_
_
TVDSV
0.50
DIFCC
1.00
TCLP
0.01
TCLE
0.00
TCLR
0.00
/2 Binary I/P
BISW1
Norm/Inv
1 _
Refer to Section
4.2.6.8.
a-1, b-2
89
s
_
_
s
_
s
_
s
_
6 F 2 S 0 7 9 0
a-1, b-2
/2 Binary O/P
xBO1
/3 Set. (BO1)
xLogic/Reset
xFunctions
/4 Functions
xBO6
Refer to Section
4.2.6.9.
/4 Logic/Reset
/3 Set. (BO6)
xLogic/Reset
xFunctions
/2 LED
xLED1
/3 LED1
xLogic/Reset
xLED2
xFunctions
Refer to Section
4.2.6.10.
/4 Logic/Reset
/4 Functions
/3 LED2
xLogic/Reset
xFunctions
/1 Test
xSwitch
/2 Switch
xBinary O/P
xLogic circuit
A.M.F.
Off/On
CLPTST
Off/N-CL/CL
IECTST
Off/On
/2 Binary O/P
/2 Logic
circuit
TermA
1 _
TermB
100
90
1 _
0
0
Operate?
ENTER=Y CANCEL=N
6 F 2 S 0 7 9 0
MANUAL
MODE
1=RECORD
1=FAULT RECORD
2=EVENT RECORD
3=DISTURBANCE RECORD
NORMAL
(DISPLAY OFF)
VIEW
PRESS ANY
BUTTON
EXCEPT FOR
"VIEW" AND
"RESET"
MENU
( DISPLAY ON )
2=STATUS
1=METERING
2=BINARY INPUT&OUPUT
METERING
(DISPLAY ON)
AUTOMODE 1
3=RELAY ELELMENT
4=TIME SYNC SOURCE
5=CLOCK ADJUSTMENT
TRIP OUTPUT
ISSUED !
VIEW
RESET
TRIP
( LED ON )
3=SETTING
(VIEW)
1=RELAY VERSION
LATEST FAULT *
(DISPLAY ON)
2=DESCRIPTION
AUTOMODE 2
3=RSM COMMUNICATION
4=RECORD
RELAY
FAILED !
VIEW
5=STATUS
RESET
ALARM
( LED ON )
6=PROTECTION
7=BINARY INPUT
8=BINARY OUTPUT
AUTO SUPERVISION *
(DISPLAY ON)
9=LED
*. "LATEST FAULT" AND "AUTO
SUPERVISION" SCREEN IS
DISPLAYED ONLY IF DATA
IS STORED
VIEW
RESET
4=SETTING
(CHANGE)
5=TEST
1=SWITCH
2=BINARY
O
3=LOGIC CIRCUIT
91
6 F 2 S 0 7 9 0
92
6 F 2 S 0 7 9 0
Appendix E
Outline of GRB150 and EB-101, -102
Case Type of GRB150: Flush Mount Type
EB-101 and EB-102
93
IN SERVICE VIEW
TRIP
ALARM
TESTING
RESET
0V
25 8
6 F 2 S 0 7 9 0
CAN
CEL ENTER
END
15.6
104
243.5
Side view
Front view
4 holes-5.5
4 holes-4.5
TB2
32
TB1
CN1
E
56
Rear view
102
TB2
A1
TB1
B1
Panel cut-out
1 2
3 4
5 6
TB3
A1
B1
A6
B6
TB1, TB2, TB3: M3.5 Ring
terminal
A18
B18
Terminal block
94
24 9
239
TB3
6 F 2 S 0 7 9 0
M4 Ring
terminal
TB1
1
205
226.5
Terminal block
Top view
TB1
70
225
70
42.5
214.4
234
252
Side view
Front view
(a) EB-101
M4 Ring
terminal
M4 Ring
terminal
TB2
TB1
1
1
205 226.5
8
12
Terminal block
Top view
6-5.5 for mounting
TB2
TB1
70
225
70
42.5
362.4
382
400
Front view
Side view
(b) EB-102
Note: When mounting varistor units longitudinally, the TB1 should be located in the down side.
Outline of varistor unit
95
6 F 2 S 0 7 9 0
96
6 F 2 S 0 7 9 0
Appendix F
External Connection
97
6 F 2 S 0 7 9 0
EB-101
TB1 -1 TB1 -4
OUTPUT CONTACTS
SIGNAL LIST (DEFAULT)
VD ERR ALARM
BO1
VD ERR ALARM
BO2
VD ERR ALARM
BO3
TRIP ALARM
BO4
TRIP ALARM
BO5
TRIP ALARM
BO6
TB2-A1
TB1 -1
TRIP - 1
TP-1
B1
A2
-2
TB1 -2 TB1 -5
B2
TP-2
TB1 -8
FRAME EARTH
TRIP - 2
A5
BO1
B5
A6
BO2
B6
A7
BO3
B7
A8
BO4
B8
A9
BO5
B9
A10
BO6
B10
TB2
A1
B1
(+)
TB3 -B3
BI1
B15
-A4
COM1-A
COM1-B
RELAY FAILURE
RELAY FAIL.
DD FAIL.
DC
SUPPLY
TB3 -A5
(+)
-B5
(-)
COM2-A
+5Vdc
DC-DC
COM2-B
TB3
0V
B1
A6
B6
IRIG-B
A16
A18
B18
A18
Terminal Block Arrangement (Rear view)
TB2-B17
B16
0V
TB3 -A6
2
6
A1
TB2-A17
TB1
1
5
FAIL TB2-A15
B18
-B6
E
IRIG-B
CASE EARTH
Note: In AC circuit wiring, the wires of the relay side should be separated from these of the CT side to
avoid the influence of noise.
98
6 F 2 S 0 7 9 0
A-phase
TB1-1
TB1-2
EB-102
B-phase
TB1-3
TB1-4
TB2-A1
TB1 -1
TB2-1
-2
TB2-2
TP-1
-3
TP-2
TB2-3
TB2-4
B2
TRIP - 1
TRIP - 2
-5
TB1-5
TB1-6
FA1
B1
A2
-4
C-phase
FAn
OUTPUT CONTACTS
SIGNAL LIST (DEFAULT)
BO1
VD ERR-A ALARM
BO2
VD ERR-B ALARM
BO3
VD ERR-C ALARM
BO4
TRIP-A ALARM
BO5
TRIP-B ALARM
BO6
TRIP-C ALARM
TB2-5
TB2-6
A5
-6
BO1
TB1-8
B5
A6
FRAME EARTH
BO2
B6
A7
BO3
B7
A8
BO4
B8
A9
BO5
B9
A10
BO6
B10
TB2
A1
B1
(+)
TB3 -B3
TB1
1
5
FAIL TB2-A15
TB3
RELAY FAILURE
BI1
B15
-A4
COM1-A
TB2-A17
A1
B1
A6
B6
IRIG-B
A18
A16
COM1-B
2
6
B18
0V
RELAY FAIL.
DD FAIL.
DC
SUPPLY
TB3-A5
(+)
-B5
(-)
COM2-A
+5Vdc
DC-DC
COM2-B
B16
0V
0V
TB3-A6
B18
-B6
E
IRIG-B
CASE EARTH
Note: In AC circuit wiring, the wires of the relay side should be separated from these of the CT side to
avoid the influence of noise.
99
6 F 2 S 0 7 9 0
100
6 F 2 S 0 7 9 0
Appendix G
Relay Setting Sheet
1. Relay Identification
2. Busbar parameters
3. Contacts setting
4. Relay setting sheet
101
6 F 2 S 0 7 9 0
Relay Setting Sheets
1. Relay Identification
Date:
Relay type
Serial Number
Frequency
AC voltage
DC supply voltage
Password
Active setting group
2. Busbar parameters
CT ratio
3. Contacts setting
(1)
BO1
BO2
BO3
BO4
BO5
BO6
102
6 F 2 S 0 7 9 0
Name
Range
Units
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
Act.gp.
Line name
VDCHK
SVCNT
IND.R
CLEN
DIF
DIFSV
TVDSV
DIFCC
TCLP
TCLE
TCLR
BISW1
Logic
Reset
In #1
LED1
In #2
In #3
In #4
Logic
Reset
In #1
LED2
In #2
In #3
In #4
Plant name
Description
HDLC
IEC
IECBR
IECBLK
Trip
Vd err
Ind.reset
Cold load
Relay fail
Sys.change
Rly.change
Grp.change
Time
1-4
Specified by user
Off(0) / On(1)
ALM&BLK(0) / ALM(1)
Off(0) / On(1)
Off(0) / F1(1) / F2(2)
10 - 600
5 - 100
0.10 - 60.00
1.00 - 10.00
0.01 - 100.00
0.00 - 100.00
0.00 - 100.00
Norm(0) / Inv(1)
OR(0)/AND(1)
Inst(0)/Latch(1)
0 - 200
0 - 200
0 - 200
0 - 200
OR(0)/AND(1)
Inst(0)/Latch(1)
0 - 200
0 - 200
0 - 200
0 - 200
Specified by user
ditto
1 - 32
0 - 254
9.6(0) / 19.2(1)
Normal(0) / Blocked(1)
N(0) / O(1) / R(2) / B(3)
N(0) / O(1) / R(2) / B(3)
N(0) / O(1) / R(2) / B(3)
N(0) / O(1) / R(2) / B(3)
N(0) / O(1) / R(2) / B(3)
N(0) / O(1)
N(0) / O(1)
N(0) / O(1)
0.1 - 3.0
V
V
s
42
TRIP
Off(0) / On(1)
43
44
45
Vd err
Time sync
GMT
Off(0) / On(1)
Off(0) / IRI(1) / RSM(2) / IEC(3)
-12 - +12
hrs
s
s
s
Contents
Active setting group
Line name
Vd check use or not
Supervision control
Indication reser by BI1
Cold Load Protection
Differential relay
Differential relay for supervision
VD err timer
DIF setting coef f icient in CLP mode.
103
Default Setting
of Relay series
101
201
1
Specified by user
On(1)
ALM&BLK(0)
On(1)
Off(0)
100
50
0.50
1.00
0.01
0.00
0.00
Norm(0)
OR(0)
Inst(0)
0
0
0
0
OR(0)
Inst(0)
0
0
0
0
Specified by user
Specified by user
1
2
19.2(1)
Normal(0)
B(3)
B(3)
B(3)
B(3)
B(3)
O(1)
O(1)
O(1)
1.0
On(1)
On(1)
Off(0)
0
Setting
6 F 2 S 0 7 9 0
104
6 F 2 S 0 7 9 0
Appendix H
Commissioning Test Sheet (sample)
1.
Relay identification
2.
Preliminary check
3.
Hardware test
3.1 User interface check
3.2 Binary input/Binary output circuit check
3.3 AC input circuit check
4.
Function test
4.1 Differential element DIF test
4.2 Supervisory element DIFSV test
5.
6.
7.
Conjunctive test
105
6 F 2 S 0 7 9 0
1.
Relay identification
Type
Serial number
Model
System frequency
Station
Date
Circuit
Engineer
Protection scheme
Witness
Preliminary check
Ratings
CT shorting contacts
DC power supply
Power up
Wiring
Relay inoperative
alarm contact
Calendar and clock
3.
Hardware test
106
6 F 2 S 0 7 9 0
4.
Function test
Measured voltage
Test voltage
Measured time
5.
6.
7.
Conjunctive test
Measured voltage
Scheme
Results
On load
Tripping circuit
107
6 F 2 S 0 7 9 0
108
6 F 2 S 0 7 9 0
Appendix I
Return Repair Form
109
6 F 2 S 0 7 9 0
Type:
GRB150
(Example: Type:
Model:
Sub No.
Model:
GRB150
201B-12-30 )
Product No.:
Serial No.:
Date:
1.
2.
Fault records, event records or disturbance records stored in the relay and relay settings are
very helpful information to investigate the incident.
Please provide relevant information regarding the incident on floppy disk, or fill in the
attached fault record sheet and relay setting sheet.
Fault Record
Date/Month/Year Time
15:09:58.442)
Faulty phase:
Prefault values
Vda:
V
Vdb:
V
Vdc:
V
110
6 F 2 S 0 7 9 0
Fault values
Prefault values
Vda:
V
Vdb:
V
Vdc:
V
3.
What was the message on the LCD display at the time of the incident?
4.
5.
(Example: 10/July/1998)
6.
111
6 F 2 S 0 7 9 0
Customer
Name:
Company Name:
Address:
Telephone No.:
Facsimile No.:
Signature:
112
6 F 2 S 0 7 9 0
Appendix J
Technical Data
113
6 F 2 S 0 7 9 0
TECHNICAL DATA
Ratings
AC current (In):
1A (fixed)
Frequency:
50Hz or 60Hz
DC power supply:
110Vdc/125Vdc
220Vdc/250Vdc
48Vdc
(Nominal range: 20% and +20% of rated voltage)
Maximum 12%
Overload rating
AC voltage input for varistor unit EB-101 or EB-102:
300V continuous
1kVrms for 0.4s
Binary input signal
Operating voltage:
Burden
DC power supply:
10 to 600V in 1V steps
Supervisory (DIFSV):
5 to 100V in 1V steps
Input impedance:
1 cycle
10%
Supervisory:
10%
114
6 F 2 S 0 7 9 0
Cold load protection (CLP)
Differential protection (DIFCC):
0.01 to 100.00 s
0.00 to 100.00 s
0.00 to 100.00 s
Communication port
Front communication port (local PC)
Connection:
Point to point
Cable type:
Multi-core (straight)
Cable length:
15m (max.)
Connector:
RS485
64kbps
Connection:
Connector:
Screw terminals
Isolation:
Contact ratings
Trip contacts:
Make and carry:
5A continuously
30A, 290Vdc for 0.5s (L/R 10ms)
Break:
Auxiliary contacts:
Make and carry:
4A continuously
10A, 220Vdc for 0.2s (L/R 5ms)
Break:
Mechanical design
Weight:
5kg
Case color:
Installation:
Flush mounting
115
6 F 2 S 0 7 9 0
Standards
Details
Atmospheric Environment
Temperature
IEC60068-2-1/2
Humidity
IEC60068-2-78
Enclosure Protection
IEC60529
Vibration
IEC60255-21-1
Response - Class 1
Endurance - Class 1
IEC60255-21-2
Seismic
IEC60255-21-3
Class 1
Dielectric Withstand
IEC60255-5
IEC60255-5
Mechanical Environment
Electromagnetic Environment
High Frequency
Disturbance
IEC60255-22-1 Class 3
Electrostatic Discharge
IEC60255-22-2 Class 3
IEC60255-22-2 Class 4
Radiated RF
Electromagnetic
Disturbance
IEC60255-22-3
Fast Transient
Disturbance
IEC60255-22-4 Class 4
116
6 F 2 S 0 7 9 0
Appendix K
Symbols Used in Scheme Logic
117
6 F 2 S 0 7 9 0
Symbols used in the scheme logic and their meanings are as follows:
Signal names
Marked with
Marked with
Marked with [
] : Scheme switch
Unmarked
AND gates
A
B
&
Output
A
1
&
Output
A
1
B
C
1
0
Other cases
Output
1
0
&
Output
A
1
B
C
0
0
Other cases
Output
1
0
Output
A
0
B
C
0
0
Other cases
Output
0
1
Output
A
0
B
C
0
1
Other cases
Output
0
1
Output
A
0
B
C
1
1
Other cases
Output
0
1
A
B
C
A
B
C
B
C
1
1
Other cases
Output
1
0
OR gates
A
B
C
A
B
C
A
B
C
118
6 F 2 S 0 7 9 0
Signal inversion
A
0
1
Output
Output
1
0
Timer
t
XXX:
Set time
XXX
0
XXX:
Set time
XXX
t
One-shot timer
A
Output
Output
XXX - YYY
S
F/F
Output
R
0
0
1
1
Output
No change
1
0
0
Scheme switch
Output
ON
Output
ON
119
A
Switch
1
ON
Other cases
Switch
ON
OFF
Output
1
0
Output
1
0
6 F 2 S 0 7 9 0
120
6 F 2 S 0 7 9 0
Appendix L
Setting Calculation
121
6 F 2 S 0 7 9 0
1. Setting of DIF
Model circuit:
Busbar
RS1
CT1
RL1
RL2
ZR
ZE1
RS2
GRB150+
EB-101/EB-102
ZE2
CT2
IFmax
Constants:
1) Resistance of CT secondary winding ............................... RS2 = 1.5 ohms
2) Resistance of secondary wiring for CT connecting lead loop most onerous
case .................................................................................. RL2 = 1.0 ohm
3) Maximum through fault current ...................................... IFmax = 50kA
4) CT ratio ............................................................................ N = 800
5) Number of CTs connected to GRB150 ............................ n = 14
6) CT secondary excitation current at GRB150 setting voltage
.......................................................................................... Ie = 3mA
7) GRB150 input impedance................................................. ZR = 667 ohms
8) CT knee-point voltage ...................................................... Vk= 1000V
9) Minimum internal fault current ........................................ IFmin = 1000A
Setting calculations :
1) Calculate voltage setting value.
VR 1.2 (RS2 + RL2) IFmax / N
1.2 (1.5 ohms + 1.0 ohm) 50000 / 800
188V
2) Calculate minimum operating current value for internal fault.
Imin = (n Ie + Ir + I) N
= (n Ie + Ir + VR / ZR) N
= (14 0.003 A + 188 / 667 ohms) 800
122
6 F 2 S 0 7 9 0
= 259A
Ir is neglected because it is less than 0.1 mA referring to voltage-current characteristic of
the varistor shown below.
Setting checks:
1)
Check that the setting voltage value VR is smaller than half of the CT knee-point voltage
Vk .
1000 / 2 = 500 V > 188V
2)
Check that the minimum internal fault current IFmin is larger than the minimum operating
current value Imin.
1000A > 259A
Note: The current sensitivity Imin can be reduced by connecting a shunt resistor across the
relay/varistor unit input. To reduce it from 259A to 400A for example, connect a
resistor of 1067 ohms[= 188V800/(400A-259A)].
2000
1800
1600
1400
Voltage
(V)
1200
1000
800
600
400
200
0.0001
0.001
0.01
0.1
Current (A)
123
10
100
1000
10000
6 F 2 S 0 7 9 0
2. Setting of DIFSV
The setting of DIFSV is determined from the maximum erroneous voltage which is generated due
to the following two factors under normal service conditions.
CT turns ratio errors
Error due to differences in the respective lengths of the CT secondary connecting
leads to the paralleling point of the differential circuit
Erroneous voltage Ver1 due to CT turns ratio errors:
The maximum erroneous voltage Ver1 is given by the following equation:
Ver1 = ZR ILmax CTer
where,
ZR:
relay impedance
124
6 F 2 S 0 7 9 0
Appendix M
IEC60870-5-103: Interoperability and
Troubleshooting
125
6 F 2 S 0 7 9 0
IEC60870-5-103 Configurator
IEC103 configurator software is included in a same CD as RSM100, and can be installed easily as
follows:
Installation of IEC103 Configurator
Insert the CD-ROM (RSM100) into a CDROM drive to install this software on a PC.
Double click the Setup.exe of the folder \IEC103Conf under the root directory, and operate it
according to the message.
When installation has been completed, the IEC103 Configurator will be registered in the start
menu.
Starting IEC103 Configurator
Click [Start][Programs][IEC103 Configurator][IECConf] to the IEC103 Configurator
software.
Note: The instruction manual of IEC103 Configurator can be viewed by clicking
[Help][Manual] on IEC103 Configurator.
IEC60870-5-103: Interoperability
1. Physical Layer
1.1 Electrical interface: EIA RS-485
Number of loads, 32 for one protection equipment
1.2 Optical interface
Glass fibre (option)
ST type connector (option)
1.3 Transmission speed
User setting: 9600 or 19200 bit/s
2. Application Layer
COMMON ADDRESS of ASDU
One COMMON ADDRESS OF ASDU (identical with station address)
3. List of Information
The following items can be customized with the original software tool IEC103 configurator.
(For details, refer to IEC103 configurator manual No.6F2S0839.)
-
Items for Time-tagged message: Type ID(1/2), INF, FUN, Transmission condition(Signal
number), COT
Items for Measurands: Type ID(3/9), INF, FUN, Number of measurand, Type of
126
6 F 2 S 0 7 9 0
measurand quantities
-
Common setting
Transmission cycle of Measurand frame
FUN of System function
Test mode, etc.
Note: To be effective the setting data written via the RS232C, turn off the DC supply of the relay and
turn on again.
3. 1 IEC60870-5-103 Interface
3.1.1 Spontaneous events
The events created by the relay will be sent using Function type (FUN) / Information numbers
(INF) to the IEC60870-5-103 master station.
3.1.2 General interrogation
The GI request can be used to read the status of the relay, the Function types and Information
numbers that will be returned during the GI cycle are shown in the table below.
For details, refer to the standard IEC60870-5-103 section 7.4.3.
3.1.3 Cyclic measurements
The relay will produce measured values using Type ID=3 or 9 on a cyclical basis, this can be read
from the relay using a Class 2 poll. The rate at which the relay produces new measured values can
be customized.
3.1.4 Commands
The supported commands can be customized. The relay will respond to non-supported commands
with a cause of transmission (COT) of negative acknowledgement of a command.
For details, refer to the standard IEC60870-5-103 section 7.4.4.
3.1.5 Test mode
In test mode, both spontaneous messages and polled measured values, intended for processing in
the control system, are designated by means of the CAUSE OF TRANSMISSION test mode.
This means that CAUSE OF TRANSMISSION = 7 test mode is used for messages normally
transmitted with COT=1 (spontaneous) or COT=2 (cyclic).
For details, refer to the standard IEC60870-5-103 section 7.4.5.
3.1.6
If the blocking of the monitor direction is activated in the protection equipment, all indications and
measurands are no longer transmitted.
For details, refer to the standard IEC60870-5-103 section 7.4.6.
3.2 List of Information
The followings are the default settings.
127
6 F 2 S 0 7 9 0
List of Information
IEC103 Configurator Default setting
INF
Description
Contents
GI Type
ID
COT
FUN
DPI
Signal No. OFF ON
--
10
255
--
--
--
Time Synchronization
--
255
--
--
--
Reset FCB
--
217
--
--
--
Reset CU
Reset CU ACK
--
217
--
--
--
Start/Restart
Relay start/restart
--
217
--
--
--
Power On
--
--
--
217
155
217
149
--
Not supported
Status Indications
16 Auto-recloser active
17 Teleprotection active
18 Protection active
19 LED reset
20 Monitor direction blocked
21 Test mode
22 Local parameter Setting
Not supported
Not supported
1, 7, 9, 12,
20, 21
1, 7, 11, 12,
20, 21
GI
--
GI
9, 11
217
131
GI
9, 11
217
132
176
133
176
134
176
135
176
136
Not supported
1, 7, 9, 11,
12, 20, 21
1, 7, 9, 11,
12, 20, 21
1, 7, 9, 11,
12, 20, 21
1, 7, 9, 11,
12, 20, 21
23 Characteristic1
GI
24 Characteristic2
GI
25 Characteristic3
GI
26 Characteristic4
GI
27 Auxiliary input1
Binary input 1
No set
28 Auxiliary input2
Binary input 2
No set
29 Auxiliary input3
Binary input 3
No set
30 Auxiliary input4
Binary input 4
No set
Supervision Indications
32 Measurand supervision I
Not supported
33 Measurand supervision V
Not supported
Not supported
Not supported
37 I>>backup operation
Not supported
38 VT fuse failure
VT failure
Not supported
39 Teleprotection disturbed
Not supported
46 Group warning
Only alarming
GI
1, 7, 9
176
104
47 Group alarm
GI
1, 7, 9
176
102
No
49 Earth Fault L2
No
50 Earth Fault L3
No
Not supported
Not supported
128
6 F 2 S 0 7 9 0
Description
Contents
GI
Type
ID
COT
FUN
DPI
Signal NO. OFF ON
Fault Indications
64
Start/pick-up L1
No set
65
Start/pick-up L2
No set
66
Start/pick-up L3
No set
67
Start/pick-up N
68
General trip
Any trip
69
Trip L1
No set
No set
No set
--
1, 7
217
70
Trip L2
71
Trip L3
72
Trip I>>(back-up)
Back up trip
Not supported
73
Fault location
Not supported
No set
74
Fault forward/line
Forward fault
Not supported
75
Fault reverse/Busbar
Reverse fault
Not supported
76
Teleprotection Signal
transmitted
Not supported
77
Not supported
78
Zone1
Zone 1 trip
Not supported
79
Zone2
Zone 2 trip
Not supported
80
Zone3
Zone 3 trip
Not supported
81
Zone4
Zone 4 trip
Not supported
82
Zone5
Zone 5 trip
Not supported
83
Zone6
Zone 6 trip
Not supported
84
General Start/Pick-up
No set
85
Breaker Failure
Not supported
86
Not supported
87
Not supported
88
Not supported
89
90
Trip I>
Not supported
91
Trip I>>
Not supported
92
Trip IN>
Not supported
93
Trip IN>>
Not supported
Not supported
Autoreclose block
Not supported
Not supported
Autoreclose indications
128
CB 'ON' by Autoreclose
129
CB 'ON' by long-time
Autoreclose
130
Autoreclose Blocked
Not supported
129
162
--
6 F 2 S 0 7 9 0
Description
Contents
GI
Type
COT
ID
FUN
Max. No.
Measurands
144 Measurand I
<meaurand I>
No
<meaurand I>
No
<meaurand I>
No
<meaurand I>
No
--
2, 7
217
Generic Function
240 Read Headings
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Tbl
Limit
Coeff
Lower
Upper
(empty)
(empty)
(empty)
Vda
short
4096
1.8998
Vdb
short
4096
1.8998
Vdc
short
4096
1.8998
(empty)
(empty)
(empty)
130
6 F 2 S 0 7 9 0
Default setting
INF
Description
Contents
Control
direction
Type
COT FUN
ID
Time synchronization
--
217
--
217
General commands
16
Auto-recloser on/off
17
Teleprotection on/off
Not supported
18
Protection on/off
19
LED reset
23
Activate characteristic 1
24
Activate characteristic 2
25
26
Not supported
(*1)
ON/OFF
20
20
217
ON
20
20
217
Setting Group 1
ON
20
20
217
Setting Group 2
ON
20
20
217
Activate characteristic 3
Setting Group 3
ON
20
20
217
Activate characteristic 4
Setting Group 4
ON
20
20
217
Generic functions
Read headings of all defined
240
groups
Read values or attributes of all
241
entries of one group
Read directory of a single
243
entry
Read values or attributes of a
244
single entry
General Interrogation of
245
generic data
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
(1) Note: While the relay receives the "Protection off" command, " IN SERVICE LED" is off.
INF
Sig off
Sig on
18
187
187
19
188
200
23
193
1000
24
194
1000
25
195
1000
26
196
1000
Rev
Valid time
: signal reverse
131
6 F 2 S 0 7 9 0
Description
Contents
GRB150
supported
Yes
Yes
Disturbance data
No
Generic services
No
Private data
Yes
Miscellaneous
Max. MVAL = rated
value times
Measurand
Current L1
Ia
No
Current L2
Ib
No
Current L3
Ic
Voltage L1-E
Vda
Configurable
Voltage L2-E
Vdb
Configurable
Voltage L3-E
Vdc
Configurable
Active power P
No
Reactive power Q
No
Frequency f
Voltage L1 - L2
Vab
No
No
Configurable
132
Comment
6 F 2 S 0 7 9 0
[Legend]
GI: General Interrogation (refer to IEC60870-5-103 section 7.4.3)
Type ID: Type Identification (refer to IEC60870-5-103 section 7.2.1)
1 : time-tagged message
2 : time-tagged message with relative time
3 : measurands I
4 : time-tagged measurands with relative time
5 : identification
6 : time synchronization
8 : general interrogation termination
9 : measurands II
10: generic data
11: generic identification
20: general command
23: list of recorded disturbances
26: ready for transmission for disturbance data
27: ready for transmission of a channel
28: ready for transmission of tags
29: transmission of tags
30: transmission of disturbance values
31: end of transmission
COT: Cause of Transmission (refer to IEC60870-5-103 section 7.2.3)
1: spontaneous
2: cyclic
3: reset frame count bit (FCB)
4: reset communication unit (CU)
5: start / restart
6: power on
7: test mode
8: time synchronization
9: general interrogation
10: termination of general interrogation
11: local operation
12: remote operation
20: positive acknowledgement of command
21: negative acknowledgement of command
31: transmission of disturbance data
40: positive acknowledgement of generic write command
41: negative acknowledgement of generic write command
42: valid data response to generic read command
43: invalid data response to generic read command
44: generic write confirmation
FUN: Function type (refer to IEC60870-5-103 section 7.2.5.1)
DPI: Double-point Information (refer to IEC60870-5-103 section 7.2.6.5)
DCO: Double Command (refer to IEC60870-5-103 section 7.2.6.4)
133
6 F 2 S 0 7 9 0
_01.csv
Second draft:
_02.csv
Third draft:
_03.csv
Revision number
The name is recommended to be able to discriminate the relay type such as GRZ100 or
GRL100, etc. The setting files remark field of IEC103 is able to enter up to 12 one-byte
characters. It is utilized for control of IEC103 setting data.
134
6 F 2 S 0 7 9 0
Troubleshooting
No.
Phenomena
Supposed causes
Check / Confirmation
Object
Communication
trouble (IEC103
communication is
not available.)
Procedure
BCU
RY
BCU
BCU
RY
RY
PRTCL1
=HDLC
PRTCL1
=IEC
COM1 (CH1)
HDLC
IEC
COM2 (CH2)
IEC
Cable
Converter
BCU
cable
BCU
BCU
135
6 F 2 S 0 7 9 0
No.
Phenomena
Supposed causes
Check / Confirmation
Object
Time can be
synchronised with
IEC103
communication.
Procedure
RY
RY
RY
RY
BCU
RY
SAS
136
6 F 2 S 0 7 9 0
Appendix N
Timing Chart of Cold load Condition
Judgment
137
6 F 2 S 0 7 9 0
Timing Chart of Cold Load Status Judgment
(1) Function 1:
Setting: [TCLP] should be set.
[TCLE],[TCLR]Not applied.
From CB close command output, the cold load condition is judged for a time.
CB closing
CB open
CB closing command
(BI1 COMMAND)
COLD LOAD
TCLP one-shot timer
(3) Function 2:
Setting: [TCLP]Not applied.
[TCLE],[TCLR]should be set.
From CB contact closing, the cold load condition is judged for a time.
CB closing
CB contact
(BI1 COMMAND)
CB open
CLOSE
OPEN
COLD LOAD
138
6 F 2 S 0 7 9 0
Appendix O
Ordering
139
6 F 2 S 0 7 9 0
Ordering
GRB150
Type:
High-impedance Differential Relay
Model:
- Single-phase protection (with EB-101)
- Three-phase protection (with EB-102)
Ratings:
50Hz, 110V/125Vdc
60Hz, 110V/125Vdc
50Hz, 220V/250Vdc
60Hz, 220V/250Vdc
50Hz, 48V/54V/60Vdc
60Hz, 48V/54V/60Vdc
Communications:
GRB150
101
201
1
2
5
6
A
B
Dual RS485
LED label:
Standard
Option: User configurable LED label
None
J
Note
EB-101: Varistor unit for single phase
EB-102: Varistor unit for three phase
140
6 F 2 S 0 7 9 0
Version-up Records
Version
No.
Date
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Aug.01, 2007
0.9
1.0
Revised Section
-6.4, 6.5
Appendices
Appendix B
3.2.1
4.5
6.7.2
Appendices
Appendices
Appendices
3.2.1
4.1.2
Appendices
2.2.3
4.4, 4.5
Appendices
4.2.1
Appendices
2.3.1
2.3.2
2.4
3.2.1
3.4.2
3.4.3
4.2.6.1, 4.2.6.4,
4.2.6.7, 4.2.6.10
Appendices
2.3.2
3.1
Appendices
Contents
First issue
Modified Figures 6.4.1, 6.4.2 and 6.5.1
Modified the Appendix M and added the Appendix N.
Changed the name of No.131.
Modified the description of Binary input signals.
Modified the description.
Modified the description of Note.
Modified the Appendix J and M.
Modified the Appendix D and M.
Modified the Appendix I, J and N.
Modified the description.
Modified the description.
Appendix F, J and N.
Modified the description about secondary winding resistance.
Modified the description.
Added the item LCD and Button operation Instruction in Appendix D, and
modified Appendix M.
Modified the description.
Modified Appendix D, M and N.
Added the title High-impedance differential protection.
Added 2.3.2 Cold Load Protection.
Modified the setting range table.
Modified Table 3.2.2 and figure 3.2.1.
Modified Table 3.4.1.
Modified the description.
Modified the description.
Modified Appendix B, D, F, G and J, and added Appendix N.
Old Appendix N shifted to Appendix O.
Modified the description and Figure 2.3.2.
Modified Figure 3.1.4.
Modified Appendix F.
141