Post Frame Buildings

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Post Frame Buildings

Introduction
Post-frame buildings are
efficient structures whose
primary framing system is
comprised of wood roof
trusses or rafters connected
to vertical timber columns or
sidewall posts. Secondary
members such as roof purlins
and wall girts support the
exterior
cladding
and
transfer
vertical
and
horizontal forces to and from
the post-frame. Figure 1
illustrates
the
common
components of a post-frame
building.
The purpose of this
document is to provide
guidance
to
post-frame
building designers for meeting
the requirements of the
International Building Code
(IBC) and to confirm that a
properly designed post-frame
building is in fact code
compliant.
The following chapters
and headings correspond to
those of the IBC:

Figure 1 Components of a Post Frame Building

Copyright 2013 American Wood Council

POST FRAME BUILDINGS

Chapter 5 General Building Heights and


Areas
Table 503 Allowable Building Heights and Areas
Post-frame buildings are wood structures and as
such are classified as Type VA or VB. The basic
allowable height and area for each occupancy group for
Type VA and VB is presented in the last two
c o l u m n s of Table 503. The allowable height may be
modified in accordance with Section 504 and the
allowable area may be modified in accordance with
Section 506 and 507. Chapter 4 contains specific
exceptions to the allowable height and areas in Table
503 and Chapter 5.

Chapter 6 Types of Construction


Table 601 Fire-Resistance Rating Requirements
for Building Elements
Per this table, there is no minimum required fire
resistance rating of the elements of Type VB
construction. With some exceptions (Notes b and d), the
minimum required fire resistance rating of the elements
of Type VA construction is one hour. There is a report
available from the National Frame Building Association
(NFBA) of a tested o ne h o u r o n e di r e ct i o nal
w a l l a ss e mb l y a n d a t w o d i r ec t i o n al - - one,
two, and three-hour post-frame wall assembly. The two
directional wall assemblies are also listed under UL
Design No. V304, BXUV.V304. A one hour roof
ceiling assembly may be constructed with wood roof
trusses in accordance with item 21-1.1 of Table
721.1(3). Other systems are available from the
Structural Building Components Association (SBCA) as
well as proprietary systems from the manufacturers of
truss metal connector plates. A compendium of all
known fire-rated truss assemblies is available from
SBCA. There are many one hour assemblies for roofs
built from dimension lumber or engineered wood.
Many of these can be found in DCA No. 3 - Fire-Rated
Wood-Frame Wall and Floor/Ceiling Assemblies.
Table 602 Fire-Resistance Rating Requirements
for Exterior Walls Base on Fire Separation
Distance
This table presents the minimum fire resistance
rating for exterior walls based on occupancy group and
fire separation distance. As previously mentioned, a
report of a tested one, two and three-hour post-frame
wall assembly is available from the NFBA. DCA No. 3
- Fire Rated Wood Wall Assemblies describes how

interior and exterior wood-frame walls can be used to


meet building code requirements for fire resistive
assemblies.
Section 602.3 Type III and Section 602.4 Type IV
Both Type III and Type IV construction allow
exterior wall assemblies to contain fire-retardant-treated
wood. Both Sections 602.3 and 602.4 include the
statement, Fire-retardant-treated wood framing
complying with Section 2303.2 shall be permitted within
exterior wall assemblies with a 2-hour rating or less.

Chapter 7 Fire and Smoke Protection


Features
Table 705.8 Maximum Area of Exterior Wall
Openings Based on Fire Separation Distance and
Degree of Opening Protection
This table presents the maximum allowable
percentage of wall openings based on fire separation
distance and fire classification of the opening.
Section 705.11 Parapets
A parapet is an extension of the wall above the
roof line. Section 705.11 requires parapets on exterior
walls of buildings. There are six exceptions to this
requirement provided in this Section. In general, it is
wise to avoid placing parapets along the eave line of
post-frame buildings. Parapets at the eave increase the
likelihood of roof leaks, and in cold climates will catch
ice and snow.
Section 706.3 Exception
This Section allows fire walls in Type V
Construction to be of combustible materials.

Chapter 12 Interior Environment


Section 1203.2 Attic Spaces
It is important that attics are ventilated in
accordance with this section.

Chapter 13 Energy Efficiency


Chapter 13 refers the designer to the International
Energy Conservation Code (IECC). The IECC has
specific requirements for residential and commercial
construction with minimum insulation values based on
climate zones. One of the benefits of post-frame
construction is that it allows for economical superinsulated buildings. Attic spaces may be easily insulated

American Wood Council

POST FRAME BUILDINGS

with R-40 or higher materials. Because of their unique


construction, post-frame walls may be easily insulated
with R-30 batts. See Figure 2.

Chapter 14 Exterior Walls


Table 1405.2 Minimum Thickness of Weather
Coverings
The most common exterior wall covering for postframe buildings is pre-painted corrugated steel siding.
But other materials such as exterior plywood, wood
sidings, brick veneers, etc. are also common. This table
provides the code prescribed minimum thickness for
weather coverings.
Section 1405.11Metal Veneers
This section provides the requirements for metal
sidings.
Section 1406 Combustible Materials on the
Exterior Side of Exterior Walls
This section provides requirements for combustible
sidings and Section 1406.2.3 provides fire blocking
requirements.

Chapter 15 Roof Assemblies and Rooftop


Structures
Section 1507.2 Asphalt shingles
Shingle and wood sheathed roofs are also common
on post-frame buildings. Section 1507.2 provides the
minimum code requirements for asphalt shingle roofs.
Section 1507.4 Metal roof panels
As with siding, the most common roof cladding
for post-frame buildings is pre-painted corrugated steel.
Section 1507.4 provides the minimum code
requirements for metal roof panels. These steel roof
systems are commonly used as horizontal diaphragms to
transfer lateral loads from the post-frame to end and
interior shear walls. When using a floating metal
roof such as standing seam, it is essential to recognize
that the floating roof does not provide a diaphragm,
and to accommodate this during structural design.

Chapter 16 Structural Design

Table 1604.3 Deflection Limits


One notable exception to the deflection limits
in Table 1604.3 is Note a. Because of its inherent
flexibility, corrugated metal can sustain relatively high
deflections without failure. If purlins or girts are used to
support interior finishes in addition to metal siding, then
they must meet the deflection limits of Table 1604.3.
Section 1604.8 Anchorage
Embedded posts must maintain a load path for uplift
loads per the provisions of Section 1604.8.1. Note that
dead load can be used to offset uplift as permitted in
Section 1605.3.

Chapter 18 Soils and Foundations


The foundation system of a post-frame building is
unique. The posts can be embedded in the ground or
anchored to a concrete foundation (Figure 4).
In all cases, vertical loads from the roof are
transferred to columns and from columns to concrete
footings or foundations, and finally to the soil. Buried
or embedded posts also can resist lateral loads by
developing partial fixity. See Figure 3.
Section 1806 Presumptive Load Bearing Values of
Soils
The foundation system must be evaluated with
respect to load bearing values of the soil. Section 1806
outlines those requirements.
Section 1807 Foundation Walls, Retaining Walls
and Embedded Posts and Poles
Standard practice for embedded posts is that a
round hole is drilled for each post approximately four
feet in the ground (or greater if required for frost
protection per 1809.5). Either a pre-cast or cast in place
round concrete pad is placed in the bottom of this hole.
Pads are usually unreinforced. The diameter of this
pad is determined so that the calculated vertical load in
the post divided by the area of the pad is less than the
allowable soil bearing pressure (per Sections 1806 and
1807). The foundation under an anchored post is
designed conventionally. The minimum 28 day concrete
strength is 2,500 psi or 3,000 psi per Items 1 and 2 in
Table 1808.8.1.

Post-frame buildings must be designed for


s tructural requirements of this chapter, just as any other
building.

American Wood Council

POST FRAME BUILDINGS

Figure 3 Post anchorage (post embedded) typical for


solid-sawn or laminated columns

Figure 4A Post anchorage (post pinned) typical for solidsawn or -laminated columns.

Figure 2 Typical post frame wall sections with (a) girts on


exterior and interior of posts, and (b) girts between posts.

Pre-cast concrete pier

Wet-set bracket

Figure 4B Post anchorage (moment connection) by wetset bracket or pre-cast concrete pier typical for solidsawn or laminated columns

American Wood Council

POST FRAME BUILDINGS

Section 1807.3 Embedded Posts and Poles


Embedded posts can resist lateral loads through
the development of partial fixity of the base. However,
there are limitations as shown in Section 1807.3.1.
Research has shown that where the roof and side walls
can act as diaphragms or shear walls, that the majority
of the lateral loads will be resisted by them. The PostFrame Design Manual, published by the National Frame
Builders Association, as well as ANSI/ASAE EP 484.2,
referenced in Section 2306.1, provide techniques for
dividing the lateral loads among frames and diaphragms.
After the design moments at the base of the posts have
been determined, the embedment depth can be checked
in accordance with Section 1807.3. More extensive
design and analysis procedures for embedded post and
pier foundations are contained in ANSI/ASAE EP 486.1.

Chapter 23 Wood
Section 2303.1.8 Preservative-treated wood
Preservative treated wood has been used
successfully in contact with the ground for many years.
The use of properly treated wood may provide assurance
that a post-frame building may last for 50 years or
more. This section and Section 1807.3 specify that wood
posts shall be treated in accordance with American
Wood Protection Association (AWPA) standard U1
(Commodity Specification A, Use Category 4B for sawn
timber posts and Commodity Specification B, Use
Category 4B for round timber posts). Waterborne
preservatives are o f t e n the preferred method of
treatment for wood in contact with the ground. Posts or
wood columns embedded in soil must be treated to a
minimum use category level of AWPA UC4B, and other
wood at or above soil level up to one foot above grade
must be treated to at least UC4A. Southern Pine has long
been a preferred species for treatment because its
cellular structure permits relatively deep and uniform
penetration of the preservative.
Section 2303.4 Trusses
Metal plate connected wood trusses shall be
designed and manufactured in accordance with
ANSI/TPI 1. Chapter 2 in ANSI/TPI 1 is titled Standard
Responsibilities in the Design and Application of MetalPlate-Connected Wood Trusses. Every post-frame
building designer should be familiar with this document,
since 1) trusses are based on the building designers
specifications and 2) long-span trusses require special
attention to bracing and erection. It is important that
building designers understand their role in the design

process relating to wood trusses. Additional information


pertaining to design and installation of metal plate
connected wood trusses is available from SBCA.
Section 2304.9 Connectors and Fasteners
Structural lumber in a post-frame building is
usually in a highly stressed state at design loads.
Therefore, it is important that all connections between
structural members be carefully designed by the postframe building designer, not left to the discretion of the
erector. When preservative-treated or fire-retardanttreated wood is used, care should be taken in the
selection of fasteners and connectors. Section 2304.9.5
covers the different applications.
Section 2304.11 Protection against decay and
termites
This section specifies the locations where wood is
required to be preservative treated.
Section 2306.1 Allowable stress design
Post-frame design is normally based on allowable
stress. The ANSI/ASAE standards cited in this section
as well as the Post-Frame Design Manual published
by the National Frame Builders Association, give
guidance to the post-frame building designer.
For additional information contact:
The information contained in this document is
intended to assist the designer of post framed
structures. Special effort has been made to assure
that the information reflects the state of the art.
However, the American Wood Council does not
assume responsibility for particular designs or
calculations prepared from this publication.

American Wood Council


222 Catoctin Circle, SE, Suite 201
Leesburg, VA 20175
www.awc.org
[email protected]
Copyright 2013 American Wood Council

American Wood Council

You might also like