GPW MTB FX Mh01ea Connect

Download as pdf or txt
Download as pdf or txt
You are on page 1of 98

GP-PRO/PBIII for Windows

Device/PLC CONNECTION MANUAL

Mitsubishi Corporation
PLC

Reading the GP-PRO/PBIII Device/PLC Connection Manual


This document is designed as an addition to the latest GP-PRO/PBIII for Windows
Device/PLC Connection manual's Mitsubishi Corporation data.
When connecting a Factory Gateway unit, please substitute the words "Factory
Gateway" for this document's "GP/GLC".

Mitsubishi Electric PLC

2.1

Mitsubishi Electric

2.1.1

System Structure

The following describes the system structure for connecting the GP to Mitsubishi
Electric PLCs.
The Cable Diagrams mentioned in the following tables are
listed in the section titled "2.1.2 Cable Diagrams".

MELSEC-A Series (using Link I/F)


CPU

Link I/F

Cable Diagram

Cables

Target Machine

Computer
Link Unit

A2A,A3A,A2U,
A3U,A4U

AJ71C24-S6
AJ71C24-S8
AJ71UC24

RS-232C
<Connection
Diagram 1 >
RS-422
<Connection
Diagram 2 >

A2US

A1SJ71C24-R2,
A1SJ71UC24-R2

A1SJ71UC24-R4

A2USH-S1

A1SJ71UC24-R4

A1SJ71UC24-R2

RS-232C
<Connection
Diagram 3>
RS-422
<Connection
Diagram 2>
RS-422
<Connection
Diagram 2>
RS-232C
<Connection
Diagram 3>

GP410-IS00-0(5m)
CA3-CBL232/5M-01 (5m)
GP230-IS11-0(5m)
CA3-CBL422/5M-01 (5m)
GP000-IS02-MS(3m)

GP/GLC
Series
ST401
GP/GLC
Series
ST400
GP/GLC
Series
ST401

GP230-IS11-0(5m)
CA3-CBL422/5M-01 (5m)
GP230-IS11-0(5m)
CA3-CBL422/5M-01 (5m)
GP000-IS02-MS(3m)

GP-PRO/PBIII for Windows Device/PLC Connection Manual

GP/GLC
Series
ST400
GP/GLC
Series
ST400
GP/GLC
Series
ST401

Mitsubishi Electric PLC

MELSEC-N Series (using Link I/F)


CPU

Link I/F

Cable Diagram

Cables

Target Machine

Computer
Link Unit

A1N, A2N, A3N

A0J2, A0J2H
A1S

A1SJ, A2SH, A1SH

A2CCPU24

AJ71C24,
AJ71C24-S3,
AJ71C24-S6,
AJ71C24-S8,
AJ71UC24
(A2N only)
A0J2-C214-S1

RS-232C
GP410-IS00-O (5m)
<Cable Diagram 1>

A1SJ71C24-R2,
A1SJ71UC24-R2

RS-232C
GP000-IS02-MS (3m)
<Cable Diagram 3>

A1SJ71C24-R4

RS-422
GP230-IS11-0(5m)
<Cable Diagram 2>

A1SJ71UC24-R4

CA3-CBL232/5M-01 (5m)
RS-422
GP230-IS11-0(5m)
<Cable Diagram 2>
CA3-CBL422/5M-01 (5m)

CA3-CBL422/5M-01 (5m)

A1SJ71UC24-R2

RS-232C
GP000-IS02-MS (3m)
<Cable Diagram 3>

Link unit on CPU

RS-232C
GP000-IS02-MS (3m)
<Cable Diagram 3>

GP-PRO/PBIII for Windows Device/PLC Connection Manual

GP/GLC
Series
ST401
GP/GLC
Series
ST400
GP/GLC
Series
ST401
GP/GLC
Series
ST400
GP/GLC
Series
ST401
GP/GLC
Series
ST401

Mitsubishi Electric PLC

MELSEC-A Series (CPU Direct Connection)


CPU

*1

Adaptor

Cable Diagram

Cables

Target Machine

RS-422

A2A,A3A,A4U,A3U,
A2U-S1,A2US-S1,
A2USH-S1,A2US

<Cable Diagram 11>*4 A-Series


Programing Console I/F
Cable (isolation type)

GP/GLC
Series

GP430-IP10-O (5m) *5*6


Diatrend Cable

ST401

DAFXIH-CABV *6
A2A,A3A,A4U,A3U,
A2U-S1,A2US-S1,
A2USH-S1,A2US

A2A,A3A,A4U,
A2U-S1,
A2USH-S1,
A2US

2-Port Adaptor *2
GP030-MD11-O

2 Port Adaptor II
GP070-MD11

*3

Mitsubishi's I/F unit


FX-2PIF
Refer to Mitsubishi's
manual

RS-422
(Refer to Mitsubishi's
A Series PLC Manual
"2 Port Adapter" for
cable diagram info.)
RS-422
(Refer to Mitsubishi's A
Series PLC Manual
"2 Port AdapterII" for
cable diagram info.)
Refer to "Connecting a
Device/PLC to the ST
unit." page 1-6
"2-Port Adaptor II"
RS-422
*4

<Cable Diagram 11>

A-Series
Programing Console I/F
Cable (isolation type)

GP/GLC
Series

GP430-IP10-O (5m) *5*6


GP070-MDCB11(5m)
cable or user-created
RS-422Cable

GP/GLC
Series

ST400

A-Series
Programing Console I/F
Cable (isolation type)
GP430-IP10-O (5m)
Diatrend Cable
DAFXIH-CABV

*6

GP/GLC
Series

*5*6

ST401

*1 Connect to the Programming Console I/F port.


*2 When a Read/Write command is sent from ladder software while data is being
transmitted between the PLC and the GP, there is a possibility the data transmission will not be completed normally.
In that case, change the GP to OFFLINE mode and perform the read and
write processing.
If CPU direct connection with any CPUs that are not on the above list, the
PLC can be damaged.
When the PLC unit has 2 ports, both cannot be connected with a GP at the
same time.
*3 When using 2 Port Adapter II, refer to its manual for the connectable PLCs.
*4 This connection is used for only GP2000 series units. When using other series
units, use the GP430-IP10-0 cable.
*5 ST Series units cannot use the GP430-IP10-0 cable.
*6 When using this cable, be sure to set the Target Machine's communication
settings to [RS-232C].

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric PLC

MELSEC-N Series (CPU Direct Connection)


CPU

*1

Adaptor

Cable Diagram

Cables

Target Machine

A-Series
Programing Console I/F
Cable (isolation type)

GP/GLC
Series

RS-422

A1N,A2N,A3N,A3H,
A1S,A2SH,A2CJS3,
A1SH,A2CCPU24,
A1SJ,A0J2H

*4

<Cable Diagram 11>

GP430-IP10-O (5m)

*5*6

Diatrend Cable
DAFXIH-CABV
A1N,A2N,A3N,A3H,
A1S,A2SH,A1SH,
A1SJ

A1S,A2N,A3H,A3N,
A1SJ,A2SH,A1SH,
A2CJ-S3,A0J2H

*2

2-Port Adaptor
GP030-MD11-O

*3

2 Port Adaptor II
GP070-MD11

RS-422
(Refer to Mitsubishi's A
Series PLC Manual "2
Port Adapter" for cable
diagram information)

ST401

*6

A-Series
Programing Console I/F
Cable (isolation type)
GP430-IP10-O (5m)

*5*6

RS-422
(Refer to Mitsubishi's A
GP070-MDCB11(5m)
Series PLC Manual
cable or user-created
"2 Port AdapterII" for
RS-422Cable
cable diagram
information)
Refer to "Connecting a
Device/PLC to the ST
unit." page 1-6
"2-Port Adaptor II"

Mitsubishi's I/F unit


FX-2PIF
Refer to Mitsubishi's
manual

RS-422
*4

<Cable Diagram 11>

GP/GLC
Series

GP/GLC
Series

ST400

A-Series
Programing Console I/F
Cable (isolation type)
GP430-IP10-O (5m)
Diatrend Cable
DAFXIH-CABV

*6

GP/GLC
Series

*5*6

ST401

*1 Connect to the Programming Console I/F port.


*2 When a Read/Write command is sent from ladder software while data is being
transmitted between the PLC and the GP, there is a possibility the data transmission will not be completed normally.

If you connect a CPU not listed here via the Direct CPU connection, you may damage the PLC.
If the PLC has two ports, both of them cannot be connected to a
GP at the same time.
*3 When using 2 Port Adapter II, refer to its manual for the connectable PLCs.
*4 This connection is used for GP2000/GLC2000 and ST Series units. When
using other series units, use the GP430-IP10-0 cable.
*5 ST Series units cannot use the GP430-IP10-0 cable.
*6 When using this cable, be sure to set the Target Machine's communication
settings to [RS-232C].

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric PLC

MELSEC-F2 Series (using Link I/F)


CPU

Adapter

Cable Diagram

Cables

Target Machine

Interface
Unit

F2-232GF

F 2-20M,F2-40M,
F2-60M

RS-232C
(Cable Diagram 1)

Digital's
GP410-IS00O(5m)cable
Mitusbishi's
F2-232CAB(3m)cable
CA3-CBL232/5M-01
(5m)

GP/GLC Series

ST401

MELSEC-FX Series (using CPU Direct Connection with


Mitsubishi's MELSEC-FX(CPU) Protocol)
CPU

Adapter

Cable Diagram

Cables

Target Machine

FX Series exclusive
Programming Console
I/F Cable (isolation type)

FX 1, *2 FX 2, *2 FX 2c, *2
FX 0, *3 FX0S, *3 FX0N, *3
FX1S, *3 FX1N, *3 FX2N *3

GP430-IP11-O (5m)

FX1NC, *3 FX2NC *3

*8

GP/GLC Series

FX3UC *3
Mitsubishi's I/F unit

FX1, FX2, FX2C, FX0,


FX0S, FX0N, FX1S, FX1N,

FX-232AW

*1 *4

FX2N, FX1NC, FX2NC, FX3UC


FX 2, *5 FX0S, *6 FX0N,

2 Port Adapter II

*6 FX1S, *6 FX1N, *6

GP070-MD11 *7

FX2N, *6 FX1NC, *6
FX2NC *6, FX3UC *6

*1

RS-232C
(Cable Diagram 1)

GP410-IS00-0(5m)
Mitusbishi Corporation's
F2-232CAB (3m)
CA3-CBL232/5M-01 (5m)
GP070-MDCB11 (5m) or
RS-422
(Refer to Mitsubishi's A Series User-Prepared cable
(RS-422)
PLC Manual "2 Port
AdapterII" for cable diagram
information)
Refer to "Connecting a
Device/PLC to the ST unit"
page 1-6 "2-Port Adaptor II"

GP/GLC Series
ST401

GP/GLC Series

ST400

Although MELSEC-FX Series and the GP uses a CPU direct connection, to


change an RS-422 signal to RS-232C's, the FX-232AW interface unit is necessary.
When connecting to FX1 , FX2 , and FX2C , it is necessary to connect the Interface Unit with the PLC using Mitsubishi's FX-422CAB.
Mitsubishi's
RS-232C

FX-422CAB

Interface Unit
FX-232AW

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric PLC

*2

When using Digital's GP430-IP11-0 for connecting an FX1 ,FX2 , or FX2C ,


use the Cable Diagram 2 shown below.
GP430-IP11-0

*3 When using Digital's GP430-IP11-0 for connecting FX0, FX0S, FX0N, FX1S FX1N,
FX2N, FX1NC, FX2NC or FX3UC be sure to use Mitsubishi's FX-20P-CADP cable.
Mitsubishi's FX-422CAB0 cannot be used

Mitsubishi's FX-20P-CADP

GP430-IP11-0

*4 When connecting to FX0, FX0S, FX0N, FX1S FX1N, FX2N, FX1NC or FX2NC , FX3UC
it is necessary to connect the Interface Unit with the PLC using Mitsubishi's
FX-422CAB0 (see Diagram 4).
Mitsubishi's
FX-422CAB0
Interface Unit
FX-232AW

Usable RS-232C cables:

GP410-IS00-O(5m)
Mitsubishi F2-232CAB (3m)
ST Series:CA3-CBL232/5M-01
or user created cable

*5 When using Digitals 2 Port Adapter II, it is necessary to connect the unit to
the GP as shown below.
* When using FX-422 CAB, a commercially
available D-SUB 25Pin female - female
Conversion Connector (Straight Full
Connection Specification) will be required.
GP070-MDCB11 or
user-created cable
(RS-422)

FX-422CAB *

2 Port Adapter II

*6 When using Digitals 2 Port Adapter II, it is necessary to connect the units to
the GP as shown below.
* Mitsubishi's FX-20P-CADP or FX-422CAB0
can also be used. When using FX-422
CAB0, a commercially available D-SUB
25Pin female - female Conversion
Connector (Straight Specification) is
required.
Mitsubishi's
FX-20P-CADP *

GP070-MDCB11 or
user-made cable
(RS-422)
(*ST Series units
2 Port Adapter II use only usercreated cable.)

*7 When using 2 Port Adapter II, refer to its manual for connectable PLCs.
*8 For the ST series units, the GP430-IP11-0 cable cannot be used.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric PLC

MELSEC-FX Series (A1FX) (using CPU Direct Connection)


CPU

A1FX

Cable Diagram

*1

Cables

Target Machine

GP410-IS00-O(5m) cable
Mitusbishi's
F 2-232CAB(3m) cable

*2

GP/GLC
Series

*1 When using an A1FX, choose the MELSEC-AnN (CPU) series as the GPPRO/PBIII project files PLC type (refer to the MELSEC-N series manuals for
the range of devices available). You will also need a 25 Pin straight cable to
adjust the connectors height to align it with that of the PLCs CPU cover.
Straight
Cable
25P
Male

Digital
GP430-IP10-O
25P
Female

*2 For ST series units, the GP430-IP10-0 cable cannot be used.

MELSEC-FX Series (using Expansion Board with


Mitsubishi's MELSEC-FX2 (LINK) Protocol)
CPU

Adapter

Cable Diagram

Target Machine

(Expansion board)

FX2N

*1

FX2N-232-BD

RS-232C
<Cable Diagram 6>

FX2N-485-BD,

RS-422
<Cable Diagram 7>

FX0N-485ADP+FX2N-CNV-BD
FX2NC,FX1NC

FX1N

FX0N-232ADP

RS-232C
<Cable Diagram 8>

FX0N-485ADP

RS-422
<Cable Diagram 7>

FX1N-232-BD

RS-232C
<Cable Diagram 6>

FX1N-485-BD,

RS-422
<Cable Diagram 7>

FX0N-485ADP+FX1N-CNV-BD
FX3UC

FX3U-232-BD

RS-232C
<Cable Diagram 6>

FX3U-485-BD

RS-422C
<Cable Diagram 7>

GP/GLC
Series
ST401
GP/GLC
Series
ST400
GP/GLC
Series
ST401
GP/GLC
Series
ST400
GP/GLC
Series
ST401
GP/GLC
Series
ST400
GP/GLC
Series
ST401
GP/GLC
Series
ST400

*1 The PLCs system version should be at least 1.06 or later. Check the PLCs
version by reading out the data from the register (D8001). For detailed information refer to the Mitsubishis FX 2N Series Micro Sequencer manuals.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric PLC

MELSEC-FX Series (using Expansion Board with Mitsubishi's


MELSEC-FX (CPU) Protocol)
CPU

Adapter

Cable Diagram

Cables

Target Machine

(Expansion board)

FX1S,FX1N

*1

FX1N-232-BD

RS-232C
<Cable Diagram 1>

GP410-IS00-O (5m)
CA3-CBL232/5M-01(5m)

RS-232C
<Cable Diagram 6>
*2

FX2N-422-BD
FX2N

GP430-IP11-O (5m)

*5

*1

FX2N-232-BD

RS-232C
<Cable Diagram 1>

GP410-IS00-O (5m)

GP/GLC
Series

Mitsubishi Electric
F2-232CAB-1 (3m)
CA3-CBL232/5M-01(5m)
RS-232C
<Cable Diagram 6>

GP430-IP11-O (5m)

*5

RS-232C
<Cable Diagram 1>

GP410-IS00-O (5m)
Mitsubishi Electric
F2-232CAB-1 (3m)
CA3-CBL232/5M-01(5m), or
Mitsubishi Electric
FX-232CAB-1 (3m)

RS-232C
<Cable Diagram 6>
*2

GP430-IP11-O (5m)

FX3U-422-BD +
Mitsubishi Electric
RS-232C/RS-422
Conversion Unit
FX-232AW

GP/GLC
Series

*1

FX3U-232-BD

FX3U-422-BD

ST401
GP/GLC
Series
ST401

*2

FX2N-422-BD
FX3UC

GP/GLC
Series
ST401
GP/GLC
Series
ST401
GP/GLC
Series

*3

GP410-IS00-O (5m)
Mitsubishi Electric
F2-232CAB-1 (3m)
CA3-CBL232/5M-01(5m)

FX3U-422-BD +
2-Port Adaptor II
GP070-MD11

RS-232C
<Cable Diagram 1>

*5

*4

RS-422
(Refer to Mitsubishi's
GP070-MDCB11 (5m) or
A Series PLC Manual
User-Prepared cable
"2 Port AdapterII" for
(RS-422)
cable diagram
information)
Refer to "Connecting
a Device/PLC to the
ST unit" page 1-6 "2Port Adaptor II"

GP-PRO/PBIII for Windows Device/PLC Connection Manual

GP/GLC
Series

ST401
GP/GLC
Series
ST401
GP/GLC
Series
GP/GLC
Series
ST401

GP/GLC
Series

ST400

Mitsubishi Electric PLC

*1

When using a GP410-IS00-O, a 9 pin <--> 25 pin conversion adaptor (straight


type) is required.
With a GP/GLC Series Unit:
Conversion Adapter for
Dsub 9-pin and Dsub 25-pin
(straight type)

GP410-IS00-O

GP/GLC

or user-created cable

Mitusbishi Electric F2-232CAB-1 (3m)


FX1S,FX1N

FX1N-232-BD

FX2N

FX2N-232-BD

FX3UC

FX3U-232-BD

With an ST Series Unit:

Conversion Adapter for


Dsub 9-pin and Dsub 25-pin
(straight type)

CA3-CBL232/5M-01

ST

or user-created cable

Mitusbishi Electric FX-232CAB-1 (3m)


FX1S,FX1N

*2

FX1N-232-BD

FX2N

FX2N-232-BD

FX3UC

FX3U-232-BD

A round Dsub 8-pin to 25-pin conversion cable is required.


(Mitsubishi Electronic FX-20P-CADP)
With a GP/GLC Series Unit:
Mitusbishi Electric
FX-20P-CADP

FX2N
FX1S,FX1N

+
+

FX2N-422-BD
FX1N-422-BD

FX3UC

FX3U-422-BD

GP-PRO/PBIII for Windows Device/PLC Connection Manual

GP/GLC
GP430-IP11-0

Mitsubishi Electric PLC

*3

When connecting to an FX3UC, use a Mitsubishi Electric FX-422CAB0 cable


to connect the FX3U-422-BD adaptor and the Interface Unit.

Mitusbishi Electric
FX-422CAB0

Mitusbishi Electric
Interface Unit
(FX-232AW)

Usable RS-232C cables:

GP/GLC/ST Series

GP410-IS00-O(5m)
FX3UC

FX3U-422-BD

Mitsubishi F2-232CAB-1 (3m)


ST Series:CA3-CBL232/5M-01
or User created cable

*4

When using Digital Electric Corporation's 2 Port Adapter II, it is necessary


to connect the units to the GP as shown below.
* Mitsubishi's FX-20P-CADP or FX422CAB0 can also be used. When using
FX-422 CAB0, a commercially available
D-SUB 25Pin female - female Conversion
Connector (Straight Specification) is
required.
Mitsubishi Electric
FX-20P-CADP

FX3UC

*5

2-Port Adaptor II
Usable RS-232C cables:

FX3U-422-BD

GP/GLC/ST Series

GP070-MDCB11 or
user-made cable
(RS-422)
(*ST Series units
use only usercreated cable.)

For ST Series units, the GP430-IP11-0 cable cannot be used.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

10

Mitsubishi Electric PLC

MELSEC-FX Series (using CPU Direct Connection with Mitsubishi's


MELSEC-FX (CPU2) Protocol)
CPU

Cable Diagram

Cable

GP2000-CBLFX/5M-01 (5M)

FX0S, FX0N, FX1S,


FX1N, FX1NC, FX2N,
FX2NC, FX3UC

GP2000-CBLFX/1M-01 (1M)

RS-422
*2

<Cable Diagram 12>

GP/GLC

*1

GP/GLC Series

CA3-CBLFX/5M-01 (5m)

ST400

CA3-CBLFX/1M-01 (1m)

*1 In the GP70 Series, only GP377 Series units can use this cable.
*2 When connecting to a Device/PLC, be sure to use one of the option cables shown here.

MELSEC-FX Series (using 1:N Connection with Mitsubishi's MELSEC-FX 1:N


Communication Protocol)
CPU

Adapter

Cable Diagram

Cables

Target Machine

Expansion Board
or Adaptor

FX1S, FX1N

FX0N-485ADP

FX1NC
FX2N

FX1N-485-BD,
FX0N-485ADP+FX1N-CNV-BD

*1

FX2N-485-BD,
FX0N-485ADP+FX2N-CNV-BD

FX2NC

FX0N-485ADP

FX3UC

FX3U-485-BD

RS-422
(4-wire)
(Cable Diagram 13)
RS-422
(2-wire)
(Cable Diagram 14)

GP/GLC Series

*2

ST400

*1 The PLCs system version should be at least 1.06 or later. Check the PLCs version by
reading out the data from the register (D8001). For detailed information refer to the
Mitsubishis FX 2N Series Micro Sequencer manuals.
*2 In the GP70 Series, only GP377 Series units can use this cable.

With a 1:n connection, a maximum of 8 PLC units can be connected.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

11

Mitsubishi Electric PLC

MELSEC-QnA Series (using Link I/F)


CPU

Link I/F

Cable Digram

Cables

Target Machine

Serial Communication Unit /


Computer
Link Unit
Q2A,Q2A-S1,Q4A

AJ71QC24

RS-232C
GP410-IS00-O (5m)
(Serial Communication Unit) <Cable Diagram 1>
*1

CA3-CBL232/5M-01 (5m)
AJ71UC24
(Computer Link Unit)

RS-422
GP230-IS11-0(5m)
<Cable Diagram 2>

*2

AJ71QC24N-R4

Q2AS,Q2ASH

RS-422
GP230-IS11-0(5m)
(for CN-2)
<Cable Diagram 2>
CA3-CBL422/5M-01 (5m)

GP/GLC
Series

RS-422
(for CN-1)
<Cable Diagram 5>

GP/GLC
Series

RS-232C
GP000-IS02-MS(3m)
(Serial Communication Unit) <Cable Diagram 3>

A1SJ71UC24-R2

A1SJ71UC24-R4

A1SJ71QC24N

Q4AR

AJ71QC24N

GP/GLC
Series
ST400

*2

Q2AS-S1

ST401

CA3-CBL422/5M-01 (5m)

A1SJ71QC24

A1SJ71UC24
(Computer Link Unit)

GP/GLC
Series

RS-422
GP230-IS11-0(5m)
<Cable Diagram 2>
CA3-CBL422/5M-01 (5m)
RS-232C
GP000-IS02-MS(3m)
<Cable Diagram 3>
RS-422
GP230-IS11-0(5m)
<Cable Diagram 2>
CA3-CBL422/5M-01 (5m)
RS-232C
GP000-IS02-MS(3m)
<Cable Diagram 3>
RS-422
GP230-IS11-0(5m)
<Cable Diagram 2>
CA3-CBL422/5M-01 (5m)
RS-232C
GP410-IS00-O (5m)
<Cable Diagram 1>
CA3-CBL232/5M-01 (5m)
RS-422
GP230-IS11-0(5m)
<Cable Diagram 2>
CA3-CBL422/5M-01 (5m)

ST400

ST400
GP/GLC
Series
ST401
GP/GLC
Series
ST400
GP/GLC
Series
ST401
GP/GLC
Series
ST400
GP/GLC
Series
ST401
GP/GLC
Series
ST400
GP/GLC
Series
ST401
GP/GLC
Series
ST400

*1 ROM : must be 7179B or higher.


*2 ROM : must be 7179M or higher.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

12

Mitsubishi Electric PLC

MELSEC-QnA Series (CPU Direct Connection)


CPU

*1

Adaptor

Cable Diagram

Cables

Target Machine

RS-422

Q4A,
Q2A,
Q2AS,
Q2AS-S1,
Q2A-S1,
Q2ASH,
Q4AR

<Cable Diagram 11>*3 GP430-IP10-O (5m) *5

Diatrend Cable
DAFXIH-CABV
*1

Q4A,
Q2A,
Q2AS,
Q2AS-S1

2-Port Adaptor

Q4A,
Q2A,
Q2ASH,
Q2AS-S1,
Q2A-S1

2 Port Adaptor II

*2

GP030-MD11-O

GP070-MD11

*2

*1

*5

GP/GLC
Series

ST401

RS-422
(Refer to Mitsubishi's A
Series PLC Manual "2 GP430-IP10-O (5m) *4*5
Port Adapter" for cable
diagram information)

GP/GLC
Series

RS-422
(Refer to Mitsubishi's A
GP070-MDCB11(5m)
Series PLC Manual
cable or user-created
"2 Port AdapterII" for
RS-422Cable
cable diagram
information)

GP/GLC
Series

Refer to "Connecting a
Device/PLC to the ST
unit." page 1-6
"2-Port Adaptor II"

ST400

*1 When using 2 Port Adapter II, refer to its manual for the connectable PLCs.
*2 When a Read/Write command is sent from ladder software while data is being
transmitted between the PLC and the GP, there is a possibility the data transmission will not be completed normally. You may need to set the GP to the
OFFLINE mode before you Read/Write in the program
*3 This connection is used for the GP2000/GLC2000 and ST series units. When
using other series unit, use the GP430-IP10-0.
*4 For the ST series units, the GP430-IP11-0 units cannot be used.
Digital's 2-port Adapter (GP030-MD11-0) will have this identification label.
Adapters that support the MELSEC-QnA unit have a circle
around the "B" or later character.
*5 When using this cable, be sure to set the Target Machine's communication
settings to [RS-232C].

GP-PRO/PBIII for Windows Device/PLC Connection Manual

13

Mitsubishi Electric PLC

MELSEC-Q Series (using Link I/F)


CPU

Link I/F

Cable
Diagram

Cables

Target Machine

Serial Communication Unit /


Computer
Link Unit

A1SJ71UC24-R2

Q02CPU-A,
Q02HCPU-A,
Q06HCPU-A

Q02CPU,Q02HCPU,
Q06HCPU,Q12HCPU,
Q25HCPU,Q00CPU,
Q01CPU,Q00JCPU

RS-232C
<Cable
Diagram 3>

A1SJ71UC24-R4

RS-422
<Cable
Diagram 2>

QJ71C24

RS-232C
<Cable
Diagram 3>
RS-422
<Cable
Diagram 2>
RS-232C
<Cable
Diagram 3>

QJ71C24-R2

GP/GLC
Series

GP000-IS02-MS (3m)

ST401
GP/GLC
Series

GP230-IS11-0(5m)
CA3-CBL422/5M-01(5m)

ST400
GP/GLC
Series
ST401
GP/GLC
Series
ST400
GP/GLC
Series
ST401

GP000-IS02-MS (3m)

GP230-IS11-0(5m)
CA3-CBL422/5M-01(5m)
GP000-IS02-MS (3m)

When connecting a link I/F to a MELSEC-Q Series unit CPU, refer to the
MELSEC-Q Series User Manual for a list of connectable (usable) devices.

MELSEC-Q Series (CPU Direct Connection)


CPU

Q02CPU-A
Q02HCPU-A
Q06HCPU-A
Q02CPU
Q02HCPU
Q06HCPU
Q12HCPU
Q25HCPU
Q00CPU
Q01CPU

Cable Diagram

RS-232C
<Cable Diagram 9>

RS-232C
<Cable Diagram 10>

Cable

Target Machine

Mitsubishi Electric
QC30R2(3m)
(Requires 9<->25 pin
conversion adaptor)
Mitsubishi Electric
QC30R2(3m)
(Does not require adaptor)
Diatrend Corporation
*1

DQCABR2-H(3m)
Diatrend Corporation

GP/GLC Series

ST401
GP/GLC Series

*1

DQCABR2-H(3m)
(Requires 9<->25 pin
conversion adaptor)

ST401

*1 When designating the length of a cable, be sure to use meters (*m).


For the available range of cable lengths, please contact the Diatrend company.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

14

Mitsubishi Electric PLC

2.1.2

Cable Diagrams

The cable diagram illustrated below and the cable diagrams recommended by Mitsubishi Electric Corporation may differ. Using these cables for your PLC, however,
will not cause any problems.
Ground your PLC's FG terminal according to your country's applicable standard. For details, refer to the corresponding PLC manual.
Connect the FG line of the Shield cable to either the GP or PLC,
depending on your environment. When using a connector hood
and grounding the FG line, be sure to use an electrical conductor.
The following connection diagrams show examples for connecting a shielded cable to the PLC.
For the RS-232C connection, use a cable length less than 15m.
If a shielded cable is connected to the RS-422 port, it must be no
longer than 600 m.
If a communications cable is used, it must be connected to the
SG (signal ground).
Cable Diagram 1
GP/GLC Series Units
Shield
1
2
3
4
5
6
7
8
20

GP
(25P
male)

FG
SD
RD
RS
CS
NC
SG
CD
ER

1
2
3
4
5
6
7
8
20

FG
SD
RD
RS
CS
DR
SG
CD
ER

PLC
(25P)

ST401 Unit
Shield
ST401
(9P
female)

Connector Shell

3
2
7
8
6
5
1
4

SD
RD
RS
CS
DR
SG
CD
ER

GP-PRO/PBIII for Windows Device/PLC Connection Manual

1
2
3
4
5
6
7
8
20

FG
SD
RD
RS
CS
DR
SG
CD
ER

PLC
(25P)

15

Mitsubishi Electric PLC


Cable Diagram 2
Turn on the PLCs termination resistance switch.
Depending on the type of PLC used, a termination resistance of
330 1/2W or 330 1/4W is needed between SDA and SDB, and
also between RDA and RDB if no DIP switch is available. For
details, refer to the corresponding PLC Manual.
GP/GLC Series Units
When using Digital's RS-422 connector terminal adapter GP070-CN10-0

When using Digital's RS-422 Cable, GP230-IS11-0

Termination
Resistance
330 1/4W 1

*1 When extending the length of the cable, be sure to insert termination resistance
between SDA and SDB.

When making your own cable connections

GP
(25P
male)

*1

PLC
(25P)

*1 When connecting the #9 and #10 pins in the GP Serial I/F, a termination resistance of 100 is added between RDA and RDB.
When making your own cable connections, we recommend using
Mitsubishi's SPEV (SB)-MPC-0.2*3P for the cable.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

16

Mitsubishi Electric PLC

ST400 Unit
When using Digital's RS-422 cable CA3-CBL422/5M-01

CA3-CBL422/5M-01
Termination
Resistance
330 1/4W 1

RDA
RDB

SDA
SDB

SDA
SDB
SG
FG

RDA
RDB
SG
FG

PLC

*1 When extending the length of the cable, be sure to insert termination resistance
between SDA and SDB.

When making your own cable connections


ST400
(9P female)
Termination
Resistance 100
Termination
Resistance 330

*1
SDA
SDB
RDA
RDB
SG
FG

Connector Shell

5
1
2
3
7
6
9
8
4

SG
RDA
RDB
SDA
SDB
CSB
ERB
CSA
ERA

PLC
(25P)

Shield

*1 Be sure to connect the shield to the Connector Shell. For information about FG
connections, refer to page 1-2 "RS422 I/F (ST400)" section's Note, in the "Connecting a Device/PLC to the ST unit."
When making your own cable connections, we recommend using
Mitsubishi's SPEV (SB)-MPC-0.2*3P for the cable.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

17

Mitsubishi Electric PLC

Cable Diagram 3
GP/GLC Series Units
GP
(25P male)

1
2
3
4
5
6
7
8
20

FG
SD
RD
RS
CS
NC
SG
CD
ER

1 CD
2 RD
3 SD
4 ER
5 SG
6 DR
7 RS
8 CS
FG

PLC
(9P)

Shield

Be sure to connect the shield line to the PLC unit's terminal block FG
terminal.
ST401 Unit
ST401
(9P female)

1 CD
2 RD
3 SD
4 ER
5 SG
6 DR
7 RS
8 CS
FG

Connector Shell

3
2
7
8
6
5
1
4

SD
RD
RS
CS
DR
SG
CD
ER

PLC
(9P)

Shield

Be sure to connect the shield line to the PLC unit's terminal block FG
terminal.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

18

Mitsubishi Electric PLC

Cable Diagram 4
GP/GLC Series Units
GP
(25P male)

1
2
3
4
5
6
7
8
20

FG
SD
RD
RS
CS
NC
SG
CD
ER
Shield

1 CD
2 RD
3 SD
4 ER
5 SG
6 DR
7
8
9
FG

PLC
(9P female)

ST401 Unit
ST401
(9P female)

Connector Shell

3
2
7
8
6
5
1
4

SD
RD
RS
CS
DR
SG
CD
ER
Shield

GP-PRO/PBIII for Windows Device/PLC Connection Manual

1 CD
2 RD
3 SD
4 ER
5 SG
6 DR
7
8
9
FG

PLC
(9P female)

19

Mitsubishi Electric PLC


Cable Diagram 5
GP/GLC Series Units
When using Digital's RS-422 connector terminal adapter GP070-CN10-0
Shield

GP070-CN10-O

Termination
Resistance
330 1/4W 1

RDA
RDB
SDA
SDB
TERM
SG
FG

1
3
16
2
15
5
18
4
17
7
8
20
21

FG
SDA
SDB
RDA
RDB
DTRA
DTRB
DSRA
DSRB
SG
SG
SG
SG

PLC

When using Digital's RS-422 connector terminal adapter GP230-IS11-0


Shield

GP230-IS11-O

RDA
RDB
SDA
SDB
SG
FG

Termination
Resistance
330 1/4W 1

1
3
16
2
15
5
18
4
17
7
8
20
21

FG
SDA
SDB
RDA
RDB
DTRA
DTRB
DSRA
DSRB
SG
SG
SG
SG

PLC

*1 When extending the length of the cable, be sure to insert termination resistance
between SDA and SDB.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

20

Mitsubishi Electric PLC


When making your own cable
GP
(25P)

Termination
Resistance
330 1/4W

9
10
16
11
15
21
18
22
19
7

TRMX
RDA
RDB
SDA
SDB
CSA
CSB
ERA
ERB
SG

*1

Shield

1
3
16
2
15
5
18
4
17
7
8
20
21

CD
SDA
SDB
RDA
RDB
DTRB
DTRB
DSRB
DSRB
SG
SG
SG
SG

PLC

*1 When connecting the #9 and #10 pins in the GP Serial I/F, a termination resistance of 100 is added between RDA and RDB.
When making your own cable connections, we recommend using
Mitsubishi's SPEV (SB)-MPC-0.2*3P for the cable.

ST400 Unit
When using Digital's RS-422 cable CA3-CBL422/5M-01
Shield

CA3-CBL422/5M-01
Termination
Resistance
330 1/4W 1

RDA
RDB
SDA
SDB
SG
FG

1
3
16
2
15
5
18
4
17
7
8
20
21

FG
SDA
SDB
RDA
RDB
DTRA
DTRB
DSRA
DSRB
SG
SG
SG
SG

PLC
(25P)

*1 When extending the length of the cable, be sure to insert termination resistance
between SDA and SDB.
Be sure to connect the FG line to the FG terminal. For information about FG
connections, refer to page 1-5 note *1, in the "Connecting a Device/PLC to
the ST unit."

GP-PRO/PBIII for Windows Device/PLC Connection Manual

21

Mitsubishi Electric PLC


When making your own cable connections
ST400
(9P female)
Termination
Resistance 100
Termination
Resistance 330

Connector Shell

1
2
3
7
8
6
4
9
5

*1

RDA
RDB
SDA
SDB
CSA
CSB
ERA
ERB
SG
Shield

1
3
16
2
15
5
18
4
17
7
8
20
21

FG
SDA
SDB
RDA
RDB
DTRB
DTRB
DSRB
DSRB
SG
SG
SG
SG

PLC
(25P)

*1 Be sure to connect the shield to the Connector Shell. For information about FG
connections, refer to page 1-2 "RS422 I/F (ST400)" section's Note, in the "Connecting a Device/PLC to the ST unit."

GP-PRO/PBIII for Windows Device/PLC Connection Manual

22

Mitsubishi Electric PLC

Cable Diagram 6
GP/GLC Series Units
GP
(25P male)

1
2
3
4
5
6
7

FG
SD
RD
RS
CS
NC
SG

2
3
4
5
6

ST401 Unit
Connector Shell

ST401
(9P female)

3
2
7
8
6
5

Shield

RD
SD
ER
SG
DR

PLC
(9P)

Shield

SD
RD
RS
CS
DR
SG

GP-PRO/PBIII for Windows Device/PLC Connection Manual

2
3
4
5
6

RD
SD
ER
SG
DR

PLC
(9P)

23

Mitsubishi Electric PLC

Cable Diagram 7
A termination resistance of 330
is needed between the PLC
connectors SDA and SDB, and also between RDA and RDB.
When using the FX2N-485-BD, FX1N-485-BD or FX3U-485-BD, be
sure the cable is less than 50 meters.
With the FX3UC, the PLC unit's termination resistance is built in
to the FX3U-485-BD expansion board. When using a 4-wire system, be sure to change the unit's dip switch to 330.
GP/GLC Series Units
When using Digital's RS-422 connector terminal adapter GP070-CN10-0
PLC
(Terminal Block)

GP070-CN10-O
Termination
Resistance
330 1/4W

RDA
RDB
SDA
SDB
TERM
SG
FG

SDA
SDB
RDA
RDB
SG

Termination
Resistance
330 1/4W
Termination
Resistance
330 1/4W

Grounding

When using Digital's RS-422 connector terminal adapter GP230-IS11-0


PLC
(Terminal Block)

GP230-IS11-O

Termination
Resistance
330 1/4W 1

RDA
RDB
SDA
SDB
SG
FG

SDA
SDB
RDA
RDB
SG

Termination
Resistance
330 1/4W
Termination
Resistance
330 1/4W

Grounding

*1 When extending the length of the cable, be sure to insert termination resistance
between SDA and SDB.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

24

Mitsubishi Electric PLC

When making your own cable


GP
(25P male)

Termination
Resistance
330 1/4W

PLC

9
10
16
11
15
7
18
19
21
22

*1

TRMX
RDA
RDB
SDA
SDB
SG
CSB
ERB
CSA
ERA

Shield

(Terminal Block)

SDA
SDB
RDA
RDB
SG

Termination
Resistance
330 1/4W
Termination
Resistance
330 1/4W

Grounding

*1 When connecting the #9 and #10 pins in the GP Serial I/F, a termination resistance of 100 is added between RDA and RDB.
Digital recommends Mitsubishi Electrics SPEV(SB)-MPC-0.2x3P cable
for this connection.

ST400 Unit
When using Digital's RS-422 cable CA3-CBL422/5M-01
PLC
(Terminal Block)

CA3-CBL422/5M-01

Termination
Resistance
330 1/4W 1

RDA
RDB
SDA
SDB
SG
FG

SDA
SDB
RDA
RDB
SG

Termination
Resistance
330 1/4W
Termination
Resistance
330 1/4W

Grounding

*1 When extending the length of the cable, be sure to insert termination resistance
between SDA and SDB.
Be sure to connect the FG line to the FG terminal. For information about FG
connections, refer to page 1-5 note *1, in the "Connecting a Device/PLC to
the ST unit."

GP-PRO/PBIII for Windows Device/PLC Connection Manual

25

Mitsubishi Electric PLC

When making your own cable


ST
(9P female)
Termination
Resistance
330 1/4W
Termination
Resistance
330 1/4W

PLC

*1
Connector Shell

1
2
3
7
5
6
9
8
4

(Terminal Block)

Shield

RDA
RDB
SDA
SDB
SG
CSB
ERB
CSA
ERA

SDA
SDB
RDA
RDB
SG

Termination
Resistance
330 1/4W
Termination
Resistance
330 1/4W

Grounding

*1 Be sure to connect the shield to the Connector Shell. For information about FG
connections, refer to page 1-2 "RS422 I/F (ST400)" section's Note, in the "Connecting a Device/PLC to the ST unit."
Digital recommends Mitsubishi Electrics SPEV(SB)-MPC-0.2x3P cable
for this connection.

Cable Diagram 8 (RS-232C)


GP/GLC Series Units
Shield

GP
(25P male)

1
2
3
4
5
6
7
8
20

FG
SD
RD
RS
CS
NC
SG
CD
ER

2
3
6
7
20

SD
RD
DR
SG
ER

PLC
(9P)

ST401 Unit
ST401
(9P female)

Shield
Connector Shell

3
2
7
8
6
5
1
4

SD
RD
RS
CS
DR
SG
CD
ER

2
3
6
7
20

SD
RD
DR
SG
ER

GP-PRO/PBIII for Windows Device/PLC Connection Manual

PLC
(9P)

26

Mitsubishi Electric PLC

Cable Diagram 9
Attaching a Ferrite Core will reduce the amount of noise in your
cable.
Attach two (2) Ferrite Cores to your cable, one at each end. Also,
as shown in the drawing below, loop the cable once around the
Ferrite Core.
When using a data communication cable that is 3m(approx. 10ft.)
or longer, please use a cable made by the Diatrend company.
Be sure all cables are less than 15 meters long.
GP/GLC Series Units
Commercially available adaptor
9pin female
(25pin male
9pin male)

Mini DIN 6pin

Mitsubishis QC30R2
PLC

GP/GLC

Ferrite Core
Ferrite Core Holders:
Secure the ferrite core in place.
3m

<Recommended Ferrite Core>


Maker :Seiwa Electronics Corporation
Model :E04SR301334
39mm
34mm
13mm

GP-PRO/PBIII for Windows Device/PLC Connection Manual

30mm

27

Mitsubishi Electric PLC


Conversion Adaptor Specifications

Straight connection type


D-Sub 25pin male Lock-screw (mm)
D-Sub 9pin male Lock nut (inch)

<Adaptor : Roas Co. Model No. ZA-403>


D-Sub 9pin male
Lock-nut (inch)

D-Sub 25pin male


Lock-screw (mm)

6 cm

ST400 Unit
The ST 400 unit does not require this adaptor and can be connected directly to
PLC.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

28

Mitsubishi Electric PLC


Cable Diagram 10
Attaching a Ferrite Core will reduce the amount of noise in your
cable.
Attach two (2) Ferrite Cores to your cable, one at each end. Also,
as shown in the drawing below, loop the cable once around the
Ferrite Core.
When using a data communication cable that is 3m(approx. 10ft.)
or longer, please use a cable made by the Diatrend company.
Be sure all cables are less than 15 meters long.
GP/GLC Series Units
25pin male

Mini DIN 6pin

Diatrends DQCABR2 (*m)


GP

PLC
Ferrite Core
Ferrite Core Holders:
Secure the ferrite core in place.

<Recommended Ferrite Core>


Maker :Seiwa Electronics Corporation
Model :E04SR301334
39mm
34mm
13mm

30mm

Other manufacturer's ferrite cores can be also used. (The size should be
the same as shown here. )

ST400 Unit
The ST400 unit requires a commercial-type conversion adaptor, such as one of the
types listed below. Wiring is the same as shown for the conversion adaptor on page
25.
<Conversion Adaptor Specifications>
Straight wiring type
D-sub 9-pin female, with lock screw (inch)
D-sub 25-pin female, with lock nut (mm)

GP-PRO/PBIII for Windows Device/PLC Connection Manual

29

Mitsubishi Electric PLC

Cable Diagram 11
These cable diagrams can only be used for GP2000/GLC2000 Series units and the ST400 unit.
GP/GLC Series Units
GP
(25P male)

Shield
1 FG
7 SG
9 TRMX
10 RDA
11 SDA
15 SDB
16 RDB
18 CSB
19 ERB
21 CSA
22 ERA

3 SDA
16 SDB
7 SG
2 RDA
15 RDB
4 CSA
17 CSB
5 ERA
18 ERB
20
21

*1

PLC
(25P male)

*1 When connecting the #9 and #10 pins in the GP Serial I/F, a termination resistance of
100 is added between RDA and RDB.

The cable length should be 5m or less.

ST400 Unit
*1
ST
(9P female)

Connector Shell

5
1
3
7
2
6
9
8
4

Termination
Resistance
100

SG
RDA
SDA
SDB
RDB
CSB
ERB
CSA
ERA

Shield
3 SDA
16 SDB
7 SG
2 RDA
15 RDB
4 CSA
17 CSB
5 ERA
18 ERB
20
21

PLC
(25P Male)

*1 Be sure to connect the shield to the Connector Shell. For information about FG connections, refer to page 1-2 "RS422 I/F (ST400)" section's Note, in the "Connecting a
Device/PLC to the ST unit."

The cable length should be 5m or less.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

30

Mitsubishi Electric PLC

Cable Diagram 12 (RS-422)


The cable diagrams given below are for the option cables, however be sure to use
an option cable when connecting to the Device/PLC.
Using a GP2000-CBLFX/5M-01, GP2000-CBLFX/1M-01 cable
PLC
(Mini DIN 8 Pin)

GP
(25P Male)

330 1/4W

7 SG
9 TERM
10 RDA
16 RDB
11 SDA
15 SDB
18 CSB
19 ERB
21 CSA
22 ERA

3 SG
6 SG
7 TXD+
4 TXD2 RXD+
1 RXDConnector Shell

Shield

Using a CA3-CBLFX/5M-01, CA3-CBLFX/1M-01 cable


PLC
(Mini DIN 8 Pin)

GP
(25P Male)

330 1/4W

5 SG
1 RDA
2 RDB
3 SDA
7 SDB
6 CSB
9 ERB
8 CSA
4 ERA

3 SG
6 SG
7 TXD+
4 TXD2 RXD+
1 RXDConnector Shell

Shield

GP-PRO/PBIII for Windows Device/PLC Connection Manual

31

Mitsubishi Electric PLC

Cable Diagram 13
Connect a terminating resistor to both ends of the cable.
When using only the FX0N-485ADP, the maximum cable length is
500m. Whe the FX1N-485-BD, FX2N-485-BD or FX3U-485-BD are
included, the maximum cable length is 50m.
As a general rule, connect the PLC at the end of the circuits wiring
(see below).
With the FX3UC, the PLC unit's termination resistance is built into
the FX3U-485-BD expansion board. When using a 4-wire system,
be sure to change the unit's dip switch to 330.
GP/GLC Series Units
When using Digital's RS-422 connector terminal adapter GP070-CN10-O
PLC
Terminal Block
330

1/4W
330

1/4W
GP070-CN10-0

Shield

PLC
Terminal Block

Shield

PLC
Terminal Block
330

RDA

SDA

SDA

SDA

RDB

SDB

SDB

SDB

SDA

RDA

RDA

RDA

330

SDB

RDB

RDB

RDB

1/4W

SG

SG

SG

SG

1/4W

FG

Shield

When making your own cable


Shield
GP
(25P male)
330 1/4W
330 1/4W

1 FG
7 SG
9 TERM
10 RDA
16 RDB
11 SDA
15 SDB
18 CSB
19 ERB
21 CSA
22 ERA

PLC
Terminal
Block
SG
SDA
SDB
RDA
RDB

Shield

GP-PRO/PBIII for Windows Device/PLC Connection Manual

PLC
Terminal
Block
SG
SDA
SDB
RDA
RDB

Shield

PLC
Terminal
Block
SG
SDA
SDB
RDA
RDB

32

Mitsubishi Electric PLC


ST400 Unit
When making your own cable
ST
(9P female)
330 1/4W
330 1/4W

*1
Connector Shell

5
1
2
3
7
6
9
8
4

SG
RDA
RDB
SDA
SDB
CSB
ERB
CSA
ERA

Shield

PLC
Terminal
Block
SG
SDA
SDB
RDA
RDB

Shield

PLC
Terminal
Block
SG
SDA
SDB
RDA
RDB

Shield

PLC
Terminal
Block
SG
SDA
SDB
RDA
RDB

*1 Be sure to connect the shield to the Connector Shell. For information about FG connections, refer to page 1-2 "RS422 I/F (ST400)" section's Note, in the "Connecting a
Device/PLC to the ST unit."

GP-PRO/PBIII for Windows Device/PLC Connection Manual

33

Mitsubishi Electric PLC


Cable Diagram 14 (RS-422 2-wire)
Connect a terminating resistor to both ends of the cable.
When using only the FX0N-485ADP, the maximum cable length is
500m. Whe the FX1N-485-BD, FX2N-485-BD or FX3U-485-BD are
included, the maximum cable length is 50m.
As a general rule, connect the PLC at the end of the circuits wiring
(see below).
With the FX3UC, the PLC unit's termination resistance is built into
the FX3U-485-BD expansion board. When using a 2-wire system,
be sure to change the unit's dip switch to 110.
GP/GLC Series Units
When using Digital's RS-422 connector terminal adapter GP070-CN10-O

110 1/2W

GP070-CN10-0

PLC
PLC
Terminal
Terminal
Unit 0
Block
SDA
SDB
RDA
RDB
SG

RDA
RDB
SDA
SDB
SG
FG

Shield
Shield

PLC
PLC
Terminal
Terminal
Unit 1
Block
SDA
SDB
RDA
RDB
SG

Shield
Shield

PLC
PLC
Terminal
Terminal
Unit n
Block
SDA
SDB
RDA
RDB
SG

110
1/2W

Shield

When making your own cable


PLC
PLC

PLC
PLC

1 FG

Terminal
Terminal

Terminal
Terminal

7 SG

Unit 0
Block

GP
(25P Male)

110 1/2W

Shield
Shield

Block
Unit 1

PLC
PLC

Shield
Shield

Terminal
Terminal
Unit n
Block

9 TERM

SG

SG

SG

10 RDA

SDA

SDA

SDA

16 RDB

SDB

SDB

SDB

11 SDA

RDA

RDA

RDA

15 SDB

RDB

RDB

RDB

110
1/2W

18 CSB
19 ERB
21 CSA
22 ERA

Shield

GP-PRO/PBIII for Windows Device/PLC Connection Manual

34

Mitsubishi Electric PLC

ST400 Unit
When making your own cable
ST
(9P female)

PLC
Terminal
Block
SG
SDA
SDB
RDA
RDB

*1
Connector Shell

110
1/2W

5
1
2
3
7
6
9
8
4

SG
RDA
RDB
SDA
SDB
CSB
ERB
CSA
ERA

Shield

PLC
Terminal
Block
SG
SDA
SDB
RDA
RDB

Shield

PLC
Terminal
Block
SG
SDA
SDB
RDA
RDB

110
1/2W

Shield

*1 Be sure to connect the shield to the Connector Shell. For information about FG connections, refer to page 1-2 "RS422 I/F (ST400)" section's Note, in the "Connecting a
Device/PLC to the ST unit."

GP-PRO/PBIII for Windows Device/PLC Connection Manual

35

Mitsubishi Electric PLC

2.1.3

Supported Devices

The following table describes the range of devices supported by the GP.

MELSEC-A Series (AnA/ AnU/ A2US/ A2USH-S1)


Setup System Area here.
Device

Bit Address

Word Address

Input Relay

X0000 ~ X1FFF

X0000 ~ X1FF0

Output Relay

Y0000 ~ Y1FFF

Y0000 ~ Y1FF0

Internal Relay

M0000 ~ M8191

M0000 ~ M8176

Latch Relay

L0000 ~ L8191

L0000 ~ L8176

Special Relay

M9000 ~ M9255

M9000 ~ M9240

Annunciator

F0000 ~ F2047

F0000 ~ F2032

Link Relay

B0000 ~ B1FFF

Timer (contact)

TS0000 ~ TS2047

Timer (coil)

TC0000 ~ TC2047

Counter (contact)

CS0000 ~ CS1023

Counter (coil)

CC0000 ~ CC1023

Particulars

L/H

Timer (current value)

TN0000 ~ TN2047

Counter (current value)

CN0000 ~ CN1023

Data Register

D0000 ~ D8191

Special Register

D9000 ~ D9255

Link Register

W0000 ~ W1FFF

File Register

R0000 ~ R8191

*1

*1 When using the File Register on AnA or AnU, use the User's Memory area in
the memory casettes listed below.
A3NMCA-0

A3NMCA-2

A3NMCA-4

A3NMCA-8

A3NMCA-16

A3NMCA-24

A3NMCA-40

A3NMCA-56

A4UMCA-8E

(only when using CPU Direct Communication)

When the File Register is setup and the memory casette is not in use, an error
will develop when communicating.

!
Caution

If a ladder program is stored in ROM when a direct


connection is used, there may be cases where the
file register may not be used.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

36

Mitsubishi Electric PLC

MELSEC-N Series (AnN/ A2C/ A1S/ A3H/A0J2/A1SJ/A2SH/A1SH/A2CJ-S3)


Setup System Area here.
Device

Bit Address

Word Address

Input Relay

X0000 ~ X07FF

X0000 ~ X07F0

Output Relay

Y0000 ~ Y07FF

Y0000 ~ Y07F0

Internal Relay

M0000 ~ M2047

M0000 ~ M2032

Latch Relay

L0000 ~ L2047

Special Relay

M9000 ~ M9255

M9000 ~ M9240

Annunciator

F000 ~ F255

F000 ~ F240

Link Relay

B0000 ~ B03FF

Timer (contact)

TS000 ~ TS255

Timer (coil)

TC000 ~ TC255

Counter (contact)

CS000 ~ CS255

Counter (coil)

CC000 ~ CC255

Particulars

*1

*2

L/H

Timer (current value)

TN000 ~ TN255

Counter (current value)

CN000 ~ CN255

Data Register

D0000 ~ D1023

Link Register

W0000 ~ W03FF

File Register

R0000 ~ R8191

*3

*1 With the A2C, the Output Relays Y01F0~Y01FF (the word is Y01F0) cannot
be setup for use on the PLC (only for A2C).
*2 MELSEC-AnN and AJ71C24-S3 (or AJ71C24) cannot be matched and used.
*3 When using the File Register on AnN or A3H, use the User's Memory area in
the memory casettes listed below.
A3NMCA-0

A3NMCA-2

A3NMCA-4

A3NMCA-8

A3NMCA-16

A3NMCA-24

A3NMCA-40

A3NMCA-56

A4UMCA-8E (only when using CPU Direct Connection)


When the File Register is setup when the memory cassette is not in use, an
error will develop when communicating.

!
Caution

If a ladder program is stored in ROM when a direct


connection is used, there may be cases where the
file register can not be used.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

37

Mitsubishi Electric PLC

MELSEC-F2 Series (Using Link I/F)


Setup System Area here.
Device

Bit Address

Word Address

Particulars

000 ~ 013,
Input Relay (X)

400 ~ 413,
500 ~ 513
030 ~ 037,

Output Relay (Y)

430 ~ 437,
530 ~ 537
050 ~ 057,
450 ~ 457,
550 ~ 557,

Timer (contact)(T)

650 ~ 657
060 ~ 067,
460 ~ 467,

C ounter (contact)(C )

560 ~ 567,
660 ~ 667
070 ~ 077,
100 ~ 177,
200 ~ 277,
470 ~ 477,
570 ~ 577

H old Relay (M )

Keep Relay (M )

300 ~ 377

State (S)

800 ~ 877,
900 ~ 977,
600 ~ 647

Timer (current v alue)

Timer (set v alue)

C ounter (current v alue)

C ounter (set v alue)

Data Register

TC 050 ~
TC 450 ~
TC 550 ~
TC 650 ~
TS050 ~
TS450 ~
TS550 ~
TS650 ~

TC 057
TC 457
TC 557
TC 657
TS057
TS457
TS557
TS657

C C 060 ~
C C 460 ~
C C 560 ~
C C 660 ~
C S060 ~
C S460 ~
C S560 ~
C S660 ~

C C 067
C C 467
C C 567
C C 667
C S067
C S467
C S567
C S667

DW700 ~ DW777

Since the word addresses in F2 Series' Timer, Counter, and Data Register
bit length is 12, some tag functionality ( i.e. N-tag, S-tag, C-tag, etc.) is
limited.

You cannot use 2 word (32 bit) data.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

38

Mitsubishi Electric PLC

MELSEC-FX Series (using CPU Direct Connection and


Mitsubishi's MELSEC-FX (CPU) Protocol on FX0 )
Setup System Area here.
Device

Bit Address

Word Address

Input Relay

X000 ~ X017

X000

Output Relay

Y000 ~ Y015

Y000

Internal Relay

M000 ~ M511

M000 ~ M496

State

S000 ~ S063

S000 ~ S048

Timer (contact)

TS000 ~ TS055

Counter (contact)

CS000 ~ CS015

Timer (current value)

TN000 ~ TN055

Counter (current value)

CN000 ~ CN015

Data Register

Particulars

L/H

D000 ~ D031

MELSEC-FX Series (using Expansion Board with


Mitsubishi's MELSEC-FX2 (LINK) Protocol)
Setup System Area here.
Device

Bit Address

Word Address

Input Relay

X0000 - X0377

X0000 - X0360

Output Relay

Y0000 - Y0377

Y0000 - Y0360

Auxilary Relay

M0000 - M7679

M0000 - M7664

State

S0000 - S4095

S0000 - S4080

Special Auxilary relay

M8000 - M8511

M8000 - M8496

Timer (contact)

TS000 - TS511

Counter (contact)

CS000 - CS255

Remarks

*1
L/H

Timer (current)

TN000 - TN511

Counter (current)

CN000 - CN255

Data Register

D0000 - D7999

Special Data Register

D8000 - D8511

*1 *3

Extended Register

R00000 - R32767

*4 *3

*2

*1 The Special Auxilary Relay and the Special Data Register are divided into three areas. These are
the Exclusive Reading Area, the Exclusive Writing Area and the System Area. For details, refer to
your PLCs manual.
*2 Word addresses CN200 to CN255 are 32 bit counters.
*3 When designating data register addresses, be sure that they do not overlap with the special register area.
For example, do not perform a write of two or more words, starting from "D7999".
When a write of two or more words is done starting from "D7999", a "Host Communication" error
(02:FA) occurs.
*4 With only FX3UC units.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

39

Mitsubishi Electric PLC

MELSEC-FX Series (using Mitsubishi's MELSEC-FX (CPU) or


MELSEC-FX (CPU2) Protocol)
Setup System Area here.
Device

Bit Address

Word Address

Input Relay

X000 - X0377

X000 - X0360

Output Relay

Y000 - Y0377

Y000 - Y0360

Internal Relay

M0000 - M7679

M0000 - M7664

Special Auxilary relay

M8000 - M8511

M8000 - M8496

State

S000 - S4095

S000 - S4080

Timer (contact)

TS000 - TS511

Counter (contact)

CS000 - CS255

Remarks
*2

*3

L/H
Timer (current value)

TN000 - TN511

Counter (current value)

CN000 - CN255

Data Register

D000 - D7999

*4 *5

Special Data Register

D8000 - D8511

*3

Extended Register

R00000 - R32767

*6

*1

*1 Addresses CN200 to CN255 are 32 bits long.


*2 Cannot perform data write.
*3 The Special Auxiliary Relay and the Special Data Register are divided into three areas. These are the Exclusive Reading Area, the Exclusive Writing Area and the System
Area. For details, refer to your PLC's manual.
*4 When designating data register addresses, be sure that they do not overlap with the
special register area.
For example, do not perform a write of two or more words, starting from "D7999".
When a write of two or more words is done starting from "D7999", a "Host Communication" error (02:FA) occurs.
*5 For the FX1S series and FACON series, addresses D1000 to D2499 are file registers.
File registers can be used based on the file data amount designated through the ladder
program.
When this amount is not specified, a "Host Communication" error (02:FA) occurs.
When changing the PLC's file data amount settings during GP-PLC communication,
be sure to turn ON/OFF the GP unit's power. As long as the screen is not changed to a
different one, the screen's file register will continue to access the memory value that
was designated before the change.
*6 With only FX3UC units.

Refer to the MELSEC-N series manuals for the A1FX's range of available devices.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

40

Mitsubishi Electric PLC

MELSEC-FX Series (using 1 : n Connection)


Setup System Area here.
Device

Bit Address

Word Address

Input Relay

X0000 - X0377

X0000 - X0360

Output Relay

Y0000 - Y0377

Y0000 - Y0360

AUX Relay

M0000 - M7679

M0000 - M7664

Special AUX Relay

S0000 - S4095

S0000 - S4080

State

M8000 - M8511

M8000 - M8496

Timer (contact)

TS000 - TS511

Counter (contact)

CS000 - CS255

Remarks

*3
L/H

Timer (current value)

TN000 - TN511

Counter (current value)

CN000 - CN255

*1

Data Register

D0000 - D7999

*3

Special Data Register

D8000 - D8511

*2

Extended Register

R00000 - R32767

*4 *5

*1 Addresses CN200 to CN255 are 32 bits long.


*2 The Special Auxiliary Relay and the Special Data Register are divided into three areas.
These are the Exclusive Reading Area, the Exclusive Writing Area and the System Area. For
details, refer to your PLC's manual.
*3 When designating data register addresses, be sure that they do not overlap with the special
register area.
For example, do not perform a write of two or more words, starting from "D7999". When a
write of two or more words is done starting from "D7999", a "Host Communication" error
(02:FA) occurs.
*4 Used only by FX3UC.
*5 (Only when using Mitsubishi Electric MELSEC-FX 1:N Communication Protocol)
The GP unit processes data internally in blocks of 8192 words. If data spans more than one
block, the following features cannot be used. When using these features, be sure all data
spans no more than a single block.
1) a-Tag settings
2) 2-Way feature block readout/writing of data.
Ex. Using Pro-Server to perform a block readout of 20 words of data, starting from R8191.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

41

Mitsubishi Electric PLC

MELSEC-QnA Series (using Computer Unit AJ71QC24/A1SJ71QC24N/


AJ71QC24N-R4/AJ71QC24N or using CPU Direct Connection)
Setup System Area here.
Device

Bit Address

Word Address

Input Relay

X0000 ~ X1FFF

X0000 ~ X1FF0

Output Relay

Y0000 ~ Y1FFF

Y0000 ~ Y1FF0

Internal Relay

M00000 ~ M32767

M00000 ~ M32752

Special Relay

SM0000 ~ SM2047

SM0000 ~ SM2032

Latch Relay

L00000 ~ L32767

L00000 ~ L32752

Annunciator

F00000 ~ F32767

F00000 ~ F32752

Edge Relay

V00000 ~ V32767

V00000 ~ V32752

Step Relay

S0000 ~ S8191

S0000 ~ S8176

Link Relay

B0000 ~ B7FFF

B0000 ~ B7FF0

Special Link Relay

SB000 ~ SB7FF

SB000 ~ SB7F0

Timer (contact)

TS00000 ~ TS22527

Timer (coil)

TC00000 ~ TC22527

Aggregate Timer (contact)

SS00000 ~ SS22527

Aggregate Timer (coil)

SC00000 ~ SC22527

Counter (contact)

CS00000 ~ CS22527

Counter (coil)

CC00000 ~ CC22527

Timer (current v alue)

TN00000 ~ TN22527

Aggregate Timer (current v alue)

SN00000 ~ SN22527

Counter (current v alue)

CN00000 ~ CN22527

Data Register

D00000 ~ D25599

Special Data Register

SD0000 ~ SD2047

Particulars

L/H

Link Data Register

W0000 ~ W63FF

Special Link Register

SW000 ~ SW7FF

File Register (normal)

R00000 ~ R32767

*1

File Register (serial)

0R0000 ~ 0R7FFF
:
1R0000 ~ 1R7FFF

*1

*1 When using File Register, a Memory Card is necessary.


Usable capacity of the File Register varies depending on the capacity of the
Memory Card.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

42

Mitsubishi Electric PLC

MELSEC-QnA Series (using Computer Unit AJ71UC24/A1SJ71UC24R2/A1SJ71UC24-R4 )


Setup System Area here.
Device

Bit Address

Word Address

Input Relay

X0000 ~ X03FF

X0000 ~ X03F0

Output Relay

Y0000 ~ Y03FF

Y0000 ~ Y03F0

Internal Relay

M00000 ~ M8191

M00000 ~ M8176

Special Relay

SM1000 ~ SM1255

SM1000 ~ SM1240

Annunciator

F0000 ~ F2047

F0000 ~ F2032

Link Relay

B0000 ~ B0FFF

Timer (contact)

TS0000 ~ TS2047

Timer (coil)

TC0000 ~ TC2047

Counter (contact)

CS0000 ~ CS1023

Counter (coil)

CC0000 ~ CC1023

Particulars

*1

L/H

Timer (current value)

TN0000 ~ TN2047

Counter (current value)

CN0000 ~ CN1023
D0000 ~ D6143

Data Register

SD1000 ~ SD1255

Special Data Register

*1

W0000 ~ W0FFF

Link Register

*1 Table data will change depending on whether the perspective is from the PLC
or the User's PC.
Device
Special
Relay
Special
Register

GP-PRO/PBIII
M9000 ~ M9255
D9000 ~ D9255

PLC Manual
SM1000 ~ SM1255
(cannot use SM0000~SM0999)
SD1000 ~ SD1255
(cannot use SD0000~SD0999)

GP-PRO/PBIII for Windows Device/PLC Connection Manual

43

Mitsubishi Electric PLC

MELSEC-QnA series communications mode selection (when using a link unit)


When using the MELSEC-QnA series unit, either mode 2 or mode 1 can be selected during the entering of the initial settings, when the GP is in the OFFLINE
mode.
Mode 2:

This is a new communications mode. It is enabled when less than 64


devices have been designated by a single screens tags. The communications speed has been improved. Select this mode when using less
than 64 devices.

Mode 1:

This mode is equivalent to the communications mode used previously.


This mode is valid for 64 or more devices have been specified by a
single screens tags. The communications speed has been improved.
Select this mode when using 64 or more devices.

If the on-screen data memory area in the GP is initilaized or if the


on-screen data is transferred from the drawing software, the GP
returns to mode 1 (its initial setting). Use the offline settings area
to select mode 2.
In mode 2, the communications speed may not always be improved depending on which tags and system area are used, as
well as how the PLC's read areas are allocated.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

44

Mitsubishi Electric PLC

MELSEC-Q Series (A mode, CPU Direct Connection)


Setup System Area here.
Device

Bit Address

Word Address

Input Relay

X0000 ~ X1FFF

X0000 ~ X1FF0

Output Relay

Y0000 ~ Y1FFF

Y0000 ~ Y1FF0

Internal Relay

M0000 ~ M8191

M0000 ~ M8176

L0000 ~ L8191

L0000 ~ L8176

Special Relay

M9000 ~ M9255

M9000 ~ M9240

Annunciator

F0000 ~ F2047

F0000 ~ F2032

Link Relay

B0000 ~ B1FFF

Latch Relay

Timer (contact)

TS0000 ~ TS2047

Timer (coil)

TC0000 ~ TC2047

Counter (contact)

CS0000 ~ CS1023

Counter (coil)

CC0000 ~ CC1023

Particulars

L/H

Timer (current value)

TN0000 ~ TN2047

Counter (current value)

CN0000 ~ CN1023

Data Register

D0000 ~ D8191

Special Data Register

D9000 ~ D9255

Link Register

W0000 ~ W1FFF

File Register

R0000 ~ R8191

*1

* 1 The amount of space available when using the File Register will vary, depending on the amount of CPU ROM/RAM available, or the amount of memory
available on the memory card.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

45

Mitsubishi Electric PLC

MELSEC-Q Series (Q mode Link I/F, CPU Direct)


Setup System Area here.
Device

Bit Address

Word Address

Input Relay

X0000 ~ X1FFF

X0000 ~ X1FF0

Output Relay

Y0000 ~ Y1FFF

Y0000 ~ Y1FF0

Internal Relay

M00000 ~ M32767

M00000 ~ M32752

Special Relay

SM0000 ~ SM2047

SM0000 ~ SM2032

Latch Relay

L0000 ~ L32767

L0000 ~ L32752

Annunciator

F0000 ~ F32767

F0000 ~ F32752

Edge Relay

V0000 ~ V32767

V0000 ~ V32752

Step Relay

S0000 ~ S8191

S0000 ~ S8176

Link Relay

B0000 ~ B7FFF

B0000 ~ B7FF0

Special Link Relay

SB000 ~ SB7FF

SB000 ~ SB7F0

Timer (contact)

TS00000 ~ TS23087

Timer (coil)

TC00000 ~ TC23087

Aggregate Timer (contact)

SS00000 ~ SS23087

Aggregate Timer (coil)

SC00000 ~ SC23087

Counter (contact)

CS00000 ~ CS23087

Counter (coil)

CC00000 ~ CC23087

Notes

L/H

Timer (current value)

TN00000 ~ TN23087

Aggregate Timer (current value)

SN00000 ~ SN23087

Counter (current value)

CN00000 ~ CN23087

Data Register

D00000 ~ D25983

Special Data Register

SD0000 ~ SD2047

Link Data Register

W0000 ~ W657FF

Special Link Register

SW000 ~ SW7FF

File Register (normal)

R00000 ~ R32767

*1

0R0000 ~ 0R7FFF

*1

1R0000 ~ 1R7FFF

*1

File Register (serial)


:

:
31R0000 ~ 31R67FF

:
*1

*1 The amount of space available when using the File Register will vary, depending on the amount of CPU ROM/RAM available, or the amount of memory
available on the memory card.
Each device range represents the maximum range available, given the
parameter settings.
Depending on your CPU, the usable device type and range may differ.
Before using only a CPU, refer to your CPU User Manual.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

46

Mitsubishi Electric Corporation PLC

2.1.4

Environment Setup

The following lists Digital's recommended PLC and GP communication settings.


Items affecting the PLC program cycle Please be aware that PLC program cycle time slows by approximately 8%
when you connect the GP to the programming port and begin communications with the GP.

MELSEC-A Series / N Series (using Calculation Link Unit)


GP Setup

Computer Link Unit Setitings

Baud Rate

19200 bps

Baud Rate

19200 bps

Data Length

7 bits

Data Bit

7 bits

Stop Bit

2 bits

Stop Bit

2 bits

Parity Bit

Even

Parity Check
Parity setting even/odd

Yes
Even

Data Flow Control

ER Control

---

Communication Format
(RS-232C)

RS-232C

Channel Setup
Mode Setup
(RS-232C)

*1

Communication Format
(RS-422)

4-wire type

Channel Setup
Mode Setup
(RS-422)
Write possible
in RUN mode.

*1

---

--Unit No.

Yes

Enable Sender

---

RS-422
8 (Format 4 protocol)
Possible

Sum Check

---

RS-232C
4 (Format 4 protocol)

Termination Resistor
Enable Receiver

*2

Yes

Termination Resistor

*2

Yes

Station Number

*1 A1SJ71C24-R2, A1SJ71UC24-R2, and A1SJ71C24-R4 do not have this setting.


*2 The A171UC24 does not have this setting.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

47

Mitsubishi Electric Corporation PLC

MELSEC-A Series / N Series (CPU Direct Connection)


GP Setup

PLC Settings

Baud Rate

9600 bps (fixed)

---

Data Length

8 bit (fixed)

---

Stop Bit

1 bit (fixed)

---

Parity Bit

Odd (fixed)

---

ER Control

---

RS-232C

---

4-wire type

---

0 (fixed)

---

Data Flow Control


Communication Format
(RS-232C)
Communication Format
(RS-422)

*1

Unit No.

*1 Only when using Digital's Programming Console I/F cable (GP430-IP10-O)


for the MELSEC-A Series unit or a Diatrend Co. DAFXIH-CABV cable.
Otherwise, a 4-wire type cable is required.

MELSEC-A2C
GP Setup

A2C Settings

Baud Rate

19200 bps

Baud Rate

19200 bps

Data Length

8 bits

Data Bit

8 bits

Stop Bit

1 bit

Stop Bit

1 bit

Parity Bit

Even

Parity Check
Parity setting even/oddd

Yes
Even

Data Flow Control

ER Control

Communication Format

RS-232C

--Channel Setup
Mode Setup

RS-232C
4 (Format 4 protocol)

---

Write possible in RUN mode Possible

---

Sum Check

Yes

Station Number

Unit No.

MELSEC-F2 Series
GP Setup
Baud Rate

9600 bps

Baud Rate

9600 bps

Data Length

7 bits

Data Bit

7 bits

Stop Bit

1 bit (fixed)

Stop Bit

1 bit (fixed)

Parity Bit

Even

Parity Bit

Even

Data Flow Control

ER Control

---

Communication Format

RS-232C

---

Unit No.

48

Interface Setitings

---

Resistor Setting

Yes

---

Sum Check

Yes

Station Number

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric Corporation PLC

MELSEC-FX Series (Expansion Board with Mitsubishi's MELSEC-FX2


(LINK) Protocol - not using FX3UC unit)
GP Setup

Computer Link Unit Settings

Baud Rate

19200 bps

Baud Rate

19200 bps

Data Length

7 bits

Data Bit

7 bits

Stop Bit

2 bits

Stop Bit

2 bits

Parity Bit

Even

Parity Bit

Even

Data Flow Control

ER Control

Communication Format
(RS-232C)
Communication Format
(RS-422)

RS-232C

Unit No.

4-wire type

--RS-232C I/F

Computer Link

RS485 (RS422) I/F

Computer Link
Station Number

*1

---

Sum Check

Yes

---

Protocol

Yes

---

Control Method

---

Header

No

---

Terminator

No

*1 Even though PLC station numbers are set using 00h to 0Fh, the GP Series
units use only 0 to 7.
It is possible to enter PLC settings via the ladder software's PC system
settings or to write data directly to data registers D8120 and D8121. For
details, refer to Mitsubishi's "FX Communication User Manual".

GP-PRO/PBIII for Windows Device/PLC Connection Manual

49

Mitsubishi Electric Corporation PLC

MELSEC-FX Series (Expansion Board with Mitsubishi's MELSEC-FX2


(LINK) Protocol - using FX3UC unit)
GP Setup

Computer Link Unit Settings

Baud Rate

19200 bps

Baud Rate

19200 bps

Data Length

7 bits

Data Bit

7 bits

Stop Bit

2 bits

Stop Bit

2 bits

Parity Bit

Even

Parity Bit

Even

Data Flow Control

ER Control

Communication Format
(RS-232C)
Communication Format
(RS-422)

RS-232C

Unit No.

4-wire type

--Computer Link
Computer Link

RS-232C I/F
RS485 (RS422) I/F

Station Number

---

Sum Check

Yes

---

Protocol

Yes

---

Control Method

---

Header

No

---

Terminator

No

*1 The termination resistance will vary depending on if a 4-wire or a 2-wire connection is


used. Termination resistance is built into the FX3U-485-BD expansion board.
*2 Even though PLC station numbers are set using 00h to 0Fh, the GP Series
units use only 0 to 7.
It is possible to enter PLC settings via the ladder software's PC system
settings or to write data directly to data registers D8120 and D8121. For
details, refer to Mitsubishi's "FX Communication User Manual".

50

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric Corporation PLC

MELSEC-FX Series *1 (using CPU Direct Connection with


Mitsubishi's MELSEC-FX (CPU) or MELSEC-FX (CPU2) Protocol )
GP Setup

FX Series Settings

Baud Rate

9600 bps (fixed)

---

Data Length

7 bits (fixed)

---

Stop Bit

1 bit (fixed)

---

Parity Bit

Even (fixed)

---

Data Flow Control

ER Control

---

RS-232C

---

4-wire

---

0 (fixed)

---

Communication Format
(When using Mitsubishi
Melsec-FX(CPU) Protocol)
Communication Format
(When using Mitsubishi
Melsec-FX(CPU2)
Protocol)
Unit No.

*1 When using the A1FX unit, use the same settings as those for the MELSEC-N
Series (CPU Direct Connection).

Caution

When using the expansion board with the above mentioned direct connection protocol, store "0" data in
D8120. Also, when using the FX3UC, be sure to set
M8070 and M8071 to OFF.
MELSEC-FX Series (1 : n Connection - not using FX3UC unit)
GP Setup

PLC Settings

Baud Rate

19200 bps

Baud Rate

19200 bps

Data Length

7 bits

Data Length

7 bits

Stop Bit

2 bits

Stop Bit

2 bits

Parity Bit

Even

Parity Bit

Even

Data Flow Control

ER

Communication Format

4-wire or 2-wire H/W Type

Unit No.

Station Number

RS-485
*1

Use Comm. Settings

Use

Sum Check

Yes

Protocol

Special Protocol

Control Method

Header

None

Terminator

None

*1 Although 00H to 0FH can be used for the PLC station numbers, use only 0 to
7 for the GP Series unit.
It is possible to enter PLC settings via the ladder software's PC system
settings or to write data directly to data registers D8120 and D8121. For
details, refer to Mitsubishi's "FX Communication User Manual".

GP-PRO/PBIII for Windows Device/PLC Connection Manual

51

Mitsubishi Electric Corporation PLC

MELSEC-FX Series (1 : n Connection - using FX3UC unit)


GP Setup

PLC Settings

Baud Rate

19200 bps

Baud Rate

19200 bps

Data Length

7 bits

Data Length

7 bits

Stop Bit

2 bits

Stop Bit

2 bits

Parity Bit

Even

Parity Bit

Even

Data Flow Control

ER

Communication Format

4-wire or 2-wire H/W Type *1

Unit No.

ER

Station Number

RS-485
*2

00h

CH

CH1

Protocol

Special Protocol

Control Method

Sum Check

Added

Comm. Settings

Use check

Header

None

Terminator

None

*1 The termination resistance will vary depending on if a 4-wire or a 2-wire connection is


used. Termination resistance is built into the FX3U-485-BD expansion board.
*2 Even though PLC station numbers are set using 00h to 0Fh, the GP Series
units use only 0 to 7.
It is possible to enter PLC settings via the ladder software's PC system
settings or to write data directly to data registers D8120 and D8121. For
details, refer to Mitsubishi's "FX Communication User Manual".

52

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric Corporation PLC

MELSEC-QnA (using Serial Communication Unit)


GP Setup

Serial Communication Unit Settings

Baud Rate

19200 bps

Data Length
Stop Bit

*1

Baud Rate

19200 bps

7 bits

Data Bit

7 bits

2 bits

Stop Bit

2 bits

Parity Bit

Even

Parity Check
Parity setting even/odd

Yes
Even

Data Flow Control

ER Control

Communication Format
(RS-232C)
Communication Format
(RS-422)

RS-232C
4-wire type

------Unit No.

--Mode Setup (RS-232C)


Mode Setup (RS-422)

4 (Format 4 Protocol
Mode)
4 (Format 4 Protocol
Mode)

Sum Check

Yes

Enable Sender
Termination Resistor
Enable Receiver
Termination Resistor

Yes

Station Number

Yes

*1 AJ71QC24-R4 , A1SJ71QC24N and AJ71QC24N can use a baud rate of


115,200bps.
When your environment setup involves using MELSEC-QnA and the
Computer Link Unit AJ71UC24 together, refer to the MELSEC-A Series' table.
Serial communication units CH1 and CH2 can communicate at the same
time, given any of the following conditions are true.
Condition 1 : The sticker on the top of the communication unit indicates
the version is AB or later.
Condition 2 : The date shown on the side of the communication unit indicates it was produced in September 1996 (9609) or later.
Condition 3 : The communication unit's ROM version is 7179M or later.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

53

Mitsubishi Electric Corporation PLC

MELSEC-QnA (CPU Direct Connection)


GP Setup

PLC Settings

Baud Rate

19200 bps

---

Data Length

8 bits

---

Stop Bit

1 bit

---

Parity Bit

Odd

---

Data Flow Control

ER Control

---

*1

Communication Format
(RS-232C)
Communication Format (RS422)

RS-232C

Unit No.

0 (fixed)

4-wire type

-------

*1 Only when using Digital's Programming Console I/F cable (GP430-IP10-O)


for the MELSEC-A Series unit or a Diatrend Co. DAFXIH-CABV cable.
Otherwise, a 4-wire type cable is required.

MELSEC-Q Series (A Mode CPU Direct Connection)


GP Setup
Baud Rate

9600bps (fixed)

Data Length

8bit (fixed)

Stop Bit

1bit (fixed)

Parity Bit

Odd (fixed)

Data Flow Control

ER Control

Communication Format

RS-232C

Unit No.

0 (fixed)

PLC Settings

MELSEC-Q Series (Q Mode CPU Direct Connection)


GP Setup
Baud Rate

19200 bps

Data Length

8bit (fixed)

Stop Bit

1bit (fixed)

Parity Bit

Odd (fixed)

Data Flow Control

ER Control (fixed)

Communication Format

RS-232C (fixed)

Unit No.

0 (fixed)

PLC Settings

Range of data transfer speeds is from 9600bps to 15,200bps. However,


the maximum speed available with GP70 Series units (except for GP-377
Series units) is 38,400bps.

54

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric Corporation PLC

MELSEC-Q Series (using A Mode CPU Computer Link Unit)


GP Setup

Computer Link Unit Settings

Baud Rate

19200bps (fixed)

Baud Rate

19200 bps

Data Length

7bits (fixed)

Data Bit

7 bits

Stop Bit

2bits (fixed)

Stop Bit

2 bits

Parity Bit

Even

Parity Check
Parity setting even/odd

Yes
Even

Data Flow Control

ER Control

Communication Format (RSRS-232C


232C)
Communication Format (RS4-wire type
422)

--Mode Setup (RS-232C)


Mode Setup (RS-422)

4 (Format 4 Protocol Mode)


4 (Format 4 Protocol
Mode)

Write possible in RUN mode Possible

Unit No.

0 (fixed)

Sum Check

Yes

Station Number

MELSEC-Q Series (Q Mode CPU Serial Communication Unit)


Serial Communication Unit Settings *1

GP Setup
Baud Rate

19200bps

Baud Rate

19200 bps

Data Length

7 bits

Data Bit

7 bits

Stop Bit

2 bits

Stop Bit

2 bits

Parity Bit

Even

Parity Check
Parity setting even/odd

Yes
Even

Data Flow Control

ER Control

Communication Format (RSRS-232C


232C)
Communication Format (RS4-wire type
422)
Unit No.

--Mode Setup (RS-232C)


Mode Setup (RS-422)

4 (Format 4 Protocol
Mode)
4 (Format 4 Protocol
Mode)

Sum Check

Yes

Station Number

*1 The setting is made by Mitsubishi's GPP function software.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

55

Mitsubishi Electric Corporation PLC

2.1.5

2-Port Feature

The 2-Port feature can be used in two ways:


(1)Via the GPs built-in 2-Port feature
(2)Via the external 2-Port Adapter II.
Both methods are described below:

When Using GP unit's Internal 2-Port feature

*1

GP
Connected to the Serial I/F
via the Programmer I/F Cable

Connect to the tool connector via Data


Transfer Cable (GPW-CB02)

Connect to Programmer Port


PC with Mitsubishis GPP software installed
Mitsubishi PLC

*1 The Device Monitor feature can also be used at the same time.
For the ST series units, however, the Device Monitor feature cannot be
used.

PLC models supporting Internal 2-Port Feature


Series

CPU

MELSEC-AnA Series

A2A, A2U-S1, A2USH-S1, A3A, A2US

MELSEC-AnN Series

A1S, A1SH, A2N, A3H, A2SH, A3N, A0J2H

MELSEC-QnA Series

Q2A, Q2A-S1, Q2AS-S1, Q2ASH, Q4A

MELSEC-FX Series *1

FX0S, FX0N, FX1S, FX1N, FX2N, FX1NC, FX2NC, FX3UC

MELSEC-Q Series

Q02CPU-A,Q02HCPU-A,Q06HCPU-A,
Q02CPU,Q02HCPU,Q06HCPU,
Q12HCPU,Q25HCPU

*1 MELSEC-FX Series' FX2 cannot use the internal 2-Port feature.

56

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric Corporation PLC

GP models supporting the Internal 2-Port Feature


Series
GP-377 Series
GP77 Series

GP-37W2 Series
GP-377R Series
GP-477R Series
GP-577R Series

GP77R Series

GP2000H
Series

GP-2301H Series
GP-2401H Series
GP-2300 Series
GP-2301 Series

GP2000 Series

GLC2000 Series

ST Series

GP-2400 Series
GP-2401 Series
GP-2500 Series
GP-2501 Series
GP-2600 Series
GP-2601 Series
GLC2300 Series
GLC2400 Series
GLC2500 Series
GLC2600 Series
ST400 Series

GP Type
GP-377L
GP-377S
GP-37W2B
GP-377RT
GP-477RE
GP-577RT
GP-577RS
GP-2301HL
GP-2301HS
GP-2401HT
GP-2300L
GP-2300T
GP-2301L
GP-2301S
GP-2301T
GP-2400T
GP-2401T
GP-2500T
GP-2501S
GP-2501T
GP-2600T
GP-2601T
GLC2300L
GLC2300T
GLC2400T
GLC2500T
GLC2600T
ST400
ST401

GP-PRO/PBIII for Windows Device/PLC Connection Manual

57

Mitsubishi Electric Corporation PLC

GPP Feature Software Package


MELSEC-A Series

MELSEC-QnA Series

MELSEC-FX Series

MELSEC-Q Series

DOS3.1.1 Series
SW31VD-GPPA type GPP feature software package or later
Windows95, Windows NT
SW0D5*-GPPW type GPP feature software package or later
DOS 3.1.1 Series
SW01VD-GPPQ type GPP feature software package
Windows95, Windows NT
SW0D5*-GPPW type GPP feature software package or later
Windows 95
SW0PC-FXGP/WIN type GPP feature software package
Windows 95, Windows NT
SW4D5C-GPPW type GPP feature software package or later
Windows 95, Windows NT
SW4D5C-GPPW type GPP feature software package or later

Internal 2-Port Feature Usage Notes


The selections USE ADAPTER MODE/CPU DIRECT MODE will be displayed only when a direct CPU connection is used.
The factory setting will become Adapter(when using 2-Port Adapter II).
This feature can be used only while the GP is in ONLINE mode.
Use Digital's transfer cable GPW-CB02.

58

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric Corporation PLC

If you transfer screen data while the GP is in ONLINE mode, the


screen will not change to the data transfer screen automatically.
Thus, you will need to change the screen manually to the
OFFLINE mode's [Main Menu/ Transfer] screen. When sending
screen data, be sure to pause or quit any GPP feature ladder
monitoring or device monitoring.
Since the internal 2-Port feature uses the GPs single tool connector, you will not be able to use optional equipment which requires the tool connector (i.e. a Barcode Reader, etc.)
Peripheral equipment which cannot be connected to the GP's tool
connector (such as a Programming Console) is not compatible
with the GP's Internal 2-Port feature. To use this type of equipment, you will need to use the external 2- Port Adapter II.
When using the GPs built-in 2-Port feature, be sure not to switch
to OFFLINE mode while the GPP software is communicating with
the PLC. Switching to OFFLINE mode will result in a communication (data transfer) break
With GP2000, GP77R and ST series units, if the 2-Port feature is
designated, the Simulation feature cannot be used. Be sure to
select Adapter or Direct when using the Simulation feature.
When using the GPs built-in 2-Port feature with the MELSEC-Q
Series, be sure to set your PC's data link speed to the same values as used by the GP. If the setting values are different, an error
will appear on the GP and your PC. The error will appear as shown
below.
<GP>
"PC's data link speed is different. (02:F5)"
<PC>
"Cannot communicate with the PC."
<e.g : GP-377 series unit's screen>

c Touch item, PLC SETTING. The


S E T U P O P E R AT I O N
SURROUNDINGS menu will
appear.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

59

Mitsubishi Electric Corporation PLC

d Touch the button, SET on the


upper right on the screen.
The SET UP OPERATION
SURROUNDINGS 2 menu
appears.

e Touch the 2-Port Feature/CPU


Direct selections right side setting box until INSIDE appears.
When using the 2-Port Adapter
II unit, select Adapter, or
CPU for a direct CPU connection. When using the 2-Port
Adapter with GP2000H or ST
Series units (Excluding
Mitsubishi's MELSEC-FX
(CPU2) Protocol), select
"Adapter + GPH".

When Using the External 2-Port Adapter Cable

*1

GP

Connected to GPs Serial I/F


Digital's 2-Port Adapter II (GP070-MD11)

Connect to Programmer Port

or
Mitsubishi PLC
(compatible
types only)

PC with Mitsubishis GPP software installed,


or a Programming Console

*1 2-Port Adapter can be used for the GP series units supporting the internal 2-Port
feature .

PLCs supported by the 2-Port Adapter II


For information about which CPUs the 2-Port Adapter II (GP070-MD11)
can connect to, refer to the 2-Port Adapter II Users Manual.

60

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric Corporation PLC

When Using the 2-Port Adapter II


Set up from the GP's OFFLINE mode when using 2-Port Adapter II.
GP User Manual (Sold separately) , "OFFLINE Mode"
GP70 Series (except GP-377 series)
The selections USE ADAPTER MODE/CPU DIRECT MODE will be displayed only when a direct CPU connection is used.
The factory setting will become 2 Port.

<e.g : GP-570 series unit's screen>

c Touch item #1, INITIALIZE. The


INITIALIZE menu will appear.

d Touch item #3, PLC


SETTING. The PLC
SETTING menu appears.

e Touch item #1, SET UP OPERATION SURROUNDINGS. The SET UP


O P E R AT I O N S U R ROUNDINGS menu will
appear.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

61

Mitsubishi Electric Corporation PLC

f Touch the USE


ADAPTER MODE/CPU
DIRECT MODE selection. The selected item is
highlighted.

GP70 Series Units

g When using the 2 port adapter II (GP070-MD11), select the 2PORT option. For GPH70
however, select 2PORT + GPH.
Select CPU when connecting CPU directly.

62

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric Corporation PLC

GP-377/GP77R/GP2000/ST Series
The selections 2 Port Mode/CPU DIRECT MODE will be displayed only when
a direct CPU connection is used.
The factory setting will become Adapter.

<e.g : GP-577R series unit's screen>

c Touch item #1, INITIALIZE. The


INITIALIZE menu will appear.

d Touch item #3, PLC


SETTING. The PLC
SETTING menu appears.

e Touch item #1, SET UP OPERATION SURROUNDINGS. The SET UP


O P E R AT I O N S U R ROUNDINGS menu will
appear.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

63

Mitsubishi Electric Corporation PLC

f Touch the USE


ADAPTER MODE/CPU
DIRECT MODE selection. The selected item is
highlighted.

ADAPTER + GPH

CPU

INSIDE

GP77R Series Units

g When using the 2 Port Adapter II (GP070-MD11), select the ADAPTER option.
When using GP2000H or ST Series units with the 2-Port Adapter (Excluding Mitsubishi's
MELSEC-FX (CPU2) Protocol), select "Adapter + GPH".
Select CPU when connecting CPU directly.
When using the internal 2-Port feature, select INSIDE option.

64

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric - Multi-Link

5.1

Mitsubishi Electric

5.1.1

System Structure

The following describes the system structure for connecting the GP to Mitsubishi
Electric PLCs.
Reference

The Cable Diagrams mentioned in the following tables are


listed in the section titled "5.1.2 Cable Diagrams".

MELSEC-A Series (using Link I/F)


CPU

Link I/F

Cable Diagram

GP

Computer Link
Unit

A2A

AJ71C24-S6

A3A

AJ71C24-S8

A4U

AJ71UC24

A2US

A1SJ71C24-R4

A2USH-S1

A1SJ71UC24-R4
A1SJ71UC24-R4

(Cable Diagram 1)
GP Series

MELSEC-N Series (Link I/F)


CPU

Link I/F

Cable Diagram

GP

(Cable Diagram 1)

GP Series

Computer
Link Unit

A1N
A2N
A3N

A0J2,A0J2H
A1S
A1SJ,A2SH,A1SH
A2CCPU24

AJ71C24
AJ71C24-S3
AJ71C24-S6
AJ71C24-S8
AJ71UC24
A0J2-C214-S1
A1SJ71C24-R4
A1SJ71UC24-R4
Link I/F on CPU unit

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric - Multi-Link

MELSEC-FX Series ( Expansion Board with Link I/F protocol) *1


CPU

Adapter

Cable Diagram

Target Machine

RS-422
<Cable Diagram 2>

GP/GLC/ST Series

Expansion
board

FX2N
FX3UC

*2

FX2N-485-BD
FX3U-485-BD

ST400

*1 Choose Mitsubishi's MELSEC-FX2(Link) as the GP-PRO/PBIII project files PLC


type.
*2 The PLCs system version should be at least 1.06 or later. Check the PLCs
version by reading out the data from the register (D8001). For detailed information refer to the Mitsubishis FX 2N Series Micro Sequencer manuals.

MELSEC-QnA Series (using Link I/F)


CPU

Link I/F

Cable Diagram

GP

Serial
Communicaiton
Unit / Computer
Link Unit
Q2A,Q2A-S1,Q4A

AJ71QC24 (serial
communication unit)

RS-422
(Cable Diagram 1)

AJ71UC24 (computer link unit)


AJ71QC24N-R4
RS-422
(Cable Diagram 1) for CN-1
A1SJ71QC24N(serial
RS-422
*2
(Cable Diagram 1)
communication unit)

Q2AS

Q2AS-S1

Q4AR

*1

A1SJ71UC24(computer link
unit)
A1SJ71QC24N
A1SJ71UC24-R4

AJ71QC24N

GP Series

RS-422
(Cable Diagram 1)
RS-422
(Cable Diagram1)

*1 ROM : must be higher than 7179B.


*2 ROM : must be higher than 7179M.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric - Multi-Link

MELSEC-Q Series
CPU

Q02CPU-A
Q02HCPU-A
Q06HCPU-A
Q02CPU
Q02HCPU
Q06HCPU
Q12HCPU
Q25HCPU
Q00CPU
Q01CPU

Link I/F
Serial
Communication
Unit / Computer
Link Unit

Cable Diagram

A1SJ71UC24-R4

RS-422
(Cable Diagram 1)

QJ71C24

RS-422
(Cable Diagram 1)

GP

GP Series

C00JCPU

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric - Multi-Link

5.1.2

Cable Diagrams

The cable doagrams illustrated below and the cable diagrams recommended by
Mitsubishi Electric Corp. may differ, however, using these cables for your PLC
operations will not cause any problems.
Cable Diagram 1
When using Digital's RS-422 connector terminal adapter GP070-CN10-O
Adapter

Adapter

PLC

Termination
Resistance
1/4W 330

RDA

RDA

SDA

RDB

RDB

SDB

Termination
Resistance
1/4W 330

SDA

SDA

RDA

SDB

SDB

RDB

SG

SG

SG

FG

FG

FG

Shield

Shield

When using Digital's Multi-link Cable, GP230-IS12-O


Terminal
(M3 screw)

Terminal
(M3 screw)
Termination
Resistance
1/4W 330
Termination
Resistance
1/4W 330

RDA

RDA

SDA

RDB

RDB

SDB

SDA

SDA

RDA

SDB

SDB

RDB

SG

SG

SG

FG

FG
Shield
Digital's Multilink Cable
GP230-IS12-O

PLC

FG
Shield
Digital's Multilink Cable
GP230-IS12-O

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric - Multi-Link

STOP

!
Important

Note:

Ground your PLC's FG terminal according to your country's applicable standard. For details, refer to the corresponding PLC manual.
Pull out the Transfer Cable Shield cover and shape it into a wire
and connect it to the PLC's FG terminal.
GP230-IS12-O Cable FG terminal is not connected to GP's FG.
If the PLC is equipped with a Termination Resistor switch, turn it ON.
If the PLC has no switch, then set up the appropriate termination
resistance on the PLC.
Fot the RS-422 connection, use a cable length less than 500m.
As a general rule, connect the PLC at either end of the circuit, not
in the middle.

When making your own cable, Mitsubishi's SPEV (SB)-MPC-0.2*3P cable is


recommended as the connection cable.
The cable connection lines are as illustrated below and should be less than
10m.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric - Multi-Link


Cable Diagram 2
Pull out a small amount of the Transfer Cables shield, make a
wire out of it and connect it to the PLCs FG terminal.
The GP230-IS12-0 cables FG terminal is not connected to the
GPs FG line.
Connect a terminating resistor to both ends of the cable.
When using the FX3UC, the unit's termination resistance is built
in to the FX3U-485-BD expansion board. When using a 4-wire
system, be sure to change the unit's dip switch to 330.
When using FX2N-485-BD or FX3U-485-BD, be sure the cable is
less than 50 meters.
As a general rule, connect the PLC at the end of the circuits
wiring (see below).

When making your own cable, the Mitsubishi SPEV (SB)-MPC-0.2x3P is


recommended.
The cable connection lines are as shown below. The cables used between
the GP and the terminals should be less than 10meters long.

GP/GLC Series Units


When using Digital's RS-422 connector terminal adapter GP070-CN10-O
Adapter

Adapter

Shield

PLC

RDA

RDA

SDA

RDB

RDB

SDB

SDA

SDA

RDA

SDB

SDB

RDB

SG

SG

SG

FG

FG

Termination
Resistance
330

Shield

Grounding

Termination
Resistance
330
Termination
Resistance
330

Grounding

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric - Multi-Link


When using Digital's GP230-IS12-0 (Multi Link Cable)
Terminal Block
(M3 screw)

Shield

Terminal Block
(M3 screw)

Shield

PLC

RDA

RDA

SDA

RDB

RDB

SDB

SDA

SDA

RDA

SDB

SDB

RDB

SG

SG

SG

FG

FG

FG

Termination
Resistance
330

STOP

Digital's
Multi-link
Cable
GP230-IS12-O

Termination
Resistance
330
Termination
Resistance
330

Digital's
Grounding
Multi-link
Cable
GP230-IS12-O

Ground your PLCs FG terminal according to your countrys applicable standard. For details refer to your PLCs manual.
Shield
GP
(25P
male)

10 RDA

SDA

16 RDB

SDB

11 SDA

RDA

15 SDB

RDB

SG

SG

Terminal
Block
(9P)

18 CSB
19 ERB
21 CSA

Grounding

22 ERA

10 meters or less

ST400 Unit
ST Unit
(9P)
Connector Shell

Shield

1 RDA
2 RDB
3 SDA
7 SDB
5 SG
6 CSB
9 ERB
8 CSA
4 ERA

Terminal Block
SDA
SDB
RDA
RDB
SG

10m or less

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric - Multi-Link

5.1.3

Supported Devices

The following describes the range of devices supported by the GP.

MELSEC-A Series (AnA/ AnU/ A2US/ A2USH-S1)


Setup System Area or Communication Information's Storing Address
here.
Device

Bit Address

Word Address

Input Relay

X0000 ~ X1FFF

X0000 ~ X1FF0

Output Relay

Y0000 ~ Y1FFF

Y0000 ~ Y1FF0

Internal Relay

M0000 ~ M8191

M0000 ~ M8176

L0000 ~ L8191

L0000 ~ L8176

Special Relay

M9000 ~ M9255

M9000 ~ M9240

Annuniciator

F0000 ~ F2047

F0000 ~ F2032

Link Relay

B0000 ~ B1FFF

---

Timer (contact)

TS0000 ~ TS2047

---

Timer (coil)

TC0000 ~ TC2047

---

Counter (contact)

CS0000 ~ CS1023

---

Counter (coil)

CC0000 ~ CC1023

---

Timer (current value)

---

TN0000 ~ TN2047

Counter (current value)

---

CN0000 ~ CN1023

Data Register

---

D0000 ~ D8191

Special Register

---

D9000 ~ D9255

Link Register

---

W0000 ~ W1FFF

File Register

---

R0000 ~ R8191

Latch Relay

Particulars

L/H

*1

* 1 When using the File Register and the AnA or AnU, use the User's memory
area in the memory cassettes.
When the File Register is setup when the memory cassette is not in use, an
error will develop when communicating.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric - Multi-Link

MELSEC-N Series (AnN/ A2C/ A1S/ A1SJ/A2SH )


Setup System Area or Communication Information's Storing Address
here.
Device

Bit Address

Word Address

Input Relay

X0000 ~ X07FF

X0000 ~ X07F0

Output Relay

Y0000 ~ Y07FF

Y0000 ~ Y07F0

Internal Relay

M0000 ~ M2047

M0000 ~ M2032

Latch Relay

L0000 ~ L2047

---

Special Relay

M9000 ~ M9255

M9000 ~ M9240

Annuniciator

F0000 ~ F255

F000 ~ F240

Link Relay

B0000 ~ B03FF

---

Timer (contact)

TS000 ~ TS255

---

Timer (coil)

TC000 ~ TC255

---

Counter (contact)

CS000 ~ CS255

---

Counter (coil)

CC000 ~ CC255

---

Timer (current v alue)

---

TN000 ~ TN255

Counter (current v alue)

---

CN000 ~ CN255

Data Register

---

D0000 ~ D1023

Link Register

---

W0000 ~ W03FF

File Register

---

R0000 ~ R8191

Particulars

*1

*2

L/H

*3

* 1 The Output Relays Y01F0-Y01FF (word Y01F0) are used by the PLC, and
cannot be set.. (only for A2C)
* 2 A MELSEC-AnN and AJ71C24-S3 (or AJ71C24) cannot be matched and used.
* 3 When using the File Register and the AnN, use the User's memory area in the
memory cassettes.
When the File Register is setup when the memory cassette is not in use, an
error will develop when communicating.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric - Multi-Link

MELSEC-FX Series (using Expansion Board with


Mitsubishi's MELSEC-FX2 (LINK) Protocol)
Setup System Area here.
Device

Bit Address

Word Address

Input Relay

X0000 - X0377

X0000 - X0360

Output Relay

Y0000 - Y0377

Y0000 - Y0360

Auxilary Relay

M0000 - M7679

M0000 - M7664

State

S0000 - S4095

S0000 - S4080

Special Auxilary relay

M8000 - M8511

M8000 - M8496

Timer (contact)

TS000 - TS511

Counter (contact)

CS000 - CS255

Remarks

*1
L/H

Timer (current)

TN000 - TN511

Counter (current)

CN000 - CN255

*2

Data Register

D0000 - D7999

*3

Special Data Register

D8000 - D8511

*1 *3

Extended Register

R00000 - R32767

*4

*1 The Special Auxilary Relay and the Special Data Register are divided into three areas. These are the Exclusive Reading Area, the Exclusive Writing Area and the System
Area. For details, refer to your PLCs manual.
*2 Word addresses CN200 to CN255 are 32 bit counters.
*3 When designating data register addresses, be sure that they do not overlap with the
special register area.
For example, do not perform a write of two or more words, starting from "D7999".
When a write of two or more words is done starting from "D7999", a "Host Communication" error (02:FA) occurs.
*4 With only FX3UC units.
*5 Address ranges will vary depending on the CPU model used.

10

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric - Multi-Link

MELSEC-QnA Series
Setup System Area or Communication Information's Storing Address
here.
Device

Bit Address

Word Address

Particulars

Input Relay

X0000 ~ X1FFF

X0000 ~ X1FF0

Output Relay

Y0000 ~ Y1FFF

Y0000 ~ Y1FF0

Internal Relay

M00000 ~ M32767

M00000 ~ M32752

Special Relay

SM0000 ~ SM2047

SM0000 ~ SM2032

Latch Relay

L00000 ~ L32767

L00000 ~ L32752

Annunciator

F00000 ~ F32767

F00000 ~ F32752

Edge Relay

V00000 ~ V32767

V00000 ~ V32752

Step Relay

S0000 ~ S8191

S0000 ~ S8176

Link Relay

B0000 ~ B7FFF

B0000 ~ B7FF0

Special Relay

SB000 ~ SB7FF

SB000 ~ SB7F0

Timer (contact)

TS00000 ~ TS22527

--------

Timer (coil)

TC00000 ~ TC22527

--------

Aggregation Timer (contact)

SS00000 ~ SS22527

--------

Aggregation Timer (coil)

SC00000 ~ SC22527

--------

Counter (contact)

CS00000 ~ CS22527

--------

Counter (coil)

CC00000 ~ CC22527

--------

Timer (current value)

--------

TN00000 ~ TN22527

Aggregation Timer
(current value)

--------

SN00000 ~ SN22527

Counter (current value)

--------

CN00000 ~ CN22527

Data Register

--------

D00000 ~ D25599

Special Register

--------

SD0000 ~ SD2047

Link Register

--------

W0000 ~ W63FF

Special Link Register

--------

SW000 ~ SW7FF

File Register (nomal)

--------

R00000 ~ R32767

*1

File Register (serial)

--------

0R0000 ~ 0R7FFF
1R0000 ~ 1R7FFF

*1

L/H

* 1 When using the File Register, a Memory Card is necessary. Depending on the
Memory Card being used, the File Register's device range differs.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

11

Mitsubishi Electric - Multi-Link

MELSEC-Q Series (A Mode CPU)


Setup System Area or Communication Information's Storing Address
here.
Device

Bit Address

Word Address

Input Relay

X0000 ~ X1FFF

X0000 ~ X1FF0

Output Relay

Y0000 ~ Y1FFF

Y0000 ~ Y1FF0

Internal Relay

M 0000 ~ M 8191

M 0000 ~ M 8176

L0000 ~ L8191

L0000 ~ L8176

Special Relay

M 9000 ~ M 9255

M 9000 ~ M 9240

Annunciator

F0000 ~ F2047

F0000 ~ F2032

Link Relay

B0000 ~ B1FFF

Latch Relay

Tim er (Contact)

TS0000 ~ TS2047

Tim er (Coil)

TC0000 ~ TC2047

Counter (Contact)

CS0000 ~ CS1023

Counter (Coil)

CC0000 ~ CC1023

Particulars

L/H

Tim er (Current Value)

TN0000 ~ TN2047

Counter (Current Value)

CN0000 ~ CN1023

Data Register

D0000 ~ D8191

Spcial Register

D9000 ~ D9255

Link Register

W0000 ~ W1FFF

File Register

R0000 ~ R8191

*1

* 1 The amount of space available when using the File Register will vary, depending on the amount of CPU ROM/RAM available, or the amount of memory
available on the memory card.

12

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric - Multi-Link

MELSEC-Q Series (Q Mode CPU)


Setup System Area or Communication Information's Storing Address here.
Device

Bit Address

Word Address

Input Relay

X0000 ~ X1FFF

X0000 ~ X1FF0

Output Relay

Y0000 ~ Y1FFF

Y0000 ~ Y1FF0

Internal Relay

M00000 ~ M32767

M00000 ~ M32752

Special Relay

SM0000 ~ SM2047

SM0000 ~ SM2032

Latch Relay

L00000 ~ L32767

L00000 ~ L32752

Annunciator

F00000 ~ F32767

F00000 ~ F32752

Edge Relay

V00000 ~ V32767

V00000 ~ V32752

Step Relay

S0000 ~ S8191

S0000 ~ S8176

Link Relay

B0000 ~ B7FFF

B0000 ~ B7FF0

Special Relay

SB000 ~ SB7FF

SB000 ~ SB7F0

Timer (contact)

TS00000 ~ TS23087

--------

Timer (coil)

TC00000 ~ TC23087

--------

Aggregation Timer (contact)

SS00000 ~ SS23087

--------

Aggregation Timer (coil)

SC00000 ~ SC23087

--------

Counter (contact)

CS00000 ~ CS23087

--------

Counter (coil)

CC00000 ~ CC23087

--------

Timer (current value)


Aggregation Timer
(current value)
Counter (current value)

--------

TN00000 ~ TN23087

--------

SN00000 ~ SN23087

--------

CN00000 ~ CN23087

Data Register

--------

D00000 ~ D25983

Special Register

--------

SD0000 ~ SD2047

Link Register

--------

W0000 ~ W657F

Special Link Register

--------

SW000 ~ SW7FF

File Register (nomal)

--------

R00000 ~ R32767

*1

--------

0R0000 ~ 0R7FFF

*1

--------

1R0000 ~ 1R7FFF

*1

--------

31R0000 ~ 31R67FF

File Register (serial)

Particulars

L/H

:
*1

* 1 The amount of space available when using the File Register will vary, depending on the amount of CPU ROM/RAM available, or the amount of memory
available on the memory card.

Note:

The device ranges given here are based on the maximum values possible
for parameter settings. Depending on your CPU, usable device types and
range may differ. Before using, refer to your CPU user manual.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

13

Mitsubishi Electric - Multi-Link

5.1.4

Environment Setup

The following lists Digital's recommended PLC and GP communication settings.

MELSEC-A Series (When using Computer Link I/F)


GP Setup

PLC ( Data Register) Setup

Baud Rate

19200 bps

Baud Rate

19200

Data Length

7 bit

Data Length

7 bit

Stop Bit

2 bit

Stop Bit

2 bit

Parity Bit

Even

Parity Check

Yes

Parity setting even/odd

Even

Data Flow Control

ER Control

Communicaiton Format

4-wire type

--------Channel setup

RS-422

Mode Setup

8 ( Format 4 protocol)

---------

Write during RUN

Yes

---------

Sumcheck

Yes

---------

Transmission area terminal resistance Present

---------

Receiving area terminal resistance

Present

Station No.

Unit No.

MELSEC-FX Series (FX2N)


GP Setup

PLC ( Data Register) Setup

Baud Rate

19200 bps

Baud Rate

19200

Data Length

Data Length

Stop Bit

Stop Bit

Parity Bit

Even

Parity Bit

Even

Data Flow Control

ER Control

Communication Format

4-wire type

H/W Type

RS485(RS422) I/F

Station No.

Station No.

---------

Use Comm. Settings

Yes

---------

Sumcheck

Yes

---------

Protocol

Yes

---------

Mode

Format 4 protocol

---------

Header

No

---------

Terminator

No

---------

PLC's Station NO. data must be written in data register D8121 and other
settings must be written in data register D8120. For details refer to
Mitsubishi's "FX Communication Users Manual".

14

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric - Multi-Link

MELSEC-FX Series (FX3UC)


GP Settings

PLC ( Data Register) Settings

Baud Rate

19200 bps

Baud Rate

19200

Data Length

Data Length

Stop Bit

Stop Bit

Parity Bit

Even

Parity Bit

Even

Data Flow Control

ER Control

Communication Format

4-wire type

Computer Link

Station No.

Station No.

ER Control

*2

RS485(RS422) I/F

*1

00h

CH

CH1

Protocol

Yes

Mode

Format 4 protocol

Sumcheck

Added

Comm. Settings

Use checking

Header

No

Terminator

No

*1 The termination resistance will vary depending on if a 4-wire or a 2-wire connection is


used. Termination resistance is built into the FX3U-485-BD expansion board.
When using a 4-wire line, use the dip switch to change the setting to 300.
*2 Even though PLC station numbers are set using 00h to 0Fh, the GP Series
units use only 0 to 15.
It is possible to enter PLC settings via the ladder software's PC system
settings or to write data directly to data registers D8120 and D8121. For
details, refer to Mitsubishi's "FX Communication User Manual".

GP-PRO/PBIII for Windows Device/PLC Connection Manual

15

Mitsubishi Electric - Multi-Link

MELSEC-QnA Series
GP Setup
Baud Rate

19200 bps

Data Length
Stop Bit

PLC ( Data Register) Setup


*1

Baud Rate

19200

7 bit

Data Length

7 bit

2 bit

Stop Bit

2 bit

Parity Bit

Even

Parity Check
Parity setting even/odd

Yes
Even

Data Flow Control

ER Control

Communicaiton Format

4-wire type
-------------------------

Unit No.

Note:

--------Mode Setup

4 ( Format 4 protocol)

Sumcheck

Yes

Transmission area terminal


resistance
Receiving area terminal
resistance
Station No.

Present
Present
0

*1 AJ71QC24N-R4, A1SJ71QC24N, AJ71QC24N can use a baud rate of


115.2kbps.
CH1 and CH2 of a serial communication unit can communicate at the
same time, given any of the following conditions.
Refer to the MELSEC A Series table when using environment with
MELSEC QnA and Computer Link I/F AJ71UC24 together.
Condition 1 : The sticker on the top of the communication unit
indicates the version is AB or later.
Condition 2 : The date shown on the side of the communication
unit indicates it was produced in September
1996 (9609) or later.
Condition 3 : The communication ROM version is 7179M or
later.

MELSEC-Q Series (using A Mode CPU Computer Link Unit)


GP Setup
Baud Rate

19200 bps (fixed)

Baud Rate

19200 bps

Data Length

7 bits (fixed)

Data Length

7 bits

Stop Bit

2 bits (fixed)

Stop Bit

2 bits

Parity Bit

Even

Parity Check
Parity setting even/odd

Yes
Even

Data Flow Control

ER Control

Communicaiton Format
(RS-422)

4-wire type

Unit No.

16

Computer Link Unit Settings

--------Mode Setup (RS-422)

8 ( Format 4 Protocol Mode)

---------

Write possible in RUN mode Possible

---------

Sumcheck

Yes

Station No.

0 (fixed)

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric - Multi-Link

MELSEC-Q Series (Q Mode CPU Serial Communication Unit)


GP Setup

Serial Communication Unit Settings *1

Baud Rate

19200 bps

Baud Rate

19200 bps

Data Length

7 bits

Data Length

7 bits

Stop Bit

2 bits

Stop Bit

2 bits

Parity Bit

Even

Parity Check
Parity setting even/odd

Yes
Even

Data Flow Control

ER Control

Communicaiton Format
(RS-422)

4-wire type
---------

Unit No.

--------Mode Setup (RS-422)

4 ( Format 4 Protocol Mode)

Sumcheck

Yes

Station No.

*1 The setting is made by Mitsubishi's GPP function software.

GP-PRO/PBIII for Windows Device/PLC Connection Manual

17

Mitsubishi Electric Corporation Appendix

Mitsubishi Electric
A.1

Maximum Number of Consecutive Device Address


The following lists the maximum number of consecutive addresses that can
be read by each PLC. Refer to these tables to utilize Block Transfer.
When the device is setup using the methods below, the Data Communication
Speed declines by the number of times the device is read.
When consecutive addresses exceed the maximum data number range
When an address is designated for division
When device types are different
To speed up data communication, plan the tag layout in screen units, as
consecutive devices. (Includes the Alarm and Trend screens.)

PLC
<MELSEC-A Series>
Device

Max. No. of Consecutive


Address

Device

Input Relay X

Data Register D

Output Relay Y

Link Register W

Internal Relay M

File Register R

Latch Relay L

Extended File
Register R

Latch Relay B
Timer (contact) TS

32 Words

Max. No. of Consecutive


Address

64 Words

Timer (current value) TN


Counter (current value)
CN

Timer (coil) TC
Counter (contact) CS
Counter (coil) CC

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Appendix-1

Mitsubishi Electric Corporation Appendix

<MELSEC-FX Series>
Mitsubishi MELSEC-FX (CPU)
Mitsubishi MELSEC-FX (CPU2)
Max. No. of
Consecutive
Addresses

Device
Input Relay (X)
Output Relay (Y)
Auxiliary Relay (M)
State (S)
Special Auxiliary Relay (M8)
Timer (contact) (TS)

32 Words

*1

Counter (contact) (CC)


Timer (current value) (TN)
Counter (current value) (CN)
Data Register (D)
Special Data Register (D8)
Extended Register (R)

127 Words

*2

*1 When using an FX3UC, the maximum number of words is 127.


*2 Only available with FX3UC units.

<MELSEC-FX Series>
Mitsubishi MELSEC-FX2 (LINK)

<MELSEC-F2 Series>

Mitsubishi MELSEC-FX 1:n Communication


Device

Max. No. of
Consecutive
Addresses

Device

Input Relay

Input Relay

Output Relay

Output Relay
Timer (contact)

Auxiliary Relay
State

32 Words

Keep Relay

Timer (contact)

State

Counter (contact)

Counter (current value)

Extended Register

Appendix-2

8 Words

Data Register W

Timer (current value)

Special Data Register

Counter (contact)
Auxiliary Relay

Special Auxiliary Relay

Data Register

Max. No. of
Consecutive
Addresses

64 Words

Timer
(current value) TC
Timer (setup value)
TS
Counter
(current value) CC
Counter (setup value)
CS

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric Corporation Appendix

<MELSEC-QnA Series>
Device

Max. No. of Consecutive


Address

Max. No. of Consecutive


Address

Aggregate Timer
(contact) SS

Input Relay X

Aggregate Timer
(coil) SC
Counter (contact)
CS

Output Relay Y
Internal Relay M
Special Relay SM

Counter (coil) CC

Latch Relay L
Annunciator F

Device

280 Words

Edge Relay V

Timer (current
value) TN
Monostable Timer
(current value) SW
Counter (current

280 Words

value) CN

Step Relay S

Data Regsiter D

Link Relay B

Special Register
SD

Special Link Relay


SB

Link Register W

Timer (contact) TS

Special Link
Register SW

Timer (contact) TC

File Register R

* For direct CPU connections, use 480 words for all devices.

<MELSEC-Q Series (CPU Direct Connection)>


Device

Max. No. of Consecutive


Address

Device

Input Relay

Special Link Relay

Output Relay

Timer (current value)


Aggregate Timer

Internal Relay

(current value)

Special Relay
Latch Relay
Annunciator

Max. No. of Consecutive


Address

Counter (current value)

Total of 960 Words

Data Register
Special Data Register

Edge Relay

Link Data Register

Step Relay

Special Link Register

Link Relay

File Register (normal)

Total of 960 Words

File Register (serial)


0R-31R

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Appendix-3

Mitsubishi Electric Corporation Appendix


Ethernet Connection
<MELSEC-A Series>
Device

Max. No. of
Consecutive
Address

Input Relay
Output Relay
Latch Relay
Special Relay
Annunciator
Link Relay

128 Words

Timer (contact)
Timer (coil)
Counter (contact)
Counter (coil)
Timer (current value)
Counter (current value)
Data Register
Special Register
Link Register
File Register

Appendix-4

258 Words

<MELSEC-Q/QnA Series>
Device

Max. No. of
Consecutive
Address

Input Relay
Output Relay
Internal Relay
Special Relay
Latch Relay
Annunciator
Edge Relay
Step Relay
Link Realy
Special Link Relay
Timer
(Current Value)
Aggregate Timer
(Current Value)
Counter (Current Value)
Data Register
Special Register
Link Register
Special Link Register
File Register
(Normal)
File Register
(Serial) 0R ~ 31R

480 Words

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric Corporation Appendix


CC-Link Intelligent Device Station
<MELSEC-A/QnA/Q Series>
Device

Max. No. of
Consecutive
Address

Iput Relay
Output Relay
Internal Relay
Special Relay
Latch Relay
Special Link Relay
Timer (contact)
Timer (coil)
Aggregate Timer (contact)
Aggregate Timer (coil)
Counter (contact)

480 Words

Counter (coil)
Timer (current value)
Aggregate Timer (current
value)
Counter (current value)
Data Register
Special Register
Link Register
Special Link Register
File Register

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Appendix-5

Mitsubishi Electric Corporation Appendix

Inverter
Device

P
OPE
OUTF
OUTC
OUTV
SPM
SSEL
SOF

Max. No. of
Consecutive
Address
1 Words
1 Double Words
1 Words
1 Double Words

SOC
SOV
FSET
RUNS
MOT
RBRK
ELOF
OCPV
COPK
IPOW
OPOW
A12D

1 Words

A34D
A56D
A78D
RUNC
INVS
RWRT
SFWE
SFWR
SFRE
SFRR
ERCL
RSET
ALLC
LNKP
SECP

Appendix-6

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric Corporation Appendix

A.2

Device Codes and Address Codes


Device codes and address codes are used to specify indirect addresses for the
E-tags or K-tags.
The word addresses of data to be displayed are coded and stored in the word
address specified by the E-tags and K-tags. (Code storage is done either by the
PLC, or with T-tag and K-tags)

PLC
<MELSEC-A Series (AnA/AnU/A2US/A2USH-S1)>
Device

Word Address

Device code
(HEX)

Address code
Save as word address value, with the
tenths position "0" removed.
Save as word address value, with the
tenths position "0" removed.
Save as word address value divided by
16.
Save as word address value minus 9000
divided by 16.
Save as word address value divided by
16.

Input Relay

X0000~

8000

Output Relay

Y0000~

8800

Bit Device Internal Relay

M0000~

9000

Special Relay

M9000~

B000

Annuniciator

F0000~

B800

Timer (current value)

TN0000~

6000

Word Address

Counter (current value) CN0000~

7000

Word Address

Data Register

D0000~

0000

Word Address

Special Register

D9000~

0000

Word Address

Link Register

W0000~

4800

Word Address

File Register

R0000~

5800

Word Address

LS area

LS0000~

4000

Word Address

Word
Device

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Appendix-7

Mitsubishi Electric Corporation Appendix

<MELSEC-A Series(AnN/A2C/A1S/A3H/A0J2/A1SJ/A2SH/A1SH/A2CJ-S3)>
Device

Bit Device

Word
Device

Word Address

Device code
(HEX)

Address code
Save as word address value, with the tenths
position "0" removed.
Save as word address value, with the tenths
position "0" removed.

Input Relay

X0000~

8000

Output Relay

Y0000~

8800

Internal Relay

M0000~

9000

Save as word address value divided by 16.

Special Relay

M9000~

B000

Save as word address value minus 9000


divided by 16.

Annuniciator

F000~

B800

Save as word address value divided by 16.

Timer (current value)

TN000~

6000

Word Address

Counter (current value) CN000~

7000

Word Address

Data Register

D0000~

0000

Word Address

Link Register

W0000~

4800

Word Address

File Register

R0000~

5800

Word Address

LS area

LS0000~

4000

Word Address

<MELSEC-F2 Series>
Device

Word Address

Device code

Address code

(HEX)

TC050~
Timer (current value)

TC450~
TC550~

TC650~
TS050~
Timer (set value)

TS450~
TS550~
TS650~

Word
Device

CC060~
Counter (current value)

CC460~
CC560~
CC660~
CS060~

Counter (set value)

CS460~
CS560~
CS660~

Appendix-8

Data Register

DW700 ~

0000

Save as word address value minus 700.

LS area

LS0000 ~

4000

Word Address

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric Corporation Appendix


<MELSEC-FX Series (FX0)>
Device

Bit Device

Word
Device

Word Address

Device code
(HEX)

Address code

Input Relay

X000~

8000

Word Address

Output Relay

Y000~

8800

Word Address

Internal Relay

M000~

9000

Save as word address value divided by 16.

State

S000~

9800

Save as word address value divided by 16.

Timer (current value)

TN000~

6000

Word Address

Counter (current value) CN000~

7000

Word Address

Data Register

D000~

0000

Word Address

LS area

LS0000~

4000

Word Address

<MELSEC-FX Series (FX1/FX2/FX2N/FX0N/FX3UC)>


Mitsubishi MELSEC-FX2(LINK)
Mitsubishi MELSEC-FX(CPU)
Mitsubishi MELSEC-FX(CPU2)
Device

Bit Device

Word
Device

Word Address

Device code
(HEX)

Address code
Save as word address value, with the tenths
position "0" removed.
Save as word address value, with the tenths
position "0" removed.

Input Relay

X0000~

0x8000

Output Relay

Y0000~

0x8800

Auxiliary Relay

M0000~

0x9000

Save as word address value divided by 16.

State

S0000~

0x9800

Save as word address value divided by 16.

Special Auxiliary Relay M8000~

0xB000

Save as word address value divided by 16.

Timer (current value)

TN000~

0x6000

Word Address value

Counter (current value)

CN000~

0x7000

Word Address value

Data Register

D0000~

0x0000

Word Address value

Special Data Register

D8000~

0x7800

Word Address value

Extended Register

R0000~

0x1000

Word Address value

LS Area

LS000~

0x4000

Word Address value

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Appendix-9

Mitsubishi Electric Corporation Appendix

<MELSEC-FX Series>
(Mitsubishi MELSEC -FX 1:n Communication)
Word Address

Device code
(HEX)

Address Code

Input Relay

X0000~

0x8000

Word Address tenth position "0" removed.

Output Relay

Y0000~

0x8800

Word Address tenth position "0" removed.

Auxiliary Relay

M0000~

0x9000

Word Address divided by 16

State

S0000~

0x9800

Word Address divided by 16

Special Auxiliary Relay

M8000~

0xB000

(Word Address - 8000) divided by 16

Timer (current value)

TN000~

0x6000

Word Address value

Counter (current value)

CN000~

0x7000

Word Address value

Data Register

D0000~

0x'0000

Word Address value

Special Data Register

D8000~

0x7800

Word Address value

Extended Register

R0000~R8191

0x1000

Word Address value

Extended Register

R8192~R16383

0x1200

Word Address - 8192

Extended Register

R16384~R24575

0x1400

Word Address - 16384

Extended Register

R24576~R32767

0x1600

Word Address - 24576

LS000~

0x4000

Word Address value

Device

LS Area

Appendix-10

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric Corporation Appendix

<MELSEC-QnA Series>
Device

Bit Device

Word
Device

Word Address

Device code
(HEX)

Address code

Input Relay

X0000~

8000

Save as word address value, with the tenths


position "0" removed.

Output Relay

Y0000~

8800

Save as word address value, with the tenths


position "0" removed.

Internal Relay

M00000~

9000

Save as word address value divided by 16.

Special Relay

SM0000~

B000

Save as word address value divided by 16.

Latch Relay

L00000~

C000

Save as word address value divided by 16.

Annuniciator

F00000~

B800

Save as word address value divided by 16.

Edge Relay

V0000~

9800

Save as word address value divided by 16.

Step Relay

S0000~

A800

Save as word address value divided by 16.

Link Relay

B0000~

C800

Special Link Relay

SB000~

A000

Timer (current value)

TN00000~

6000

Word Address

Aggregate Timer
(current value)

SN00000~

5000

Word Address

Counter (current value) CN00000~

7000

Word Address

Data Register

D0000~

0000

Word Address

Special Register

SD0000~

6800

Word Address

Link Register

W0000~

4800

Word Address

Special Link Register

SW000~

7800

Word Address

File Register (normal)

R00000~

5800

Word Address

0R0000~

0600

Word Address

1R0000~

0800

Word Address

LS0000~

4000

Word Address

File Register (serial)


LS area

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Save as word address value, with the tenths


position "0" removed.
Save as word address value, with the tenths
position "0" removed.

Appendix-11

Mitsubishi Electric Corporation Appendix

<MELSEC-Q Series>
Word Address

Device code
(HEX)

Input Relay

X0000 ~

8000

Save as word address value, with the


tenths position "0" removed.

Output Relay

Y0000 ~

8800

Save as word address value, with the


tenths position "0" removed.

Device

Bit Device

Internal Relay

M0000 ~

9000

Save as word address value divided by 16.

Special Relay

SM0000 ~

B000

Save as word address value divided by 16.

Latch Relay

L0000 ~

C000

Save as word address value divided by 16.

Annunciator

F0000 ~

B800

Save as word address value divided by 16.

Edge Relay

V0000 ~

9800

Save as word address value divided by 16.

Step Relay

S0000 ~

A800

Save as word address value divided by 16.

Link Relay

B0000 ~

C800

Special Link Relay

SB000 ~

A000

TN00000 ~

Timer (current value)

Save as word address value, with the


tenths position "0" removed.
Save as word address value, with the
tenths position "0" removed.

6000

Word Address

Aggregate Timer (Curren SN00000 ~

5000

Word Address

Counter (current value)

CN00000 ~

7000

Word Address

Data Register

D00000 ~

0000

Word Address

Special Data Register

SD0000 ~

6800

Word Address

Link Data Register

W0000 ~

4800

Word Address

Special Link Register

SW000 ~

7800

Word Address

File Register (normal)

R0000 ~

5800

Word Address

0R0000 ~

0600

Word Address

1R0000 ~

0800

Word Address

2R0000 ~

0A00

Word Address

3R0000 ~

0C00

Word Address

4R0000 ~

0E00

Word Address

29R0000 ~

4200

Word Address

30R0000 ~

4400

Word Address

31R0000 ~

4600

Word Address

Word Device

File Register (serial)

Appendix-12

Address code

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Mitsubishi Electric Corporation Appendix


CC-Link Remote Device Station
Device
Word Device LS area

Word Address

Device code
(HEX)

LS0000 ~

4000

Address code
Word Address

CC-Link intelligent Device Station


E-tag or K-tag indirect addresses cannot be designated by CC-Link Intelligent Device Station.

Inverter
Device

Parameter (except for Pr.37 of FREQROLS500 and FREQROL-E500)


Parameter (Pr.37 of FREQROL-S500 or
FREQROL-E500)
Operation mode
Output frequency (rpm)
Output current
Output voltage
Special monitor
Output frequency
Output current
Output voltage
Set frequency value
Run speed
Motor torque
Regenerative brake
Electronic thermal load factor
Output current peak value
Converter output voltage peak value
Word Device Input power
Output power
Alarm (latest Nos. 1 & 2)
Alarm (latest Nos. 3 & 4)
Alarm (latest Nos. 5 & 6)
Alarm (latest Nos. 7 & 8)
Run command
Inverter status monitor
Run frequency write (E2PROM)
Set frequency write (RAM and E2PROM)
Set frequency write (only RAM)
Set frequency read (E2PROM)
Set frequency read (RAM)
Error all clear
Inverter reset
Parameter all clear
User clear
Link parameter extended settings
No. 2 parameter change
LS area

Word Address

Device code
(HEX)

Address code

0000 ~

8000

Word Address

P0037
OPE0
OUTF0
OUTC0
OUTV0
SPM0
SOF0
SOC0
SOV0
FRS0
RUNS0
MOT0
RBRK0
ELOF0
OCPV0
COPK0
IPOW0
OPOW0
A12D0
A34D0
A56D0
A78D0
RUNC0
INVS0
RWRT0
SFWE0
SFWR0
SFRE0
SFRR0
ERCL0
RSET0

8200
8400
8600
8800
9000
9200
9400
9600
9800
A000
A200
A400
A600
A800
B000
B200
B400
B600
B800
C000
C200
C400
C600
C800
D000
D200
D400
D600
D800
E000
E200

ALLC0

E400

LNKP0
SECP0
LS0000 ~

E600
E800
4000

Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address
Word Address

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Appendix-13

Mitsubishi Electric Corporation Appendix

A.3

Address Conversion Tables


Addresses can or cannot be converted depending on the address combination.
The combinations which cannot be converted vary with the external
device manufacturers. See the following address global conversion table to
convert the addresses correctly.

How to Read the Tables


The symbols used in the table have the following meanings:
: If Conversion Mode is "Word", both word and bit devices will be converted.
If Conversion Mode is "Bit", only bit devices will be converted.
: When the selected conversion mode is [Word], only Word addresses are
converted. Selecting [Bit] will convert only bit addresses.
: If Conversion Mode is "Word", only word devices will be converted.
: When [Bit] mode is selected, the system converts only bit addresses.
(Blanks cannot be converted)
For the timers and counters, the bit indicates the contact or coil used, and
the word indicates the current value (elapsed value) or setting value
<Mitsubishi MELSEC-FX (1:N Communication)>

Before Conversion

After Conversion
Input Relay
Output relay
AUX Relay
State
Special AUX Relay
Timer (contact)
Counter (contact)
Timer (current value)
Contact (current value)
Data Register
Special Data Register
Extended Register
R00000 to R8191
Extended Register
R8192 to R16383
Extended Register
R16384 to R24575
Extended Register
R24576 to R32767
LS

M8

TS

CS TN CN




D8

LS

GP-PRO/PBIII for Windows Device/PLC Connection Manual

Appendix-1

Mitsubishi Electric Corporation Appendix

<Mitsubishi MELSEC-FX2 (LINK)>

Before Conversion

After Conversion
Input Relay
Output relay
AUX Relay
State
Special AUX Relay
Timer (contact)
Counter (contact)
Timer (current value)
Contact (current value)
Data Register
Special Data Register

M8

TS

CS TN CN




D8

Extended Register

LS

LS

D8

<Mitsubishi MELSEC-FXSeries (CPU)>


<Mitsubishi MELSEC-FXSeries (CPU2)>

Before Conversion

After Conversion

Appendix-2

Input Relay
Output relay
AUX Relay
State
Special AUX Relay
Timer (contact)
Counter (contact)
Timer (current value)
Contact (current value)
Data Register
Special Data Register

M8

TS

CS TN CN




LS

Extended Register

LS

GP-PRO/PBIII for Windows Device/PLC Connection Manual

You might also like