SVC For Voltage Stabilization and Harmonic Suppression in Rolling Mill
SVC For Voltage Stabilization and Harmonic Suppression in Rolling Mill
rolling mill
90 kV
0-66 Mvar (capacitive)
33 Mvar/5th
16,5 Mvar/5th
16,5 Mvar/7th
3-phase symmetrical closed-loop
reactive power control
Air cooled thyristor valves with
magnetic triggering
220/90 kV
HOT STRIP
MILL
ROUGHING
MILL
5th
7th
16,5 Mvar 16,5 Mvar
5th
33 Mvar
Pmax
(MW)
83
45
Single-line diagram
Qmax
(Mvar)
62
86
TCR
66 Mvar
90 kV