Selecting, Sizing Transformers For Commercial Buildings - Consulting-Specifying Engineer PDF

This document discusses selecting and sizing transformers for commercial buildings. It describes the different types of transformers used, including dry-type, sealed dry-type, cast-coil, and oil-filled transformers. It discusses factors to consider like location, voltage ratings, loads, and capacity. The document recommends sizing transformers at least 20% larger than required load to allow for future growth. It provides an example of properly sizing a transformer based on load calculations.

Uploaded by

Ashok Kumar Jena
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
388 views4 pages

Selecting, Sizing Transformers For Commercial Buildings - Consulting-Specifying Engineer PDF

This document discusses selecting and sizing transformers for commercial buildings. It describes the different types of transformers used, including dry-type, sealed dry-type, cast-coil, and oil-filled transformers. It discusses factors to consider like location, voltage ratings, loads, and capacity. The document recommends sizing transformers at least 20% larger than required load to allow for future growth. It provides an example of properly sizing a transformer based on load calculations.

Uploaded by

Ashok Kumar Jena
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

5/18/2015

Selecting,sizingtransformersforcommercialbuildings|ConsultingSpecifyingEngineer

Research
Username
Forgotpassword?

Trending

*******

Webcasts

Newsletters

Magazine

Subscribe
ManageAccount

NewProducts

Power

Sponsoredby:

Fire,LifeSafety

Electrical,Lighting

BuildingTypes

CodesandStandards

HVAC

Selecting,sizingtransformersforcommercialbuildings
Whilecommercialbuildingdesignschange,theirelectricalloadsremainfundamentallyunchanged.Properlysizingandselecting
transformersensuresthattheseloadsareaccommodated.
ByRalphBaeza,PE,LEEDAP,TLCEngineeringforArchitecture,Miami

06/09/2011

Share

Transformers,alongwithotherpowerdistributionapparatus,remainafundamentalcomponentinelectricalsystemsdistribution
forcommercialbuildings.Thisarticlepresentsseveralusefuldesignconceptsforselectingandsizingtransformersinthe
designofelectricalsystemsforcommercialbuildings.
Transformerschangevoltagelevelstosupplyelectricalloadswiththevoltagestheyrequire.Theysupplytherequiredincoming
electricalservicetothebuildings.Transformerprimaryandsecondaryvoltagescanbe2,4004,1607,20012,470and13,200
for15kVClass,and120,208,240,277,and480for600VClass.
Transformersarelocatedeitheroutdoorsorinsidebuildingsinanelectricalroomorotherareasaspermittedbycode.The
electricalphasecharacteristicsassociatedwiththetransformersprimarysideis3phase,3wireorDeltaconnected.The
secondaryis3phase,4wireorWyeconnected.
Constructiontypes
Therearedifferentconstructiontypesfortransformersusedincommercial
buildings.Ourunderstandingoftheirgeneralcharacteristicswillallowthe
designerandendusertomaketheproperselectionfortheelectricalsystem
application.Followingaresomeofthetransformertypesavailableintheindustry
alongwithafewoftheircharacteristics:
Ventilateddrytypetransformersare
ventilatedbyair,uselargerspacefor
clearance,andusedifferent
insulatingmaterialstoaugmentthe
dielectricstrengthoftheair.They
containanenclosuresurroundingthe
windingsfortheirmechanical
protectionandthesafetyof
personnel.Thistypeisthemostcommontobeusedinthebuildingindoor
electricalsystemdistribution.SeeTable1fortypicaldrytypetransformerratings,
dimensions,andweights.

Weeklym
acquisitio
update:M

Achieving
buildinge
performan

Transfers

Arcflash

Yourque
answered
Systems:
Reduction
240.87Re

Energyef
webcast:
frequency
(VFDs),va
drives(VS
motors

YorkLXs
packaged

Graduatin
tointellig

Casestud
anintellig
system

Video:Re
SanDiego
Center:C

Sealeddrytypetransformersaresimilartodrytypeinmostoftheircharacteristics.
Thedifferenceistheycontainanenclosedtankwithnitrogenorotherdielectricgas
toprotectthewindings.Theycanbeinstalledoutdoorsorindoors.Theyareuseful
inareaswithacorrosiveordirtyatmosphere.
Castcoiltransformersareconstructedwiththeprimaryandsecondarywindings
encapsulatedinreinforcedresin.Theycanbeinstalledwheremoistureorairborne
contaminantsexist.
Nonventilateddrytypetransformersaresimilartotheventilatedtypebutaretotally
enclosed.Thistypecanbeinstalledinareaswithcorrosiveordirtyatmospheric
conditionswhereitwouldbeimpossibletouseaventilatedtypetransformer.
Oilfilledtransformersareconstructedwiththewindingsencasedinanoiltighttank
filledwithinsulatingmineraloil.Itisgoodpracticetoregularlytestthistypeof
transformerinordertodeterminedielectricbreakdown,whichaffectsitsusefullife.
Applicationtypes
Therearedifferentwaysinwhichtransformersareinstalledandusedaspartofa
commercialbuildingelectricalsystem.Theseapplicationtypesinclude:
Indoordistributiontransformersareusedwithpanelboardsandareseparately
mountedtosupplythespecificelectricalloadrequirementsinasystemspecific
applicationwithinthesystemdistribution.Severaltransformertypesratedhigherthan600Vforoilinsulatedtype,higherthan
35,000Vfordrytype,andothertransformersratedhigherthan600Varerequiredtobelocatedinvaultrooms,whichmustbe
builtwithfireratedenclosuresdependingonthetransformertypeandapplicablelocalauthorityrequirements,whenindoors.
Transformersthatarenotover600Vandarepartoftheindoorbuildingelectricalsystemdistributionhavebothprimaryand
http://www.csemag.com/singlearticle/selectingsizingtransformersforcommercialbuildings/4efa064775c5e26f27bfce4f0a61378e.html

1/4

5/18/2015

Selecting,sizingtransformersforcommercialbuildings|ConsultingSpecifyingEngineer
Transformersthatarenotover600Vandarepartoftheindoorbuildingelectricalsystemdistributionhavebothprimaryand
secondaryvoltagesbelow600Vwiththemostcommonvoltagelevelchangefrom480Vto208Y/120V.

Padmountedtransformersareinstalledoutsideandareconsideredthefirstoptionforsupplyingserviceentrancevoltageto
thebuildingelectricalsystembasedontheprojectsizeandrequirements.Theytypicallyhaveprimaryvoltageshigherthan600
Vandsecondaryvoltageslowerthan600Vwithcompartmentsfortheassociatedprotectivedevicesassembledinanintegral
tamperresistantandweatherproofunit.
Inaddition,thesizeofthecommercialfacilitywilldeterminetheappropriateapproachfordesigningtheelectricaldistribution
systemforthespecificapplication.Inthiselectricalsystemdesign,thetransformercanbeusedaspartofasubstation,primary
unitsubstation,secondaryunitsubstation,ornetworkconfiguration.
Sizing
TheelectricalsizeofthetransformerloadisratedinkVA.Thisratingprovidestheassociatedpoweroutputdeliveredfora
specificperiodbytheloadsconnectedtothetransformeronthesecondarysideoftheequipment.Theloads,whichare
calculatedaspartofthebuildingelectricalsystemdesignphase,areshownintheconstructiondocumentsrespective
equipmentschedulesinVAorkVA.
Ageneralapproachtodeterminingtransformercapacityandselectingtheproperratingforthedesignapplicationistoobtain
thecalculateddesignloadfromtherespectiveelectricalscheduleandadd20%sparecapacityforfutureloadgrowthtobe
shownintheequipmentschedule,unlessotherwisedirectedbythefacilitybasedondesignparameters.Forexample,the
codebaseddemandloadofa208Y/120V,3phase,4wirepanelboardis42kVA,whichdoesdonotincludesparecapacity
forfuturegrowth.Therefore,thetransformersizerequiredforconvertingthesystemvoltagefrom480V,3phase,3wireto208
Y/120V,3phase,4wireis:
TransformersizeinkVA=42kVAx1.25=52.5kVA
Therefore,a75kVAtransformerwouldbeselectedforthisapplicationoutoftheavailablestandardratingsfora480Vprimary
to208Y/120Vsecondary.Themostcommonbuildingindustrystandardratingsare3,6,9,15,30,37.5,45,75,112.5,150,
225,300,500,750,and1,000kVA.
Theabovesimplecalculationmeetstheintenttoachievethenormallifeexpectancyofatransformer,whichisbasedonthe
followingbasicconditions:
ThetransformerisequaltoorlessthanitsratedkVAandratedvoltage.
Theaveragetemperatureofthecoolingairduringa24hourperiodis86F.
Thetemperatureofthecoolingairatnotimeexceeds104F.
Selecting
TransformerselectionstartswiththekVAratingrequiredtosupplytheloadsconnectedintheelectricalsystem.Another
considerationforindoordistributiontransformersisthetypeofload:linearornonlinear.Linearloadsincluderesistiveheating
andinductionmotorsnonlinearloadsareproducedbyelectronicequipmentthatcontributestothedistortionoftheelectrical
powersignalsbygeneratingharmonics.Theharmonicsresultingfromnonsinusoidalcurrentsgenerateadditionallossesand
heatingofthetransformercoils,whichreducethetransformerlifeexpectancy.
IndoortransformersfornonlinearloadscanbeselectedwithaKrating,whichallowsthetransformertowithstandnonlinear
conditionsintheelectricalsystem.Kratedtransformersdonotmitigateoreliminateharmonics.However,theydoprotectthe
transformeritselffromdamagecausedbyharmonics.Forharmonicmitigation,Kratedtransformerscanbecombinedwith
harmonicfiltersorchokes.Forlinearloadapplications,transformersshouldbeselectedwithlowercorelosses.Otherfactors
thatshouldbeconsideredinselectingtransformersarevoltageratingsforbothprimaryandsecondary,voltagetaps,efficiency,
impedancevalue,typeofcoolingandtemperaturerise,voltageinsulationclass,basicimpulselevel,andsoundlevel.
Practicalapplications
Inthepasttwoyears,twolargeprojectsinMiamiDadeCountyhavebeenbuilt:the
FloridaInternationalUniversityfootballstadiumandMiamiInternationalAirportSouth
Terminal.Bothprojectsincludeddrytype480V,3phaseto208Y/120VVstepdown
transformers(inNEMA2enclosures),rangingfrom15kVAto112.5kVAinthe
electricalsystemdistributiondesign.
The18,688seatFIUfootballstadiumwasdesignedwithabout12transformersas
partoftheelectricalsystemdistributioninordertosupplygeneralusereceptacles,
smallmotors,andotherloadsinthestadiumbuildingstructureandtheattachedfield
housebuilding.TheMIASouthTerminalexpansionwasdesignedwithabout50
transformerswithsimilarintentasthestadiumsbutamorediversegroupofloadsfor
the208Y/120V3phase,4wiresystem,whichalsoincludedlightingloads,signage,telecommunication,securitysystems,
andotherloadspartofthisbuildingproject(Figure1).

http://www.csemag.com/singlearticle/selectingsizingtransformersforcommercialbuildings/4efa064775c5e26f27bfce4f0a61378e.html

2/4

5/18/2015

Selecting,sizingtransformersforcommercialbuildings|ConsultingSpecifyingEngineer

Installation
Theinstallationofpowertransformersandtransformervaultsmustcomply
withtherequirementsofNationalElectricalCode(NFPA70)article450and
specificlocalauthorityhavingjurisdictionrequirements.Someprinciplesto
considerfortransformerinstallationincludelocatingtheminisolatedrooms
withproperventilation,clearances,andaccessibility.Otherwise,theycanbe
installedonopenwallsorsteelcolumnsorabovesuspendedceilings.
Inaddition,thereareotherspecificrequirementsbasedonthetransformer
type,suchasweatherproofenclosuresfordrytypetransformersinstalled
outdoorsoratransformervaultroomforoilinsulatedtransformersinstalled
indoors.Inaddition,agooddesignandinstallationrequiretheproper
transformerfeederandovercurrentprotectiondevicesizebasedonNEC
articles240,250,450,andapplicablesectionsofArticle310(Figure2).
Lookingahead
Transformersremainafundamentalcomponentofelectricaldistribution
systems.Equipmentoperationcharacteristicswillcontinuetochange.
However,theiroperatingprincipleswillremainwiththesame.Theindustry
trendistocontinuebuildingtransformerswithlesscorelosses,andthat
complywithEnergyStarefficiencyrequirements.
BaezaisaprincipalandseniorelectricalengineeratTLCEngineeringfor
ArchitectureinMiami.Heisaregisteredprofessionalengineerwithmore
than29yearsofexperienceinelectricalengineering,projectmanagement,
buildingdesign,andconstruction.
RelatedNews:
HOKhiresdirectorofengineeringservices08.05.201210:31
Understandingstandbypowersystemgrounding14.12.201100:00
Avoidhiddendangerswhenapplying30cycleratedtransfer
switches12.12.201100:00
Quickconnecttapboxgeneratorsrestorespowerafter
outage07.10.201111:31
Circuitprotectioninhospitals08.07.201100:00
Hospitalincludessophisticatedelectricalsystem08.07.201100:00
Tallorderforsuperhighrises23.05.201100:00
<Backto:Home

Postacomment
Loginorcreateanaccounttosubmityourcommentforthisarticle.
Nocomments

Events&Awards

MagazineArchives

PurePower

2015ProductoftheYear

40UnderForty:GetRecognized

MEPGiantsProgram

ConsultingSpecifyingEngineer'sProductofthe
Year(POY)contestisthepremierawardfornew
productsintheHVAC,fire,electrical,and...

ConsultingSpecifyingEngineermagazineis
dedicatedtoencouragingandrecognizingthemost
talentedyoungindividuals...

TheMEPGiantsprogramliststhetopmechanical,
electrical,plumbing,andfireprotectionengineering
firmsintheUnitedStates.

More

Articles
CareerSmart
CaseStudiesandWhite
Papers
Codes&Standards
Magazine

Blogs

NewProducts
NewProducts
Innovationsfromthe
Industry
CSEProduct&Media
Showcase

Topics
Automation,Controls
Codes&Standards
ElectricalSystems
Fire&LifeSafety
HVAC/R

More

Training,Tools
AppsforEngineers
CareerSmart
CaseStudyDatabase
Videos

More

EventsandAwards News,Views,Blogs Newsletters


40Under40
MEPGiants
ProductoftheYear
UpcomingEvents

CareerSmart
Collaboratingagainst
counterfeitelectrical
products
CuttheCopper

Codes&Standards
ElectricalSolutions
Fire&LifeSafety
HVAC
NewsWatch:Data

http://www.csemag.com/singlearticle/selectingsizingtransformersforcommercialbuildings/4efa064775c5e26f27bfce4f0a61378e.html

Advertising
CaseStudyDatabase
Listing
ContactUs
Innovationsfromthe
Industry

AboutUs

TermsofUse
AppsforEngin
ControlEngine
AboutCFEMe
AdvisoryBoard

3/4

5/18/2015
IndustryRoundup
MagazineArchives
ProjectsinProgress

Selecting,sizingtransformersforcommercialbuildings|ConsultingSpecifyingEngineer
ProductoftheYear

Lighting
Plumbing,Piping

EngineeringChange
IEEEPowerPerspectives
IndustryNews
InsightsonPower
ResearchAnalystBlogs
RSSFeeds
SocialMedia
Understanding
Specifications,Codes,
andStandards

Centers
NewsWatch:Educational
Facilities
NewsWatch:Hospitals
PurePower

http://www.csemag.com/singlearticle/selectingsizingtransformersforcommercialbuildings/4efa064775c5e26f27bfce4f0a61378e.html

InternetProfiles
Magazine
CSEProduct&Media
Showcase

HowtoContrib
ContactUs
Magazine
ContentStream
MagazineArch
EGSAOnPea
Performance
PlantEngineeri
PrivacyPolicy
PurePower
Subscribe

4/4

You might also like