An Overview of Short Circuit Current (Part 3) : Sample Calculation For Small LT System
An Overview of Short Circuit Current (Part 3) : Sample Calculation For Small LT System
com
http://electrical-engineering-portal.com/an-overview-of-short-circuit-current-part-3
Continued from previous technical article: An Overview Of Short Circuit Current (part 2)
Calculation basis
1/ The busbar and switchgear of Marshalling kiosk is sized for short time rating as per contribution from MV source
through LT transformer.
2/ For circuits connected by transformer PU system is particularly suitable. By selecting suitable base kV for circuits
the per unit reactance and resistance remains same, referred to either side (HV or LV) of transformer.
3/ For circuits connected by transformer same base kVA is selected for both the circuits ( HV and LV) because power
remains constant throughout so same base kVA should be considered throughout.
4/ As a rule only two bases should be selected first and from these two the remaining bases should be calculated.
This is so because kV, kVA, I and Z are interrelated. They must obey ohms law. If we select base kVA and base kV
than other base like base I and base Z are calculated from base kV and base kVA.
Vice-versa will be inconvenient that is selecting base I and Z and calculating other bases like kV and kVA will make
calculation difficult.
Input data to be collected:
1. Transformer Rating
= 0.63 MVA
= 11/0.433 kV
3. Frequency
= 50Hz
4. Transformer Impedance
= 5% = 0.05 PU
= 40 kA
= 3 x 40 x 11 = 762 MVA
Calculation
Actual Fault Current available at AC distribution board
Base MVA
= 0.63
Base kV
= 11
Base Current in kA
= 192.1
= 0.0008
= 0.05
= 0.0508
Fault current contribution in kiloAmpers from MV system at LV side through (Switchyard) LT Transformer:
= Fault MVA x 1000 x 1000 / (3 x 0.433 x 1000 x
1000)
= 12.40 x 1000 x 1000 / (3 x 0.433 x 1000 x 1000)
= 17.245 kA
= 0.0052
PU impedance of cable from LT
transformer to ACDB
= ((PU resistance)2+(PU reactance)2)=
(0.0092+ 0.07052) = 0.011
Size of conecting cable in Sq mm from ACDB
to BMK = 3.5C x 35 Al, XLPE
Resistance in Ohms/kM of connecting cable
from ACDB to BMK = 0.671
Total resistance over route length = 0.671 x 50
/1000 = 0.034
PU resistance = Actual Resistance x Base
kVA/(Base kV2 x 1000)
= 0.034 x 0.63 x 1000 / (0.415 x 0.415 x
1000) = 0.12
Reactance in Ohms/kM of connecting cable
from ACDB to BMK = 0.0783
Total reactance over route length = 0.0783 x
50 /1000 = 0.004
PU reactance = Actual Reactance x Base
kVA/(Base kV2x 1000)
= 0.004 x 0.63 x 1000 / (0.415 x 0.415 x
1000) = 0.14
PU impedance of cable from ACDB to BMK =
((PU resistance)2+(PU reactance)2) =
((0.12)2+(0.14)2) = 0.124
Total PU Impeadnce of connecting cable from LT transformer to BMK = 0.011 + 0.124 = 0.134
Total PU Impedance from LT Transformer to BMK = PU Impedance of Transformer + Total PU
Impedance of connecting cable from LT transformer to BMK = 0.05 + 0.134 = 0.1842
Fault MVA at BMK busbar = Base MVA/Total Impedance = 0.63 / 0.1842 = 3.42
Fault current in kiloAmps at BMK busbar = Fault MVA x 1000x 1000 / (3 x 0.415 x 1000 x 1000)
= 3.42 x 1000 x 1000 / (3 x 0.415 x 1000 x 1000) = 4.757 kA
Hence selection of 10kA busbar and switchgear components like MCB is safe and appropriate as per the actual
fault level existing at BMK main busbar.
Si. No
Equipment
CURRENT RATING
CALCULATED SHORT
TERM CURRENT
RATING IN kA
OPTIMUM SELECTION
OF SHORT TIME
CURRENT RATING IN kA
RMS
Symmetrical
Assymmetrical
peak value =
nxRMS
Symmetrical
RMS
Symmetrical
Assymmetrical
peak value =
nxRMS
Symmetrical
Main LT board
17.24
34.5 (n=2)
35
73.5 (n=2.1)
Marshalling kiosk
4.75
7.1 (n=1.5)
10
17 (n= 1.7)
References:
1. Indian Standard 8623, part-1-SPECIFICATION FOR LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR
ASSEMBLIES
2. Indian Standard 10118, part-2-CODE OF PRACTICE FOR THE SELECTION, INSTALLATION AND
MAINTENANCE OF SWITCHGEAR AND CONTROLGEAR
3. The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies- Research paper DATE: November 17,
1999 REVISION: 0 by AUTHOR: John Merrell
4. Short-circuit-current Calculating Procedures by Donald Beeman, Alan Graeme Darling, and R. H. Kaufmann
5. Industrial Power Engineering and Applications Handbook by K.C. Agrawal