Understanding Time Current Curves
Understanding Time Current Curves
Understanding Time Current Curves
versus time. Current is shown on the horizontal axis using a logarithmic scale and is plotted as amps X 10 . Time is
X
shown on the vertical axis using a logarithmic scale and is plotted in seconds X10 .The light blue curve is a
switchgear feeder circuit breaker curve. The violet curve is the switchgear main circuit breaker curve. The red curve is
the transformer primary fuse curve. The orange curve is the transformer damage curve. The green curves are the
cable damage curves. Each one of these items will be explained. The system represented by this curve is well
coordinated and adequately protected from damage. It also has minimal arc flash hazard category ratings due to low
instantaneous circuit breaker trip values.
The one line diagram (see Figure 2) and TCC plot show a typical hypothetical industrial power system. There is a
utility delivery point with power supplied at a medium voltage level (in this case 4,160 V), which feeds the primary
side of a 2.5 MVA power transformer through a medium voltage fused switch containing an E Class fuse. The 480 V
secondary side of the transformer feeds a piece of low voltage power switchgear utilizing draw out low voltage power
circuit breakers for the main and feeder circuit breakers. The TCC plot also displays the transformer and cable
damage curves. These curves are based on accepted industry consensus standards published by the American
National Standards Institute (ANSI, for the transformer) and the Insulated Cable Engineers Association(ICEA, for the
cables). Interpreting the damage curves is fairly straight forward. Operating conditions (overcurrent protection) must
be kept to the left of the damage curve to guarantee no permanent damage is done to the transformer or cable in
question. Operating conditions that allow operation to the right of the damage curve subject the device in question to
currents that can cause permanent irreversible damage, a shortened lifespan, and possible catastrophic failure.
Therefore, the overcurrent and circuit breaker coordination schemes must take this into account during the initial
design phase.
There are two transformer damage curves (shown in orange on Figure 1) one is dashed, the other is solid. The
solid damage curve is unbalanced and takes into account a de-rating factor for transformer winding type and fault
type. The dashed damage curve is the 100% rating curve with no de-rating consideration. The transformer inrush
current is also plotted a single point on the TCC diagram. Again, as part of the initial design, the transformer inrush
current must be to the left of the transformer primary fuse curve, otherwise the fuse will open when the transformer is
energized. These differences in the unbalanced and 100% damage curves can be mitigated with additional protective
relaying to allow the 100% curve to be used for power system design without the risk of transformer damage.
There are three cable damage curves (shown in green on Figure 1). There is one curve for each cable represented
on the one line diagram. As part of the initial design, the overcurrent interrupting device must limit the fault current to
left of the damage curve to prevent permanent damage. The damage curves for the cables are dependent on size,
insulation type and raceway configuration.
This post was written by David Paul. David is a Principle Engineer atMAVERICK Technologies, a leading automation
solutions provider offering industrial automation, strategic manufacturing, and enterprise integration services for the
process industries. MAVERICK delivers expertise and consulting in a wide variety of areas including industrial
automation controls, distributed control systems, manufacturing execution systems, operational strategy, business
process optimization and more.
The next section of the curve moving up the time axis is the long time section. Long time settings cover the time
range from 0.5 to 1000 sec. The purpose of long time settings is to allow a time-based delay to elapse before tripping
the circuit breaker for low level current faults. This allows low level faults time to clear themselves and allows
electrical equipment to operate in a temporarily overloaded condition provided it will not produce permanent damage
to the equipment. Examples of these types of overcurrents would be the overloading of a power transformer or large
motor for a few minutes. The long time pickup setting sets ultimate trip value of the circuit breaker. Generally circuit
breakers are set at their maximum long time setting and cannot exceed the rating of the circuit breaker. They can be
set at reduced values which shifts the curve to the left on the current axis. There is also a knee in the long time
portion of the curve. The long time knee can be shift up the time axis by increasing the long time delay setting.
Conversely, the knee can be shifted lower by decreasing the long term delay setting. The described curve shifts are
depicted on the TCC plots below.
Another factor to notice in the curves is that they have a width to them. This is due to tolerance of the trip elements in
the circuit breaker. The curves below will show the differences in this deadband for the same circuit breaker using an
electronic versus non electronic trip mechanism.
Notice the difference in the tolerance in the trip curve of the feeder circuit breaker. The circuit breaker unit itself is the
same for both curves so the tripping delays are constant. Settings for both trip units were set as similar as possible to
each other so performance could be easily compared. Notice there is more tolerance +/- in the non-electronic trip unit
due to analog component tolerances and electro-mechanical devices inside the trip unit. The transition points on the
electronic trip curve between instantaneous, short time and long time are much more distinct and accurate because
of the digital microprocessor based trip. In the non-electronic trip the transition points have time based decay curves
associated with them due to the physics of the electro-mechanical trip elements. It is simply impossible to improve the
performance of the non electronic trip because of the physical limits of the components.
As can be seen in the above TCC curves electronic trip units provide the engineer greater ability to accurately and
selectively coordinate the electrical power system. Because of the obsolesce and lack of repair parts for older nonelectronic trip units the replacement of these units with electronic trips units can improve system coordination and
reduce arc flash values in a properly designed electrical power system.
This post was written by David Paul. David is a Principle Engineer at MAVERICK Technologies, a leading automation
solutions provider offering industrial automation, strategic manufacturing, and enterprise integration services for the
process industries. MAVERICK delivers expertise and consulting in a wide variety of areas including industrial
automation controls, distributed control systems, manufacturing execution systems, operational strategy, business
process optimization and more.
In the coordinated example the main and feeder circuit breakers are selectively coordinated and the main circuit
breaker provides adequate protection for the power transformer. Coordination between the MCC main fuse and the
feeder circuit breaker was also improved. Coordination improvements to these circuit breakers included the following
changes:
- Main Circuit Breaker Long Time Pickup (LTPU) from 2880 to 3200
- Main Circuit Breaker Short Time Pickup (STPU) from 1.5 to 5
- Main Circuit Breaker Short Time Delay (ST DLY) from Min. to Int.
- Main Circuit Breaker Instantaneous Pickup from 3 to disabled
- FB3 Circuit Breaker Long Time Pickup (LTPU) from 1 to .95
- FB3 Circuit Breaker STPU from 4 to 5
- FB3 Circuit Breaker Instantaneous Pickup from 15 to 9
There is overlap of the MCC main fuse and the feeder circuit breaker time current curves for long term low level
overloads. This overlap could be eliminated if a larger long time pickup setting was used in the feeder circuit breaker.
Increasing this setting would then require the upsizing of the feeder cable to maintain conformance with the National
Electric Code. Coordination involves tradeoffs and selections that require engineering experience and judgment to
find the most optimal settings. In many real world cases it is impossible to coordinate all possible cases. As such,
engineering judgment is required to coordinate the most likely scenarios and create the most reliable system.
Additionally, Arc Flash hazard category reductions generally result in diminished selective coordination. Conversely,
improved coordination may result in increased arc flash hazard categories in some cases. In the above example Arc
flash hazard category ratings for both the uncoordinated and the coordinated cases were unchanged even with
improved coordination. It is possible to achieve these optimized results through the use of engineered selections. It is
for these reasons that the selection of overcurrent device ratings and settings be left to power system engineers
experienced in industrial power systems.
This post was written by David Paul. David is a Principle Engineer at MAVERICK Technologies, a leading automation
solutions provider offering industrial automation, strategic manufacturing, and enterprise integration services for the
process industries. MAVERICK delivers expertise and consulting in a wide variety of areas including industrial
automation controls, distributed control systems, manufacturing execution systems, operational strategy, business
process optimization and more.