G 4170
G 4170
G 4170
25REZG
190--600 V
EPA-Certified for Stationary
Emergency Applications
Ratings Range
Standby:
60 Hz
24--25
24--31
kW
kVA
50 Hz
18--20
19--25
Gas
Standard Features
D Kohler Co. provides one-source responsibility for the
generating system and accessories.
D The generator set and its components are prototype-tested,
factory-built, and production-tested.
D The 60 Hz generator set offers a UL 2200 listing.
D The generator set accepts rated load in one step.
D The 60 Hz generator set meets NFPA 110, Level 1, when
equipped with the necessary accessories and installed per
NFPA standards.
D A one-year limited warranty covers all systems and
components. Two- and five-year extended warranties are
also available.
D Alternator features:
d The unique Fast-Responset II excitation system delivers
excellent voltage response and short-circuit capability
using a permanent magnet (PM)-excited alternator.
d The brushless, rotating-field alternator has broadrange
reconnectability.
D Other features:
d Kohler designed controllers for guaranteed system
integration and remote communication. See Controllers
on page 3.
d The electronic, isochronous governor incorporates an
integrated drive-by-wire throttle body actuator delivering
precise frequency regulation.
4P4
4Q4
Voltage
120/208
127/220
120/240
120/240
139/240
220/380
277/480
347/600
110/190
115/200
120/208
110/220
110/220
220/380
230/400
240/416
120/240
110/220
Ph
3
3
3
1
3
3
3
3
3
3
3
1
3
3
3
3
1
1
Hz
60
60
60
60
60
60
60
60
50
50
50
50
50
50
50
50
60
50
Natural Gas
130_C Rise
Standby Rating
kW/kVA
Amps
25/31
87
25/31
82
25/31
75
24/24
100
25/31
75
25/31
47
25/31
38
25/31
30
20/25
76
20/25
72
18/23
62
19/19
86
20/25
66
20/25
38
20/25
36
18/23
31
25/25
104
20/20
91
LP Gas
130_C Rise
Standby Rating
kW/kVA
Amps
25/31
87
25/31
82
25/31
75
24/24
100
25/31
75
25/31
47
25/31
38
25/31
30
20/25
76
20/25
72
18/23
62
19/19
86
20/25
66
20/25
38
20/25
36
18/23
31
25/25
104
20/20
91
RATINGS: All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. Standby Ratings: The standby rating is applicable to varying loads for the duration of a
power outage. There is no overload capability for this rating. Prime Power Ratings: At varying load, the number of generator set operating hours is unlimited. A 10% overload capacity is available for one
hour in twelve. Ratings are in accordance with ISO-8528-1 and ISO-3046-1. For limited running time and continuous ratings, consult the factory. Obtain technical information bulletin (TIB-101) for ratings
guidelines, complete ratings definitions, and site condition derates. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability
whatsoever. For dual fuel engines, use the natural gas ratings for both the primary and secondary fuels.
G4-170 (25REZG) 1/12f
Alternator Specifications
Specifications
Manufacturer
Type
Exciter type
Leads: quantity, type
4P4
4Q4
Voltage regulator
Insulation:
Material
Temperature rise
Bearing: quantity, type
Coupling
Amortisseur windings
Voltage regulation, no-load to full-load
One-step load acceptance
Unbalanced load capability
Peak motor starting kVA:
480 V, 380 V 4P4 (12 lead)
240 V, 220 V 4Q4 (4 lead)
Alternator
Kohler
4-Pole, Rotating-Field
Brushless, PermanentMagnet
12, Reconnectable
4, 110--120/220--240
Solid State, Volts/Hz
NEMA MG1
Class H
130_C, Standby
1, Sealed
Flexible Disc
Full
Controller Dependent
100% of Rating
100% of Rated Standby
Current
(35% dip for voltages below)
121 (60 Hz), 88 (50 Hz)
62 (60 Hz), 62 (50 Hz)
Application Data
Engine
Engine Specifications
Manufacturer
Engine: model, type
Cylinder arrangement
Displacement, L (cu. in.)
Bore and stroke, mm (in.)
Compression ratio
Piston speed, m/min. (ft./min.)
Main bearings: quantity, type
Rated rpm
Max. power at rated rpm, kW (HP)
Engine power at standby rating, kW (HP)
Cylinder head material
Piston type and material
Crankshaft material
Governor type
Frequency regulation, no-load to full-load
Frequency regulation, steady state
Frequency
Air cleaner type, all models
Engine Electrical
60 Hz
50 Hz
General Motors
Industrial Powertrain
3.0 L, 4-Cycle
Natural Aspiration
4 Inline
3.0 (181)
101.6 x 91.4 (4.00 x 3.60)
8.2:1
329 (1080)
274 (900)
2 Bolt
1800
1500
33 (44)
27.5 (37)
33 (44)
27.5 (37)
Cast Iron
High Silicon Aluminum
Nodular Iron
Electronic
Isochronous
0.5%
Fixed
Dry
Exhaust
Exhaust System
Exhaust manifold type
Exhaust flow at rated kW, m3/min. (cfm)
Exhaust temperature at rated kW, dry
exhaust, _C (_F)
Maximum allowable back pressure,
kPa (in. Hg)
Exhaust outlet size at engine hookup,
mm (in.)
60 Hz
50 Hz
Dry
7.1 (250)
5.9 (208)
688 (1270)
10.2 (3.0)
64 (2.5) OD
60 Hz
50 Hz
Electronic, Distributor
Negative
12
70
12
1, 630
12
Fuel
Fuel System
Fuel type
Fuel supply line inlet
Natural gas fuel supply pressure, kPa
(in. H2O)
LPG vapor withdrawal fuel supply
pressure, kPa (in. H2O)
Dual fuel engine, LPG vapor withdrawal
fuel supply pressure, kPa (in. H2O)
Fuel Composition Limits *
Methane, % by volume
Ethane, % by volume
Propane, % by volume
Propene, % by volume
C4 and higher, % by volume
Sulfur, ppm mass
Lower heating value,
MJ/m3 (Btu/ft3), min.
60 Hz
50 Hz
Natural Gas, LP Gas, or
Dual Fuel
1 NPTF
1.74--2.74 (7-11)
1.24--2.74 (5-11)
1.24 (5)
Nat. Gas
LP Gas
90 min.
4.0 max.
1.0 max.
85 min.
0.1 max.
5.0 max.
0.3 max.
2.5 max.
25 max.
33.2 (890)
84.2 (2260)
Application Data
Lubrication
Controllers
Lubricating System
Type
Oil pan capacity, L (qt.)
Oil pan capacity with filter, L (qt.)
Oil filter: quantity, type
60 Hz
50 Hz
Full Pressure
3.8 (4.0)
4.1 (4.3)
1, Cartridge
Cooling
Radiator System
60 Hz
50 Hz
50 (122)
Ambient temperature, _C (_F) *
Engine jacket water capacity, L (gal.)
6.8 (1.8)
Radiator system capacity, including
engine, L (gal.)
14.9 (3.9)
Engine jacket water flow, Lpm (gpm)
42 (11)
35 (9)
Heat rejected to cooling water at rated
kW, dry exhaust, kW (Btu/min.)
34.1 (1940) 28.4 (1617)
Water pump type
Centrifugal
Fan diameter, including blades, mm (in.)
533 (21)
Fan, kWm (HP)
1.5 (2.0)
1.0 (1.2)
Max. restriction of cooling air, intake and
discharge side of radiator, kPa (in. H2O)
0.125 (0.5)
* Enclosure with enclosed silencer reduces ambient temperature
capability by 5_C (9_F).
Operation Requirements
Air Requirements
Radiator-cooled cooling air,
m3/min. (scfm)]
Combustion air, m3/min. (cfm)
Heat rejected to ambient air:
Engine, kW (Btu/min.)
Alternator, kW (Btu/min.)
[ Air density = 1.20 kg/m3 (0.075 lbm/ft3)
Fuel Consumption ]
Natural Gas, m3/hr. (cfh) at % load
100%
75%
50%
25%
LP Gas, m3/hr. (cfh) at % load
100%
75%
50%
25%
] Nominal fuel rating:
60 Hz
50 Hz
200 (7100)
2.1 (74)
167 (5916)
1.75 (62)
9.2 (522)
4.5 (259)
15.4 (860)
3.75 (216)
60 Hz
50 Hz
Standby Ratings
10.5 (366)
8.8 (305)
8.5 (297)
7.1 (248)
5.5 (194)
4.6 (162)
3.3 (115)
2.8 (96)
Standby Ratings
4.5 (156)
3.8 (130)
3.6 (127)
3.0 (106)
2.4 (83)
2.0 (69)
1.4 (50)
1.2 (42)
Standard Features
D
D
D
D
D
D
D
D
Alternator Protection
Battery Rack and Cables
Electronic, Isochronous Governor
Gas Fuel System (includes fuel mixer, electronic secondary gas
regulator, gas solenoid valve, and flexible fuel line between the
engine and the skid-mounted fuel system components)
Integral Vibration Isolation
Local Emergency Stop Switch
Oil Drain Extension
Operation and Installation Literature
Available Options
Approvals and Listings
- CSA Approval
- IBC Seismic Certification
- UL 2200 Listing
Enclosed Unit
- Sound Enclosure (with enclosed critical silencer)
- Weather Enclosure (with enclosed critical silencer)
Open Unit
- Exhaust Silencer, Critical (kit: PA-352663)
- Flexible Exhaust Connector, Stainless Steel
Fuel System
- Dual Fuel NG/LPG (automatic changeover)
- Flexible Fuel Line
(required when the generator set skid is spring mounted)
- Gas Filter
- LP Liquid Wtihdrawal (vaporizer)
- Secondary Gas Solenoid Valve
Controller
- Common Fault Relay
- Communication Products and PC Software
(Decision-Makerr 550 controller only)
- Customer Connection
(Decision-Makerr 550 controller only)
- Dry Contact (isolated alarm)
(Decision-Makerr 550 controller only)
- Input/Output Module
(Decision-Makerr 3000 controller only)
- Remote Annunciator Panel
- Remote Audiovisual Alarm Panel
(Decision-Makerr 550 controller only)
- Remote Emergency Stop
- Run Relay
Cooling System
- Block Heater, 1000 W, 110--120 V
- Block Heater, 1000 W, 190--240 V
[recommended for ambient temperatures below 10C (50F)]
- Radiator Duct Flange
-
Electrical System
Alternator Strip Heater
Battery
Battery Charger, Equalize/Float Type
Battery Heater
Line Circuit Breaker (NEMA1 enclosure)
Line Circuit Breaker with Shunt Trip (NEMA1 enclosure)
Miscellaneous
Air Cleaner Restrictor Indicator
Certified Test Report
Engine Fluids (oil and coolant) Added
Rated Power Factor Testing
Rodent Guards
Literature
General Maintenance
NFPA 110
Overhaul
Production
Warranty
- 2-Year Basic
- 5-Year Basic
- 5-Year Comprehensive
-
Other Options
_______________________________________________
_______________________________________________
_______________________________________________
_______________________________________________
_______________________________________________
_______________________________________________
_______________________________________________
_______________________________________________