SIPROTEC

Numerical Protection Relays


7RW600 UV/OV & Frequency

Protection
Systems
Catalog
SIP 2004

Editorial

SIPROTEC
more than just protection
ONE bay, ONE IED (Intelligent Electronic Device)
Siemens is the world market leader in delivering
combined protection &
control relays. We provide
control functionality with
the CFC (Continuous function chart), which is accepted as state-of-art in
industrial automation
(SIMATIC STEP 7) and
makes the life for the protection engineers easier.
ONE DIGSI
Parameterisation - Software
serves all products
Siemens is the first supplier
to meet this strong
customer demand to have
one software for all
protection products. DIGSI
can handle previous
versions and the bus-bar
protection while providing
unrivalled functionality.
ONE single source for all
products and services
Siemens provides a full
product range for all market segments. In order to
provide optimal services
we have concentrated resources for important functions, e.g. one product
management, one product
development, one factory,
etc. We will support you in
planning, engineering,
commissioning, relay
co-ordination, type test,
etc. all over the world.

This is the latest edition of the printed SIPROTEC Catalog. This


edition - which is now available - contains many suggestions by our
readers, along with information regarding innovations and supplementary products. The SIPROTEC Catalog is also available on
CD ROM.
One of the new highlights is the SIPROTEC protection relays with
IEC 61850 communication. IEC 61850 was created by relay experts
and manufacturers alike. The goal of this standard is to achieve an
object-oriented communication structure within substations.
SIPROTEC protection relays and bay control units are the first to
feature the IEC 61850 standard. With the substation configurator, a
part of DIGSI 4, SIPROTEC units as well as other makes can be
configured in accordance with IEC 61850.

This SIPROTEC Catalog is supplemented by multimedia computer


animation tools.
+ CD-ROM SIPROTEC 4 you Features, Applications, Relays
+ CD-ROM SIPROTEC 4 you Start Up.
+ CD-ROM SIPROTEC 4 you IEC 61850 & ETHERNET.
You can order the printed SIPROTEC Catalog (and all the CD
ROMs) via the Internet free of charge. Please fill in a form at
www.siprotec.com/catalog. You may also consult your Siemens
representative or send us an e-mail ([email protected]).
This catalog will assist you by increasing your understanding of our
products and therefore help you to optimally and conveniently
utilize the available features and functionality. We wish you a pleasant and productive experience with SIPROTEC.

Bernhard W. Niessing
Vice President
Protection and Power Quality

Product Selection
Relay Functions

Page
1/2

1 Product Selection

Relay Functions

7SJ45
7SJ46
7SJ600
7SJ602
7SJ61
7SJ62
7SJ63
7SJ64

ANSI No.*

Description

14

Locked rotor protection

21

Distance protection, phase

21N

Distance protection, earth (ground)

21FL

Fault locator

24

Overfluxing (V/f protection)

25

Synchronizing, synchronism check

27

Undervoltage

27/34

Stator earth fault 3rd harmonic

32

Directional power

32F

Forward power

32R

Reverse power

37

Undercurrent or underpower

40

Loss of field

46

Load unbalance, negative phasesequence overcurrent

47

Phase-sequence voltage

Protection functions

Type

7VH60
7UT512
7UT513
7UT612
7UT613
7UT63
7SS60
7SS52

7SD600
7SD5
7SD610

Differential

Overcurrent

7SA513
7SA522
7SA6

Distance

Pilot wire differential


Line differential

48

Motor starting protection

49

Thermal overload

49R

Rotor thermal protection

49S

Stator thermal protection

50

Instantaneous overcurrent

50N

Instantaneous earth
fault overcurrent

50BF

Breaker failure

51GN

Zero speed and underspeed device

51

Overcurrent-time relay, phase

51N

Overcurrent-time relay, earth

51V

Overcurrent-time relay,
voltage controlled

59

Overvoltage

59N

Residual voltage earth


fault protection

59GN

Stator earth-fault protection

64

100 % Stator earth-fault protection


(20 Hz)

64R

Rotor earth fault

Standard function
Option
* ANSI/EEE C 37.2: IEEE Standard Electrical Power System Device Function Numbers
l

1/2

Siemens SIP 2004

Voltage, frequency

7VK61
7VK512

7VE51
7VE6

7SV512
7SV600

7RW600

Breaker failure

Breaker management
Auto-reclosure +
synchronism check
Synchronizing

7UM61
7UM62

7UM511
7UM512
7UM515
7UM516

Generator and
motor protection

Generator protection

1 Product Selection

ANSI No.*

Description

14

Locked rotor protection

21

Distance protection, phase

21N

Distance protection, earth

21FL

Fault locator

24

Overfluxing (V/f protection)

25

Synchronizing, synchronism check

27

Undervoltage

27/34

Stator earth fault 3rd harmonic

32
32F

Protection functions

Type

Directional power

Forward power

32R

Reverse power

37

Undercurrent or underpower

40

Loss of field

46

Load unbalance, negative phasesequence overcurrent

47

Phase-sequence voltage

48

Incomplete sequence, locked rotor

49

Thermal overload

49R

Rotor thermal protection

49S

Stator thermal protection

50

Instantaneous overcurrent

50N

Instantaneous earth-fault
overcurrent

50BF

Breaker failure

51GN

Zero speed and underspeed dev.

51

Overcurrent-time relay, phase

51N

Overcurrent-time relay, earth

51V

Overcurrent-time relay,
voltage controlled

59

Overvoltage

59N

Residual voltage earthfault protection

59GN

Stator earth-fault protection

64

100 % Stator earth-fault protection


(20 Hz)

64R

Rotor earth fault

Standard function
Option
* ANSI/EEE C 37.2: IEEE Standard Electrical Power System Device Function Numbers
l

Siemens SIP 2004

1/3

1 Product Selection

Relay Functions

7SJ45
7SJ46
7SJ600
7SJ602
7SJ61
7SJ62
7SJ63
7SJ64

ANSI No.*

Description

67

Directional overcurrent

67N

Directional earth-fault overcurrent

67G

Stator earth-fault
directional overcurrent

68

Out-of-step protection

74TC

Trip circuit supervision

78

Out-of-step protection

Protection functions

Type

7VH60
7UT512
7UT513
7UT612
7UT613
7UT63
7SS60
7SS52

7SD600
7SD5
7SD610

Differential

Overcurrent

7SA513
7SA522
7SA6

Distance

Pilot wire differential


Line differential

79

Auto-reclosure

81

Frequency protection

81R

Rate of frequency change protection

Vector jump supervision

85

Carrier interface/remote trip

86

Lockout function

87G

Differential protection generator

87T

Differential protection transformer

87BB

Differential protection busbar

87M

Differential protection motor

87L

Differential protection line

87N

Restricted earth-fault protection

Standard function
Option
* ANSI/EEE C 37.2: IEEE Standard Electrical Power System Device Function Numbers
l

1/4

Siemens SIP 2004

7SV512
7SV600

7RW600

Voltage, frequency

7VE51
7VE6

Breaker failure

Breaker management
Auto-reclosure +
synchronism check
Synchronizing

7VK61
7VK512

7UM511
7UM512
7UM515
7UM516
7UM61
7UM62

Generator and
motor protection

Generator protection

1 Product Selection

ANSI No.*

Description

67

Directional overcurrent

67N

Directional earth-fault overcurrent

67G

Stator earth-fault
directional overcurrent

68

Out-of-step protection

74TC

Trip circuit supervision

78

Out-of-step protection

79

Auto-reclosure

81

Frequency protection

81R

Protection functions

Type

Rate of frequency change protection

Vector jump supervision

85

Carrier interface/remote trip

86

Lockout function

87G

Differential protection generator

87T

Differential protection transformer

87BB

Differential protection busbar

87M

Differential protection motor

87L

Differential protection line

87N

Restricted earth-fault protection

Standard function
Option
* ANSI/EEE C 37.2: IEEE Standard Electrical Power System Device Function Numbers
l

Siemens SIP 2004

1/5

11 Generator Protection / 7RW600

SIPROTEC 7RW600
Numerical Voltage, Frequency and Overexcitation Protection Relay
Function overview

Line protection
Voltage protection
Frequency protection
Generator protection

LSP2001-afpen.tif

Voltage protection
Frequency protection
Overexcitation protection
Transformer protection
Voltage protection
Overexcitation protection
Power system decoupling
Voltage protection
Frequency protection
Load shedding
Fig. 11/75 SIPROTEC 7RW600 voltage, frequency and overexcitation protection relay

Description
The SIPROTEC 7RW600 is a numerical
multifunction protection relay for connection to voltage transformers. It can be used
in distribution systems, on transformers
and for electrical machines. If the
SIPROTEC 7RW600 detects any deviation
from the permitted voltage, frequency or
overexcitation values, it will respond according to the values set. The SIPROTEC
7RW600 can be used for the purposes of
system decoupling and for load shedding if
ever there is a risk of a system collapse as a
result of inadmissibly large frequency
drops. Voltage and frequency thresholds
can also be monitored.
The SIPROTEC 7RW600 voltage,
frequency and overexcitation relay can be
used to protect generators and transformers in the event of defective voltage control,
of defective frequency control, or of full
load rejection, or furthermore islanding
generation systems.
This device is intended as a supplement to
Siemens substation systems and for use in
individual applications. It has two voltage
inputs (V; Vx) to which a variety of functions have been assigned. While input V
serves all of the implemented functions,
input Vx is exclusively dedicated to the
voltage protection functions. The scope of
functions can be selected from three
ordering options.

Siemens SIP 2004

Frequency protection
Rate-of-frequency-change protection
Status measured values
Monitoring functions
Hardware
Software
Event logging
Fault recording
Continuous self-monitoring
Hardware
Auxiliary voltages:
24, 48 V DC
60, 110, 125 V DC
220, 250 V DC, 115 V AC
Local operation
LCD for setting and analysis
Housing for
Flush-mounting 1/6 19-inch 7XP20;
Surface-mounting 1/6 19-inch 7XP20
Communication ports
Personal computer
Via RS485 RS232 converter
Via modem
SCADA
IEC 60870-5-103 protocol
Bus-capable

11/79

11

11 Generator Protection / 7RW600

Application
The SIPROTEC 7RW600 is a numerical
multifunction protection relay for connection to voltage transformers. It can be
used in distribution systems, on transformers and for electrical machines.
If the SIPROTEC 7RW600 detects any
deviation from the permitted voltage,
frequency or overexcitation values, it will
respond according to the values set. The
SIPROTEC 7RW600 can be used for the
purposes of system decoupling and for
load shedding if ever there is a risk of a
system collapse as a result of inadmissibly
large frequency drops. Voltage and frequency thresholds can also be monitored.

Fig. 11/76 Function diagram

The SIPROTEC 7RW600 voltage,


frequency and overexcitation relay can be
used to protect generators and transformers in the event of defective voltage
control, of defective frequency control,
or of full load rejection, or furthermore
islanding generation systems.
Applications
ANSI

IEC

Protection
functions

27

V<, t; t = f (V<)

Undervoltage
protection

59 59N V>>, t; V>, t


81 81R

24

11

11/80

f>; f<; -

df

dt

>; +

V
V
>,t ; = f (t )
f
f

Overvoltage
protection
df Frequency
dt protection, rateof-frequencychange protection
Overexcitation
protection

Fig. 11/77

Siemens SIP 2004

11 Generator Protection / 7RW600

Construction

Protection functions

The SIPROTEC 7RW600 relay contains, in


a compact form, all the components
needed for:

Acquisition and evaluation of measured


values
Operation and display
Output of messages, signals and
commands
Input and evaluation of binary signals
Data transmission (RS485) and
Auxiliary voltage supply.
The SIPROTEC 7RW600 receives AC voltages from the primary voltage transformer.
The secondary rated voltage range, 100 to
125 V, is adapted internally on the device.
There are two device variants available:

The first version, for panel flush


mounting or cubicle mounting, has its
terminals accessible from the rear.
The second version for panel surface
mounting, has its terminals accessible
from the front.

Overvoltage protection
The overvoltage protection has the function of detecting inadmissible overvoltages
in power systems and electrical machines
and, in such event, it initiates system
decoupling or shuts down the generators.
Two voltage measuring inputs (V, Vx) are
provided on the unit. These must be connected to two phase-to-phase voltages. The
input voltages are processed separately in
two two-stage protective functions. From
these, two principle connection variants
are derived.
Fig. 11/81, Fig. 11/82, and Fig. 11/83, on
page 11/83, show the following connection
examples:
Fig. 11/81:
Separated connection, used for overvoltage
protection and earth-fault detection
Fig. 11/82:
Two-phase connection to a voltage
transformer
Fig. 11/83:
Alternative V connection

LSP2002-afpen.tif

Undervoltage protection

Fig. 11/78
Rear view of surfacemounting case

The main function of the undervoltage


protection is protecting electrical machines
(e.g. pumped-storage power generators
and motors) against the consequences of
dangerous voltage drops. It separates the
machines from the power system and thus
avoids inadmissible operating states and
the possible risk of stability loss. This is a
necessary criterion in system decoupling.
To ensure that the protection functions in
a physically correct manner, when used in
conjunction with electrical machines, the
positive-sequence system must be evaluated.
The protection function can be blocked,
via a binary input, causing a drop in energizing power. The auxiliary contact of the
circuit-breaker can be used for this purpose with the circuit-breaker open. Alternatively, undervoltage acquisition can be
activated on a conductor-separated basis
(V<,Vx< ).
Additionally, it is possible to use an
inverse-time undervoltage protection
function for motor protection. The tripping time depends in the undervoltage
drop. A time grading is possible.

Siemens SIP 2004

Frequency protection
The frequency protection can be used to
protect against overfrequency or against
underfrequency. It protects electrical
machines and plants/substations against
adverse effects in the event of deviations in
the rated speed (e.g. vibration, heating,
etc.), detects and records frequency fluctuations in the power system, and disconnects certain loads according to the
thresholds set. It can also be used for the
purposes of system decoupling, and thus
improves the availability of in-plant power
generation.
The frequency protection function is
implemented via voltage input V. From
the sampled voltage, the frequency is measured by means of various filter functions.
The system thus remains unaffected by
harmonics, ripple control frequencies and
other disturbances.
The frequency protection function operates
over a wide frequency range (25-70 Hz).
It is implemented (optionally for overfrequency or for underfrequency) on a fourstage basis; each stage can be individually
delayed. The frequency stages can be
blocked either via the binary input or by
an undervoltage stage.
Rate-of-frequency-change protection
The rate-of-frequency-change protection
calculates, from the measured frequency,
the gradient of frequency change df/dt. It
is thus possible to detect and record any
major active power overloading in the
power system, to disconnect certain consumers accordingly, and to restore the
system to stability. Unlike frequency protection, rate-of-frequency-change
protection already reacts before the frequency threshold is undershot. To ensure
effective protection settings, power system
studies are recommended. The rate-of-frequency-change protection function can
also be used for the purposes of system
decoupling.
The rate-of-frequency-change protection
function is implemented on a four-stage
basis; each stage can be individually
delayed. It detects and records any negative or positive frequency gradient. The
measured result is generally released as
soon as the rated frequency is undershot
or overshot.
Rate-of-frequency-change protection can
also be enabled by an underfrequency or
overfrequency stage.

11/81

11

11 Generator Protection / 7RW600

Protection functions
Overexcitation protection
The overexcitation protection detects and
records any inadmissibly high induction
V
(B ~ )
f
in electrical equipment, e.g. generators or
transformers, that may occur as a result of
a voltage increase and/or frequency drop.
Increased induction of this nature may
lead to saturation of the iron core, excessive eddy current losses, and thus to inadmissible heating.
It is recommended to use the overexcitation protection function in power systems
subject to large frequency fluctuations
(e.g. systems in island configuration or
with weak infeed) and for electrical block
units that are separated from the system.
The overexcitation protection function
calculates, from the maximum voltage (V,
Vx) and the frequency, the ratio V/f. This
function incorporates an independent
warning and tripping stage and a curve
which is dependent on and adaptable to
the object to be protected and which takes
due account of the objects thermal behavior. Incorrect adaptation of the voltage
transformer is also corrected. The overexcitation protection function is effective
over a broad frequency range (25 to 70 Hz)
and voltage range (10 to 170 V).

Fig. 11/79 Tripping range of overexcitation protection

Features

11

Serial data transmission


The SIPROTEC 7RW600 relay is fitted
with an RS485 port, via which a PC can
be connected, thus providing, in conjunction with the DIGSI operating and
analysis program, a convenient tool for
configuring and parameter setting. The
DIGSI program (which runs under
MS-Windows) also performs fault recording and fault evaluation. The
SIPROTEC 7RW600 relay can also be
linked, via the appropriate converters,
either directly or over an optoelectronic
connection (optical fiber) to the interface
of the PC or substation control system
(IEC 60870-5-103 protocol).

11/82

Fig. 11/80 Wiring communication

Siemens SIP 2004

11 Generator Protection / 7RW600

Connection diagrams

Fig. 11/81
Connection of a phase-to-phase voltage V
and a displacement voltage Vx

Fig. 11/82
Connection of two phase-to-phase voltages V
to one voltage transformer set

Fig. 11/83
Connection to voltage transformers in V-configuration

Fig. 11/84
Communication port

11

Fig. 11/85
Typical auxiliary voltage wiring

Siemens SIP 2004

11/83

11 Generator Protection / 7RW600

Technical data
Hardware

Serial port (isolated)

Measuring circuits (v.t. circuits)

Type

Rated voltage VN

100 to 125 V

Test voltage

2 kV AC for 1 min

Rated frequency fN

50 or 60 Hz

Connections

Data cable at housing, two data


wires, one frame reference for connection of a PC or similar

Transmission speed

At least 1200 baud, max. 19200 baud

Dynamic range

170 V

Power consumption

0.2 VA

Thermal overload capacity,


continuous
for 10 s

200 V
230 V

Unit design
Case 7XP20

Power supply via integrated DC/DC converter

For dimensions, see dimension


drawings, part 16

Rated auxiliary voltage Vaux

24/48 V DC
60/110/125 V DC
220/250 V DC, 115 V AC

Weight
Flush mounting/cubicle mounting Approx. 4 kg
Surface mounting
Approx. 4.5 kg

Maximum ripple at rated voltage

12 %

Power consumption
Quiescent
Energized

Degree of protection
to IEC 60529/EN 60529

Approx. 2 W
Approx. 4 W

Specifications

Binary inputs

Insulation tests

Number

Voltage range

24 to 250 V DC

Standards

Voltage test (type test)


Over open command contacts

Number of relays, total


Number of relays
with 2-channel energization

Impulse withstand capability


(SWC) test (type test)
All circuits, class III

Contacts per relay (K1 to K5)


Contact for relay (K6)

1 NO contact
1 NC contact or 1 NO contact
(set via jumper)

Command contacts

Switching capacity
Make
Break

1000 W/VA
30 W/VA

Test crosswise:
Measurement circuits, pilot-wire
connections, power supply, binary
inputs, class III, (no tests crosswise
over open contacts, RS485 interface
terminals)

Switching voltage

250 V (AC/DC)

EMC tests, immunity; type tests

Permissible current,
continuous
0.5 s

5A
30 A

Standards

LEDs
Ready-to-operate (green)

Marshallable displays (red)

Fault indication (red)

1.5 kV (rms), 50 Hz
5 kV (peak); 1.2 / 50 s; 0.5 J
3 positive and 3 negative impulses
at intervals of 5 s

IEC 60255-22 (product standard)


EN 50082-2 (generic standard)
DIN VDE 0435, Part 303

High-frequency test
2.5 kV (peak), 1 MHz, = 15 s,
IEC 60255-22-1, class III
400 shots/s duration 2 s
and DIN VDE 0435 Part 303, class III
Electrostatic discharge
IEC 60255-22-2, class III
and IEC 61000-4-2, class III
Irradiation with RF field
Non-modulated, IEC 60255-22-3
(report), class III
Amplitude-modulated,
IEC 61000-4-3, class III
Pulse-modulated,
IEC 6100-4-3, class III

11/84

IEC 60255-5, ANSI / IEEE C37.90.0

Voltage test (routine test)


All circuits except auxiliary
2.0 kV (rms), 50 Hz
voltage and RS485
Auxiliary voltage and RS485 only 2.8 kV DC

17 V, 75 V

2 switching thresholds (adjustable)

IP 51

Electrical test

Maximum bridging time


20 ms at VAUX (24 V DC)
following failure of auxiliary voltage 50 ms at VAUX (110 V DC)

Current consumption, independent Approx. 2.5 mA


of operating voltage

11

RS485

4 kV/6 kV contact discharge,


8 kV air discharge, both polarities,
150 pF, Ri = 330
10 V/m, 27 to 500 MHz
10 V/m, 80 to 1000 MHz,
80 % AM, 1 kHz
10 V/m, 900 MHz, repetition
frequency 200 Hz, duty cycle 50 %

Siemens SIP 2004

11 Generator Protection / 7RW600

Technical data
EMC tests, immunity; type tests

During transport

Fast transients
2 kV, 5/50 ns, 5 kHz, burst length
IEC 60255-22-4 and IEC 61000-4-4, 15 ms, repetition rate 300 ms, both
class III
polarities, Ri = 50 , duration 1 min

Standards

IEC 60255-21 and IEC 60068-2

Vibration
IEC 60255-21-1, class 2
IEC 60068-2-6

Sinusoidal
5 to 8 Hz: 7.5 mm amplitude;
8 to 150 Hz: 2 g acceleration
Sweep rate 1 octave/min
20 cycles in 3 orthogonal axes

Conducted disturbances induced by 10 V, 150 kHz to 80 MHz,


radio-frequency fields, amplitude80 % AM, 1 kHz
modulated, IEC 61000-4-6, class III
Power frequency magnetic field
IEC 61000-4-8, class IV

30 A/m continuous, 50 Hz
300 A/m for 3 s, 50 Hz
0.5 mT; 50 Hz

Shock
IEC 60255-21-2, class 1
IEC 60068-2-27

Oscillatory surge withstand


capability ANSI/IEEE C37.90.1
(common mode)

2.5 kV to 3 kV (peak),
1 MHz to 1.5 MHz, decaying
oscillation, 50 shots per s, duration 2
s, Ri = 150 to 200

Half-sinusoidal
acceleration 15 g, duration 11 ms,
3 shocks in each direction of 3
orthogonal axes

Continuous shock
IEC 60255-21-2, class 1
IEC 60068-2-29

Fast transient surge withstand


capability ANSI/IEEE C37.90.1
(common mode)

4 to 5 kV, 10/150 ns, 50 shots per s,


both polarities, duration 2 s, Ri = 80

Half-sinusoidal
acceleration 10 g, duration 16 ms,
1000 shocks in each direction
of 3 orthogonal axes

Radiated electromagnetic
interference ANSI/IEEE C37.90.2

10 to 20 V/m, 25 to 1000 MHz,


amplitude- and pulse-modulated

High-frequency test
Document 17C (SEC) 102

2.5 kV (peak, alternating polarity),


100, 1, 10 and 50 MHz,
decaying oscillation, Ri = 50

Climatic stress tests

EMC tests, emission; type tests


Standard

EN 50081-* (generic standard)

Conducted interference voltage,


aux. voltage only CISPR 11,
EN 55022, DIN VDE 0878 Part 22,
limit value, class B

150 kHz to 30 MHz

Temperatures
Recommended temperature during
service
Temperature tolerances:
During service
During storage
During transport
(storage and transport in
standard works packaging)

5 to +55 C
(legibility may be impaired
> +55 C)
20 to +70 C
25 to +55 C
25 to +70 C

Humidity

Interference field strength CISPR 11, 30 to 1000 MHz


EN 55011, DIN VDE 0875 Part 11,
limit value, class A
Mechanical stress tests

Permissible humidity stress


It is recommended to arrange the
units in such a way that they are not
exposed to direct sunlight or pronounced temperature changes that
could cause condensation

Annual average 75 % relative humidity, on 30 days during the year 95


% relative humidity, condensation
not permitted!

Vibration, shock stress and seismic vibration


During operation

Functions

Standards

IEC 60255-21 and IEC 60068-2

Undervoltage protection

Vibration
IEC 60255-21-1, class 2
IEC 60068-2-6

Sinusoidal
10 to 60 Hz: 0.035 mm amplitude
60 to 150 Hz: 0.5 g acceleration
Sweep rate 1 octave/min
20 cycles in 3 orthogonal axes

Setting range V<, Vx<Vp<

20 to 120 V (in steps of 1 V)

Delay times

0 to 60 s (in steps of 0.01 s) or


(i.e. non-effective)

Shock
IEC 60255-21-2, class 1
IEC 60068-2-27

Half-sinusoidal
acceleration 5 g, duration 11 ms
3 shocks in each direction of
3 orthogonal axes

Seismic vibration
IEC 60255-21-3, class 1

Sinusoidal
1 to 8 Hz: 4 mm amplitude
(horizontal axis)
1 to 8 Hz: 2 mm amplitude
(vertical axis)
8 to 35 Hz: 1 g acceleration
(horizontal axis)
8 to 35 Hz: 0.5 g acceleration
(vertical axis)
Sweep rate 1 octave/min
1 cycle in 3 orthogonal axes

IEC 60068-2-59

Time multiplier for


inverse characteristic
Pickup time
Reset time
Reset ratio

0.1 to 5 s
50 ms
50 ms
1.05

Tolerances
Voltage pickup
Delay times

3 % of setting value or 1 V
1 % of setting value or 10 ms

Overvoltage protection
Setting range
V>, V>>
Vx>, Vx>>
Delay times

0 to 60 s or (in steps of 0.01 s)

Pickup time
Reset time
Reset ratio

50 ms
50 ms
0.95

Tolerances
Voltage pickup
Delay times

Siemens SIP 2004

20 to 170 V (in steps of 1 V)


10 to 170 V (in steps of 1 V)

3 % of setting value or 1 V
< 1 % of setting value for V > Vn
1 % of setting value or 10 ms

11/85

11

11 Generator Protection / 7RW600

Technical data
Frequency protection

Fault recording

Number of frequency stages f> or f< 4

Instantaneous value fault record


Measured values
Pattern

Setting range f> or f<

40 to 68 Hz (in steps of 0.01 Hz)

Delay times

0 to 60 s or (in steps of 0.01 s)

Undervoltage blocking

20 to 100 V or (in steps of 1 V)

Pickup time f>, f<


Reset times f>, f<
Reset difference
Reset ratio (undervoltage blocking)

Approx. 100 ms
Approx. 100 ms
Approx. 20 mHz
1.05

Tolerances
Frequencies f>, f<
Undervoltage blocking
Delay times

5 mHz at f = fN and V = VN
10 mHz at f = fN
3 % of setting value or 1 V
1 % of setting value or 10 ms

Rate-of-frequency-change protection

Fault record duration


Start signal
R.m.s. fault record
Measured values
Pattern
Fault record duration
Starting signal

V, Vx
1.00 ms (50 Hz)
0.83 ms (60 Hz)
Max. 5 s
Tripping, energization, binary input,
PC
V, Vx, f-fN
10 ms (50 Hz)
8.3 ms (60 Hz)
Max. 50 s
Tripping, energization, binary input,
PC

Operational measured values


Measured values

V, Vx, V1, V/f, f

Measuring range voltage


Tolerance

0 to 170 V
2 V or 5 %

0.4 to 10 Hz/s or (in steps of 0.1


Hz/s)

Measuring range overexcitation


Tolerance

0 to 2.4
5%

Delay times

0 to 60 s or (in steps of 0.01 s)

Undervoltage blocking

20 to 100 V or (in steps of 1 V)

Measuring range frequency


Tolerance

25 to 70 Hz
0.05 Hz or 5 MHz at f = fN

Number of
rates-of-frequency-changing stages
Setting range

df
dt

df
dt

Approx. 200 ms

CE conformity

df
Reset ratio pickup
dt

Approx. 0.6

Reset ratio (undervoltage blocking)

1.05

This product is in conformity with the Directives of the European Communities on the harmonization of the laws of the Member States relating to
electromagnetic compatibility (EMC Council Directive 89/336/EEC) and
electrical equipment designed for use within certain voltage limits (Council
Directive 73/23/EEC).

Pickup time

Tolerances
df
Changes of frequencies
dt
In the 45 to 50 Hz range
In the 54 to 60 Hz range

100 mHz/s at fN = 50 Hz and V = VN


150 mHz/s at fN = 60 Hz and V = VN

Undervoltage blocking V<

3 % of setting value or 1 V

Delay times

1 % of setting value or 10 ms

This unit conforms to the international standard IEC 60255, and the German standard DIN 57435/Part 303 (corresponding to VDE 0435/Part 303).
The unit has been developed and manufactured for application in an industrial environment according to the EMC standards.
This conformity is the result of a test that was performed by Siemens AG in
accordance with Article 10 of the Council Directive complying with the
generic standards EN 50081-2 and EN 50082-2 for the EMC Directive and
standard EN 60255-6 for the low-voltage Directive.

Overexcitation protection

11

Warning stage

V / VN
f / fN

1 to 1.2 (in steps of 0.01)

Tripping stage

V / VN
f / fN

1 to 1.4 (in steps of 0.01)

Delay times,
warning and tripping stages
Curve values V/f
Associated delay times
Cooling-down time

0 to 60 s, or (in steps of 0.01 s)


1.1 / 1.15 / 1.2 / 1.25 / 1.3 / 1.35 / 1.4
0 to 20000 s (in steps of 1 s)
0 to 20000 s (in steps of 1 s)

Voltage transformer adaption factor 0.5 to 2 (in steps 0.01)


Pickup response time (stage curve)

50 ms

Reset time (stage curve)


Reset ratio

60 ms
0.95

Tolerances
Overexcitation V/f
Delay times (stage curve)
Delay times (dependent curve)

3 % of setting value
1 % of setting value or 10 ms
5 % with respect to V/f value 0.5 s

11/86

Siemens SIP 2004

11 Generator Protection / 7RW600

Selection and ordering data

Description

Order No.

7RW600 numerical voltage, frequency and


overexcitation protection relay

7RW6000-A0-A0

Rated auxiliary voltage


24, 48 V DC
60, 110, 125 V DC
220, 250 V DC, 115 V AC
Unit design
For panel surface mounting, terminals on the side
For panel flush mounting/cubicle mounting, terminals on the rear

2
4
5
B
E

Languages
English
German
Spanish
French

0
1
2
3

Scope of functions
Voltage and frequency protection
Voltage, frequency and rate-of-frequency-change protection
Voltage and overexcitation protection

0
1
2

Serial system interface


With RS485 port

Accessories

DIGSI 4
Software for configuration and operation of Siemens protection units
running under MS Windows (version Windows 95 and higher)
device templates, Comtrade Viewer, electronic manual included
as well as Getting started manual on paper, connecting cables (copper)
Basis
Full version with license for 10 computers, on CD-ROM
(authorization by serial number)

7XS5400-0AA00

Demo
Demo version on CD-ROM

7XS5401-0AA00

Professional
Complete version:
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation)

7XS5402-0AA00

11

SIGRA
(generally contained in DIGSI Professional, but can be ordered additionally)
Software for graphic visualization, analysis and evaluation of fault records.
Can also be used for fault records of devices of other manufacturers
(Comtrade format). Running under MS Windows 95/98/ME/NT/2000/XP Professional.
Incl. templates, electronic manual with license for 10 PCs.
Authorization by serial number. On CD-ROM.
7XS5410-0AA00
Converter V.24 - RS485*
With communication cable for the SIPROTEC 7RW600
numerical voltage, frequency and overexcitation relay; length 1 m
With plug-in power supply unit 230 V AC

7XV5700-0oo00 1)

With plug-in power supply unit 110 V AC

7XV5700-1oo00 1)

Converter, full-duplex FO cable, RS485, with built-in power supply unit


Auxiliary voltage 24 - 250 V DC and 110 / 230 V AC
Manual for 7RW600
English

7XV5650-0BA00

C53000-G1176-C117-4

1) Possible versions see part 14, page 14/61


* RS485 bus system up to 115 kbaud
RS485 cable and adaptor
7XV5103-oAAoosee part 14,
page 14/5

Siemens SIP 2004

11/87

11 Generator Protection / 7RW600

Connection diagrams
Fig. 11/86
Connection circuit
diagram of 7RW600
voltage and frequency
protection with presetting of marshallable
binary inputs and
command contacts.
(Ordering Code:
7RW600x-xBxxx-;
7RW600x-xExxx-).

Fig. 11/87
Connection circuit
diagram of 7RW600
voltage and overexcitation protection with
presetting of
marshallable binary inputs and command
contacts.
(Ordering Code:
7RW600x-xBxxx-;
7RW600x-xExxx-).

11

11/88

Siemens SIP 2004

11 Generator Protection / 7RW600

Dimension drawings in mm / inch


Dimension drawings for 1/6 x 19" housing (7XP20)

Side view

View from the rear

Panel cutout

Fig. 16/15
Housing for panel flush mounting/
cubicle mounting, terminals at rear (1/6 x 19")

11

Front view

Side view

Fig. 16/16
Housing for surface mounting,
terminals at top and bottom (1/6 x 19")

Siemens SIP 2004

11/89

11 Generator Protection / 7RW600

Dimension drawings in mm / inch


Dimension drawings for 1/6 x 19" housing (7XP20)

Front view

Side view

Fig. 16/17
Housing for panel surface mounting, terminals on
the side (1/6 x 19")

11

11/90

Siemens SIP 2004