Nitoflor Conductive
Nitoflor Conductive
Nitoflor Conductive
constructive solutions
Design criteria
Description
Electrical properties
Surface resistance
(ASTM F150-78):
Bulk resistance:
(DIN 51953)
(ASTM F150-78)
Charge decay (Fed. Spec.
101 C Method 4046):
Body voltage decay
(Stephen Halperin &
Associates Ltd):
60 N/mm2
2
40 N/mm
2
18 N/mm
97 mg weight loss
0.03 mm depth to
wear
0.2 mm indentation
20oC
35oC
24 hrs
18 hrs
48 hrs
36 hrs
4
6
5 x 10 to 1 x 10 ohms
4
6
5 x 10 to 1 x 10 ohms
4
5 x 10 to 1 x 106 ohms
5000 v to zero in less
than 0.1 seconds.
5000 v to Zero in 0.4
seconds using
conductive heel straps or
conducive shoes.
Chemical properties
Nitoflor Conductive provides excellent resistance to a wide
range of industrial chemicals.
For details of specific chemical resistance, consult the local
Fosroc office.
Page 1
Nitoflor Conductive
Maintenance
The service life of a floor can be considerably extended by
good housekeeping and regular cleaning. The ability of a
conductive floor to effectively control static electricity can be
affected by a surface layer of dirt, grease or other residue.
Nitoflor conducting floors should not be treated with waxes
or polishes. For specific floor maintenance schedules
consult the local Fosroc office.
Application clauses
Application instructions
Nitoflor Conductive should be installed by specialist
applicators who must follow the procedures laid down in the
Product Application Guide. Fosroc works with a network of
such applicators who have been fully trained in the correct
installation procedures.
The following steps are involved which would normally take
place over a 3 to 5 day period.
Thoroughly prepare the floor surface. Correct surface
preparation helps to achieve the necessary adhesive
bond between the substrate and the new floor.
All existing expansion or movement joints should be
followed through the new coating surface. Joints should
be cleaned and prepared.
Apply Nitoprime 25 and Nitoprime 30 and allow to cure.
Porous substrates may require two coats of primer.
Install joint and earthing connections in full accordance
with Fosroc's Product Application Guide.
Apply Nitoflor Conductive Undercoat. This provides a
conductive passage to earth and correct application and
strict adherence to coverage rates are critical to the final
electrical properties of the completed floor.
constructive solutions
11.8 kg packs
17.7 kg sacks
0.5 kg packs
30 kg packs
5 kg packs
5 kg packs
5 litre pack
Coverage
Page 2
2
18 m /packa at 2
mm thickness
2
35 m / pack
2
5 m / pack
2
5 m / pack
Nitoflor Conductive
The coverage figures given are theoretical due to wastage
factors and the variety and nature of possible substrates,
particle coverage figures will be reduced. Typically, an
additional 10% should be allowed for surface irregularities
and wastage although this will vary with site conditions.
UN packaging regulations
To comply with current regulations, all products of a
hazardous nature which are subjected to a sea crossing as
part of their delivery requirements, must be packed in UN
approved receptacles.
When a known sea crossing is involved, whether locally or
for export, Fosroc will supply in the correct UN packaging.
Where Fosroc are requested to deliver within a mainland
boundary but the Purchaser intends to onward ship, it is
incumbent upon the Purchaser to specify that UN packaging
is required at the time of placing the order.
39oC
o
59 C
o
33 C
Disposal
Storage
Storage conditions
Additional information
Shelf life
o
o
Store in dry conditions between 5 C and 30 C, away from
sources of heat and naked flames, in the original, unopened
packs. If stored at high temperatures the shelf life may be
reduced.
Precautions
Health and safety
Nitoflor Conductive, Nitoflor Conductive Undercoat,
Nitoprime 25, Nitoprime 30 and Fosroc Solvent 102 should
not come in contact with skin or eyes, or be swallowed.
Ensure adequate ventilation and avoid inhalation of vapors.
Some people are sensitive to resins, hardeners and
solvents. Wear suitable protective clothing, gloves and eye
protection. If working in confined areas, suitable respiratory
protective equipment must be used.
The use of barrier
Important note:
Fosroc products are guaranteed against defective materials and manufacture and are sold subject to its standard Conditions for
the Supply of Goods and Services, copies of which may be obtained on request. Whilst Fosroc endeavours to ensure that any
advice, recommendation, specification of information it may give is accurate and correct, it cannot, because it has no direct or
continuous control over where or how its products are applied, accept any liability either directly or indirectly arising from the use
of its products, whether or not in accordance with any advice, specification, recommendation of information given by it.
www.fosroc.com
email: [email protected]
Regional Offices
Jeddah Sales Office
Jeddah Showroom
Riyadh
Dammam
Khamis Mushayt
Yanbu
Makkah
Medinah
Jubail
CSD
Registered Office: Industrial Area, Phase 4, Road No. 414, Street No. 407
Page 3
FO SA/NITOFLOR CONDUCTIVE/05/A