Manual For HRV
Manual For HRV
Manual For HRV
Fan
Fan
Filter mesh
Heating exchanged core
Fan
15002000
1500
2000 Air volume
Fan
Wire control box
Filter mesh
Heating exchanged core
CONTENTS
PAGE
PRECAUTIONS........................................................................................1
ACCESSORY........................................................................................... 1
INSTALLATION........................................................................................ 2
WIRING...................................................................................................6
SPECIFICATION PARAMETER................................................................ 10
HRV APPLICATION................................................................................ 15
MAINTENANCE & UPKEEP.................................................................... 15
Make sure Earth Leakage Breaker is the type of all poles drop-out.
Be sure to ground.
Do not connect the ground wire to gas or water pipes, lightning rod
or a telephone ground wire.
Incomplete grounding may result in electric shocks.
Make sure that all wiring is secured, the specified wires are used,
and no external forces act on the terminal connections or wires.
Improper connections or installation may result in overheating or
fore.
When wiring the power supply and connecting the remote
controller wiring and transmission wiring, position the wires so that
the electric parts box lid can be securely fastened.
Improper positioning of the electric parts box lid may result in
electric shocks, fire or the terminals overheating.
TRAIL RUN.............................................................................................15
CAUTION
1.
PRECAUTIONS
WARNING
Failure to observe a warning may result in electric shock,
fire hazard or personal injury
CAUTION
Failure to observe a caution may result injury or damage
to the equipment.
2.
WARNING
Ask your dealer or qualified personnel to carry out installa
tion work. Do not try to install the machine yourself.
Improper installation may result in leakage, electric shocks
or fire.
Installation should be done following the installation manual
and no changes should be made to the unit.
Incorrect installation may cause leaking, electric shock, or
incorrect installation may cause leaking, electric shocks, or
fire. Injuries may result if the HRV falls.
Install the unit on a foundation strong enough to withstand
the weight of the unit.
A foundation of insufficient strength may result in the
equipment falling and causing injuries.
Do not allow exhaust air to enter the outside air intake vent.
This may cause the air of the room to become contami
nated, harming the health.
Locate the outside air intake vent so that it does not take in
exhaust air which contains combustion air, etc.
Incorrect installation may cause a loss of oxygen in the
room, leading to serious accidents.
Make sure that a separate power supply circuit is provided
for this unit and that all electrical work is carried out by
qualified personnel according to local laws and regulations
and this installation manual.
An insufficient power supply capacity or improper electrical
construction may lead to electric shocks or fire.
Insufficient power supply capacity or incorrect wiring may
cause electrical shocks or fire.
ACCESSORY
Table 2-1
Name
Qty.
Shape
Purpose
Installation
and owners
manual
This
manual
Butt-joint wire
of wire control
display panel
(6 meters)
(RoHS)
HRV wire
controller
(RoHS)
Name
Purpose
I&O manual
3.
INSTALLSTION
WARNING
The accessories needed for installation must be retained in
your custody until the installation work is completed. Do not
discard them.
NOTE
3.3 Preparations Before Installation
Be sure to instruct customers how to properly operate the unit
(especially maintenance of air filter, and operation procedure)
by having them carry out operations themselves while looking
at the, manual.
CAUTION
When moving the unit during or after unpacking, make sure to
lift it by holding its hanger brackets. Do not exert any pressure
on other parts, especially duct connecting flange.
Wooden
Wooden
structure
structure
Put rectangular sticks across the beams, and set pendant bolts.
Wooden span
Beam
Ceiling
CAUTION
Install the units, power supply wiring and connecting wires
at least 1 meter away from televisions or radios in order to
prevent image interference or noise. (Depending on the
radio waves, a distance of 1 meter may not be sufficient
enough to eliminate the electric noise.)
Pendant bolt
3.4 Installation
Before installation, please confirm all external parts are
stand in their place and without damage.
Suspended bolt
Pendant bolt
Concrete iron
Embedded bolt
(With embedded
bolt in pipe)
OPERATION
Fig. 3-2
-7
~43
Room TEMP .
-7
~43
Room humidity
Protection device may start if running the unit outside the above
condition, which will prevent the unit from operation.
Unitmm
1000
450
Operating conditions
400
450
Maintenance space
W
I&O manual
6. Key dimensions of the unit and air duct installation. (See the following attached picture Fig.3-4~3.7 & Table 3-1 )
HRV-200
666
264
Wire
control
box
75
Lifting lug
Door
144
580
20
100
290
Air return
vent
By-pass
system
510
Air supply
vent
725
Fig. 3-4
HRV-300~HRV-1000
W
N2
Wire
control
box
Door
75
W2
By-pass
system
Air return
vent
W1
Air supply
vent
L1
Fig. 3-5
Table 3-1
I&O manual
Model
L1
W1
W2
N2
HRV-300
744
675
599
657
315
270
100
19
144
111
HRV-400
744
675
804
862
480
270
100
19
144
111
HRV-500
824
754
904
960
500
270
107
19
194
111
HRV-800
1116
1045
884
940
428
388
85
19
242
170
HRV-1000
1116
1045
1134
1190
678
388
85
19
242
170
HRV-1500
1200
1500
Wire
control
box
Door
540
600
250
Flange demension
300
1170
350
Air supply
vent
326
20
1550
Air return
vent
50
50
120
1600
320
346
370
Fig. 3-6
HRV-2000
1550
1400
Wire
control
box
Door
540
700
250
1600
20
Flange demension
50
300
326
1370
350
Air supply
vent
Air return
vent
50
1650
120
320
346
370
Fig. 3-7
I&O manual
4.
WIRING
Table 4-2
WARNING
Model
HRV-
Power supply
Table 4-1
Tightening torque (Nm)
Terminal base of remote controller/
Signal transmission wire (X2M)
Terminal base of power supply (XIM)
Grounding terminal (M4)
I&O manual
0.79-0.97
1.18-1.44
1.44-1.94
1500, 2000
Signal phase
Three phases
Frequency 220-240V/50Hz
220-240V/60Hz
/voltage
380-415V/50Hz
220-240V/60Hz
Phase
Input current
Main switch
/fuse(A)
15/15
15/15
3 (Yellow/green
5 (Yellow/green
wire
is
grounding
wire is grounding
Wires qty
wire)
wire)
Code wire
cross
-section
(mm2)
2.5
2.5
HRV Electric
Control Box
Signal
Receiving
Board
Electric Control
Box s terminal CN10
10-core
Connecting
Wire Group
5-core Connecting
Group
Signal
Receiving
Board
A BC D E
Grounding
Connecting
to wire controller
Fig. 4-1
Wire Controller
Bottom Cover
Wood Mounting
Screw (M420)
When installing the Wire Controller Cover,be
sure there is a hole in the wall to avoid the Wire
Controller Back Cover being fixed directly to the
wall which is not allowed for the Wire Joint
extrudes out of the Wire Controller Back Cover
When installing the Wire Controller, you should adjust the bottom of the Wire Controller Board to
the Wire Controller Back Cover which should be fixed first, then press the other end of the Wire
Controller Board.
Fig. 4-2
CAUTION
1. Never turn screws too tightly, or else the cover would be dented or the Liquid Crystal breaks.
2. Please leave enough space for maintain and upkeep the wire controller.
I&O manual
Display board
Jointion
Wire
controller
Transformer
CN1
Green/Yellow
Power supply
Capacity1
Supply
Fan
Capacity2
By-pass
valve
Exhaust
Fan
XP2
XS2
2-way
terminal base
Black
Network modular
Red
Communicate with
centralized controller
Fig. 4-3
Display board
Jointion
Wire
controller
CN1
Transformer
Brown
Brown
Brown
Mid-terminal base
Yellow
Blue
Black
Red
White
Blue
Blue
White
By-pass
valve
Relay 2
Relay 1
Current inductor
Red
Blue
Black
Red
White
4-way
terminal base
Network modular
Yellow
Black
Brown
Yellow
Green/Yellow
White Red Black
Supply
Fan
Green/Yellow
Power supply
Exhaust
Fan
Green/Yellow
Fig. 4-4
I&O manual
Communicate with
centralized controller
XP2
XS2
Current inductor
Yellow
Display board
XP1 XS1
Wire
controller
CN1
Transformer
Brown
Brown
Brown
Mid-terminal base
Yellow
Mid-terminal base
Yellow
Black
Black
Red
White
By-pass
valve
Red
Relay 2
Relay 1
Blue
Blue
White
Black
Black
Black
Current inductor
Network modular
Brown
4-way
terminal base
Yellow
XP2
XS2
Current inductor
Yellow
Green/Yellow
Black
White Red Black
Power supply
Supply
Fan
Exhaust
Fan
Green/Yellow
Communicate with
centralized controller
Green/Yellow
Fig. 4-5
No.
Operation
lamp
Timer
lamp
Defrosting
lamp
Alarm
lamp
Explanation
T4 sensor error
T1 sensor error
Current protection
Phase absent,
phase error
Note:
I&O manual
5.
SPECIFICATION PARAMETER
Model
Power
supply
HRV-200
HRV-300
HRV-400
HRV-500
220-240V
50Hz/
220-240V
60Hz
HRV-800
HRV-1000
HRV-1500
HRV-2000
380-415V
3N~ 50Hz/
220-240V
3N~ 60Hz
Outline
demension
Air outlet
vents demen Weight (kg)
-sion (mm)
Static
pressure
(Pa)
866655264
144
23
75
200
944722270
144
26
75
300
944927270
144
31
80
400
10381026270
194
41
80
500
12861006388
242
62
100
800
12861256388
242
79
100
1000
16001270540
346326
163
160
1500
16501470540
346326
182
170
2000
Table 4-5
Cooling
Model
Input power(kW)
Heating
Current(A)
50Hz
60Hz
50Hz
60Hz
HRV-200
60
50
65
55
0.09
0.42
HRV-300
60
50
65
55
0.12
0.55
HRV-400
60
50
65
60
0.14
0.20
0.7
1.0
HRV-500
60
50
70
60
0.19
0.26
0.9
1.2
HRV-800
60
50
70
60
0.43
0.50
2.0
2.3
HRV-1000
60
50
70
60
0.48
0.58
2.2
2.8
HRV-1500
60
50
70
60
0.93
1.74
2.5
5.9
HRV-2000
60
50
70
60
1.12
1.83
2.6
6.1
note
1For the units model of HRV-*(*=2001000)there are 3-speed
adjustable air-volume HiMedLowbut for the units model of
HRV-*(*=15002000)there are only 1-speed air-volume which do not
be adjust.
2For the units model of HRV-*(*=2001000)all the parameters in
the manual is measured at the high speed air-volume.
I&O manual
10
Static pressure
(Pa)
Brake power
(W)
75
207
20
60
215
20.3
40
320
21
20
241
21.3
255
22
270
260
250
240
230
220
210
200
20
40
60
80
100
120
150
170
HRV-200
Fig. 5-1
Static pressure
(Pa)
Brake power
(W)
75
297
39
60
309
40
40
331
41
20
346
42
366
43
360
350
340
330
320
310
300
290
20
40
60
80
100
120
150
170
HRV-300
Fig. 5-2
I&O manual
11
Static pressure
(Pa)
Brake power
(W)
80
407
79
60
454
81
40
499
83
20
543
84
586
87
750
700
650
600
550
500
450
400
20
40
60
80
100
120
150
170
HRV-400
Fig. 5-3
Static pressure
(Pa)
Brake power
(W)
80
507
118
60
527
120
40
560
124
20
580
126
620
130
675
650
625
600
575
550
525
500
20
40
60
80
100
120
150
170
HRV-500
Fig. 5-4
I&O manual
12
Static pressure
(Pa)
Brake power
(W)
100
829
357
80
862
363
50
923
375
25
966
381
1021
392
1150
1100
1050
1000
950
900
850
800
20
40
60
80
100
120
150
170
HRV-800
Fig. 5-5
Static pressure
(Pa)
Brake power
(W)
150
980
358
120
1020
382
75
1090
405
40
1140
431
1206
454
1300
1250
1200
1150
1100
1050
1000
950
20
40
60
80
100
120
150
170
HRV-1000
Fig. 5-6
I&O manual
13
Static pressure
(Pa)
Brake power
(W)
160
1460
885
130
1590
944
90
1700
1000
50
1880
1064
2006
1120
2150
2050
1950
1850
1750
1650
1550
1450
20
40
60
80
100
120
150
170
HRV-1500
Fig. 5-7
Static pressure
(Pa)
Brake power
(W)
170
1920
1072
130
2090
1144
90
2235
1213
50
2472
1289
2618
1360
2620
2520
2420
2320
2220
2120
2020
1920
20
40
60
80
100
120
150
170
HRV-2000
Fig. 5-8
I&O manual
14
6. HRV APPLICATION
6.1 Operation Priciple
HRV seriesHRV (Heat Recovery Ventilation) employ
advanced technique and technics, the heat exchanged
core forming by special paper that be processed with
chemical treatment, which could create the optimum result
in temperature, humidity and cooling recovery.
High efficiency heat exchanged core: When air flow formed
by exhaust air and outdoor air through the heat exchanged
core in cross way, because of temperature difference in
the two sides of flat partition board, the heat transmission
is occurred. In summer, outdoor air acquire cooling from air
exhaust to decrease environment temperature; In winter,
outdoor air acquire heating from air exhaust to increase
temperature, that is to say, it realizing the energy recovery
during air exhaust process to exchange the heating in
heat exchanged core to outdoor air.
8. TRIAL RUN
8.1 Please Confirm The Following Points
Before The Test Operation:
8.1.1 The unit is installed correctly completed.
8.1.2 Tubing and wiring are correctly completed.
8.1.3 The drainage is unimpeded.
8.1.4 The heating insulation works well.
8.1.5 The ground wiring is connected correctly.
8.1.6 The power voltage fits the rated voltage of HRV.
8.1.7There is no obstacle at the outlet and inlet of HRV.