ACMV Services
ACMV Services
ACMV Services
I.
The Air-Cooled Split-Type Air Conditioner shall compose of an indoor unit and an
air-cooled outdoor unit. The indoor unit shall include an evaporator, an evaporator
fan, a fan motor, and an auxiliary control component enclosed in a cabinet
for indoor installation. The air-cooled outdoor unit shall include a condenser, a
condenser fan, a compressor, and other components enclosed in a weatherproof
cabinet. Both units shall be properly assembled, internally wired, thoroughly tested,
and charged with R-22 refrigerant at the factory and shall comply with relevant
standard.
The indoor cabinet shall be constructed of finished steel, baked resin paint for a
bottom panel and a top panel, and reinforced plastic for side panels and front grilles.
The cabinet interior shall be insulated by incombustible and self-extinguishable
diabetic material. The service panels shall be easily removal for service access to the
unit components. Facility of auto louver shall be incorporated.
The evaporator coil shall be the multi-pass cross-finned tube type, equipped with
aluminum plate fins, mechanically bonded to seamless oxygen-free copper tubes.
The fins shall be spaced at more than 12 fins per 25 mm. The coil shall be cleaned,
dehydrated and tested for leakage at the factory.
The evaporator fan shall be the forward-curved centrifugal type, statically and
dynamically balanced, and directly driven by a motor. The fan motor shall be
permanently lubricated.
A filter shall be of washable type and equipped at the air intake of the unit.
The outdoor cabinet shall be constructed of finished steel, baked with synthetic resin
paint. The fan guard wire net shall be mounted on top of the unit.
The condenser coil shall be the multi-pass cross-finned type, equipped with aluminum
plate fins mechanically boned to seamless oxygen-free copper tubes. The coil shall
be cleaned, dehydrated and tested for leakage at the factory.
The condenser fan shall be an aluminum propeller type, statically and dynamically
balanced, and the fan shall be directly driven by a motor for up-flow air discharge.
The motor shall be permanently lubricated, and shall be protected from water
invasion.
ACS-1
The
unit shall contain a hermetic
multi-cylinder
reciprocating compressor.
The compressor shall be a star-delta type, and equipped with vibration-proof rubber.
The hermetic compressor shall be a welded shell type, and shall be spring suspended
internally. The compressor shall be protected against a breakdown by the overcurrent
relay, pressure switch and a built-in internal thermostat.
The magnetic switch box incorporated in the unit shall contain magnetic contactors
for all motors, including condenser fan motor overcurrent relays; three minutes restart delay circuit and auxiliary relays.
All drain & refrigerant pipes and electrical wiring shall run in electrical trunking.
The refrigerant pipe work material shall be of copper and the drain pipe shall be of
PVC. All insulated pipe work shall be with 19 mm or thicker thickness of high
quality closed cell insulation tubing to prevent water condensation on the insulation.
The thermal conductivity shall not exceed 0.26 Btu/hr ft/deg. F/in or 0.0374 w/mk.
II.
MANUFACTURERS WARRANTY
During the first year after hand-over, should the compressor for any Air-conditioning
System develop any fault, it shall be replaced with a brand new one inclusive of gas.
After the first year, the compressor shall continue to carry a warranty in accordance
with the manufacturers terms and conditions.
The manufacturers warranty card shall be submitted and handed over to the Engineer
together with the air-conditioner.
III.
The Contractor shall at his own expense, provide the necessary skilled labour,
facilities and materials for the testing, balancing, control setting and commissioning
of the air-conditioning system under this Contract.
The Contractor shall in general, carry out his own test and satisfy himself that the test
has been satisfactory prior appointment for the Engineer or his representative to
witness the test.
All successful tests shall be witnessed by the Engineer or his representative.
Tests to be carried out after complete installation shall be as specified hereunder.
ACS-2
1.0
1.1
GENERAL
Unit shall be Air-Cooled, SMMS Type Air Conditioner consisting of one outdoor unit and
multiple indoor units, each having capability to cool independently of requirements of the
rooms.
COP of 4.25 (8HP CDU system, heating operation) achieved by Toshibas unrivalled
Super Modular Multi System (SMMS) technologies and newly developed components.
Part load operation. A VRF system can achieve energy efficient operation especially in a
separated room layout as shown. Not all of the indoor units operate at the same time so
the system is almost always operating with a partial indoor unit load.
New high-performance bell mouth with smooth flow. Enlarged suction radius provides
smoother flow.
DC fan motor- Pressure fluctuations due to interference have been suppressed. Efficiency
is high, and noise has been reduced. High output / high-efficiency DC motor.
Vector-controlled inverter. The inverter boosts efficiency by controlling R410A and a
twin-rotary DC compressor. Efficient circuit built-in; new PIM and Smooth sine curve
realizes higher efficiency and less noise.
SMMS high performance COP. Partial load performance is the most important value for a
VRF with fluctuating performance due to changes in the number of units operating and/or
fluctuations in the air conditioning load.(10050% partial load operation)
New large-diameter propeller fan (flash wing fan). Enlarged fan diameter 630 710.
The concave leading edge of the fan blades reduces flow interference between adjacent
blades.
Outdoor heat-transfer.
- Compact heat-transfer tube with intakes on four sides.
- Heat-transfer tube with improved heat-transfer coefficient of the inner surface.
- Configuration of the finned heat-transfer tube.
R410A refrigerant is using for SMMS system. An ozone layer depletion coefficient of
zero has become absolutely essential for an advanced air conditioning system.
Twin-rotary DC compressor Two DC twin-rotary compressors (dual configuration) are
equipped per module (basic outdoor unit).
DC driven motor with rare earth magnet
- Compact- Higher efficiency
- Higher power motor torque
Precise manufacturing technology in the compression parts
- Higher efficiency (in wide range)
- Higher reliability
AS -1
1.3
1.4
1.5
FLEXIBLE BRANCHING
The versatility of the SMMS means that virtually any imaginable configuration of the
refrigerant Y-type branches and/or header piping can be used in an application to give the
shortest, most cost-effective piping installation. The piping can be run in any direction to
facilitate refurbishment work. The diameter of the liquid and gas pipes is reduced due to
the utilization of R410A refrigerant (in some units). More effective use of pipe shafts is
also possible, resulting in greater savings in installation costs.
AS -2
1.6
1.7
1.8
AS -3
2.0
REFRIGERANT CIRCUIT
The refrigerant circuit shall include an accumulator, liquid and gas shut off valves
solenoid valves and an electronic expansion valve. All necessary safety devices should be
provided to ensure the safety operation of the system.
Contractor shall supply and install all steel sleeves for piping penetrations through walls
partitions, floor slab and structural beams as required. Sleeves shall be as shown and as
specified with particular attention to caulking of the gap between pipes and sleeves to
satisfy fire separation and vibration isolation requirements.
2.1 Accumulator
The cylindrical accumulator shall be constructed from mild steel plates pressed
into shape. The accumulator shall have sufficient capacity to prevent any liquid
refrigerant from flowing back into the compressor suction.
2.2 Safety Devices
The following safety devices shall be part of the condensing unit. High pressure
switch, fuse, crankcase heater, fusible plug, over current relay for compressor,
thermal protectors for compressor and fan motors, recycling guard timer,
Compressor discharge gas temperature protection, Negative phase protection,
defective phase protection, Undervoltage protection Compressor contactor
chattering protection, Power transformer overheating protection & Abnormal high
pressure protection.
2.3 Pressurize Testing
The complete refrigerant circuit should be subjected to a pressure test of 28.0 kg
sq. cm. for at least 24 hours without any drop in pressure.
2.4 Pipe Materials
The refrigerant pipe shall be of de-oxidized phosphorous seamless copper pipe
conform to JIS H300 - C1220T.
The refrigerant (suction) piping shall be copper-gard pre-insulated pipe factory
fabricated using Single Machine-Injected System for Polyurethene Foam. The
Copper Tube Standard shall be AS1571/NZS 1571. The insulation shall be
machine injected polyurethane foam with a minimum overall density of 45Kg/m.
An environmental friendly gas shall be used as the blowing agent. The properties
of the polyurethane foam:
1)
Thermal conductivity, K-value : 0.017Kcal/m.h c
2)
Density
: 45kg/m
3)
Blowing agent used
: R141b gas ( cfc free )
The Standard Jacket Material used shall be Galvanised Steel Spiral lock-seam duct
with a minimum thickness of 1.5mm .
1 inch insulation with equivalent density of at least 0.0374 W/mK as per ASTM
C177 standard shall be used for discharge piping. All refrigerant piping exposed to
weather shall be boxed up by using stainless steel plate.
AS -4
3.0
4.0
CONTROL
The control system should be connected by using 2-wire multiplex transmission system
links a single outdoor unit to multiple indoor unit with a 2-core cable. In addition, the
control system must come equipped with automatic address setting function (No manual
setting of addressing by means of rotary switches etc is allowed). An automatic checking
function for connections error of wiring and piping must come standard with the system.
Computerised PID control shall be used to maintain a correct room temperature with
minimum power consumption. Unit shall be equipped with its own 2 speed fan controller,
timer on/off switch, thermostat and LED indicators.
It shall also be equipped with a self diagnosis circuit for easy and quick maintenance and
service. It shall be able to indicate malfunction code displays. The LCD Remote Controller
shall memorize the latest malfunction code for easy maintenance.
VARIABLE SPEED DRIVE (VSD)
A variable speed drive (VSD) unit shall be used to drive the compressor motor and in-built
into the outdoor unit / condenser assembly. The VSD shall be capable of changing the
speed of the compressor using Pulse Width Modulation (PWM) technique proportionately
according to the cooling load requirement. The output of the inverter shall be of smooth
sine wave type.
4.1
4.2
The Unified On/Off Controller should be able to connect up to 16 groups (each group
consists of maximum up to 16 Fan Coil Units ) or 128 nos. of Fan Coil Units and it
should have the following functions :
Up to 64 groups must be able to be controlled by this device. More than 1 group can
be consolidated into a zone, which can be registered, to allow the following settings by
the zone.
Temperature Setting
Switching between Operation Modes
Setting of Direction and Fan Speed
Disabling/Enabling the Individual Remote Control
This eliminates the need for repeating the same setting operation for each Group.
Function to allow Collective Setting for all Groups must also be available.
5.0
5.1
BACNET Gateway
A gateway to ASHRAE 135 (IEEE802.3) Local Area Network System can be performed
via the BACNET Gateway. The VRV communication system can be linked to any BMS
which is operating within the specification approved by BACNET.
The BACNET Gateway shall enable the following functions to be performed by BMS:
5.2
AS -7
6.0
6.1
6.2
6.3
7.0
SERVICING
The Contractor shall be responsible for the recommended Servicing of the installation and
preparation of instructions for its operation and maintenance during the defect liability
period.
8.0
9.0
9.1
General Requirements
It is the responsibility of the manufacturer to ensure that the product is inspected and
tested at all stages of the manufacturing process in accordance to the
requirementsasstipulated in the specification. The cost of all inspection and tests shall be
borne by the manufacturer and shall be deemed to be included in the tender price.
The approval or passing of any such inspection and tests shall not prejudice the right of the
Company to reject the product if it does not comply with this specification when installed
or it does not give complete satisfaction in service. This condition shall apply only if the
causes of the above mentioned situations are due to any deficiency or wrong doing on the
part of the manufacturer toward the fulfilment of the requirements of this specification.
9.2
Acceptance Test
All test results carried out by the manufacturer shall be made available for inspection
during acceptance testing. The acceptance tests to be carried out by the manufacturer and
AS -8
If any sample fails in any of the tests, two further samples shall be taken from the same
batch and submitted to the same tests in which the original sample failed. If both
additional samples pass the tests, all units in the batch from which they were taken shall
be regarded as complying with the requirements of this specification. If either of the
additional samples fails, the batch from which they were taken shall be regarded as failing
to comply with the specification.
10.0
TRAINING
Successful tenderer shall be required to provide adequate training for the Company
personnel on the installation, operation and maintenance of the equipment supplied. The
costs involved shall be borne by the successful tenderer.
AS -9
ELECTRICAL
1.
General
The Contractor shall supply and install the complete electrical installation for the electrical
supply and control of all items of equipment in this Contract. The air conditioning control
panel and earthing to air-conditioning units will be included.
All motors shall be wired complete with isolating switches, thermal overload, starters, etc.
and shall be identical make except where approval is given for special purpose motors.
Wiring throughout shall be in accordance with the I.E.E. wiring rules and the latest
amendments thereto and with any requirements of Local Supply Authority. Only licensed
and approved Electrical Contractors shall be employed.
Conduits shall be screwed galvanised throughout unless otherwise approved, and shall not
be less than in. in dia. All conduit used on the works, shall be new, free from burrs and
rough edges and shall be kept dry at all times. Inspection type fittings may be used where
necessary to facilitate the drawing in of conductors. All conduit work is to be completed
and inspected by the Engineer before wiring is commenced. Where flexible conduit is
necessary for any connection type of conduit may be used. Exposed wiring will not be
permitted.
2.
Cable Trunking
For ease of wiring of various systems, cables may be grouped and run on metal trunking.
They shall manufactured from galvanized mild steel of not less than 18 s.w.g for size up to
4by 4and not less than 16 s.w.g. for large sizes. The metal trunking shall be treated
with an etch type rust inhibitor and painted to approved in two coats of finishing enamel in
selected colour.
Trunking shall be supported adequately by suitable brackets fabricated from galvanised
mild steel flat.
Trunking runs shall be erected completely before any cable is drawn in and the number of
cables installed shall be such that a space factor of 45% is not exceeded.
All trunking shall have a copper earthing strip of appropriate size.
All wiring shall be looped and shall not contain joints, except where connections are made
at numbered terminal strips on the equipment. Standard colouring of conductors shall be
used throughout the installation and where necessary the colouring shall be indicated on
the air-conditioning wiring diagrams.
A earth wire shall be run to each motor and control and shall earth the equipment as
required by the Wiring Rules. In no case shall the earth wire be less than 2.5mm and it
shall terminate in an approved manner.
The Contractor shall submit lay outs and details of the proposed electrical installation to
the Engineer for approval in all case before work begins.
AS -10
3.
Supply
Electricity supply for the air-conditioning installation shall be 415 volts 50 cycles, 3 phase,
4 wire and shall be terminal and connected at the main air-conditioning switchboard, by
others. Termination boxes for the cables shall be supplied.
4.
Earthing
Earthing shall be carried out to the requirements of the specifications, all requirements of
the D.E.P and SESCO. Provided suitable earth leakage protection where required by the
supply Authority.
All power outlet, motors and accessories shall have an earthing conductor. A separate
earthing conductor shall be provided from the switchboard or distribution board for each
and every circuit. Sub-circuit earthing conductors shall be not less than 2.5mm sq. (green
PVC sheathed) and sub-main earthing conductors shall be not less than 6-mm sq. (green
PVC sheathed).
AS -11
VENTILATION FAN
1.
GENERAL
Fans shall be capable of giving the specified performance when tested in accordance
with B.S. 848. Although estimated values of the resistance to air-flow of items of
equipment may be indicated this does not relieve the Sub-Contractor of the
responsibility for providing fans capable of delivering the required air volume
through the system.
Each fan shall be capable of continuous operation, having the capacity as indicated in
the Schedule of Equipment & Works and/or in the drawings when running at the
specified speed against the friction in the system as installed.
Fans shall be properly selected to handle the air quantity specified with noise level
less than 60 db. Silencers shall be installed where the fan cannot achieve this sound
level.
2.
VE-1
DUCTWORK
1.
GENERAL
The contractor shall supply and install all ductwork required to the dimensions and
details shown on the drawings and in accordance with the following: Duct dimensions indicated on the drawings are clear internal dimensions, the first
dimension given being that of the side shown in any view.
Internally insulated ducts shall be increased in size to maintain the clear internal
dimension.
It is the responsibility of this contractor to check actual spaces available on site,
prior to fabrication of the ducts. If any departures from the drawings are deemed
necessary, the contractor shall submit details of such departures and reasons to the
Consulting Engineer for approval.
All ductwork installations shall also meet Local Fire Authority's requirements.
2.
AD-1
Birmingham
Gauges
Transverse
Joint
Bracing
Max. Spacing
of Joint or
Bracing
Up to 12
24
Drive Slip
Nil
13to 24
22
Drive Slip
Nil
25to 30
22
1barred
Drive Slip
1x 1x 16g
angle
4 ft
31to 60
20
1barred
Drive Slip
1x 1x 16g
angle
4 ft
61to 90
20
1 barred
Drive Slip
1 x 1x
16g angle
4 ft
Over 91
20
2x 2x
3/16barred
Drive Slip
2x 2
angle
4 ft
Longitudinal joints used in the above duct construction shall be Pittsburgh lock on the
corners and grooved seams elsewhere.
Alternatively, ducts of maximum side exceeding 40" may be constructed of 22g
material using angle flanged joints at 4'0" maximum centres as specified above for
transverse joints and 1 1/2" inside standing seams at 30" max. centres for longitudinal
joints.
Gaskets to flanged joints shall be of soft rubber of jointing material similar to Prestik.
Bolt and rivet centres all flanges shall not exceed 4".
Spot welding shall not be used. Slips shall be made from material two gauges heavier
than the duct.
Bends without turning vanes shall have an internal radius equal to at least 3/4" of the
duct width. Square bends shall have double section turning vanes constructed of 24gauge material and in accordance with the standard drawings.
The sides of transformation pieces shall have a slope of not greater than 1 in 7 for
expansions and 1 in 4 for contractions.
AD-2
3.
FLEXIBLE CONNECTIONS
Connections between ductwork and any item of equipment that may move or
vibrate shall be made using flexible connections of fibreglass reinforced PVC of
minimum length of 3 inches. Flexible connections shall be securely fastened at
each end and be air tight.
Where shown on the drawings final connections to outlets shall be made with
flexible ductwork to permit relocation of the outlet within 1'0" of its original
position in any direction.
The flexible ductwork shall be formed from spirally wound aluminium corrugated
and lock formed with factory applied insulation and polythene vapour barrier. The
ducting shall be of approved manufacture and shall be installed as per
manufacturer's recommendations. To make final connections to outlets, the outlet
shall be fitted with a plenum box with spigot connection suitable for the size of
connection to be made.
4.
SEALING OF DUCT
Ducts shall be air-tight at the operating pressure.
Machine folded joints in ductwork shall be smooth and air tight. Slips shall be
caulked at each corner. Any hand formed joint in ductwork shall be fully caulked.
Non hardening caulking compound shall be used for caulking. Air leak at any
portion of duct work during testing shall be dismantled and made good.
5.
SPLITTERS
Splitters for adjustment of air distribution to the respective branches shall be
installed whether indicated on the drawings or not.
Splitter shall be made from not less than 22g galvanised steel in double streamless
section securely fastened to a 1/2 inch steel rod which pivotted in bronze or nylon
bushes fixed to the duct and provided with a lockable type quadrant for splitters of
length under 20 inches. Splitters of length 20 inches and over shall have steel rods
hinged to the air entering edge and passing through a suitable clamp on the side of
the large duct to permit positional adjustment and provide rigid anchorage in any
position.
Splitters may be of the fixed type if the branch duct serves only one outlet but most
be of the adjustable type if more than one outlet are served on the same branch duct.
6.
AD-3
Horizontal ducts shall be supported at centre by steel rods or straps as follows: Sides of
Rectangular Duct
Support Material
Spacing
Up to 36" in width
1"x10" galvanised
steel strap
8 ft
Up to 60" in width
1 1/2"x10g galvanised
steel strap
6 ft
Up to 84" in width
1 1/2"x1 1/2"x1/8"
angle 3/8 dia rod
4 ft
2"x2"x3/16" angle
4 ft
Where ducts pass through floors, walls or partitions, the free space shall be
adequately caulked with suitable diameter asbestos rope or felt gasket and a neat
sheet metal angle flange arranged to cover the free space.
Vertical duct shall be supported at not more than 6 ft. at each floor level.
Up to 26" in width
Up to 60" in width
Up to 84" in width
Maximum stress in hanger's rod, strap and bolts shall not exceed 5,500 psi.
Diameter of bolts shall not be less than 3/8". All steel angles and rolled steel flat
used of hangers shall be treated for protection of corrosion.
7.
All ductwork detail drawings shall be submitted to the Engineer for approval
before fabrication.
2.
3.
Turning vanes or air turns shall be used on all duct bends where the radiums
of the bend is less than 1-1/2 times the width of the duct and on all right
angle bends. Turning vanes and air turns shall be streamlined.
4.
AD-4
8.
9.
AD-5
2.
3.
DI-1
4.
VAV SYSTEM
a)
b)
c)
Temperature Controller
Temperature controllers shall be compatible with the electrically actuated
VARIABLE GEOMETRY VAV terminal such as the VARI_DISC and WBD and
shall be capable of controlling up to 6 units simultaneously (1 master and 5 slaves).
They shall be of the standard Proportional/Integral type able to accurately control
flow such that room temperature is within 0.5C of set point.
All temperature controllers must be catered for by 24V or 240V power supply
brought either to a pair of terminals fitted within a control panel or a 5 amp socket
outlet adjacent to the master unit. A temperature sensor must be supplied with each
controller.
DI-2
d)
Ribbon Cable
Ribbon slaving cable provided with sockets at both ends shall be used to
interconnect master/slave and slave/slave VAV terminals. Slaving cable shall be
purchased from the controls supplier to ensure compatible master/slave unit
operation.
5.
DI-3