EQuest Tutorial
EQuest Tutorial
eQUEST
Introductory Tutorial, version 3.63
Table of Contents
Simulation Basics
Background Information
eQUEST = DOE-2 + Wizards + Graphics
Overview of the Process
Building Blocks of Simulation
Data Requirements
HVAC Zoning
Keep it Simple but not too simple
Simplifying HVAC Zoning
Computational Steps in eQUEST
Types of Heat Transfer Surfaces in DOE-2
Types of Internal Loads
Quick Start
1
3
4
5
8
10
11
13
14
15
16
17
17
20
22
23
25
28
General Information
Building Footprint
Customized Building Footprint
Importing DWG Files for Custom Footprints
Custom HVAC Zoning
Building Envelope Constructions
Building Interior Constructions
Exterior Doors
Exterior Windows
Exterior Window Shades
Roof Skylights
Daylight Zoning (ground floor)
Daylight Zoning (typical and top floors)
Activity Areas Allocation
Occupied Loads by Activity Area
Unoccupied Loads by Activity Area
Main Schedule Information
HVAC System Definitions
HVAC Zone Temperatures & Air Flows
Package HVAC Equipment
HVAC System Fans
HVAC Fan Schedules, System 1
HVAC Fan Schedules, System 2
Zone Heating & Economizer
Hot & Cold Deck Rests
Cooling Primary Equipment
Primary Equipment Heat Rejection
29
30
31
34
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
Detailed Interface
Building Shell Module
Project & Site Module
Internal Loads Module
Water-Side HVAC Module
Air-Side HVAC Module
Utility & Economics Module
63
64
65
66
67
68
69
70
71
72
73
74
75
76
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
92
96
97
98
99
100
101
102
103
103
104
104
105
105
107
107
108
108
109
Parametric Runs
110
Graphical Reports
111
Detailed Reports
DOE-2
DOE-2
DOE-2
DOE-2
LOADS Reports
SYSTEM Reports
PLANT Reports
ECONOMICS Reports
112
113
114
115
116
117
119
120
121
122
123
124
126
130
131
132
133
134
blank intentionally
Simulation Basics
Simulation Basics
The reader who is already familiar with building energy use simulation may
wish to skip this section, and continue this tutorial at the next section (Quick
Start). For the reader who is new to the use of building energy use simulation,
this section provides an overview from a "how-to" perspective. Two Energy
Design Resources (EDR) publications will also be very helpful to the new
simulation practitioner, providing an overview and a perspective of the role
simulation plays in the energy-efficient design process. Both are highly
recommended and are briefly described below and on the following page.
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Background Information
Integrated Energy Design
Today's building designers must view their design responsibilities from a
much broader, even global, perspective. From operating costs, to energy
efficiency, to broader issues of sustainability, the quality of building design
decisions can only be as good as the information entering the design process,
i.e., the performance levels our building design projects ultimately realize is a
function of how well informed our design decisions are.
Globally Optimum Building Design
Operating
Costs
Energy
Use
Environmental
Impacts
Simulation Basics
Background Information
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Building Simulation
In recent years, the remarkable gains in desktop computing power and
simulation tool technology have placed unprecedented analytical power
literally at the finger tips of building design professionals. Building designers
and developers can now take their intended building designs for a "test drive"
before "signing on the dotted line", something previously only possible under
the most generous design budgets.
Parametric Runs
Graphical Reports
Detailed Reports
Simulation Basics
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Simulation Basics
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Before "building" anything, including your simulation model, first consider and
collect the following
Analysis Objectives (Begin with the End in Mind)
Try to approach your simulation model with a clear understanding of
the design questions you wish to answer using your simulation model.
Simplifications that you build into your model will both unclutter your
model so you can focus on the important issues and at the same time, limit the
questions you can use your model to answer. Experience will teach you how
best to strike this important balance for each new project.
Building Site Information and Weather Data
Important building site characteristics include latitude, longitude and
elevation, plus information about adjacent structure or landscape
capable of casting significant shadows on your proposed (or existing)
building. Your eQUEST CD (or download) comes with long-term average
weather data (~30-year average) for the sixteen standard climate zones in
California. For users outside of California, over 650 weather files are
available via automatic download (as-needed). Some international locations
are also available. Visit http://DOE2.com/download/weather/ to browse
available eQUEST weather locations.
Building Shell, Structure, Materials, and Shades
eQUEST is interested in the walls, roof, and floor of your proposed
building only in so far as they transfer or store heat (or "coolth"). You
will need to have some idea of the geometry (dimensions) and
construction materials of each of the heat transfer surfaces in your proposed
building. Only the most significant need be included (e.g., many modelers
omit parapet walls or walls inclosing unconditioned spaces since they do not
directly enclose conditioned space). This will include glass properties of
windows and the dimensions of any window shades (e.g., overhangs and fins).
eQUEST provides users with simple, user-friendly, choices for each of these.
Introductory Tutorial, page 5 of 134
Simulation Basics
Simulation Basics
Utility Rates
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Economic Parameters
Energy Design Resources concurs with a growing chorus
including the U.S. DOE's Federal Energy Management Program
(FEMP) and the National Institute of Standards and Technology
(NIST) in recommending life-cycle economics above simple payback
methods of economic analysis. Because energy efficiency investments
usually return benefit over the entire life of the building or system,
considering their life-cycle impact is most appropriate. Imagine selecting a
variable rate mortgage based on no more information than the initial
interest rate. While few would be comfortable ignoring the longer-range
terms of any loan or investment, it is common practice among building
developers and designers to recommend building efficiency investments
with equal shortsightedness. A summary discussion of life-cycle costing
with examples, including a comparison to simple payback is now part of
eQUEST v 3.63 (right click on any input field in eQUEST and select
Tutorials and Reference, then Life-Cycle Costs). While life-cycle
economics analysis is included in eQUEST, several free life-cycle cost
tools and resources are also available to the interested user. These include
the Building Life-Cycle Cost Program from NIST (free at
http://www1.eere.energy.gov/femp/information/download_blcc.html), and
User-Friendly Life-Cycle Costing, an Excel form of the widely used
NIST/BLCC methodology (free at http://www.doe2.com). Energy Design
Resources also offers eVALUator, user-friendly life cycle economics tool
that goes beyond traditional life-cycle cost tools by including payroll and
productivity data, lease rates, and occupancy rates. eVALUator is available
free at http://www1.eere.energy.gov/femp/information/download_blcc.html.
Simulation Basics
Data Requirements
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
The image below illustrates in detail, the type of data you should
either assemble prior to developing your simulation model, or
confirm in the course of your modeling, and the point in the design
process each item of building information typically becomes finalized.
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Item
Architectural
building and zone areas
envelope construction materials
Design
Construction
Source
Schematic
Development
Documents
plan sheets
wall sections
building elevations
building elevations
window schedule
or specifications
Mechanical
HVAC zoning
HVAC plans
HVAC plans
equipment descriptions
control sequences
equipment schedules
or specifications
control diagrams
or specifications
Electrical
lighting equipment
lighting layout
or lighting schedule
x
x
Internal Loads
peak occupancy (by zone)
peak lighting (by zone)
peak equipment (by zone)
owner, operator
lighting plans
mech or owner
Operations
per zone:
occ, lights, equip schedules
owner or operator
thermostat schedules
owner or operator
fan kW
owner or operator
control sequences
Economic
utility schedules (all fuels)
equipment costs
life-cycle cost parameters
utility representative
designer or
manufacturer
owner
Simulation Basics
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
assignment
Graphical Reports
Detailed Reports
INFORMATION
date3
date2
date1
DATES
ARCHITECTURAL
floor plans
space layout/areas, surface orientations
elevations
surface areas (windows, doors)
building/wall/roof sections
materials composition
site plans
adjacent structures and landscape
roof plans
skylights and overhangs
gross area & net (conditioned area)
ENVELOPE MATERIALS
glazing shading coefficient, u-value, frame type, interior shading
u-values: wall, roof, ceiling, skylight, slab & spandral
MECHANICAL
HVAC plans
approximate HVAC zoning layout
equipment types
approx equipment sizes, design conditions, & efficiencies
anticipated control sequences
OPERATIONS
per HVAC zone
occupancy, lights & equipment schedules
thermostat settings and schedules
per air handler
anticipated coil leaving air temperatures
minimum outside air
fan schedules
anticipated fan static & efficiency
central plant (if applicable)
chilled & hot water temperatures
equipment control sequences
ECONOMIC
base case first costs (for equipment & systems affected by ECM's)
ECM first costs
applicable & optional utility rates
POTENTIAL ECM's
envelope
lighting
mechanical
Simulation Basics
HVAC Zoning
Simulation Basics
Quick Start
Schematic Wizard
LOADING
ZONE
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
when modeling existing buildings, refer to the actual zoning indicated by the
HVAC plans, if available
for new buildings and when simplifying the zoning of an existing building
consider:
magnitude and schedule of internal loads
magnitude and schedule of solar gains
schedule of fan system operations
outside air requirements
intended efficiency measures (ECM's)
location of thermostats called out on the HVAC plans
In general, provide:
one exterior zone per major orientation (12 to 18 feet deep)
one internal zone per use schedule
one plenum zone (if plenum returns) for each air handler to be modeled
separately
one zone each for special uses (e.g., conference rooms, cafeterias, etc.)
separate ground and top floor zones
Currently, eQUEST provides the user with two automatic zoning schemes,
one-zone-per-floor, and simple core-vs-perimeter zoning. Based on this user
selection, eQUEST will automatically zone your model for you.
Simulation Basics
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Simulation Basics
Parametric Runs
Graphical Reports
Detailed Reports
Results for
10-story model
Results for
3-story model
(with multiplier)
On the other hand, it is possible to over simplify a model, i.e., the results are
no longer consistent with more complete or complex versions of the same
model. The graph below presents results from the same building. The graph
on the left presents results from a standard core vs perimeter HVAC zoning
scheme while the results on the right are for the same building assuming one
zone per floor. Notice that the largest difference between the two models is
that the single zone-per-floor model significantly under-predicts heating
electric use.
Standard Zoning
Over-Simplified Zoning
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Tenant and leasing flexibility may dictate that the building be divided up in
a manner that facilitates flexible leasing of space assignment requirements.
Ceiling space limitations or manufacture terminal equipment size
limitations may cause a larger number of smaller units to be specified than
strictly required by the rules on the previous page.
Acoustical privacy requirements may separate supply to adjacent areas.
Code requirements may separate supply to adjacent areas (e.g., separate
return for smoking areas).
Common ways that modelers simplify the zoning and size of their models
include the following.
Simulation Basics
LOADS
Instantaneous
Gain
Space
Load
SYSTEMS
Heat
Extraction
Coil
Load
PLANT
Primary
Energy/Demand
ECONOMICS
Utility
Rate
page 14 of 134, Introductory Tutorial
Utility Costs
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Simulation Basics
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Quick Start
Quick Start
Things to Know Before Getting Started with eQUEST
Simulation Basics
Quick Start
EEM Wizard
Schematic Wizard
DD Wizard
Detailed Interface
Parametric Runs
Graphical Reports
Detailed Reports
What Comes in the Package? There are two main parts to eQUEST:
1) the Wizards (both for building creation and EEM analysis) and 2) the
Detailed Interface (including Results Reporting).
Wizards. eQUESTs Wizards are intended to simplify and speed up the
Quick Start
Parametric Runs
Graphical Reports
Detailed Reports
evaluate the energy use performance impact resulting from building design
alternatives (i.e., design options). This is typically done by simulating at
least two versions of a building, one with and one without some specific
alternative(s). If this is done via the wizards, eQUEST refers to this as EEM
Analysis. If this is done in the Detailed Interface, eQUEST refers to this as
Parametric Analysis. Since EEM Analysis uses the EEM Wizard, it is
quicker and easier than Parametric Analysis but provides less detailed control
of the design alternatives. Parametric Analysis provides more detailed control
of the design alternatives but requires more detailed preparation and input.
EEM Analysis is introduced in this tutorial. Both EEM Analysis and
Parametric Analysis are covered in the eQUEST Modeling Procedures Quick
Reference Guide.
Help & Documentation. Item Help (brief, one paragraph to one page,
explanation of the requested item),Topic Help (topical help), and Tutorials
(step-by-step illustrated examples) are available via right mouse click at any
eQUEST input field in the Wizards or the Detailed Interface. The Item Helps
and Topic Helps are drawn from the ~3000-page six volume DOE-2.2
Reference Manual. These DOE-2.2 reference manual is also available in PDF
format via separate download from www.DOE2.com. New users should start
by reading this eQUEST Introductory Tutorial and then move onto the
eQUEST Modeling Procedures Quick Reference Guide. Both are available via
right mouse click at any input field.
On-Screen Data Types. Font color is used to identify which input values
displayed on eQUEST screens are defaults versus user inputs, etc. (see
Detailed Interface Basics in the Quick Reference Guide):
red
user input (or wizard input written to the Detailed Interface INP file
green
eQUEST (or DOE-2.2) default values
dk blue Library values
lt blue
User-defined default values
magenta values based on formula-like expressions
purple
linked values
Quick Start
and tabular formats. Some of these report results for a single run, others report
comparisons for multiple runs. Parametric reports are also available for EEM
Wizard runs and Parametric Runs. Summary Reports (only one is currently
available, but more to come) provide high level sanity check type results.
Detailed Simulation (DOE-2) Reports are text-based that provide very
detailed results. Hourly Reports provide optional hour-by-hour (8760) listings
of hourly simulation variables which can be easily exported to spreadsheets.
Each of these is overviewed in this tutorial. For more details, see Results
Reporting in the Modeling Procedures Quick Reference Guide):
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
(identified by their file extension, i.e., the last three characters in their name)
PD2
stores the building description input into the Wizards (user inputs only,
no defaults) viewed and modified using the Wizards.
INP
PRD
SIM
Quick Start
Installing eQUEST
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Quick Start
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
Parametric Runs
EEM Wizard
Graphical Reports
Detailed Reports
Figure 2, License
Agreement Screen
Quick Start
Figure 4, Component
Locations Screen
Figure 6, Installation
Complete Screen
Quick Start
Testing eQUEST
1
Simulation Basics
Quick Start
1
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
5
4
Quick Start
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Quick Start
Tour / Overview
Start eQUEST: Start eQUEST session by double clicking on the
eQUEST icon from your desktop, from your Start button, or from
Windows Explorer (the default location is "C:\Program Files\eQUEST
").
Create a new building description using eQUESTs Wizards: From
the Startup Options dialog (see the first image below right), select
"Create a New Project via the Wizard" (the default), then press
.
You are then asked which wizard youd like to use, the Schematic
Design Wizard, or the Design Development Wizard (see the second
image below right). Select to use the Schematic Design Wizard.
Review or modify as many of the Schematic Design Wizards inputs
as you prefer. The wizard screens include:
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Quick Start
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Selecting the Finish button in the wizard saves your wizard inputs
into your project PD2 file, writes an INP file (which contains the
DOE-2.2 input file), and navigates you to eQUESTs Detailed
Interface. The Detailed Interface is a Windows interface to DOE-2.2.
Use eQUESTs Schematic Design Wizard to modify an existing
model: You can return to eQUESTs Schematic Design Wizard,
modify your wizard inputs and regenerate your building model,
provided that the original building model was generated by the wizard.
Any edits made to your model directly in the Detailed Interface (see
"Review or edit detailed project inputs" below) will NOT be reflected
in the Schematic Design Wizard.
If you wish to save your original building model prior to making
changes, then save the model by clicking the toolbar button,
selecting File/Save or pressing Ctrl-S before launching the wizard.
Launch the wizard by clicking on the Schematic Design Wizard button
on the eQUEST analysis tool bar (near the top of the eQUEST
screen). If you wish to save your modified model under a new file
name, then visit the first wizard screen and modify the Project Name
field prior to selecting the Finish button from the wizard. This will
cause the modified model to be saved using the new project name.
Use eQUESTs Energy Efficiency Measure (EEM) Wizard to
quickly & easily explore your preferred design alternatives: After
creating a new building description (e.g., using the Schematic Design
Wizard) or loading an existing building description (previously created
using the Schematic Design Wizard), from the eQUEST analysis tool
bar you can launch the EEM Wizard to quickly describe up to ten
design alternatives to your base building description. You can then
automatically simulate any or all of these alternative cases and view
the simulation results as either individual or comparative graphs.
Advanced design simulation was never so quick and easy.
Perform a simulation: From the eQUEST analysis tool bar (near the
top of the eQUEST screen), press the Run Simulation button to
perform an annual simulation of the base building design description
and/or of any of your design alternatives.
Review simulation results: Upon completionof the simulaiton, select
(or from the eQUEST analysis tool bar,
press the Results Review mode button) to view eQUESTs graphic
output reports. In the Results View screen, at the bottom of the results
tree diagram (left side of the screen) select the
tab,
then select one or more projects for which you wish to view results.
Select the
tab, then selectany of the Single-Run Reports.
Quick Start
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Simulation Basics
Quick Start
Schematic Wizard
General Info
Bldg Footprint
Constructions
Exterior Doors
Windows
Skylights
Daylighting
Activity Areas
Occupied Loads
Unoccupied Loads
Main Schedules
Alt. Schedules
HVAC Sys Type
1)
2)
Chillers
Cooling Towers
CHW Control
3)
Boilers
HW Control
DHW Equip
Utility Charges
Project Info
4)
NOTES:
Four startup options are available:
Open a recent project. The list is maintained for projects on the local
machine, listed in reverse-chronological order (most recent first). This list
is maintained across program updates and re-installations.
Open an existing project. Selecting this option enables the user to browse
his/her machine/network for an eQUEST input file. Subsequent SAVES
will store files to the "browsed" location.
Create a new project via the Wizards. This is the default option and
eQUEST's main advantage over other modeling tools. Use this startup
option to create your new eQUEST models "from scratch". The pages that
follow illustrate the use of the Schematic Design Wizard.
Generate a Skycalc weather file. Skycalc is a spreadsheet-based
skylighting design tool available from www.EnergyDesignResources.com.
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
General Information
Simulation Basics
Quick Start
Schematic Wizard
General Info
Bldg Footprint
Constructions
Exterior Doors
Windows
Skylights
Daylighting
Activity Areas
Occupied Loads
Unoccupied Loads
Main Schedules
Alt. Schedules
HVAC Sys Type
1)
2)
3)
4)
5)
6)
7)
8)
In this example, match the inputs shown on the screen captures in red font.
Project Name. Select a project name - used to name the project files and
project folder.
Building Type. This selection is used to set defaults for most wizard inputs
that follow, e.g., building size, HVAC system type(s), etc. Changing this
selection will cause user inputs entered "downstream" to be reset.
Weather file Location Set. There are 4 choices: "California (Title24)" (the
16 CA zones), "All eQUEST Locations" (US-wide coverage), Canadian
Locations, and "User Selected" (browse dialog to find any DOE-2
weather files). If the weather file is not on the hard drive, when the
simulation is run ( ), it is automatically obtained from the DOE-2 site.
Utility/Rates. For California (Title24) locations, eQUEST automatically
selects the utility and rate based on the selected region and building size.
Custom (user input) rates can also be selected and stored for later re-use.
See the Utility Charges for more information.
Number of Floors. For # floors above grade > 3, the Schematic Wizard
models only 3 floors and uses a multiplier on the middle (typical) floor.
Cooling/Heating. Selecting the coil types will default the available HVAC
system types and plant equipment (if any). See screen 19 for more details.
Daylighting. Enables/disables daylighting-related screens.
Usage Details. Simplified are On/Off step function schedules, Hourly
Endue Profiles predefined hourly usage profiles.
Building Footprint
Simulation Basics
Quick Start
Schematic Wizard
General Info
Bldg Footprint
Constructions
Exterior Doors
Windows
Skylights
Daylighting
Activity Areas
Occupied Loads
Unoccupied Loads
Main Schedules
Alt. Schedules
HVAC Sys Type
Zone Temp. & Air
Packaged Equip
HVAC Fans
1)
Fan Sch #1
Fan Sch #2
Zone Ht & Econo
Deck Resets
WSHP Equip
Chillers
Cooling Towers
CHW Control
2)
Boilers
HW Control
DHW Equip
Utility Charges
Project Info
3)
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
4)
5)
NOTES:
Footprint Shape. Select a preferred standard building footprint shape, then
edit the footprint dimensions, or select "custom" and either draw a custom
footprint from scratch or customize one of the standard footprints. Note
that two floor areas are reported: the first is based on Bldg Area / # Floors
(from previous screen) and the second is based on the dimensions entered
on this screen. The selected footprint shape applies to all floors in this
shell (floor footprint shape). IMPORTANT NOTE: the Schematic
Wizard can have only one shell per project. The Design Development
Wizard can have more than one shell per project.
Zoning Pattern. Currently, there are three main options: perimeter-vs-core,
one-per-floor, and "custom". For perimeter-vs-core zoning, use Perimeter
Zone Depth to alter the depth of all perimeter zones. Alternately, select
"custom" and either draw a custom zoning pattern from scratch or
customize one of the standard zoning patterns (see below).
Building Orientation. Note that this input describes the direction that "Plan
North" faces, i.e., the compass direction that the top of the plan sheet
actually faces. Confirm that you have selected this correctly by referring to
the North arrow (true north) on the building footprint diagram.
Floor Heights. Note that these heights apply to all floors in the project.
Pitched Roof. Use this to specify a hip roof or gable roof (accepts only
Roof Pitch in degrees, and roof overhang projection).
Packaged Equip
HVAC Fans
Fan Sch #1
Fan Sch #2
Zone Ht & Econo
Deck Resets
WSHP Equip
Chillers
Cooling Towers
CHW Control
Boilers
HW Control
DHW Equip
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
NOTES:
1) Drawing Control Buttons.
Use these buttons in the upper left
area of the screen to select vertices, to zoom, and to pan.
2) Zoom Button . Select the zoom button then use the left mouse button to
make a vertical "stroke" on the drawing image. A downward mouse stroke
zooms back. An upward stroke zooms in. Zoom back to give some extra
room to customize the standard shape. Pan as preferred.
3) Select vertices. Select the pointer button , then single click on any
existing vertex in the drawing (do not double click). Vertices will appear
in one of three colors:
red (i.e., not the currently selected vertex),
light blue (i.e., currently selected and ready to copy), or
yellow (i.e., currently selected and ready to move).
Left mouse clicks toggle the selected vertex between light blue and
yellow.
4) Move an existing vertex. Select any vertex. Make it yellow (by single
clicking as needed do not double click). Drag the yellow vertex to a new
preferred location.
5) Create a new vertex (same as copy an existing vertex). Select any vertex.
Make it light blue (by single clicking as needed do not double click).
Drag the light blue vertex to a new preferred location.
6) Repeat steps 2 through 5 as preferred. See notes and example image on the
following page.
NOTES:
Rules to know regarding custom building footprints in eQUEST:
1) Maximum Number of Vertices. 120 vertices max for any one polygon.
2) Order to Create Vertices. Vertices are enumerated (and MUST be created)
in counter-clockwise order.
3) Legal Polygon Shapes. A building footprint polygon cannot have any
cutouts (i.e., no donut shapes), no line segments can cross another segment
in the same polygon (e.g., no figure eight shapes).
Packaged Equip
HVAC Fans
Fan Sch #1
Fan Sch #2
Zone Ht & Econo
Deck Resets
WSHP Equip
Chillers
Cooling Towers
CHW Control
OTHER NOTES:
Boilers
HW Control
DHW Equip
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
HW Control
DHW Equip
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
After selecting a DWG file from the Open dialog, the DWG File Open
dialog will be presented (above).
"1 DWG Unit =". This is the unit conversion used in the original DWG
file. It is normally sufficient to allow the settings for DWG units to default
(e.g., "inches").
Occupied Loads
Unoccupied Loads
Main Schedules
Alt. Schedules
HVAC Sys Type
Zone Temp. & Air
Packaged Equip
"Drawing origin in Building Model Units". This entry should be the world
coordinates of a point in the DWG file that the user wants to coincide with
the origin of the eQUEST drawing screen (i.e., eQUEST building origin).
The origin of the eQUEST building will be the point on the Custom
Building Footprint screen where the vertical and horizontal axes intersect
(i.e., X=0, Y=0).
HVAC Fans
If the user can first open the DWG file in a CAD program, a point can be
selected (e.g., the lower left hand corner of the building in plan view) as
the building origin and its coordinates relative to the world coordinate
system determined. The X and Y values for these world coordinates
should be entered at "Drawing origin in Building Model Units".
Chillers
If a user does not have a CAD program that can read a DWG file (e.g.,
AutoCAD), allow this value to default.
Select
then
Fan Sch #1
Fan Sch #2
Zone Ht & Econo
Deck Resets
WSHP Equip
Cooling Towers
CHW Control
Boilers
HW Control
DHW Equip
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
After importing the DWG file, if no image is apparent on the screen, the
drawing origin coordinates (entered or defaulted) probably placed the
DWG image outside the current viewing extents. To find the imported
image, zoom out using the button (perhaps "way out"!). If you had to
zoom "way out", the imported drawing may appear as a relatively small
object.
In most cases, it will be necessary to align the DWG image with the origin
on the drawing screen. To move it to the origin of the drawing screen, pan
the DWG image only by selecting both the "DWG-only" button and the
pan button , then pan as required.
IMPORTANT NOTE!
As you pan the DWG image to align with the eQUEST drawing screen
origin, it may become necessary to readjust (i.e., zoom) the drawing
screen extents. To readjust the drawing screen extents, you will want to
turn OFF the DWG Drawing Only button first , then select the zoom
button and adjust the zoom of the drawing image, as preferred. If you
need to pan the DWG image further (to get it to align with the eQUEST
drawing screen origin), select both the and the buttons again, then
continue to pan as required. When you are finished adjusting the position
of the DWG image relative to the drawing origin, remember to turn off the
button.
If you inadvertently use the button and the button together (i.e., by
forgetting to turn off the button before zooming), this will adjust the
scale of the DWG image! which may not be what you intended. To
repair an inadvertent change of scale to the DWG image, revisit the DWG
button, then reset the scale
Drawing Properties dialog by selecting the
value for "1 DWG Unit =" to its original value (i.e., 1.0).
HW Control
DHW Equip
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Ext. Stairs
Simulation Basics
Quick Start
Schematic Wizard
General Info
Bldg Footprint
Stage
Stage
Auditorium
Auditorium
DWG Import
Constructions
Exterior Doors
Windows
Skylights
Daylighting
Activity Areas
Occupied Loads
Unoccupied Loads
Main Schedules
Alt. Schedules
HVAC Sys Type
Zone Temp. & Air
Packaged Equip
HVAC Fans
Fan Sch #1
Fan Sch #2
Zone Ht & Econo
Deck Resets
WSHP Equip
Chillers
Cooling Towers
CHW Control
Separate DWG file imported with footprint and zone boundaries only
Experienced CAD users may wish to create a DWG file containing only
the essential information need by eQUEST. This can be done by first
tracing around the building image in a CAD program (e.g., using the
PLINE command) and tracing the preferred HVAC zone boundaries then
saving the footprint and zone boundaries as a separate DWG file (e.g., via
the WBLOCK command in AutoCAD)
The images on this page illustrate a DWG drawing that was first traced to
identify only the building shell and HVAC zone boundaries (above left).
This "tracing" was saved as a separate DWG file (above right), which was
then imported to provide a cleaner image to trace in eQUEST.
Boilers
HW Control
DHW Equip
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
If a "full" DWG file is imported into eQUEST (not one that has been
simplified as suggested on the previous page), the user may find it helpful
to "turn off" the irrelevant layers to avoid clutter on the eQUEST screen
before attempting to "trace" it. Do this via the drawing layers button .
will display the DWG Layers list
Selecting the drawing layers button
dialog. Selecting any layer on the list will cause the DWG drawing
elements assigned to the selected layer to blink on and off. This should aid
the user to identify the assigned drawing elements. Uncheck any DWG
drawing elements that clutter the view of the thermally significant features
of the drawing, e.g., the exterior building envelope and interior partitions
associated with HVAC zone boundaries.
Chillers
Cooling Towers
CHW Control
Boilers
HW Control
DHW Equip
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
With the DWG file aligned in the background as desired and using
conventions described previously on page 24, start by clicking on any
point or vertex on the drawing screen, then trace around the imported
DWG file image, proceeding in a counter clockwise order (image above).
Packaged Equip
HVAC Fans
Fan Sch #1
Fan Sch #2
Deck Resets
WSHP Equip
Chillers
Cooling Towers
CHW Control
Boilers
HW Control
DHW Equip
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Zoning Pattern. From the Building Footprint screen, users may select
either predefined HVAC zoning (e.g., perimeter-vs-core, one-per-floor) or
custom HVAC zoning. As with the building footprint, predefined zoning
patterns may be customized or you can start from scratch ("Blank Slate")
to create a completely custom HVAC zoning plan (see below shows one
zone completed) or "trace" around an imported DWG image. Select
"Create New Zone" to begin drawing or tracing each new zone.
WSHP Equip
Chillers
Cooling Towers
CHW Control
Boilers
HW Control
DHW Equip
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
1)
2)
3)
4)
NOTES:
Roof Surfaces and Above Grade Walla Construction. Default
constructions are based on building type (selected previously). Selections
for construction constrain the available Insulation choices.
Roof/Wall Exterior Finish and Color. Choices for Finish and Color are
used to define the ext. surface solar absorptance and ext. film resistance.
Ground Floor and Below Grade Wall Construction. Prior input for the
number of below grade floors determines whether below-grade walls are
displayed. The Ground Floor may have earth contact or may be over a
crawl space, unconditioned space, or garage.
Infiltration. Click this report
button to display the
infiltration dialog. Three
choices of infiltration
specification are available:
CFM/ft2 of ext. wall area,
CFM/ft2 of floor area, and air
changes per hour.
Parametric Runs
Graphical Reports
Detailed Reports
1)
Fan Sch #1
Fan Sch #2
Zone Ht & Econo
Deck Resets
WSHP Equip
2)
3)
Chillers
Cooling Towers
CHW Control
Boilers
HW Control
DHW Equip
4)
NOTES:
Building Interior Constructions. Default constructions are based on
building type (selected on Screen1). Selections for interior constructions,
as well as prior inputs (e.g., number of above grade floors, floor height)
constrain the available Interior Finish and Insulation options.
Vertical walls. For open office plans, select Air (none).
Floors. Note that these are interior floors. Normally, interior floors will
have no insulation applicable (see next item).
Slab Penetrates Wall Plane. This check box is viewable only if the
Construction for the interior floors is one of the Concrete choices. If the
interior concrete floors penetrate the exterior wall plane, i.e., the slab edge
is exposed to outdoor ambient conditions, check this box to reveal slab
edge insulation and finish options.
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Exterior Doors
Simulation Basics
Quick Start
Schematic Wizard
General Info
Bldg Footprint
Constructions
Exterior Doors
Windows
Skylights
Daylighting
Activity Areas
Occupied Loads
Unoccupied Loads
Main Schedules
Alt. Schedules
NOTES:
1) Door Type. Currently, six door types (i.e., categories) are available: opaque,
overhead (opaque), glass, sliding/atrium glass, air lock glass entry, and glass
revolving. Construction details and u-value for opaque doors are per ASHRAE
Handbook of Fundamentals.
2) # Doors by Orientation. All doors are placed only on the ground floor and are
centered along the applicable facade(s).
3) Door Construction / Glass Types / Frame Types. Opaque door type and frame
type selections are per the ASHRAE Handbook of Fundamentals. Glass doors
are from the DOE-2 glass library (see DOE-2.2 Volume 4: Appendices for a
listing).
Up to three types of doors may be defined using eQUEST's Schematic Design
Wizard.
Exterior Windows
Simulation Basics
Quick Start
Schematic Wizard
General Info
Bldg Footprint
Constructions
Exterior Doors
Windows
Skylights
Daylighting
Activity Areas
Occupied Loads
Unoccupied Loads
Main Schedules
Alt. Schedules
HVAC Sys Type
Zone Temp. & Air
Packaged Equip
HVAC Fans
1)
Fan Sch #1
Fan Sch #2
Zone Ht & Econo
2)
Deck Resets
WSHP Equip
Chillers
Cooling Towers
CHW Control
Boilers
HW Control
DHW Equip
Utility Charges
3)
Project Info
DD Wizard
Detailed Interface
4)
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
5)
1)
2)
3)
4)
5)
NOTES:
Exterior Window Overhangs and Fins. Select preferred placement of fins
and overhangs and which glass types they apply to (check boxes).
Shade Depths. Indicate preferred overhang and/or fin depths, by
orientation.
Distance from Window. Indicate the distance an overhang is above the top
of the adjacent windows, or fins are left and right of the adjacent windows.
Window Blinds/Drapes. Currently, this control is only available in the
Schematic Design Wizard if Usage Details on SD Wizard Screen #1 is
set to Hourly Enduse Profiles. Use this to specify the use of interior
drapes and blind. (This control is always available in the DD Wizard.)
Window Blinds/Drapes Season
Definitions. This button allows you to
define window interior shade
management using up to three seasons,
which can differ from the seasons
defined previously for all other
building schedules in the project.
Roof Skylights
Simulation Basics
Quick Start
Schematic Wizard
General Info
Bldg Footprint
Constructions
Exterior Doors
Windows
Skylights
Daylighting
Activity Areas
Occupied Loads
Unoccupied Loads
Main Schedules
Alt. Schedules
HVAC Sys Type
Zone Temp. & Air
Packaged Equip
HVAC Fans
Fan Sch #1
Fan Sch #2
1)
2)
3)
WSHP Equip
Chillers
Cooling Towers
4)
CHW Control
Boilers
HW Control
5)
DHW Equip
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
6)
NOTES:
Skylit Rooftop Zones. Select from 3 automatic skylight zone assignments
(perimeter only, core only, all) or indicate custom zone assignments.
Skylight layout diagram. In the skylight layout diagram, click (with left
mouse button) on zones to install or uninstall skylights (acts as a toggle).
Amount of Skylights. Indicate percent floor area coverage by skylights.
Confirm desired number. NOTE: the actual # of skylights cannot be
entered directly. You can only enter the % Coverage.
Typical Skylight Dimensions. Indicate/confirm the typical skylight
dimensions. "Width1" is horizontal to the layout diagram. "Width2"
measures along the vertical axis of the layout diagram.
Skylight Glazing Type. Glazing is Diffusing: select this option is the
skylight glazing is translucent. Domed: select this option if the skylight
surface is domed (now uses an improved calculation that captures the
effects of the doomed surface on reflectance).
Skylight Light Well. The default skylight well depth = flr-to-flr ht flr-toclg ht. To eliminate the light well, input Depth = 0.0.
DOE-2 note: eQUEST creates a separate WINDOW for each skylight.
For skylights in roofs above plenums, eQUEST actually places the
skylights in a dummy roof (i.e., with negligible heat transfer) located at
actual roof height, but assigned to the conditioned zone(s) the skylights
serve. Additional light well details can be input in the Detailed Interface
(e.g., splayed light wells, well efficiency).
1)
2)
3)
4)
5)
6)
7)
NOTES:
Up to 3 Daylight Zoning dialogs are available, one each for a ground (see
above), typical (i.e., middle), and top floor (see following page) depending
on the # of floors entered on the 1st wizard screen. These screens are
displayed ONLY if Daylighting was selected on the 1st screen.
Daylit From. Select the daylighting source (side glazing and/or top
glazing). Daylit from top lighting is available only for zones with roofs
(i.e., top floor zones) that contain skylights.
Daylight layout diagram. In the daylight layout diagram, click on zones to
activate or deactivate (toggle) daylighting (only for zones with glass).
Daylit Area Method. Daylit controlled area calcd by either of two Title24 methods or by user input (displays items # 4 & 5).
# of Photosensors per Zone. Select either 1 or 2 photosensors per zone.
% Lights Controlled and Design Light Level. Indicate the fraction of zone
lighting controlled by the daylight sensors and the Photosensor Location,
i.e., height above floor and % depth of zone (from zone window wall to
back wall). Side-to-side placement is done automatically by eQUEST
(centers sensor along length of 1st window in zone, avoiding skylights).
Design Light Level. eQUEST will assume this lighting level results from
the associated lighting power (from the Occupied Loads screen) and will
supplement calculated daylight levels using artificial lights as needed.
Lighting Controller. Indicate lighting controller type and its properties.
NOTES:
Input options for these screens are identical to the ground floor daylight
zoning screen). Toplighting (e.g., for core zones) is available only in skylit
areas (i.e., top floor zones with skylights). Note: on these screens, Daylit
Area Method was defaulted to CA Title-24 2008.
Having viewed the daylighting screens, before proceeding further,
return to the first screen, and set Daylighting to "No". Daylighting
analysis will be incorporated in the EEM runs.
1)
2)
3)
4)
NOTES:
eQUEST users specify internal loads (lights, people, and equipment) via
"activity areas". eQUEST then allocates these loads to each HVAC zone
according to default or user-specified allocations for each activity area (by
% of the total building).
Area Types. Select activity area types from the list of available area types.
This list was developed from regulatory/code sources, e.g., ASHRAE,
CEC. Select up to eight area types.
Percent Area. Indicate a percent allocation for each activity type (must
sum to 100%). Default percentages are based on selected building type.
Design Occupant Density and Ventilation. Indicate preferred occupancy
density and outside air ventilation rates (cfm per person). Defaults are
based on ASHRAE 62. Note that these entries should be considered
DESIGN levels for each. If diversity is to be applied for typical (not
design) operations, enter % occupancy, lights, or equipment < 100% on
the Schedule Information screens (Screens # 17 and 18).
Assignment Priority. Use these assignment priorities to control eQUEST's
allocation priorities. For example, a lobby activity area is expected to be
located in perimeter zones at the ground floor. eQUEST will use these
priorities but the percentage assignments will take precedence.
NOTES:
1) Lighting, task Lighting, Plug Loads. Indicate/confirm peak loads for lights
(ambient and task) and plugs (equipment), by activity area. These loads
are normally considered to be installed load. Defaults are taken from
California Title24 requirements.
2) Main/Alt Schedule flag. Use these "radio buttons" as flags to indicate
whether one or two usage schedules are necessary to describe building
usage patterns. These schedules will be detailed on subsequent screens.
Cooling Towers
CHW Control
Boilers
HW Control
DHW Equip
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
NOTES:
eQUEST usage schedules assume two levels of activity, occupied and
unoccupied. Use this screen to indicate load levels during unoccupied
hours as a percent of the occupied levels indicated on the previous two
screens.
NOTES:
eQUESTs Schematic Design Wizard permits up to two building usage
schedules, a main schedule and an alternate schedule. This example
employs only one schedule (i.e., no alternate schedules indicated on the
Occupied Loads screen, two screens prior to this one). These building
usage schedules are used to indicate to the simulation engine the
appropriate level of internal load for each hour of the year.
1) Day 1 - Day 3. Indicate how many day types are required to describe the
building usage, e.g., one day for hospitals (each day is equally occupied),
two days for office buildings (weekday and weekend days).
2) Occupancy/Lights/Equipment %. Indicate the level of load for people,
lights, and equipment during occupied hours (as a percentage of installed
load indicated on previous screens).
3) Second Season. Check this box if you wish to specify a second schedule
season. The default second seasons are based on building type, e.g.,
summer for schools, December for retailers. Repeat the previous two steps
as necessary.
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
1)
2)
3)
4)
NOTES:
The Schematic Design Wizard permits up to two HVAC system types
(templates) to be described. The defaults are based on building type &
HVAC equipment type from the first screen. The number of actual
systems used in the model (in the Detailed Interface) varies and depends
on system type. Single zone system types yield one system per zone.
Multiple zone type systems assume one AHU per floor.
Cooling/Heating Source. eQUEST's HVAC system type selections are
categorized by cooling/heating coil type. Select the appropriate coil types.
Defaults are taken from input for coil types on the first screen.
System Types. Select your preferred system type (choices are constrained
by coil type selections). Default system types are based on building type.
Return Air Path. Select return air path (direct, plenum, ducted). eQUEST's
Schematic Design Wizard constructs separate zones above ceilings if the
floor-to-floor height exceeds the floor-to-ceiling height from the 3rd
screen. Whether such an above-ceiling zone is a return air plenum or an
unconditioned zone is determined by the selection for return air path.
System Assignment to Thermal Zone. If two systems are input (as shown
above), eQUEST prompts to learn which zones are served by which
system. For this example, do not specify a second system type by right
clicking on the System 2 Cool Source and selecting restore default.
IMPORTANT NOTE: More than two HVAC System Types are permitted
NOTES:
eQUEST requires separate inputs for indoor thermostat setpoints and
indoor design temperatures. Defaults are based on building type and
California Title24.
1) Thermostat Setpoints. These thermostat setpoints correspond to the hours
indicated as occupied and unoccupied on previous screens.
2) Design Temperatures. Indoor design temperatures are used by eQUEST to
size air flow requirements. Default values are based on building type and
Title24. Supply temperatures are the temperatures of the conditioned air
entering (supplied to) the zones, not the temperature of the air leaving the
coils. Coil-leaving temperatures are based on a variety of factors,
including fan heat gain (for draw-through fans), duct losses, coil by-pass
factors, mixed air temperature, and humidity control requirements. Coilleaving temperatures are calculated by the simulation engine.
3) Air Flows. Minimum Design Flow is used to set a minimum design flow
rate. This is a minimum for sizing the design zone air flow. VAV
Minimum Flow is used to set a minimum flow rate for VAV terminals
during hourly operations.
Space is provided for t-stat & design temperature and air flow inputs for
up to two HVAC systems (shown above but not part of the example).
Detailed Reports
1)
2)
3)
4)
NOTES:
This Package HVAC Equipment dialog is displayed only if a package
HVAC system type was selected as one of the two system types on the
HVAC System Definitions screen (screen #19). In the image shown
above, the package equipment controls appear only on the right side of the
screen because on screen #19, the package system type was indicated as
the second system type (shown above for illustration purpose only).
Overall Size. There are two choices for this input: Auto-size and
specify. Auto-size means no size is specified by the user, rather, the
size of the cooling equipment is automatically determined during the
simulation. Specify means the user inputs overall cooling capacity, in
which case, a second input field is displayed in which the user indicates
the total size of the package cooling equipment (in tons). Note that this is
not the typical unit size of the size of any one specific unit, but rather, the
sum of the anticipated tonnage for all system #2 package equipment.
Typical Unit Size. This input does not determine or restrict the ultimate
size of any package unit, rather, it is only used to select the appropriate
minim efficiency level. NOTE: the efficiency indicated or user input here
will be used for ALL package systems. Use the Zone Group capabilities of
the DD Wizard to get around this simplification in the Schematic Wizard.
Condenser Type. Water-Cooled DX systems have been added as of
version 3.37. If Water-Cooled is selected, a separate condenser loop
and tower is provided (separate from any central plant).
Efficiency. Used to input or indicate the efficiency of every package unit
in the project (see Typical Unit Size, immediately above).
1)
Deck Resets
WSHP Equip
Chillers
Cooling Towers
2)
CHW Control
Boilers
HW Control
DHW Equip
Utility Charges
Project Info
3)
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
4)
NOTES:
In the example shown above, System Fan inputs are shown for two system
types (right and left sides of the dialog), only because two system types
were selected on the HVAC System Definitions screen (screen #19).
Fan Power. Specify fan power (e.g., total static, not just external static).
Note that while eQUEST accepts fan power inputs either in units of inches
of static pressure or brake horsepower, switching units does not convert
user input; rather, it resets input to the default for the selected units.
Fan Motor Efficiency. Specify fan motor efficiency as "Standard", "High",
or "Premium". The Energy Policy Act of 1992 (EPAct) requires that most
commercial and industrial motors manufactured or imported into the U.S.
after October 1997 meet or exceed a minimum standard. "High" efficiency
complies with EPAct, Title24, and ASHRAE 90.1 minimum requirements.
"Standard" would be appropriate only for older, existing fan motors.
Fan Flow & OA. The eQUEST Wizard default is to allow DOE-2 to
automatically sizes fan flow (based on simulated building peak sensible
load during the simulation, i.e., not in the wizard). Click on the Fan Flow
& OA button to display the Supply Fans screen (inset above). Flow =
Auto-size is shown above (the default), which also displays an input for
a safety sizing ratio (1.15 above). Select Flow = Specify to display total
CFM input (total across all AHUs to be created by this template).
Fan Type. Fan types input provides the simulation engine with part-load
fan performance data. The fan "curves" used by eQUEST's Schematic
Design Wizard are based on the CEC's ACM manual.
NOTES:
The second season portion of the HVAC system schedule illustrated above is
displayed only if the Second Season is checked. This is included in the image
shown above for illustration purposes only.
eQUEST HVAC system schedules follow the building usage schedules
described previously, with the exception that their start and stop times are
offset by the hours indicated at the top of the system schedule screens. A
separate fan schedule is permitted for each of the two (max) HVAC systems.
The first of two fan system schedule screens is shown above.
1) Fan Hours Before Open and After Close. Indicate/confirm the lead and lag
times assumed for fan operations. These controls add fan operation hours
before opening and after closing, as indicated (based on building usage
schedules). Negative inputs are accepted. Negative inputs would turn on or
off fans while occupants were still in the building.
2) Remaining inputs. Confirm all remaining fan schedule inputs. Since these
values default based on the building usage schedule, normally few edits
are required.
3) Second Season. For this example, leave this unchecked (the second season
is included above for illustrative purposes only).
NOTES:
This second system fan schedule is available only if a second system type
is input on the HVAC System Definitions screen, i.e., screen #19 (not part
of this example shown above for illustrative purposes only). By default,
the second fan system schedule copies the first fan system schedule.
1) Default Schedule Based On. Indicate/confirm whether the fan schedule for
the second system type defaults based on HVAC System #1. If Main
Activity Area Schedule is selected, controls similar to the System #1
schedule screen are displayed allowing specification of fan operation lead
and lag time (before and after occupancy as defined on the main Activity
Area Screen).
2) Remaining inputs. Confirm all remaining fan schedule inputs. Since these
values default based on the building usage schedule, normally few edits
are required.
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
NOTES:
1) Zone Heat. Indicate whether zone baseboards are used for heating (default
is no baseboards for all building types). Indicate/confirm terminal reheat
delta-t (input available only for reheat-type systems).
2) Economizer. Indicate whether an air-side economizer is installed. Three
air-side economizers types are available: drybulb (the economizer is
enabled whenever the OA temperature is < the max allowed by High
Limit), enthalpy (the economizer is enabled whenever the OA enthalpy
is < the a default max, i.e., 30 Btu/lb), and dual enthalpy (the
economizer is enabled whenever the OA enthalpy is < the RA enthalpy).
A high limit economizer temperature (above which no economizer action
is assumed) is also displayed and acts as the primary high limit for drybulb
economizers and as a secondary limit for enthalpy economizers. For DX
compressor systems, a compressor lock-out option is also displayed.
Space is provided for zone heat and economizer inputs for up to two
HVAC systems. The left side of this dialog displays inputs for HVAC
System Type #1. The right side of this dialog displays inputs for HVAC
System Type #2 (if selected on the HVAC System Definitions screen,
screen #19 (shown above for illustrative purposes only).
NOTES:
1) Cold Deck Rest Type. Currently, there are three choices:
"Warmest" - the cold deck is reset as much as possible, i.e., to just
meet the demand of the warmest zone on the system. To implement
this strategy typically requires a building automation system.
CHW Control
Boilers
WSHP Equip
Chillers
Cooling Towers
HW Control
DHW Equip
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
1)
2)
3)
4)
5)
NOTES:
The Schematic Design Wizard permits up to two types of chillers to be
modeled (but multiple chillers of each type). For equally sized chillers,
default chiller control assumes the 1st chiller will lead and the 2nd chiller
will lag. When two chillers are operating, both are equally loaded. This
Cooling Primary Equipment dialog is displayed only if a CHW-based
system type was selected as one of the two system types on screen #19.
CHW Loop Head and Design Delta T. Used to specify the total pressure
drop (ft of head) and design delta T for the CHW loop, which governs the
pump power (kW). IMPORTANT: See the item help for these (right click).
Pump Configuration. Select/confirm the preferred pump placement.
Circulation pumps can be placed in any of three configurations: only at the
loop, only at the chiller, at both the loop and the chiller(s). IMPORTANT:
eQUESTs wizards only provide a single CHW plant with primary loops
(no secondary loops). See the Detailed Interface for more options.
CHW Loop Flow. Indicate/confirm loop as either constant or variable. If
loop flow is set to variable, the Schematic Design Wizard prompts for the
method of pump control (single speed, two speed, or VSD).
Loop Pump Head/Flow. These inputs are used only to size the pump. Use
CHW Loop Head and Design Delta T to size the pressure drop & flow of
the entire loop.
Chiller Count/Size/Efficiency. By default, chillers are auto-sized, i.e.,
automatically sized by DOE-2. To specify the chiller size, select
Specify". Chiller efficiency defaults based on chiller type and size.
NOTES:
This dialog is displayed only if a CHW system was selected on screen #19
and condenser type = Water-Cooled or Remote Air-Cooled on screen #31.
1) Condenser Types (previous screen). There are four choices: WaterCooled, Packaged Air-Cooled (condenser electric is included in the chiller
efficiency), Remote Air-Cooled, Remote Evap-Cooled. Which inputs are
displayed on this dialog depend on the Condenser Type on screen #31.
2) CW Loop Head and Design Delta T. Used to specify the total pressure
drop (ft of head) and design delta T for the CW loop, which governs the
pump power (kW). IMPORTANT: See the item help for these (right click).
3) Condenser Pump Head/Flow. These inputs are used only to size the CW
pump. Use CW Loop Head and Design Delta T to size the entire loop.
4) Condenser Configuration. Four condenser types available: open (crossflow and counter-flow) towers, open towers with heat exchangers, fluid
coolers, and dry coolers (default differ by primary equipment types).
5) Temperature Control. Two condenser temperature control options are
supported in the Wizards: fixed and reset. The control set point (fixed or
minimum) is defaulted based on temperature control method.
6) Capacity Control. Capacity control options include: single speed (cycling),
two speed, VSD, bypass, and discharge dampers.
7) Remote Air-Cooled Condensers. Inputs are provided for Condenser Fan
Control, Setpoint Control, and Setpoint Temperature. The same inputs are
provided for evaporative condensers, plus Design Wetbulb.
NOTES:
This CHW System Control dialog is displayed only if a CHW-based
system type was selected as one of the two system types on the HVAC
System Definitions screen (screen #19).
1) Setpoint is. Three CHW setpoint control options are supported: "fixed"
(constant setpoint, no reset); "Load Reset" (reset based on load); "OA
reset" (reset based on outdoor air temperatures). In the reset cases, both
minimum and maximum CHW temperatures are input.
2) CHW System Operation. Three CHW system operation modes are
supported: "Standby" (the default, loop operates whenever system fans are
on); "Demand" (loop operates only when there is a load); "Scheduled"
(scheduled either as on/off or based on outdoor air temperature, e.g.,
operates only during scheduled hours when outdoor temperatures
exceeded the OA Temperature). The schedule corresponding to a
scheduled system operation defaults to follow either the first or second
HVAC system schedule, depending on which is system is cooled by CHW
coils.
3) CHW Setpoints. Depending on choice of reset control, CHW setpoints are
required to specify CHW min and max temperatures (Setpoint is = Reset
or OA Reset), or CHW setpoint value (Setpoint is = Fixed).
1)
Cooling Towers
CHW Control
Boilers
2)
HW Control
DHW Equip
Utility Charges
Project Info
DD Wizard
3)
Detailed Interface
EEM Wizard
Parametric Runs
4)
Graphical Reports
Detailed Reports
5)
NOTES:
This dialog is displayed only if a HW system type was selected on the
HVAC System Definitions screen (screen #19). eQUEST's Schematic
Design Wizard permits up to two boilers to be modeled. Boiler control
assumes that the first boiler will lead and the second boiler will lag and
that when two boiler are operating, both are equally loaded (no
preferential loading).
HW Loop Head and Design Delta T. Used to specify the total pressure
drop (ft of head) and design delta T for the HW loop, which governs the
pump power (kW). IMPORTANT: See the item help for these (right click).
Pump Configuration. Select/confirm the preferred pump placement.
Circulation pumps can be placed in any of three configurations: only at the
loop, only at the boiler(s), at both the loop and the boiler(s). IMPORTANT:
eQUESTs wizards only provide a single CHW plant with primary loops
(no secondary loops). See the Detailed Interface for more options.
HW Loop Flow. Indicate/confirm loop as either constant or variable. If
loop flow is set to variable, the Schematic Design Wizard prompts for the
method of pump control (single speed, two speed, or VSD).
Loop Pump Head/Flow. Loop Pump Head/Flow. These inputs are used
only to size the pump. Use HW Loop Head and Design Delta T to size the
pressure drop & flow of the entire loop.
Boiler Size/Efficiency. By default, boilers are auto-sized, i.e.,
automatically sized by DOE-2. To specify the boiler size, select Specify".
Boiler efficiency defaults based on boiler type and size.
NOTES:
This HW System Control dialog is displayed only if a HW-based system
type was selected as one of the two system types on screen #19.
1) Setpoint is. Three HW setpoint control options are supported: "fixed"
(constant setpoint, no reset); "Load Reset" (reset based on load); "OA
reset" (reset based on outdoor air temperatures). In the reset cases, both
minimum and maximum HW temperatures are input.
2) HW System Operation. Three HW system operation modes are supported:
"Standby" (the default, loop operates whenever system fans are on);
"Demand" (loop operates only when there is a load); "Scheduled"
(scheduled either as on/off or based on outdoor air temperature, e.g.,
operates only during scheduled hours when outdoor temperatures are less
than the OA Temperature). The schedule corresponding to a scheduled
system operation defaults to follow the CHW system schedule but a "radio
button" selection is available to change the default to either the first or
second HVAC system schedule.
3) HW Setpoints. Depending on choice of reset control, HW setpoints are
required to specify HW min and max temperatures (Setpoint is = Reset or
OA Reset), or HW setpoint value (Setpoint is = Fixed).
1)
WSHP Equip
Chillers
Cooling Towers
CHW Control
2)
Boilers
HW Control
DHW Equip
Utility Charges
Project Info
3)
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
4)
NOTES:
eQUEST's Wizards permit one domestic hot water tank to be modeled.
Storage capacity and input rating are estimated by the Wizard using rules
of thumb. If the user selects California Title 24 compliance from the first
screen, then a different pair of DHW screens are available (non-residential
and residential), depending on building type and activity area types.
Hot Water Usage. Hot water usage, in gallons per person per day, defaults
based on building type, per the ASHRAE Fundamentals Handbook. A
schedule is automatically associated with the usage whose peak rate
(gals/person/hour) is also taken from the same ASHRAE source.
Inlet Water Temperature. Inlet water temperature accepts two inputs,
"Equals Ground Temperature" and "Specify". "Equals Ground
Temperature" uses ground temperature data from the weather files to
estimate inlet water temperatures which vary by month. "Specify" allows
the user to set a constant inlet water temperature all months.
Recirculation %. In DOE-2.2, recirculation in domestic water loops is
optional. Where there is no recirculation, it is assumed that local water
pressure is sufficient to provide service on demand. Entering a number for
Recirculation % greater than "0" (typically 10% to 15%) indicates that the
loop uses pumped recirculation. If pumped recirculation is used, the user
is prompted to enter pump head and motor efficiency.
Tank Insulation R-value. This value is used only if Storage Capacity > 0.
In the Schematic Design Wizard, DHW tank stand-by losses are assumed
to be lost to outdoor ambient conditions.
NOTES:
This Electric Utility Charges dialog is displayed only if a Electric Utility
Rate was selected as Custom on Screen #1).
1) Rate Name. Enter a rate name that is sufficiently descriptive to allow this
rate to be stored in the library for future use. Click the
button to save
this rate for future retrieval (retrieve via Utility = File on screen #1).
2) Type. Three choices a re possible: Uniform Charges (for rates that
charge the same kWh charge for all kilowatt hours but which may vary
seasonally common for residential rates, shown above), Block
Charges (for rates having provisions such for consumption up to xxxxx
kWh per month, the charge will be yyy $/kWh, all consumption in excess
of xxxxx kWh per month will be charged at zzz $/kWh this is the
default and most common commercial/industrial rate), and Time-of-Use
Charges (for rates whose charges vary by time of day, e.g., on-peak vsmid-peak vs off-peak time periods this is a less common
commercial/industrial rate).
3) Customer Charge. May be specified in $ per month or $ per day.
4) Uniform Charges. Specify a peak demand or consumption charge that is
constant with quantity and time, but may vary between two seasons. The
units are $/kW (peak demand) and $/kWh (consumption).
5) Second Season. A second season can be selected (as displayed above).
While the screen capture shown above is for the Uniform Charge rate Type,
the Customer Charge and Uniform Charges are often applicable to the other
rates types (Block Charges and Time-of-Use Charges).
1)
Fan Sch #2
Zone Ht & Econo
2)
Deck Resets
WSHP Equip
Chillers
Cooling Towers
CHW Control
Boilers
HW Control
DHW Equip
3)
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
4)
NOTES:
The Electric Utility Charges dialog is displayed only if an Electric Utility
Rate was selected as Custom on Screen #1).
Type. The screen above is for rate Type = Block Charges. Block charge
structures tend to charge less for increased blocks of consumption.
Block Type. Two selections are available.
"Incremental Blocks" mean that the size of each successive block is stated
in terms of the SIZE of the block, i.e., how many kWh are in each block,
e.g., the first x,xxx kWhs , the next y,yyy kWhs .
"Cumulative Blocks" mean that the size of each successive block is stated
in terms of the UPPER LIMIT of the blocks, i.e., the upper boundary of
each block, e.g., the first x,xxx kWhs , up to y,yyy kWhs .
Energy Blocks. Two selections are available.
"kWh Block": where energy block sizes (or upper limits) are pre-defined
based on the units of energy consumed. For example, $0.07 for the first
10,000 kWh, $0.05 for the remainder.
"kWh/kW Block": where energy block sizes (or upper limits) are based on
a multiplier on peak electric demand. For example, $xxxx for the first
kWh block, where the size of the first kWh block is determined by using a
predefined multiplier times the peak electrical demand for each month.
This type of block will tend to vary in size from one month to the next.
Second Season. A second season can be selected (as displayed above).
NOTES:
The Electric Utility Charges dialog is displayed only if an Electric Utility
Rate was selected as Custom on Screen #1).
1) Type. The screen above is for rate Type = Time-of-Use Charges. Timeof-Use or TOU rates charge a different amount for demand and/or
consumption, depending on when it is used, i.e., what time of day.
2) TOU Period. Up to five Time-of-Use periods are available to describe a
TOU rate. Five choices for Electric Rate Time of Use Period are available:
"On-Peak"
Typically used to represent the most expensive electric
use time period during the day, e.g., summer afternoons.
"Off-Peak"
Used to represent the least expensive electric use time
period during the day, e.g., weekends and summer evenings.
"Mid-Peak"
Used to represent the periods of the day, if any, where
the cost of electric serve are higher than Off-Peak but lower than On-Peak,
e.g., summer mornings.
"Super On-Peak" Occasionally, time-of-use rates employ more than three
time-of-use periods. Super On-Peak is intended to be used for rate periods
more expensive than the On-Peak time period.
"Super Off-Peak" Similar to Super On-Peak, except for rate periods less
expensive than the Off-Peak time period.
3) Second Season. A second season can be selected (as displayed above).
NOTES:
The Electric Utility Time-of-Use Periods dialog is displayed only if the
Electric Utility Rate Type was selected to be Time-of-use Charges on
the Electric Utility Charges screen (previous screen).
1) TOU Periods Timeline. First select a TOU period by clicking on the
preferred color box from the TOU legend. Then use your mouse to color
the TOU timeline bar to indicate which hours are governed by which TOU
period. The number of TOU colors in the legend will depend on the
selection for TOU periods on the previous screen.
2) Season 2. A second season is displayed only if a second season was
selected on the previous screen (as displayed above).
Boilers
HW Control
DHW Equip
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
NOTES:
This Electric Utility Charges dialog is displayed only if a Gas Utility Rate
was selected as Custom on Screen #1). This screen is identical in design
to the Electric Utility Charges screen (two screens previous), except that
no TOU option is available (TOU options are rare for natural gas rates).
IMPORTANT NOTE:
WSHP Equip
button in the
To save your wizard utility rates for future use, click the
upper right area of the screen to save this rate. Retrieve a saved wizard
utility rate by selecting Utility = File on screen #1.
Chillers
Cooling Towers
CHW Control
Boilers
HW Control
DHW Equip
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
1)
Main Schedules
Alt. Schedules
HVAC Sys Type
2)
3)
Fan Sch #2
Zone Ht & Econo
Deck Resets
WSHP Equip
Chillers
Cooling Towers
4)
CHW Control
Boilers
HW Control
DHW Equip
Utility Charges
5)
Project Info
DD Wizard
Detailed Interface
EEM Wizard
6)
Parametric Runs
Graphical Reports
Detailed Reports
7)
IMPORTANT NOTE:
Currently, the utility rate save feature can only be used to save utility rates
defined entirely within the wizard. eQUESTs wizards are designed to cover
the common inputs, leaving more advanced utility rate features (e.g., ratchets,
rate limiters, rate qualifiers, etc.) to be modeled using refinements added in
the Detailed Interface. Currently, there is no simple (one-click) way to save
utility rates which are refined or modified in the Detailed Interface (e.g., to
add advanced features), for later re-use in new wizard projects. The simplest
method currently available to save your custom utility rates is done from
within the detailed interface and requires a text editor. The steps to save your
advanced utility rates and then later retrieve them for use in the Wizard are:
Leave the Wizard, i.e., proceed to the Detailed Interface (in the Wizard, press
the Finish button). Once youre in the Detailed Interface, add any necessary
advanced rate features in the Detailed Interface and save your project.
Within your project folder (see the installation guide portion of this tutorial for
options on where your eQUEST project files are stored), locate and open the
project INP file (project file with INP file extension) using any text editor
(e.g., Windows NotePad or WordPad).
In the INP file, find the BLOCK-CHARGE and UTILTY-RATE commands
(always near the bottom of the INP file) and copy these into a separate text
file. Be sure to include the command terminators (double periods ..). See a
file named DOE2-BDL Utility Rate Documentation.pdf found in the
eQUEST 3\Rates folder for a detailed description of these DOE-2 BDL
commands.
If your rates included schedules (e.g., for seasonal or time-of-use periods),
you will need to find and copy all DAY-SCHEDULE-PD, WEEKSCHEDULE-PD, and SCHEDULE-PD commands for all utility rate-related
schedules. Place these at the top of the separate text file (i.e., before the
BLOCK-CHARGE and UTILTY-RATE commands).
Name you separate text files (containing your utility rate-specific DOE-2 BDL
commands) any thing you wish and use ERT as a file extension for the
electric rates. Use GRT for gas rates. Select your file names to clearly
identify the utility company and tariff name.
Place these ERT and GRT files in the eQUEST\Rates folder. (see the
installation guide portion of this tutorial for options on where eQUEST data
files are stored). See the Readme.txt file in the eQUEST\Rates folder for
more information.
The next time you start eQUEST, these ERT and GRT files will be selectable
from within the Wizard (screen #1). Select Utility Electric or Utility Gas =
-file- to see a listing of all the ERT and GRT files youve stored in the
eQUEST\Rates folder.
Project Information
Simulation Basics
Quick Start
Schematic Wizard
General Info
Bldg Footprint
Constructions
Exterior Doors
Windows
Skylights
Daylighting
Activity Areas
Occupied Loads
Unoccupied Loads
Main Schedules
Alt. Schedules
HVAC Sys Type
NOTES:
1) Building Owner and Building Location. Currently, the building location
and building owner input on this screen is not output anywhere, therefore,
it is useful only as project description information in the Wizard only.
2) Component Name Prefix and Suffix. These input fields are provided to
enable Schematic Design (SD) Wizard users to prepare separate building
descriptions, then compile them together into a multi-building project in
the Detailed Interface. See the follow page for a description of this
process.
To leave the Schematic Design Wizard and proceed to the detailed interface ,
button in the lower right hand portion of the screen.
click on the
button, eQUEST writes a "DOE-2" input (*.INP)
After pressing the
file. This is a text input file containing DOE-2s BDL (Building Description
Language) input language.
DOE-2 BDL requires that every object within an INP file be uniquely named.
Using the Prefix/Suffix fields on the Project Information screen (last screen in
the schematic wizard), avoids redundant default component names by adding
your unique characters as a prefix and/or suffix to the name of every
component in the BDL input (INP) file.
Procedure:
On the Project Information Screen, use the Component Name Prefix and
Suffix fields to uniquely name every project component. These input fields are
provided to enable Schematic Design (SD) Wizard users to prepare separate
building descriptions, then compile them together into a multi-building project
In the Detailed Interface. Characters input in these two fields are added as
prefixes and/or suffixes to all building component names.
For example, suppose we wish to create a small two building campus for our
eQUEST project. To do so, we could prepare the first building description in
the Schematic Wizard, then on the Project Information Screen, enter a unique
identifier in the prefix field, e.g., Bdg1. In this case, Bldg1 would be
added as a prefix (first four characters) to every component name in the INP
file for our first building. Note that we are limited to a total of four characters
(prefix + suffix). Press Finish to leave the SD Wizard and proceed to the
Detailed Interface. From within the Detailed Interface), save your file
(File/Save).
Start a new SD Wizard project (or return to the previous project Wizard
screens). On Screen #1, name the project to reflect your second building.
After describing the second building in the SD Wizard, enter Bld2 as a
prefix on the Project Information Screen. Leave the SD Wizard (proceed to
the Detailed Interface) and save your file.
In the Detailed Interface, change the Mode to Detailed Data Edit (from the
Mode menu at the top of the Detailed Interface screen). Import the first project
into the second project (from the menus at the top of the Detailed Interface
screen, File/Import). Save-As to save and rename the combined project.
DHW Equip
Utility Charges
Project Info
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
DD Wizard
Simulation Basics
If the reader has not reviewed the previous section describing the Schematic
Design (SD) Wizard, they should do so prior to reviewing this section as the
DD Wizard employs most of the same screens as the SD Wizard and those
common screens will not be covered again in this section. Note however, that
the screens are arranged somewhat differently in the DD Wizard to allow
more flexibility. There are also a few new screens in the DD Wizard. Only the
new screens (i.e., not covered in the previous section) will be reviewed here.
The DD Wizard groups the input screens into categories, e.g., Building Shell,
Air-Side Systems, etc. The organization for the DD Wizard is shown below.
Quick Start
Schematic Wizard
DD Wizard
Project Navigator
Building Shell
Air-Side Systems
WLHP Systems
CHW plant Equip
HW Plant Equip
DHW Equipment
Detailed Interface
EEM Wizard
Parametric Runs
Launch
eQUEST
Graphical Reports
Detailed Reports
Project/Site/Utility/
Schedule Seasons
Building
Shell(s)
Building
Shell
Building
Shell
Air-Side
System(s)
Building
Shell
Building
Shell
CHW Plant
DD Wizard
Project
Navigator
WLHP Plant
HW Plant
DHW Equipment
In the DD Wizard, users can specify multiple building shells (i.e., separate
buildings, floors, wings, etc.), and multiple Air-Side HVAC System
templates, however, it currently only allows the description of one central
plant per project. Multiple central plants are permitted in the Detailed
Interface. The central screen in the DD Wizard is the Navigator, so-called
because all of the other DD Wizard screen groups are connected to one
another by the Navigator.
DD Wizard
Begin eQUEST by doubling clicking on the eQUEST icon from your desktop,
or from your Start button, or from Windows Explorer. From the Startup
Options Dialog, select "Create a New Project via the Wizard", and press OK.
DD Wizard
Project Navigator
Project & Site
Building Shell
Air-Side Systems
WLHP Systems
CHW plant Equip
HW Plant Equip
DHW Equipment
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
1) General Information screen. The information collected on this screen is very similar to the
General Information Screen for the SD Wizard (page 25), except that the inputs for building
size, number of floors, and heating/cooling source, which have been relocated to the shell
and air-side system screens.
2) Note that the button in the lower right corner is not labeled Finish as it is in the SD Wizard.
In the DD Wizard, this is labeled Continue to Navigator or Return to Navigator. Click
Continue to Navigator to proceed to the Navigator.
page 76 of 134, Introductory Tutorial
DD Wizard
Project Navigator
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Project Navigator
Project & Site
Building Shell
Air-Side Systems
WLHP Systems
CHW plant Equip
HW Plant Equip
DHW Equipment
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
The Project navigator is the command center for the DD Wizard. From this
screen, users select which screens they wish to visit. This screen is also used
to create multiple building shells and air-side systems.
Multiple building shells are used to define separate building floors whose
shape or zoning or height differ from one another, or to define different wings
of buildings or separate buildings (e.g., a campus of buildings).
You can also create multiple air-side systems. This adds flexibility in
specifying which areas of a project are served by different HVAC systems.
1) Project / Site / Utility. Access General Information, Compliance Analysis
Settings, Project Seasons Definitions, and Utility Charges.
2) Building Shell. Define the building shell, including the building operations
scheduling and internal loads.
3) Air-Side Systems. Define multiple air-side HVAC system templates.
4) Package HVAC Condenser Water Equip. Define WC DX equipment.
5) WSHP Plant Equipment. Define water source heat pump equipment
specifications (only one WSHP plant per project).
6) GSHP Plant Equipment. Define ground source heat pump equipment
specifications (only one GSHP plant per project).
7) CHW and HW Plant Equipment. Use this to access central cooling and
heating plant equipment specifications (currently, one plant per project).
8) DHW Equipment. Use this to access domestic hot water equipment
specifications (currently, only one DHW system type per project).
NOTE: Since most of the DD Wizard screens are identical to the Schematic
Wizard screens described previously, only those screens that are unique to the
DD Wizard, or were not previously described, will be included below.
Detailed Reports
DD Wizard
DD Wizard
This screen differs slightly from its counterpart in the SD Wizard, in that this
screen contains some of the data relocated from the DD Wizard General
Information Screen (compare to SD Wizard Screen #1, page 25).
1) Shell Name. Use this field to name the currently selected shell component.
A shell might be a separate building on a small campus of buildings, or a
floor (or floors) with a unique common footprint, or a floor (or floors)
with a unique common zoning scheme, or separate wings of a building.
2) Specify Exact Site Coordinates. This is an optional control that would
generally only be invoked to help locate a shell relative to another shell in
the same project.
3) Area and Floors. These inputs function in an identical manner to their
counterparts in the Schematic Wizard (see SD Wizard Screen #1).
4) Use Floor Multipliers. Use this check box to grant or deny permission to
sue floor multipliers. This control is displayed only when the number of
floors above grade (or below grade) exceeds 4. (See Simulation Basics at
the beginning of this Tutorial, Keep it Simple but not too simple)
5) Shell Multiplier. Use this to implicitly model multiple shells identical to
the one you are describing.
Detailed Reports
DD Wizard
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Project Navigator
Project & Site
Building Shell
Bldg Footprint
Air-Side Systems
WLHP Systems
CHW plant Equip
HW Plant Equip
DHW Equipment
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Most of the controls on the DD Wizard Building Footprint screen are identical
to their counterparts in the SD Wizard. One difference is the addition above,
of the Specify Zone Depth check box.
1) Specify Zone Depth. Use this check mark box to invoke default shapes by
using he aspect ratio (width in plan view divided by height in plan view) of
the footprint. For example, this is convenient to indicate that a building
footprint is twice as long as it is wide.
2) Pitched Roof. Click on the button below the Pitched Roof check box to view
the pitched roof dialog (see next page).
Building Shell screens 3 through 11 are identical (or nearly identical) to their
counterparts in the SD Wizard (see pages 26 - 44 above).
DD Wizard
DD Wizard
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Project Navigator
Project & Site
Building Shell
Ops. Schedules
Air-Side Systems
WLHP Systems
CHW plant Equip
HW Plant Equip
DHW Equipment
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Use this screen to indicate only the occupancy start and stop times for the project
(for up to three seasons as illustrated above).
1) Use. Select the use option that best describes the operational characteristics of
the building for each Building Operation Season. The choices for Season Use
vary by building type. For example, a building type of "Restaurant, Full
Service (full menu)" has the following choices for Season Type (Use):
"Closed for Business", "Low Meals Served", "Typical Meals Served" and
"High Meals Served."
2) Opens at & Closes at. Use these inputs to indicate the occupancy start and
stop times for the project. Since the DD Wizard uses only Hourly Enduse
Profiles for scheduling, these start and stop times are used to roughly shape
the hourly schedule profiles (see page 80).
DD Wizard
This screen differs slightly from its counterpart in the Schematic Wizard, in
that this screen contains assignment priority choices for Mid and Top floors.
Compare to SD Wizard Screen #13 (see page 44, when Usage Details on
SD Wizard Screen #1 is set to Simplified Schedules).
6) Show Zone Groups. For the DD Wizard, this option is selected by default.
This enables the presentation of the Zone Groups screen (see two pages
following).
7) Occupancy Profiles by Season. Up to three lists (one for each season) are
presented at the bottom of this screen, containing a list of all seasonal
profiles. The
button at the right lower corner of this screen, allows user
access to the hourly profiles (see the following page).
Graphical Reports
Detailed Reports
DD Wizard
DD Wizard
This screen is available only if the Show Zone Groups Screen check box is
selected on the Activity Areas Allocation screen (previous screen). This
screen is used to accomplish two things: (A) assign activity area types by zone
or zone group, and (B) assign air-side HVAC systems by zone or zone group.
1) Zone Groups. The list box in the upper left corner of the dialog lists
predefined zone groups, e.g., ground floor core zones, second floor
perimeter zones, etc. Create new zone groups or delete existing zone
groups by selecting the buttons below the zone groups list box.
2) Floor Plan Views. Zone assigned to the currently selected zone group are
displayed in dark green in floor plan views. Any zones not assigned to a
zone group are displayed in pale red.
3) To assign or re-assign zones to zone
groups, left click on a zone in any of
the floor plan views, and select
Assign Zone to Active Group or
Assign Zone to Other Group.
4) Activity Area Types. Assign or adjust activity area assignments to zone
groups by editing the Percent (%) column of the Activity Area spreadsheet
control in the upper right area of the dialog. %s must sum to 100% for
each zone group. The resulting area (sqft) is also reported for the selected
zone group. Percent and sqft is also reported for the whole building (shell).
5) HVAC System. Assign air-side systems to zone groups by first selecting a
preferred zone group then selected the preferred HVAC system template.
Detailed Reports
DD Wizard
This dialog is available only if Hourly Enduse Profiles are specified. This
screen allows users to select which non-HVAC endues are to be included in
the model of this building shell.
1) Interior Enduses. Check all interior enduses you desire to include in your
model. Interior enduses are those that contribute to space thermal loads
i.e., felt by one or more thermostats.
2) Exterior Enduses. Check all exterior enduses you desire to include in your
model. Exterior enduses are those that do not contribute to space
thermal loads i.e., are not felt by one or more thermostats.
Each endue selected on the screen above enables a screen such as the one
illustrated below, one for each enduse selected.
DD Wizard
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
DD Wizard
This screen is similar to its counterpart in the Schematic Design Wizard. The
only difference is the provision for seasonal thermostat setpoints (up to three
seasons, the number of seasons is determined on the Project & Site Data,
Season Definitions screen).
DD Wizard
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Air-Side HVAC System template screens 4 (System Fans), 6 (Zone Heating &
Economizer), and 7 (Deck Resets) are identical to their counterparts in the SD
Wizard (see pages 52, 55, & 56 above).
Air-Side HVAC System template screens 4 (System Fans), 6 (Zone Heating &
Economizer), and 7 (Deck Resets) are identical to their counterparts in the SD
Wizard (see pages 52, 55, & 56 above).
Detailed Interface
Detailed Interface
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
the Detailed Interface, this is not recommended for beginning users. Note that
any changes made within the Detailed Interface are not communicated back to
the Wizards or to the EEM Wizard (i.e., not stored in the INP file), thus, if the
user returns to the SD or DD Wizard and leaves the Wizard via the Finish
button, ANY edits made within the Detailed Interface will be lost, i.e., the INP
file will be overwritten by the inputs contained within the SD or DD Wizard.
Similarly, the EEM Wizard can only communicate with the SD & DD
Wizard. ANY edits in the Detailed Interface are ignored in the EEM runs.
Advanced users will find advantages to editing models directly within the
Detailed Interface. To edit within the Detailed Interface, users must first
change from the Wizard Data Edit mode to the Detailed Data Edit mode. This
is done from the menu bar. Pull down the Mode menu and select Detailed
Data Edit (see below). A warning/confirmation message (see below) will be
displayed to confirm the change of mode.
Detailed Interface
Detailed Interface
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Detailed Interface
Component Tree
Upon exiting the Schematic Design Wizard, the user arrives at eQUEST's
Detailed Interface. By default, the user is placed within the Building Shell
module. All of eQUEST's Detailed View modules are accessible via the module
navigation bar near the top of the screen (the large icons described on the
previous page). Screens for eQUEST's Detailed View modules are divided into
two main areas:
1) Actions / Component Tree View (two tabbed views on the left). The
Actions tab contains the available actions buttons (e.g., Building Creation
Wizard, EEM Wizard, Run Simulations, Perform Title 24 Compliance, Review
Simulation Results). This view is presented by default for the Wizard Data Edit
mode. The Detailed Component Tree can also be selected from the tab at the
lower left area of the Actions/Tree View. The detailed component tree at left
shows all major tree components for the Building Shell module (the example
shown at left has been reduced to show only the principal component levels by
selecting the "minus" icon at left of each component).
2) Detailed Tab View (detailed views on the right). The Building Shell Detailed
View module currently has three tab views, "2-D Geometry", "3-D Geometry",
and "Spreadsheet". The 2-D tab is shown above. The following page shows the
other tab views.
Detailed Interface
Detailed Reports
NOTES:
Change to the 3D Geometry View by clicking on the "3D Geometry" tab at
the top of the detailed diagram area. NOTE: the missing floor in the 3-D
image above results from using Floor Multipliers on Bldg Shell screen #1
(page 75). The missing floor is implicating modeled via a floor multiplier of
2 on the mid (typical) floor.
Rotate & Tilt: To rotate the 3D image, press and hold down the control key
while simultaneously pressing and holding the left mouse button. After a
short wait, e.g., 1 second, the displayed image of the building will change
from solid to wire frame (see example below). With the wire frame displayed
(and both the control key and left mouse button still depressed), slowly move
the mouse cursor left-to-right this will rotate the building image. Let go of
the left mouse button and control key to redisplay a solid building image.
Repeating the same steps, move the mouse cursor vertically
on the screen to tilt the building image.
Zoom: Repeat the same steps using control-right mouse to
zoom (via a vertical mouse stroke).
Wire Frame vs Solid View: Users may find it convenient
to toggle between solid view and wire frame view. First
click on the 3D view (left mouse button), then press either
the "s" or "w" key to select solid or wire frame view. The
wire frame view can help confirm location of interior walls.
Detailed Interface
Component Tree
Detailed Interface
Detailed Reports
NOTES:
Component Tree
After clicking on a selected building component in the 3D view (see
previous page), click on the "Spreadsheet" tab to view details of the
component (see example above) row for selected item highlighted.
Alternately, click on any item
in the component tree
(example at right) to display
details of the selected
component on the Spreadsheet
tab. The item selected in the
tree will also be highlighted in
the 3D (example on previous
page) and 2D View.
Right click on any item in the
component tree, 2D View, or
3D View and select
"Properties" to display a
tabbed dialog of details for the
selected component (example
at left).
Detailed Interface
Component Tree
Detailed Interface
Component Tree
1) Component Tree. The component tree at right shows all major tree
components for the Internal Loads module (the example shown at left has
been reduced to show only the principal component levels). Right mouse
click on any item in the tree and select properties, to display a tabbed
dialog showing internal load details.
2) Detailed Tab View. The Internal Loads Detailed View module
currently has two tab views, "Internal Loads", and "Spreadsheet".
Internal Loads
Tabbed Dialog
Detailed Interface
Component Tree
Detailed Interface
NOTES:
Component Tree
1) Component Tree (on the left). The image at left shows all major tree components for
the Air-Side module.
2) Detailed Tab View. The Air-Side HVAC module has two tab views:
"Air-Side HVAC System" and "Spreadsheet". These tabs are used to
review/input/modify features of the project air-side equipment.
Right mouse click on any item in the component tree or Air-Side HVAC
System tab view to display a tabbed dialog providing detailed information
for the selected component.
Air-Side Equipment
Tabbed Dialog
Detailed Interface
Component Tree
1) Component Tree (on the left). The image at left shows all major tree components for the
Utility and Economics module.
2) Tabbed Detailed View The Utility and Economics Detailed View
module currently has only one tab view, "Spreadsheet". This tab view is
used to review/input/modify features of utility rates and life-cycle costs.
Right mouse click on any item in the component tree to
display a tabbed dialog providing detailed information
for the selected component.
Utility Rate
Tabbed Dialog
EEM Wizard
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
The following pages will illustrate the EEM Wizard for these EEMs.
Roof Insulation
High Efficiency Lighting
Side Daylighting
Fan VSD and Low Static
Top Daylighting
CHW Pump VSD
High Perf. Daylight Glass
High Eff. WC Chillers
High Eff. Packaged VAV
To begin, click the
button. This will
launch the Energy Efficiency Measure
Creation dialog (right). From this dialog,
select the desired measure category, e.g.,
for increased roof insulation, select
Building Envelope. For the Measure
Type, select Roof Insulation.
Click on OK to display the EEM Run Information screen. Specify the EEM
Run Name as you prefer.
EEM Wizard
From the EEM Run Information dialog (previous screen), select the
button to display the EEM Details screen. Select a preferred
roof insulation alternative. Press Done to return to the EEM Run Info screen.
DD Wizard
Detailed Interface
EEM Wizard
Roof Insulation
Side Daylighting
Top Daylighting
Glass Type
Efficient Lights
VSD Fans
CHW Pump VSD
Efficient Chillers
Package VAV
Run Simulations
Parametric Runs
Graphical Reports
Detailed Reports
From the EEM Run Information dialog (previous page), select the
button to create another EEM run. To specify side daylighting, first select
Measure Category = Internal Loads and Measure Type = Daylighting (see
below). Note that for the second and subsequent EEM cases, an additional
selection is displayed on the EEM Run Information screen. The additional
selection allows the user to select which previous EEM run will serve as the
base case for the new EEM case, i.e., which case it will be based on.
EEM Wizard
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Roof Insulation
Side Daylighting
Top Daylighting
Glass Type
Efficient Lights
VSD Fans
CHW Pump VSD
Efficient Chillers
Package VAV
Run Simulations
Parametric Runs
Graphical Reports
Detailed Reports
EEM Wizard
For High Performance Glass, repeat the same procedures to obtain the
following EEM Details Screen.
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Roof Insulation
Side Daylighting
Top Daylighting
Glass Type
Efficient Lights
VSD Fans
CHW Pump VSD
Efficient Chillers
Package VAV
Run Simulations
Parametric Runs
Graphical Reports
Detailed Reports
For High Efficiency Lighting, repeat the same procedures to obtain the
following EEM Details Screen.
EEM Wizard
Detailed Reports
EEM Wizard
Run Simulations
Parametric Runs
Graphical Reports
Detailed Reports
EEM Wizard
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Roof Insulation
Side Daylighting
Top Daylighting
Glass Type
Efficient Lights
VSD Fans
CHW Pump VSD
Efficient Chillers
Package VAV
Run Simulations
Parametric Runs
Graphical Reports
Detailed Reports
SD Wizard Screen #1
EEM Wizard
On screen #19 (see below), confirm that the default HVAC system is Package
VAV with HW Reheat.
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Roof Insulation
Side Daylighting
Top Daylighting
Glass Type
Efficient Lights
VSD Fans
CHW Pump VSD
Efficient Chillers
Package VAV
Run Simulations
Parametric Runs
Graphical Reports
Detailed Reports
EEM Wizard
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Roof Insulation
Side Daylighting
Top Daylighting
Glass Type
Efficient Lights
VSD Fans
CHW Pump VSD
Efficient Chillers
Package VAV
Run Simulations
Parametric Runs
Graphical Reports
Detailed Reports
Parametric Runs
Parametric Runs
The Parametric Runs capability of eQUEST provides a means to define
and simulate multiple, alternative simulation cases, where each new case
is a parametric variation of the base case. This capability differs from the
EEM Wizard in that the EEM Wizard operates to modify the base building
as defined in the SD or DD Wizard (i.e., as contained in the PD2 file)
while the Parametric Run feature of eQUEST operates to modify the base
building as defined in the Detailed Interface (i.e., the INP file). In general,
Parametric Runs can be more detailed and flexible than the EEM Wizard,
but typically requires more insight and steps to define. Both the EEM
Wizard and Parametric Runs produce the Parametric Reports.
The parametric Runs section has been expanded and relocated to the
eQUEST Modeling Procedures Quick Reference Guide (available via right
click from any eQUEST input field, then select Tutorials and Reference).
See Parametric Runs there.
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Graphical Reports
Graphical Reports
A summary of eQUESTs graphical reports is presented in this section.
For a more detailed summary of eQUESTs graphical reports, see the
eQUEST Modeling Procedures Quick Reference Guide, Results
Reporting.
Simulation Basics
Detailed Interface
Quick Start
Schematic Wizard
DD Wizard
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
you are using to view results must have a printer driver installed.
The illustration below shows the current Report Tree, accessed by clicking
the
tab at the bottom left area of the screen. Note that some of
the reports are designed to display results for single runs. Most of the other
available reports are designed to compare several runs (i.e., EEM's).
Whether single-run or comparison reports are selected, you must also
select the run (single-run report) or runs (comparison report) to be
displayed from the project tree (accessed by clicking the
tab at the bottom left area of the screen). In the case of comparison reports,
the project tree includes a "plot order" designation (see example, below
right). Clicking on the plot order designation acts as a toggle to include or
exclude the selected run from the currently selected comparison report.
Examples of all of the available graphical reports are presented on the
following pages.
Graphical Reports
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Single Run Reports:
Mnthly Energy, End Use
Ann. Energy, End Use
Mnthly Utility Bills
Mnthly Peak, End Use
Ann. Peak, End Use
Peak Day Profile
Comparison Reports:
Mnthy Total Energy
Ann. Utility Bills
Mnthly Utiltiy Bills
Ann. Energy, End Use
Ann. Electric Use
Parametric Run Reports:
Annual Building Summary
Annual Enduse Summary
Detailed Reports
Graphical Reports
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Single Run Reports:
Mnthly Energy, End Use
Ann. Energy, End Use
Mnthly Utility Bills
Mnthly Peak, End Use
Ann. Peak, End Use
Peak Day Profile
Comparison Reports:
Mnthy Total Energy
Ann. Utility Bills
Mnthly Utiltiy Bills
Ann. Energy, End Use
Ann. Electric Use
Parametric Run Reports:
Annual Building Summary
Annual Enduse Summary
Detailed Reports
Graphical Reports
(Single-Run Report)
Graphical Reports
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Single Run Reports:
Mnthly Energy, End Use
Ann. Energy, End Use
Mnthly Utility Bills
Mnthly Peak, End Use
Ann. Peak, End Use
Peak Day Profile
Comparison Reports:
Mnthy Total Energy
Ann. Utility Bills
Mnthly Utiltiy Bills
Ann. Energy, End Use
Ann. Electric Use
Parametric Run Reports:
Annual Building Summary
Annual Enduse Summary
Detailed Reports
Graphical Reports
(Single-Run Report)
Graphical Reports
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Single Run Reports:
Mnthly Energy, End Use
Ann. Energy, End Use
Mnthly Utility Bills
Mnthly Peak, End Use
Ann. Peak, End Use
Peak Day Profile
Comparison Reports:
Mnthy Total Energy
Ann. Utility Bills
Mnthly Utiltiy Bills
Ann. Energy, End Use
Ann. Electric Use
Parametric Run Reports:
Annual Building Summary
Annual Enduse Summary
Detailed Reports
Important Notes:
1) To be able to view Monthly Peak Day Electric Load Profiles report, you must first load the
hourly reporting variables used to populate the peak day profiles on this report. This is done
from the Building Description area of eQUEST's detailed interface. Start at the Component
Tree in the Project & Site module (see the following page).
2) Specifying hourly reporting will increase the size of the detailed results SIM file by ~4 MB.
3) This is a 2 page report. Page 2 reports peak profiles for July through December
Graphical Reports
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Single Run Reports:
Mnthly Energy, End Use
Ann. Energy, End Use
Mnthly Utility Bills
To load the hourly reporting variables used to populate the peak day
profiles on Monthly Peak Day Electric Load Profiles report, in the
Building Description area of eQUEST's detailed interface, go to the
Component Tree in the Project & Site module. Right click on "Hourly
Reports" and select "Create Hourly Reports". From the "Create Hourly
Reports" dialog, click the "Load Component From Library" button. On
the "Hourly Report Selection" dialog, select both the "Category" and
"Entry" to be "Hourly Reports" (currently the only choices), then click
"OK" (twice). This will display the "Hourly Results Selection" dialog.
You may be interested to review these variable selections, but NO
changes should be made.
Graphical Reports
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Single Run Reports:
Mnthly Energy, End Use
Ann. Energy, End Use
Mnthly Utility Bills
Mnthly Peak, End Use
Ann. Peak, End Use
Peak Day Profile
Comparison Reports:
Mnthy Total Energy
Ann. Utility Bills
Mnthly Utiltiy Bills
Ann. Energy, End Use
Ann. Electric Use
Parametric Run Reports:
Annual Building Summary
Annual Enduse Summary
Detailed Reports
Graphical Reports
(Comparison Report)
Graphical Reports
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Single Run Reports:
Mnthly Energy, End Use
Ann. Energy, End Use
Mnthly Utility Bills
Mnthly Peak, End Use
Ann. Peak, End Use
Peak Day Profile
Comparison Reports:
Mnthy Total Energy
Ann. Utility Bills
Mnthly Utiltiy Bills
Ann. Energy, End Use
Ann. Electric Use
Parametric Run Reports:
Annual Building Summary
Annual Enduse Summary
Detailed Reports
Graphical Reports
(Comparison Report)
Graphical Reports
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Single Run Reports:
Mnthly Energy, End Use
Ann. Energy, End Use
Mnthly Utility Bills
Mnthly Peak, End Use
Ann. Peak, End Use
Peak Day Profile
Comparison Reports:
Mnthy Total Energy
Ann. Utility Bills
Mnthly Utiltiy Bills
Ann. Energy, End Use
Ann. Electric Use
Parametric Run Reports:
Annual Building Summary
Annual Enduse Summary
Detailed Reports
Graphical Reports
page 1 of 2
Annual Energy and Demand
(Parametric Report)
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Single Run Reports:
Mnthly Energy, End Use
Ann. Energy, End Use
Mnthly Utility Bills
Mnthly Peak, End Use
Ann. Peak, End Use
Peak Day Profile
Comparison Reports:
Mnthy Total Energy
Ann. Utility Bills
Mnthly Utiltiy Bills
Ann. Energy, End Use
Ann. Electric Use
Parametric Run Reports:
Annual Bldg Summary
Annual Enduse Summary
Detailed Reports
These reports are produced automatically for EEM or Parametric simulation runs. Each page of
the parametric results reports are divided vertically into three sections which report: 1) total, 2)
incremental or 3) cumulative results. One row per case (run). All are annual results.
1) The upper third reports total annual results for energy, demand, and utility costs for each case.
2) The middle third reports incremental annual savings for each case. The incremental savings
reports the impact (i.e., benefit or penalty) associated with each case. This is calculated by
subtracting the results for the current case from the results for the previous case.
3) The bottom third of each table reports cumulative annual savings for each package of
measures, i.e., the cumulative savings assume that the parametric cases were run on top of
previous cases and report the benefit or penalties associated with the growing package of
efficiency measures, relative to the Base Case. This is calculated by subtracting the annual
results for each case from the annual results for the Base Case.
IMPORTANT NOTE: If all EEM runs were run on top of the Base Case, i.e., not on top of other
EEM cases, the cumulative and incremental results will be identical.
DOE-2 Note: Total annual energy results are from the DOE-2 BEPU report. Demand results
are from the DOE-2 PS-E report. Utility costs results are from the DOE-2 ES-E report. Peak
cooling load is from the DOE-2 SS-D report.
page 124 of 134, Introductory Tutorial
Graphical Reports
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Single Run Reports:
Mnthly Energy, End Use
Ann. Energy, End Use
Mnthly Utility Bills
Mnthly Peak, End Use
Ann. Peak, End Use
Peak Day Profile
Comparison Reports:
Mnthy Total Energy
Ann. Utility Bills
Mnthly Utiltiy Bills
Ann. Energy, End Use
Ann. Electric Use
See previous page for an explanation of the format of this parametric report.
Graphical Reports
page 1 of 4
Annual Electric Energy by Enduse
(Parametric Report)
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Single Run Reports:
Mnthly Energy, End Use
Ann. Energy, End Use
Mnthly Utility Bills
Mnthly Peak, End Use
Ann. Peak, End Use
Peak Day Profile
Comparison Reports:
Mnthy Total Energy
Ann. Utility Bills
Mnthly Utiltiy Bills
Ann. Energy, End Use
Ann. Electric Use
Parametric Run Reports:
Annual Bldg Summary
Annual Enduse Sum.
Detailed Reports
Graphical Reports
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Single Run Reports:
Mnthly Energy, End Use
Ann. Energy, End Use
Mnthly Utility Bills
Mnthly Peak, End Use
Ann. Peak, End Use
Peak Day Profile
Comparison Reports:
Mnthy Total Energy
Ann. Utility Bills
Mnthly Utiltiy Bills
Ann. Energy, End Use
Graphical Reports
page 3 of 4
Elec. Non-Coincident Peak Demand by Enduse
(Parametric Report)
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Single Run Reports:
Mnthly Energy, End Use
Ann. Energy, End Use
Mnthly Utility Bills
Mnthly Peak, End Use
Ann. Peak, End Use
Peak Day Profile
Comparison Reports:
Mnthy Total Energy
Ann. Utility Bills
Mnthly Utiltiy Bills
Ann. Energy, End Use
Ann. Electric Use
Parametric Run Reports:
Annual Building Summary
Graphical Reports
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Single Run Reports:
Mnthly Energy, End Use
Ann. Energy, End Use
Mnthly Utility Bills
Mnthly Peak, End Use
Ann. Peak, End Use
Peak Day Profile
Comparison Reports:
Mnthy Total Energy
Ann. Utility Bills
Mnthly Utiltiy Bills
Ann. Energy, End Use
Detailed Reports
Detailed Reports
Simulation Basics
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
Detailed Reports
THERMAL LOAD
P
P
Detailed Interface
LS-L
Parametric Runs
Graphical Reports
SYSTEM Reports
PLANT Reports
P/T
Lights
T
T
Process Electric
Process Fuel
Econo. Reports
P/T
OTHER
DD Wizard
LOADS Reports
Equipment / Plugs
% Lighting Reduction
Schematic Wizard
Detailed Reports
Solar Gain
DAYLIGHTING
Quick Start
EEM Wizard
LS-K
LS-J
LS-K
LS-I
Simulation Basics
Total (Lights/Plugs/Process)
LS-H
LS-G
LS-E
T
P/T
LS-F
OTHER ENERGY
ELECTRIC ENERGY
LS-C
LS-A
Space Level
Info
LS-B
LS-A
Notes:
T = Total energy or Total load reported for these items
P = Peak demand or Peak load reported for these items
Duplicate reports are provided for each LOADS report (if DESIGN-DAYs are used) where the
first set of reports provides results for the design day conditions. A complete second set reports
the annual simulation results.
Left-to-right order of report columns above corresponds to top-down order of reports printed in
the "DOE-2" output files
Detailed Reports
NOTES:
T = Total energy or Total load reported for these items
P = Peak demand or Peak load reported for these items
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
SS-G
P/T
P/T
Baseboard Heat
P/T
Pre-heat
P/T
P/T
P/T
P
P
P
P
P/T
P/T
P/T
P/T
P/T
P/T
P/T
P/T
P/T
P/T
OTHER ENERGY
Auxiliary/Fan/Pump Elec
P/T
P/T
P/T
Waste Heat
HOURS
Hours Heat/Cool/Float/Available
Fan Hours
Hours at RH ranges
SPACE TEMPERATURE
Min / Max
Scatter Plot
OTHER
Air Flow
Heat/Cool Capacity
Heat/Cool E-I-R
Heat/Cool Addition/Extraction
ELECTRIC ENERGY
SS-O
SS-Q
P/T
SS-F
SS-P
SS-N
SS-L
SS-R
SS-K
SS-J
P
T
HP Heat/Cool Performance
Sensible/Latent Summary
ZONE
SS-I
P/T
SS-H
P/T
SS-C
SS-M
SS-E
P/T
SS-A
AIR HANDLER
SS-P
THERMAL ENERGY
SS-D
BUILDING
Econo. Reports
PLANT Reports
SS-B
SYSTEM Reports
LOADS Reports
Detailed Reports
Graphical Reports
Detailed Reports
THERMAL LOAD
by Total Plant
by Plant Equipment
BEPU
PS-H
BEPS
PS-F
PS-A
P/T
P/T
P/T
P/T
Equipment Capacity
P/T
P/T
P/T
P/T
Annual
Monthly
Annual
Quick Start
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
Parametric Runs
Graphical Reports
Detailed Reports
UTILITY ENERGY
Simulation Basics
LOADS Reports
SYSTEM Reports
PLANT Reports
Econo. Reports
Monthly
by Utility Type
by Utility Meter
by End Use
Annual
P/T
P/p/T
Monthly
P/T
P/p/T
Annual
P/T
P/p/T
Monthly
P/T
P/p/T
P/p/T
P/p/T
P/p/T
P/p/T
by Plant Equipment
HOURS
P/T
P/T
NOTES:
T = Total energy or Total load reported for these items
P = Peak demand (COINCIDENT) reported for these items
P = NON-COINCIDENT Peak demand reported for these items
Detailed Reports
NOTES:
T = Total energy or Total costs reported for these items
P = Peak demand or Peak demand costs reported for these items
Schematic Wizard
DD Wizard
Detailed Interface
EEM Wizard
by Utility Rate
by Block or TOU Charge
Component Charges
P/T
P/T
Component Charges
P/T
Component Charges
P/T
Component Charges
P/T
Pollutant Production
LIFE-CYCLE Results
Costs
Savings
Investment Statistics
Energy
Operations
Energy
Operations
Energy + Operations
Discounted Payback
S-I-R, cost
S-I-R, energy
Things to add:
Pitched roofs (Screen 3 shows check mark, but the dialog is not illustrated).
New Screen 22 now provides water-cooled condensers for DX.
New aspect ratio control on DD Wiz footprint screen.
Confirm Screen # and Screens # (new Screen #22 will cause screen #s > 21 to be wrong).
HVAC Summary results screens
Pollutant Production
MONTHLY Results
T
T
ES-H
Energy Use
Total Utility Costs ($)
Summary of Pollutants
by Utility Rate
ES-G
ANNUAL Results
ES-D
Econo. Reports
ES-C
PLANT Reports
SYSTEM Reports
LOADS Reports
ES-B
Detailed Reports
ES-A
Graphical Reports
Parametric Runs