Ies Indoor Report Photometric Filename: Itl47874.Ies DESCRIPTION INFORMATION (From Photometric File)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

IES INDOOR REPORT

PHOTOMETRIC FILENAME : ITL47874.IES


DESCRIPTION INFORMATION (From Photometric File)
IESNA:LM-63-1995
[DATE]06/25/98
[TEST]ITL47874
[MANUFAC]LEXALITE INTERNATIONAL CORPORATION
[LUMCAT]MODEL 812 ACRYLIC WITH CONIC ACRYLIC LENS
[LUMINAIRE]FORMED PRISMATIC CLEAR ACRYLIC REFLECTOR WITH CLEAR PRISMATIC
[MORE]CONICAL ACRYLIC LENS SECURED BY METAL RETAINING RING. WHITE
[MORE]PAINTED METAL MOUNTING COLLAR.
[LAMP]ONE 70-WATT PHOSPHOR COATED ED-17 METAL HALIDE, VERTICAL BASE-UP
[MORE]POSITION.
[_MOUNTING]PENDANT/SUSPENDED
CHARACTERISTICS
Total Rated Lamp Lumens
Total Luminaire Efficiency
Luminaire Efficacy Rating (LER)
Total Luminaire Watts
Ballast Factor
CIE Type
Spacing Criteria (0-180)
Spacing Criteria (90-270)
Spacing Criteria (Diagonal)
Basic Luminous Shape
Luminous Length (0-180)
Luminous Width (90-270)
Luminous Height

5600
94.5 %
76
70
1.00
Semi-Direct
2.28
2.28
2.02
Circular w/ Sides
0.00 ft
1.04 ft (Diameter)
0.73 ft

LUMINANCE DATA (cd/sq.m)


Angle In
Degrees

Average
0-Deg

Average
45-Deg

Average
90-Deg

45
55
65
75
85

10570
7683
4553
3149
3150

10570
7683
4553
3149
3150

10570
7683
4553
3149
3150

Photometric Toolbox Professional Edition (c) copyright 1995-2008 by Lighting Analysts, Inc.
Calculations based on published IES Methods and recommendations, values rounded for display purposes.
Results derived from content of manufacturers photometric file.

Page 1

IES INDOOR REPORT


PHOTOMETRIC FILENAME : ITL47874.IES
CANDELA TABULATION

0.0
2.5
5.0
7.5
10.0
12.5
15.0
17.5
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
42.5
45.0
47.5
50.0
52.5
55.0
57.5
60.0
62.5
65.0
67.5
70.0
72.5
75.0
77.5
80.0
82.5
85.0
87.5
90.0
92.5
95.0
97.5
100.0
102.5
105.0
107.5
110.0
112.5
115.0
117.5
120.0
122.5
125.0
127.5
130.0
132.5

0
618
630
638
651
671
689
711
739
775
811
842
870
899
934
976
1022
1071
1110
1124
1102
1027
914
797
690
599
515
446
387
340
309
281
262
249
245
245
249
254
264
274
285
297
308
317
324
325
322
314
301
285
266
246
221
194
169

Photometric Toolbox Professional Edition (c) copyright 1995-2008 by Lighting Analysts, Inc.
Calculations based on published IES Methods and recommendations, values rounded for display purposes.
Results derived from content of manufacturers photometric file.

Page 2

IES INDOOR REPORT


PHOTOMETRIC FILENAME : ITL47874.IES
CANDELA TABULATION - (Cont.)
135.0
137.5
140.0
142.5
145.0
147.5
150.0
152.5
155.0
157.5
160.0
162.5
165.0
167.5
170.0
172.5
175.0
177.5
180.0

142
117
102
96
93
93
103
118
132
139
142
138
123
98
72
50
29
23
21

Photometric Toolbox Professional Edition (c) copyright 1995-2008 by Lighting Analysts, Inc.
Calculations based on published IES Methods and recommendations, values rounded for display purposes.
Results derived from content of manufacturers photometric file.

Page 3

IES INDOOR REPORT


PHOTOMETRIC FILENAME : ITL47874.IES
ZONAL LUMEN SUMMARY
Zone

Lumens

%Lamp

%Fixt

0-30
0-40
0-60
0-90
90-120
90-130
90-150
90-180
0-180

656.65
1273.94
2839.72
3862.15
941.17
1160.07
1333.02
1430.08
5292.23

11.7
22.7
50.7
69
16.8
20.7
23.8
25.5
94.5

12.4
24.1
53.7
73
17.8
21.9
25.2
27
100

Total Luminaire Efficiency = 94.5%


ZONAL LUMEN SUMMARY
Zone

Lumens

0-10
10-20
20-30
30-40
40-50
50-60
60-70
70-80
80-90
90-100
100-110
110-120
120-130
130-140
140-150
150-160
160-170
170-180

61.9
204.3
390.45
617.29
848.65
717.13
449.39
302.86
270.18
299.58
333.13
308.47
218.9
112.54
60.41
58.65
34.09
4.32

Photometric Toolbox Professional Edition (c) copyright 1995-2008 by Lighting Analysts, Inc.
Calculations based on published IES Methods and recommendations, values rounded for display purposes.
Results derived from content of manufacturers photometric file.

Page 4

IES INDOOR REPORT


PHOTOMETRIC FILENAME : ITL47874.IES
COEFFICIENTS OF UTILIZATION - ZONAL CAVITY METHOD
Effective Floor Cavity Reflectance 0.20
RC
RW

80
70 50 30 10

70
70 50 30 10

50
50 30 10

30
50 30 10

10
50 30 10

0
0

0
1
2
3
4
5
6
7
8
9
10

106 106 106 106


95 90 86 82
86 78 71 65
78 68 60 53
71 59 51 44
65 52 44 37
59 46 38 32
55 42 33 27
50 37 29 24
47 34 26 21
44 31 23 18

101 101 101 101


90 86 82 78
81 74 68 62
73 64 57 51
67 56 48 42
61 50 42 36
56 44 36 30
51 40 32 26
47 36 28 23
44 32 25 20
41 30 23 18

91
77
66
58
51
45
40
36
32
29
27

82
69
59
52
45
40
36
32
29
27
24

73
62
53
46
41
36
32
29
26
24
22

69
54
44
36
30
25
21
18
16
14
12

91
74
61
52
44
38
33
29
26
23
21

91
71
57
47
39
33
28
24
21
19
17

82
66
55
47
40
35
30
27
24
21
19

82
64
52
43
36
30
26
22
20
17
15

73
60
50
42
36
31
27
24
22
19
17

Photometric Toolbox Professional Edition (c) copyright 1995-2008 by Lighting Analysts, Inc.
Calculations based on published IES Methods and recommendations, values rounded for display purposes.
Results derived from content of manufacturers photometric file.

73
58
47
39
33
28
24
21
18
16
14

Page 5

IES INDOOR REPORT


PHOTOMETRIC FILENAME : ITL47874.IES
POLAR GRAPH

1124

843

562

281

Maximum Candela = 1124 Located At Horizontal Angle = 0, Vertical Angle = 45


# 1 - Vertical Plane Through Horizontal Angles (0 - 180) (Through Max. Cd.)
# 2 - Horizontal Cone Through Vertical Angle (45) (Through Max. Cd.)

Photometric Toolbox Professional Edition (c) copyright 1995-2008 by Lighting Analysts, Inc.
Calculations based on published IES Methods and recommendations, values rounded for display purposes.
Results derived from content of manufacturers photometric file.

Page 6