Edwards Signaling EBPS6A Data Sheet
Edwards Signaling EBPS6A Data Sheet
Remote Booster
Power Supplies
EBPS6A, EBPS10A
MEA
476-91-E
Vol.13
Overview
Standard Features
Page 1 of 4
S85005-0125
D ATA S H E E T
Not to be used for installation purposes. Issue 5
Application
Dimensions
D5
D2
D3
Side View
D4
Front View
D1
D6
Side View
Top View
All knockouts
for 3/4 in conduit
(1.9 cm)
D1
D2
D3
D4
D5
D6
17.0 in
(43.2 cm)
3.5 in
(8.9 cm)
13.0 in
(33.0 cm)
6.5 in
(16.5 cm)
3.375 in
(8.6 cm)
12.0 in
(30.4 cm)
Wire routing
The EBPS enclosure has mounting brackets for up to three Signature modules to the right of the circuit board.
Engineering Specification
Supply, where needed, Edwards EBPS Series Booster Power
Supplies (EBPS) that are interconnected to and supervised by the
main system. The EBPS shall function as a stand-alone auxiliary
power supply with its own fully-supervised battery compliment.
The EBPS battery compliment shall be sized to match the requirements of the main system. The EBPS shall be capable of supervising and charging batteries having the capacity of 24 ampere-hours
for Mass Notification/Emergency Communication (MNEC), life
safety and security applications, and the capacity of 65 amperehours for access control applications.
The EBPS shall provide a minimum of four independent, fully supervised Class B circuits that can be field configurable for notification appliance circuits or auxiliary 24 Vdc power circuits. EBPS
NACs shall be convertible to a minimum of two Class A NACs.
Each EBPS output circuit shall be rated at 3 amperes at 24 Vdc.
Each output circuit shall be provided with automatically restoring
overcurrent protection. The EBPS shall be operable from the main
system NAC and/or Edwards Signature Series control modules.
EBPS NACs shall be configurable for continuous, 3-3-3 temporal
or optionally, California rate. Fault conditions on the EBPS shall
not impede operation of main system NAC. The EBPS shall be
provided with ground fault detection circuitry and a separate AC
fail relay.
Page 2 of 4
Notes
1. Maintain 1/4-inch (6 mm) spacing between power-limited and nonpower-limited
wiring or use type FPL, FPLR, or FPLP cable per NEC.
[2] Power-limited and supervised when not configured as auxiliary power. Nonsupervised when configured as auxiliary power.
[3] Source must be power-limited. Source determines supervision.
4. When using larger batteries, make sure to position the battery terminals towards
the door.
S85005-0125
D ATA S H E E T
Not to be used for installation purposes. Issue 5
Typical Wiring
Single or cascaded booster
anywhere on a notification appliance circuit
Fire Alarm
Control Panel
Sense 2 Input
Sense 1 Input
To next signaling
device, booster, or
EOL resistor
NAC Circuit
NAC Circuit
NAC output #1
NAC output #2
NAC output #3
NAC output #4
Booster Power
Supply
+
EOL 47 k
E-NAC Module
E-IDC1B
Module
Data in from
previous device
or loop controller
Data out to
next device
+ +
+
+
UL listed
EOL 15 KOhm
IN
Sense 1 COM
OUT
IN
Sense 2 COM
OUT
NO
Trouble COM
NC
EOL 47 K
+
+
200 mA AUX
Continuous
UL listed
EOL 15 KOhm
UL listed
EOL 15 k Ohm
TB5
IN
Sense 1 COM
OUT
IN
Sense 2 COM
OUT
NO
Trouble COM
NC
Page 3 of 4
NAC1/
AUX1
NAC2/
AUX2
NAC3/
AUX3
NAC4/
AUX4
UL listed
EOL 15 k Ohm
+
TB5
NAC1/
AUX1
NAC2/
AUX2
NAC3/
AUX3
NAC4/
AUX4
200 mA AUX
Continuous
EOL 47 K
E-NAC Module
E-NAC Module
Data out to
next device
+
S85005-0125
D ATA S H E E T
Not to be used for installation purposes. Issue 5
Specifications
Model
AC Line Voltage
Contact us...
Phone: 1-800-336-4206
Web: www.edwardssignaling.com
Edwards Signaling is
an EDWARDS brand.
3 Farm Glen Boulevard
Farmington, CT 06032
In Canada, contact Chubb Edwards...
Email: [email protected]
Web: www.chubbedwards.com
2013 UTC Fire & Security Americas
Corporation, Inc. All rights reserved.
Specifications subject to change
without notice. Edwards is part of UTC
Climate, Controls & Security, a unit of
United Technologies Corporation.
Notification Appliance
Circuit Ratings
Trouble Relay
Auxiliary Outputs
Input Current
(from an existing NAC)
Booster Internal
Supervisory Current
Booster Internal Alarm
Current
Signature Mounting
Space
Maximum Battery Size
Ordering Information
Catalog
Number
EBPS6A
EBPS10A
Description
Shipping
Wt. lb (kg)
13 ( 5.9)
13 ( 5.9)
Related Equipment
12V6A5
7.2 Amp Hour Battery, two required
12V10A
10 Amp Hour Battery, two required
BC-1
Battery Cabinet (up to 2 - 40 Amp Hour Batteries)
BC-2
Battery Cabinet (up to 2 - 17 Amp Hour Batteries)
12V17A
18 Amp Hour Battery, two required (see note 1)
12V24A
24 Amp Hour Battery, two required (see note 1)
12V40A
40 Amp Hour Battery, two required (see notes 1, 2)
12V50A
50 Amp Hour Battery, two required (see notes 1, 2)
12V65A
65 Amp Hour Battery, two required (see notes 1, 2)
1.
2.
S85005-0125
D ATA S H E E T
Not to be used for installation purposes. Issue 5
06-27-13
Page 4 of 4
3.4 (1.6)
9.5 (4.3)
58 (26.4)
19 (8.6)
13 ( 5.9)
20 (9.07)
32 (14.5)
40 (18.14)
49 (22.2)