User Manual 1 2 3 KVA UPS Epsilon
User Manual 1 2 3 KVA UPS Epsilon
User Manual 1 2 3 KVA UPS Epsilon
UPS EPSILON
www.qbex.com
Table of Contents
1. Important Safety Warning 4
1-1. Transportation..........................................................................................
1-2. Preparation..............................................................................................
1-3. Installation................................................................................................
1-4. Operation.................................................................................................
1-5. Maintenance, service and faults..............................................................
4
4
4
5
5
3. Operations....... 8
4. Troubleshooting... 21
5. Storage and Maintenance 22
6. Specifications.. 23
1-4. Operation
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and
read carefully the following instructions before installing the unit. Do not operate this unit before reading through
all safety information and operating instructions carefully.
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective earthing of the
UPS system and of all connected loads.
1-1. Transportation
The UPS system features its own, internal current source (batteries). The UPS output sockets
or output terminals block may be electrically live even if the UPS system is not connected to the
building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the
mains.
Prevent no fluids or other foreign objects from inside of the UPS system.
Please transport the UPS system only in the original package to protect against shock and impact.
1-2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS
system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to
acclimate the environment.
Do not install the UPS system where it would be exposed to direct sunlight or near heater.
1-3. Installation
Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS
output sockets.
Place cables in such a way that no one can step on or trip over them.
Do not connect domestic appliances such as hair dryers to UPS output sockets.
Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to
the UPS system.
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer) to connect the
UPS system to the building wiring outlet (shockproof outlet).
Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the con
nected devices does not exceed 3.5mA.
UPS
The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified
maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet),
components inside the UPS system are still connected to the battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no
current is present and no hazardous voltage exists in the terminals of high capability capacitor such as
BUS-capacitors.
Only persons are adequately familiar with batteries and with the required precautionary measures may
replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
Caution - risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages
may occur between the battery terminals and the ground. Before touching, please verify that no voltage is
present!
Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary
measures specified below and any other measures necessary when working with batteries:
Remove wristwatches, rings and other metal objects
use only tools with insulated grips and handles.
When changing batteries, install the same number and same type of batteries.
Do not attempt to dispose of batteries by burning them. This could cause battery explosion.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
Do not dismantle the UPS system.
UPS
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please
keep the original package in a safe place for future use.
2K(L) TOWER
NOTE: There are two different types of online UPS: standard and long-run models. Please refer to the following
model table.
Model
1K
2K
3K
Type
Standard
Model
1KL
2KL
3KL
Type
Long-run
IEC Tipo
3K(L) TOWER
IEC Tipo
NEMA Tipo
NEMA Tipo
IEC Tipo
NEMA Tipo
1K(L) RACK
NEMA Tipo
2K(L) RACK
AC input
10
11
Output terminal
12
13
Input terminal
UPS
IEC Tipo
NEMA Tipo
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
For 208/220/230/240VAC models: The power cord is supplied in the UPS package.
For 110/115/120/127VAC models: The power cord is attached to the UPS. The input plug is a NEMA
5-15P for 1K, 1KL, 1.5K and 1.5KL models, NEMA 5-20P for 2K and 2KL models.
Note: For Low voltage models: Check if the site wiring fault indicator lights up in LCD panel. It will be illuminated
when the UPS is plugged into an improperly wired utility power outlet (Refer to Troubleshooting section).
3K(L) RACK
IEC Tipo
NEMA Tipo
For socket-type outputs, there two kinds of outputs: programmable outlets and general outlets. Please
connect non-critical devices to the programmable outlets and critical devices to the general outlets.
During power failure, you may extend the backup time to critical devices by setting shorter backup time
for non-critical devices.
For terminal-type input or outputs, please follow below steps for the wiring configuration:
a) Remove the small cover of the terminal block
b) Suggest using AWG14 or 2.1mm2 power cords. Suggest using WG12-10 or 3.3mm2-5.3mm2 power
cords for NEMA type.
c) Upon completion of the wiring configuration, please check whether the wires are securely affixed.
d) Put the small cover back to the rear panel.
RS-232 port
Intelligent slot
For optimal computer system protection, install UPS monitoring software to fully configure UPS
shutdown. You may insert provided CD into CD-ROM to install the monitoring software. If not, please
follow steps below to download and install monitoring software from the internet:
UPS
USB port
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery
run capability during this initial charge period.
Connect a single modem/phone/fax line into surge-protected IN outlet on the back panel of the UPS unit. Connect
from OUT outlet to the equipment with another modem/fax/phone line cable.
Keep the pin 1 and pin 2 closed for UPS normal operation. To activate EPO function, cut the wire between pin 1
and pin 2.
10
3. Operations
UPS
Button
ON/Mute Button
Function
Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn
on the UPS.
Mute the alarm: When the UPS is on battery mode, press and hold this button
for at least 5 seconds to disable or enable the alarm system. But its not applied
to the situations when warnings or errors occur.
Up key: Press this button to display previous selection in UPS setting mode.
Switch to UPS self-test mode: Press and hold ON/Mute button for 5 seconds
to enter UPS self-testing while in AC mode, ECO mode, or converter mode.
Display
Function
OFF/Enter
Button
Select Button
ON/Mute
+ Select Button
Turn off the UPS: Press and hold this button at least 2 seconds to turn off the
UPS in battery mode. UPS will be in standby mode under power normal or
transfer to Bypass mode if the Bypass enable setting by pressing this button.
Confirm selection key: Press this button to confirm selection in UPS setting
mode.
Switch LCD message: Press this button to change the LCD message for input
voltage, input frequency, battery voltage, output voltage and output frequency.
It will return back to default display when pausing for 10 seconds.
Setting mode: Press and hold this button for 5 seconds to enter UPS setting
mode when UPS is in standby mode or bypass mode.
Down key: Press this button to display next selection in UPS setting mode.
Switch to bypass mode: When the main power is normal, press ON/Mute and
Select buttons simultaneously for 5 seconds. Then UPS will enter to bypass
mode. This action will be ineffective when the input voltage is out of acceptable
range.
Fault information
Indicates that the warning and fault occurs.
Indicates the warning and fault codes, and the codes are listed in
details in 3-5 section.
Mute operation
Indicates that the UPS alarm is disabled.
Load information
Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
OVER LOAD
SHORT
Indicates overload.
Indicates the load or the UPS output is short circuit.
P1
12
Abbreviation
Indicates the UPS connects to the mains.
ECO
Display content
Meaning
ENA
Enable
DIS
Disable
ESC
Escape
HLS
High loss
LLS
Low loss
BAT
Battery
CF
Converter
EP
EPO
FA
Fan
TP
Temperature
CH
Charger
BATT. FAULT
LOW BATT.
UPS
Display
Parameter 1
14
Battery Mode
Low Battery
Overload
Fault
Continuously sounding
Bypass Mode
Parameter 2
Parameter 3
Setting
Setting
Setting
16
Interface
Setting
Parameter 2 & 3: Set the acceptable high voltage point and low
voltage point for ECO mode by pressing Down key or Up key.
HLS: High loss voltage in ECO mode in parameter 2.
For 208/220/230/240 VAC models, the setting range in
parameter 3 is from +7V to +24V of the nominal voltage.
For 110/115/120/127 VAC models, the setting range in
parameter 3 is from +3V to +12V of the nominal voltage.
UPS
Interface
Setting
Setting
Interface
Setting
Online mode
ECO mode
Frequency
Converter
mode
Battery mode
Bypass mode
Standby mode
LCD display
Setting
Parameter 3:
Set up backup time limits for programmable outlets.
0-999: setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices on
battery mode.
18
Description
UPS
Operating mode
4. Troubleshooting
Icon
Fault event
Fault code
Icon
01
13
Bus over
02
14
SHORT
Bus under
03
27
BATT. FAULT
Bus unbalance
04
28
BATT. FAULT
11
Over temperature
41
12
Over load
43
OVER LOAD
Icon (flashing)
Low Battery
LOW BATT.
Overload
OVER LOAD
Over Charge
EPO enable
Fan Failure
Over temperature
Charger failure
Out of bypass voltage range
20
Alarm
EP
FA
CH
If the UPS system does not operate correctly, please solve the problem by using the table below.
Symptom
No indication and alarm even
though the mains is normal.
The icon
and the
warning code flashing
on LCD display and alarm is
sounding every second.
The icon
and
flashing on LCD display and
alarm is sounding every
second.
The icon
and
flashing on LCD display and
alarm is sounding every
second.
UPS is overload
EP
The icon
and OVER LOAD is
flashing on LCD display and
alarm is sounding twice every
second.
Remedy
Possible cause
UPS
Fault event
Symptom
Fault code is shown as 1, 2,
3, 4, 11, 12, 13 and 41 on
LCD display and alarm is
continuously sounding.
Possible cause
Remedy
The icon
and the
warning code flashing
on LCD display and alarm is
sounding every second.
FA
6. Specifications
CAPACITY
INPUT
Voltage
Range
Batteries defect
1000 VA / 800 W
Low Line Transfer
OUTPUT
160 VAC / 140 VAC / 120 VAC / 110 VAC 5 % or 80 VAC / 70 VAC / 60 VAC / 50 VAC 5 %
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
175 VAC 5 % or 85 VAC 5 %
300 VAC 5 % or 150 VAC 5 %
290 VAC 5 % or 145 VAC 5 %
40Hz ~ 70 Hz
Single phase with ground
0.99 @ 220-230 VAC (input voltage)
208/220/230/240VAC or 110/115/120/127 VAC
3% (Batt. Mode)
47 ~ 53 Hz or 57 ~ 63 Hz
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
Overload
Transfer
Time
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25C ambient
temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.
3:1
Harmonic Distortion
5-1. Operation
Zero
4 ms (Typical)
Pure Sinewave
EFFICIENCY
~ 85%
AC Mode
Battery Mode
~ 88%
~ 83%
BATTERY
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During storage,
recharge the battery in accordance with the following table:
Storage Temperature
Recharge Frequency
Charging Duration
-25C - 40C
Every 3 months
1-2 hours
40C - 45C
Every 2 months
1-2 hours
Standard
Model
Battery Type
Numbers
Recharge Time
Charging Current
Charging Voltage
Long-run
Model
12 V / 7 AH
3
12 V / 9 AH
12 V / 7 AH
12 V / 9 AH
3
6
6
4 hours recover to 90% capacity (Typical)
1.0 A(max.)
41.0 VDC 1%
82.1 VDC 1%
Depending on the capacity of external batteries
4.0 A or 8.0 A(max.)
41.0 VDC 1%
82.1 VDC 1%
PHYSICAL
Tower
Case
Dimension, D X W X H
Net Weight (kgs)
Rack
Case
Dimension, D X W X H
Net Weight (kgs)
ENVIRONMENT
Operation Humidity
Noise Level
MANAGEMENT
14
26
16
10
17
13
28
13
580x438x133[3U] (mm)
420x438x88[2U] (mm)
10
29
17
31
17
* Derate capacity to 60% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 208VAC.
22
Tabla de Contenido
1. Aviso Importante de Seguridad.....................................................................
26
1-1. Transporte......................................................................................................
1-2. Preparacin....................................................................................................
1-3. Instalacin......................................................................................................
1-4. Operacin.......................................................................................................
1-5. Mantenimiento, servicio y fallas......................................................................
26
26
26
27
27
2. Instalacin y ajuste.......................................................................................
28
28
31
3. Operacin......................................................................................................
34
34
35
36
37
41
42
42
42
4. Solucin de problemas..................................................................................
5. Almacenamiento y Mantenimiento................................................................
6. Especificaciones............................................................................................
43
44
45
1-1. Transporte
Por favor transporte el sistema UPS solo en el empaque original para proteger de choques e impactos.
1-2. Preparacin
Puede ocurrir condensacin si el sistema UPS es movido directamente desde un ambiente fro a caliente. El
sistema UPS debe estar absolutamente seco antes de ser instalado. Por favor, espere al menos dos horas
para que el sistema de UPS para aclimatarse al medio ambiente.
No instale el sistema UPS donde pueda estar expuesto a la luz directa del sol o cerca de calor.
1-3. Instalacin
No conecte aplicaciones o dispositivos los cuales puedan sobrecargar el sistema UPS (e.g. impresora lser)
a la salida del UPS.
Ubique los cables de una forma adecuada que nadie pueda pisar o tropezar con ellos.
No conecte aplicaciones domesticas como secador de pelo a las tomas de salida del UPS.
El UPS puede ser operado por cualquier individuo sin previa experiencia.
Conecte el sistema UPS slo a una salida puesta a tierra que debe ser fcilmente accesible y cerca del
sistema de UPS.
Por favor, use slo cable de red certificado (por ejemplo, el cable de red de su ordenador) para conectar el
sistema UPS a la toma de corriente de un edificio.
Por favor use solo cable certificado para conectar las cargas al sistema UPS.
Cuando instale el equipo, asegrese que la suma de corrientes de fuga del UPS no excedan 3.5mA.
26
No desconecte el cable principal en el sistema UPS o los cables de salida del edificio durante la
operacin, ello anulara la proteccin de tierra del UPS y de todas las cargas conectadas.
El sistema UPS cuenta con su propia fuente de corriente interna (bateras). Las tomas de salida
del UPS o bloque de salida de los terminales puede ser elctricamente activo, incluso si el
sistema UPS no est conectado a la toma de cableado del edificio.
Para desconectar completamente el sistema de UPS, presione primero el OFF / Enter para
desconectar la red elctrica.
UPS
Por favor cumpla estrictamente con todas las advertencias e instrucciones de operacin de este manual. Guarde
este manual apropiadamente y lea cuidadosamente las siguientes instrucciones antes de instalar la unidad. No
opere esta unidad antes de leer cuidadosamente atravs de toda la informacin de seguridad e instrucciones de
operacin.
1-4. Operacin
El sistema UPS opera con voltajes peligrosos. Reparaciones solo pueden llevarse acabo por personal de
mantenimiento calificado.
Precaucin Riesgo de descarga elctrica. Incluso despus de que la unidad est desconectada de la red
elctrica (enchufe del cableado del edificio), componentes internos del sistema UPS an est conectado a la
batera y elctricamente activo y peligroso.
Antes de realizar cualquier tipo de servicio y / o mantenimiento, desconecte las bateras y compruebe que no
hay corriente presente y no existe tensin peligrosa en los terminales del condensador de alta capacidad
como BUS-condensadores.
Slo las personas que estn debidamente familiarizados con bateras y con las medidas necesarias de
precaucin puede reemplazar las bateras y supervisar las operaciones. Las personas no autorizadas deben
mantenerse alejados de las bateras.
Precaucin Riesgo de descarga elctrica. El circuito de la batera no est aislado de la tensin de entrada.
Tensin peligrosa puede ocurrir entre los terminales de la batera y el suelo. Antes de tocar, por favor
verifique que no haya tensin!
Bateras podra causar descargas elctricas y tienen una alta corriente de corto circuito. Por favor, tome las
medidas cautelares indicadas a continuacin y las dems medidas necesarias cuando se trabaja con las
bateras:
Retrese relojes de pulsera, anillos y otros objetos.
Utilizar slo herramientas con mangos y manija aisladas.
No intente desechar las bateras por la quema de ellos. Esto podra provocar una explosin de la batera.
No abrir o destruir las bateras. Escape de electrolitos puede causar lesiones en la piel y los ojos.
Puede ser txico.
Por favor reemplace el fusible solo con el mismo tipo y amperaje a fin de evitar riesgos de incendio.
No desmonte el sistema UPS.
2. Instalacin y ajuste
UPS
NOTE: Antes de instalar, por favor inspeccione la unidad. Asegrese que no hay nada daado dentro del
empaque. Por favor mantenga el empaque original en un lugar seguro para futuros usos.
2K (L) TORRE
NOTA: Hay dos tipos diferentes de UPS online: Modelo estndar y larga duracin. Por favor refirase a la
siguiente tabla.
Modelo
1K
2K
3K
Tipo
Estndar
Modelo
1KL
2KL
3KL
Tipo
Larga
duracin
Tipo IEC
28
Tipo IEC
Tipo NEMA
Tipo IEC
Tipo NEMA
3K (L) TORRE
Tipo NEMA
1K(L) RACK
Tipo NEMA
Entrada AC
10
Terminal de Salida
11
12
Terminal de entrada
UPS
Tipo IEC
2K(L) RACK
Conecte el UPS conector de tres hilos, dos polos y receptculo conectado a tierra. Evite el uso de cables de
extensin
Tipo IEC
Tipo NEMA
Para modelos 208/220/230/240VAC: El cable de alimentacin esta incluido en el empaque del UPS.
Para modelos 110/115/120/127VAC: El cable de alimentacin esta conectado al UPS. El conector de
entrada es un NEMA 5-15P para modelos 1K y 1KL, NEMA 5-20P para modelos 2K y 2KL.
Nota: Para modelos de bajo voltaje: Revise si el indicador de falla en cableado del sitio esta indicando falla en
el panel frontal. Este se iluminara cuando el UPS esta conectado no apropiadamente (Refirase a la seccin de
Gua de Fallas).
3K(L) RACK
Tipo IEC
30
Tipo NEMA
Para las salidas tipo socket, hay dos clases de salidas: salidas programables y salidas generales. Por
favor conecte dispositivos no crticos a las salidas programables y dispositivos crticas a las salidas
generales. Durante una falla de alimentacin de entrada, usted puede extender el tiempo de respaldo a
dispositivos crticos, acortando el tiempo de respaldo para dispositivos no crticos.
Para terminal tipo entrada o salida, por favor siga los pasos siguientes para configuracin del cableado:
a) Remueva la pequea tapa del bloque de terminales
b) Sugerido usar cable AWG14 o 2.1mm2 para el cable de alimentacin. Sugerido usar cable WG12-10
o 3.3mm2-5.3mm2 para el cable de alimentacin tipo NEMA.
c) Una vez completada la configuracin del cableado, por favor compruebe que los cables estn firme
mente fijados.
d) Ponga la pequea tapa en el panel trasero.
Ranura Inteligente
Para permitir la vigilancia del apagado y arranque del UPS y monitoreo del estatus, conecte un el cable de
comunicacin al Puerto USB/RS-232 y otro al Puerto de comunicacin de su PC. Con el software de monitoreo
instalado, usted puede programar el horario de encendido / apagado y monitoreo del UPS atravs de su PC.
El UPS esta equipado con una ranura perfecta inteligente para ambas tarjetas SNMP o AS400. Cuando instale la
tarjeta SNMP o AS400 en el UPS, provee avanzadas opciones de comunicacin y monitoreo.
PS. El Puerto USB y RS-232 no pueden trabajar al mismo tiempo.
Nota: Las bateras quedaran cargadas totalmente durante las primeras cinco horas de
operacin normal. No espere respaldo de la capacidad total de la batera durante el periodo
de carga inicial.
UPS
Puerto USB
Presione el botn de ON/Mute ubicado en el panel frontal por dos segundos para encender el UPS.
Mantenga el pin 1 y el pin 2 cerrado para operacin normal del UPS. Para activar la funcin de EPO, abra el
cable entre pin 1 y pin 2.
32
3. Operaciones
UPS
Botn
ON/Mute Botn
OFF/Enter
Botn
Select Botn
ON/Mute
+ Select Botn
Funcin
Encienda el UPS: Presione el botn de ON/Mute por lo menos 2 segundos
para que encienda el UPS.
Alarma de Silencio (Mute): Cuando el UPS est en modo batera, presione
este botn y espere por lo menos 5 segundos para deshabilitar o habilitar el
sistema de alarma. Esto no se aplica a situaciones de advertencia o cuando
ocurre un error.
Tecla de subir (Up key): Presione este botn par ver la pantalla anterior en el
modo de ajustes del UPS.
Cambiar el UPS a modo de auto-prueba: Presione el botn ON/Mute y
espere por 5 segundos para iniciar el autodiagnstico mientras el UPS esta en
modo AC, modo ECO, o modo Inversor.
Apague el UPS: Presione este botn y espere por lo menos 2 segundos para
apagar el UPS en modo de batera. El UPS debe estar en modo de espera
con la energa normal o transferir a modo de Bypass en caso de estar
habilitado.
Confirmar tecla de seleccin: Presione este botn para confirmar lo
seleccionado en modo ajustes del UPS.
Cambiar mensaje en LCD: Presione este botn para cambiar el mensaje de
la pantalla para voltaje de entrada, frecuencia de entrada, voltaje de batera,
salida de voltaje y salida de frecuencia. Este regresara por defecto al display
inicial cuando pasen 10 segundos.
Modo Ajustes: Presione este botn y espere 5 segundos para entrar al modo
de ajustes del UPS cuando el UPS esta en modo de stanbye o bypass.
Tecla de bajar (Down key): Presione este botn para seleccionar la siguiente
pantalla en el modo de ajustes del UPS.
Cambiar a modo de bypass: Cuando el suministro de energa es normal,
presione ON/Mute y seleccione los botones simultneamente por 5
segundos. Luego el UPS entrara en modo de bypass. Esta accin no ser
eficiente cuando los rangos de entrada de voltaje no son aceptables.
Mostrar
Funcin
Informacin de Falla
Indica advertencia y ocurri una falla.
Indica advertencia y cdigo de falla, el detalle de los cdigos esta
listado en la seccin 3-5.
Operacin de Silencio
Indica que la alarma del UPS est deshabilitada.
Informacin de Carga
Indica el nivel de carga de 0-25%, 26-50%, 51-75%, y 76-100%.
OVER LOAD
SHORT
Indica sobrecarga.
Indica la carga o el circuito de salida del UPS est en corto circuito.
P1
34
Abreviacin
ECO
Contenido de la pantalla
Significado
ENA
Habilitado
DIS
Deshabilitado
ESC
Escape
HLS
Alta perdida
LLS
Baja perdida
BAT
Batera
CF
Conversor
EP
EPO
FA
Ventilador
TP
Temperatura
CH
Cargador
BATT. FAULT
LOW BATT.
UPS
Mostrar
Parmetro 1
36
Modo Batera
Baja Batera
Sobrecarga
Falla
Pita Continuamente
Modo Bypass
Parmetro 2
Parmetro 3
Ajuste
Interfaz
Ajuste
UPS
Interfaz
Ajuste
Ajuste
Ajuste
38
Ajuste
Interface
Ajuste
Modo Online
Modo ECO
Modo de
conversor de
Frecuencia
Modo Batera
Modo Bypass
Modo Standby
Pantalla LCD
Ajuste
40
Descripcion
UPS
Modo Operacin
4. Solucin de Problemas
Evento de falla
Cdigo falla
Icono
01
13
02
14
SHORT
03
27
BATT. FAULT
Bus desbalanceado
04
28
BATT. FAULT
Inversor en falla
11
Sobre temperature
41
12
Sobre carga
43
OVER LOAD
Icon (Parpadeando)
Batera baja
LOW BATT.
Sobrecarga
OVER LOAD
Batera desconectada
Sobrecarga
EPO Habilitado
Ventilador Fallo
Sobre temperature
Falla de carga
Fuera del Rango de voltaje
en bypass
42
Alarma
EP
FA
CH
Si el sistema no opera correctamente, por favor resuelva el problema usando la tabla siguiente
Sintomas
El icono
y
el
cdigo de advertencia parpadea en la pantalla y la alarma
suena cada segundo.
El icono
y
parpadea
en la pantalla y la alarma
suena cada segundo.
El icono
y
parpadean en la pantalla y la
alarma suena cada segundo.
Contacte su distribuidor.
Contacte su distribuidor.
EP
El icono
y OVER LOAD
est iluminando en la pantalla
y la alarma suena dos veces
cada segundo.
Solucin
Posible causa
UPS
Evento de error
Sintomas
Posible causa
El tiempo de batera es ms
corto que el valor nominal.
El icono
y el cdigo
de advertencia
parpadeando en la pantalla
y la alarma pitando cada
segundo.
FA
Solucin
Contacte su distribuidor
6. Especificaciones
CAPACIDAD*
ENTRADA
Rango
Voltaje
Defecto de Bateras
SALIDA
1000 VA / 800 W
160 VAC / 140 VAC / 120 VAC / 110 VAC 5 % or 80 VAC / 70 VAC / 60 VAC / 50 VAC 5 %
( basado en porcentaje de Carga 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
175 VAC 5 % or 85 VAC 5 %
300 VAC 5 % or 150 VAC 5 %
290 VAC 5 % or 145 VAC 5 %
40Hz ~ 70 Hz
Fase monofsica con tierra
0.99 @ 220-230 VAC (input voltage)
208/220/230/240VAC or 110/115/120/127 VAC
3% (Modo Batera)
47 ~ 53 Hz or 57 ~ 63 Hz
Voltaje de salida
Regulacin de voltaje AC
Rango de Frecuencia
(Rango sincronizado)
Rango de Frecuencia (Modo Batera)
Sobre carga
5. Almacenamiento y Mantenimiento
Corriente de cresta
Distorsin Armnica
5-1. Operacin
Tiempo
transferencia
El UPS no contiene partes reparables por el usuario. Si la vida til de las bateras (3~5 aos a 25C a temperatura
ambiente) ha sido excedida, las bateras deben ser reemplazadas. En este caso, por favor contacte a su
distribuidor.
3:1
Modo AC A Batera
Inversor a Bypass
Almacenar
Antes de almacenar, cargue el UPS 5 horas. Almacene el UPS cubierto en posicin vertical en lugar fresco y
seco. Durante el almacenamiento, recargue la batera de acuerdo a la siguiente tabla:
Temperatura almacenaje
Frecuencia de recarga
Duracin de la carga-
25C - 40C
Cada 3 meses
1-2 horas
40C - 45C
Cada 2 meses
1-2 horas
Zero
4 ms (Tpico)
Onda seno pura
EFICIENCIA
~ 85%
Modo AC
Modo Batera
~ 88%
~ 83%
BATERIA
Modelo
Estandar
Tipo Batera
Nmero
Tiempo de recarga
Corriente de carga
Voltaje de carga
Modelo
de larga
duracin
12 V / 7 AH
3
12 V / 9 AH
12 V / 7 AH
12 V / 9 AH
3
6
6
4 horas recuperado al 90% capacidad (Tpica)
1.0 A(max.)
41.0 VDC 1%
82.1 VDC 1%
Dependiendo de la capacidad de las bateras externas
4.0 A or 8.0 A(max.)
41.0 VDC 1%
82.1 VDC 1%
FISICAS
Tipo
Torre
Dimension, D X W X H
Peso Neto (kgs)
Tipo
Rack
Dimension, D X W X H
Peso Neto (kgs)
AMBIENTE
Operacin Humedad
Nivel de Ruido
SOFTWARE
14
26
16
10
17
13
28
13
580x438x133[3U] (mm)
420x438x88[2U] (mm)
10
29
17
31
17
* Derateado capacidad a 60% en modo conversor de frecuencia y a 80% cuando el voltaje de salida es ajustado a 208VAC.
44
Manual Usuario
UPS EPSILON
www.qbex.com