PB-18 Input Data: 1. General Details

This document contains input data for an air handling system called PB-18 that serves two zones. It includes general details, components, zone assignments, thermostat settings, sizing calculations, and equipment specifications. The system has a supply airflow of 5095.2 L/s from a forward curved fan and provides 725 L/s of outdoor air. Zone 1 has a supply airflow of 4313.6 L/s and zone 2 has 628.7 L/s. Central cooling is provided by an air-cooled DX unit with an estimated maximum load of 102 kW and design efficiency of 2.96 EER.

Uploaded by

amirin_king
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
94 views2 pages

PB-18 Input Data: 1. General Details

This document contains input data for an air handling system called PB-18 that serves two zones. It includes general details, components, zone assignments, thermostat settings, sizing calculations, and equipment specifications. The system has a supply airflow of 5095.2 L/s from a forward curved fan and provides 725 L/s of outdoor air. Zone 1 has a supply airflow of 4313.6 L/s and zone 2 has 628.7 L/s. Central cooling is provided by an air-cooled DX unit with an estimated maximum load of 102 kW and design efficiency of 2.96 EER.

Uploaded by

amirin_king
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 2

PB-18 Input Data

Project Name: BANYU_URIP_PROJECT_REV


Prepared by: wen

11/13/2014
03:43PM

1. General Details:
Air System Name ...................................................................................... PB-18
Equipment Type ........................................................ Packaged Rooftop Units
Air System Type ........................................................................ Dual Duct CAV
Number of zones ............................................................................................... 2
2. System Components:
Ventilation Air Data:
Airflow Control .................................................... Constant Ventilation Airflow
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Unocc. Damper Position ......................................................................... Closed
Damper Leak Rate ............................................................................................ 0 %
Outdoor Air CO2 Level .................................................................................. 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................... 14.4 C
Coil Bypass Factor ..................................................................................... 0.100
Cooling Source ........................................................................... Air-Cooled DX
Schedule ............................................................................... JFMAMJJASOND
Capacity Control ........................................... Constant Temperature - Fan On
Central Heating Data:
Supply Temperature ..................................................................................... 24.0 C
Heating Source .................................................................. Electric Resistance
Schedule ............................................................................... JFMAMJJASOND
Capacity Control ........................................... Constant Temperature - Fan On
Supply Fan Data:
Fan Type ................................................................................. Forward Curved
Configuration ...................................................................................... Blow-thru
Fan Performance .......................................................................................... 700 Pa
Overall Efficiency ............................................................................................ 65 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................. 2 %
Duct Leakage .................................................................................................... 3 %
Return Duct or Plenum Data:
Return Air Via ............................................................................. Ducted Return
3. Zone Components:
Space Assignments:
Zone 1: Zone 1-LER
SUBSTATTION_PB_18
Zone 2: Zone 2-LIR
SUBSTATTION_PB_18_LIR

x1
x1

Thermostats and Zone Data:

Zone

Cooling T-Stat
Occ.
(C)

Cooling T-Stat
Unocc.
(C)

Heating T-Stat
Occ.
(C)

Heating T-Stat T-Stat Throttling


Unocc.
Range
(C)
(C)

Diversity
Factor
(%)

Direct
Exhaust
Airflow
(L/s)

Direct Exhaust
Fan
(kW)

24.0

27.0

21.1

15.6

1.70

100

0.0

0.0

24.0

27.0

19.0

15.6

1.70

100

0.0

0.0

Thermostat Schedule ............................................................................... PB-18


Unoccupied Cooling is ........................................................................ Available
Supply Terminals Data:
Zone
1
2

Terminal Type
CAV mix box
CAV mix box

Hourly Analysis Program v4.50

Min. Airflow
Fan Performance Fan Efficiency
6.00 ACH
6.00 ACH

Design Supply
Temperature
-

Page 1 of 2

PB-18 Input Data


Project Name: BANYU_URIP_PROJECT_REV
Prepared by: wen

11/13/2014
03:43PM

Zone Heating Units:


Zone ............................................................................................................... All
Zone Heating Unit Type ............................................................................. None
Zone Unit Heat Source ...................................................... Electric Resistance
Zone Heating Unit Schedule ................................................. JFMAMJJASOND
4. Sizing Data (Computer-Generated):
System Sizing Data:
Cold Deck Supply Temperature ................................................................... 14.4
Supply Fan Airflow ................................................................................... 5095.2
Ventilation Airflow ....................................................................................... 725.0
Hot Deck Supply Temperature ..................................................................... 24.0

C
L/s
L/s
C

Hydronic Sizing Specifications:


Chilled Water Delta-T ..................................................................................... 5.6 K
Hot Water Delta-T ........................................................................................ 11.1 K
Safety Factors:
Cooling Sensible ............................................................................................. 10 %
Cooling Latent ................................................................................................. 10 %
Heating .............................................................................................................. 0 %
Zone Sizing Data:
Zone Airflow Sizing Method .................................. Sum of space airflow rates
Space Airflow Sizing Method .............................. Individual peak space loads

Zone

Supply Airflow
(L/s)

Zone Htg Unit


(kW)

Reheat Coil
(kW)

4313.6

628.7

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ......................................................................... 102.0
Design OAT .................................................................................................. 35.0
Equipment Sizing ............................................................................. Auto-Sized
Capacity Oversizing Factor ............................................................................... 0
ARI Performance Rating .............................................................................. 2.96
Conventional Cutoff OAT ............................................................................. 12.8
Low Temperature Operation ................................................................ Not used

Hourly Analysis Program v4.50

kW
C
%
EER
C

Page 2 of 2