Daikin CAT 218-3 LR RoofPak Applied RAH RDS Catalog
Daikin CAT 218-3 LR RoofPak Applied RAH RDS Catalog
Daikin CAT 218-3 LR RoofPak Applied RAH RDS Catalog
Catalog 218-3
Table ofContents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
A New Standard in Rooftop Air Handling Systems . . . . . . . 3
Blow-through Heating and/or Cooling Features . . . . . . . . . 6
Draw-through Heating and/or Cooling Features . . . . . . . . 7
Features and Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Unit Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Supply and Return Fan Section . . . . . . . . . . . . . . . . . . . . . . 8
Supply and Return Air Plenum . . . . . . . . . . . . . . . . . . . . . . . 9
Variable Air Volume Control . . . . . . . . . . . . . . . . . . . . . . . . . 9
Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Steam Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Hot Water Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Outside/Return Air Section . . . . . . . . . . . . . . . . . . . . . . . . . 12
Filter Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Static Air Mixers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Sound Attenuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Humidifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Roof Curbs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Heating and Cooling Coils . . . . . . . . . . . . . . . . . . . . . . . . . 15
Cooling Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Intelligent Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Unit Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
MicroTech III Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . 29
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Unit Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Split Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Curb Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Acoustical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . 29
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Variable Air Volume Application . . . . . . . . . . . . . . . . . . . . . 32
Multiple Air Handler Control . . . . . . . . . . . . . . . . . . . . . . . . 32
Fan Operating Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Fan Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Indoor Fan and Motor Heat,
Blow-through vs. Draw-through Cooling . . . . . . . . . . . . . . 33
Altitude Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
System Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Coil Freeze Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Piping and Condensate Drainage . . . . . . . . . . . . . . . . . . . 36
Zone Sensor Placement . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Unit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Winter Shipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Field-Installed Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Face and Bypass Damper Option . . . . . . . . . . . . . . . . . . . 37
Table ofContents
Unit Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Selecting Unit Size and Arrangement . . . . . . . . . . . . . . . . 38
Selecting Cooling Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Selecting Heating Coils and Equipment . . . . . . . . . . . . . . . 39
Selecting Fans and Motors . . . . . . . . . . . . . . . . . . . . . . . . 40
Selecting Unit Size and Arrangement . . . . . . . . . . . . . . . . 41
Selecting Heating Equipment at 50Hz . . . . . . . . . . . . . . . . 41
Selecting Motors at 50 Hz . . . . . . . . . . . . . . . . . . . . . . . . . 42
Selecting RAH O77CL Chilled Water Coils . . . . . . . . . . . . 42
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Cooling Capacity Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
RDS 800C and 802C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
RAH 047C and 077C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Heating Capacity Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Component Pressure Drops . . . . . . . . . . . . . . . . . . . . . . . . 57
RDS 708B, 800C, and 802C . . . . . . . . . . . . . . . . . . . . . . . 57
Fan Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
DWDI Supply Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
SWSI Supply Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Propeller Exhaust Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Return Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Section Options and LocationsRDS 708B . . . . . . . . . . . 79
Application ConsiderationsRDS 800C and 802C . . . . . . 83
Section Options and LocationsRDS 800C . . . . . . . . . . . 84
Section options and locationsRDS 802C . . . . . . . . . . . . 85
Section Options and LocationsRAH 047C . . . . . . . . . . . 88
Unit ConsiderationsRAH 077C . . . . . . . . . . . . . . . . . . . . 90
Section Options and LocationsRAH 077C . . . . . . . . . . . 91
Recommended Clearances . . . . . . . . . . . . . . . . . . . . . . . . . 96
Service Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Gas Piping Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Unit Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Roof Curb WeightsRDS 800C and 802C . . . . . . . . . . . 104
Engineering Guide SpecificationRDS 708 . . . . . . . . . . . 110
Engineering Guide Specification
RDS 800, 802, RAH 047 to 077 . . . . . . . . . . . . . . . . . . . . 115
www.DaikinApplied.com
Introduction
Introduction
Agency Listed
Agency Certification
Certification in accordance with the
forced circulation air cooling and air
heating coils certification program,
which is based onAHRI Standard 410.
MEA
MEA Numbers
Type RAH 047C & RAH 077C
MEA
28-91E, Vol.II
147-96E
Nomenclature
RAH 047 C S A
Model
RDS, RAH
www.DaikinApplied.com
Introduction
Daikin RAH & RDS air handling equipment trace their history
to the late 1970s. With decades of innovation, design flexibility,
durable construction, low capitol and operating cost, make RAH
and RDS the preferred HVAC solution for thousand of most
prominent building projects. RAH & RDS are ideal options for
a job where energy efficiency, reliability, indoor air quality and
acoustic are top priorities. Along with providing high quality
and state-of-the-art technology, RAH & RDS offer the following
valuable features and benefits to satisfy a wide range of diverse
applications.
Daikin RoofPak air handlers are applicable to schools, offices,
shopping centers, manufacturing facilities, etc.
www.DaikinApplied.com
Introduction
Unit Flexibility
The Daikin rooftop air handler is designed to meet the degree
of emphasis has been put on providing increased requirements
of the present and the future. Along with flexibility. Units are
a semi-custom air handler with the providing high quality and
state-of-the-art innovation, a large flexibility to satisfy a wide
range of application specifications.
Table 1: Availability of options per unit size
Factory Installed Options
Factory wired electrical
Starters and outlet
VFDs
Electrical
Unit Size
708
800/802
047077
Available
Limited availability
Disconnect
Lights with receptacle
Available
Available
Limited availability
Limited availability
Available
Available
SWSI AF
Propeller exhaust
Limited availability
Temperature controls
Static pressure controls
Valve packages
Controls
Limited availability
Smoke detectors
Available
Available
Freezestats
Damper actuators
2" angular
Cartridge filters
Filters
Coils
Available
Limited availability
Limited availability
Available
Available
Limited availability
DWDI FC or AF
Available
SWSI AF
Limited availability
Limited availability
Available
Available
Limited availability
[1]
Available
Available
Special Sections
Limited availability
Electric Heat
Face + Bypass
Double wall with R6.5 insulation
Construction
Available
Limited availability
Available
17
11
13
10
14
7
12
16
8
5
15
Standard insulation
Drive selection
www.DaikinApplied.com
11
9
4
13
7
17
10
Industrial furnace
13
www.DaikinApplied.com
12
15
11
12
16
2
1
14
14
16
17
15
Blank sections
Unit Construction
Nominal unit cooling capacities from 15 to 135 tons. Units
up to 52-feet long can be shipped completely assembled.
Weather resistant cabinet design with standing top seams
and cross-broken top panels to provide positive drainage.
Pre-painted exterior surfaces that withstand a minimum
750 hour salt spray test per ASTM B117.
Full size, double-wall hinged access doors on both sides
of each section. All positive pressure door latches have a
safety catch designed to prevent the door from opening
rapidly when the cabinet is under positive pressure.
Single lever latch mechanism and door holders on each
access door.
Heavy-gauge galvanized steel unit base with formed
recess to seat on roof curb gasket and provide positive
weathertight seal.
Heavy duty lifting brackets strategically placed for
balanced cable or chain hook lifting.
Full double-wall construction is available throughout the
unit to protect R-6.5 insulation, enhance performance and
satisfy IAQ requirements.
Perforated liners are available in the plenum areas to
enhance sound performance.
Available auxiliary blank sections provide the flexibility for
factory-installed or field-installed specialty equipment.
Factory-mounted and factory-wired service lights with
switch and outlet are available in each fan section.
Figure 1: Standing top seam
www.DaikinApplied.com
Gas Heat
Extensive selection flexibility from 200 to 2,000 MBh
output can satisfy wide ranging needs.
Two-stage, 3:1 and patented SuperMod 20:1 modulating
control provides the flexibility to solve diverse needs.
All gas burners exceed ASHRAE Standard 90.1 efficiency
requirement of 78% for low fire and 80% for high fire with
efficiencies as high as 88% and 85%, respectively.
The complete furnace assembly is ETL or ETL-Canada
listed.
Special order capability with FM or IRI/FIA gas trains.
All burner assemblies are factory tested and adjusted
prior to shipment.
Heat exchangers are a two-pass, drum-and-tube design
with stainless steel primary and secondary surfaces.
Air temperature rise capability of up to 100F on most
models.
Burners are forced draft type with all controls and valves
housed in the burner vestibule.
Electric Heat
Steam Heat
Steam heating coils are 1-row or 2-row, 5/8-in O.D.
copper tube/aluminum fin jet distributing type with
patented HI-F5 fin design.
Rated in accordance with ARI Standard 430.
Four different steam coil selections offered to size heating
output to application needs.
Factory-installed, two-way modulating control valve,
piping and modulating spring return actuator provide
system control and full flow through the coil in the event
of a power failure.*
Available with factory-mounted freezestat.
Figure 8: Blow-through airflow configuration
Exhaust fans are in parallel with the supply fan and may
only operate during the economizer mode to control
building pressure. They do not handle the return duct at
ESP design conditions.
NOTE: Return fans and exhaust fans have different
performance characteristics and are not
interchangeable. See page 26 for application
recommendations.
800C
802C
047C
077C
Filter Section
Selection flexibility includes large face, area angular filter
racks with 2-inch, 30% panel filters, or high efficiency
cartridge filter assemblies with pre-filters.
Sound Attenuators
Factory-installed downstream of the supply fan to
dampen fan noise in sound sensitive applications.
Can reduce sound levels by as much as half in the lower
octave bands and more than half in the higher octave
bands.
Tedlar coating available for added protection of the
acoustic insulation.
Figure 13: Factory-installed sound attenuators
Humidifiers
Factory installed steam humidifier distribution grids
downstream of the supply air fan.
Roof Curbs
Constructed in accordance with NRCA guidelines with
12-gauge galvanized steel.
Fits inside the unit base around the perimeter of air
handling section.
Duct frames are provided as part of each curb assembly
to allow duct connections to be completed before the unit
is placed.
Gasket seals between the curb duct frame and the unit.
Heating Coils
Hot Water Coils
Water heating coils are offered in two counterflow
arrangements to satisfy a variety of design needs. The onerow, half serpentine circuit allows increased water velocity
for low heat applications. For water coils operating under
normal supply and pressure drop conditions, the two-row, full
serpentine circuit offers exceptional capacity for high heating
demands.
Figure 16: Hot water coil circuitings
Daikin offers a broad variety of coil types, fin spacings, row and
circuiting combinations, which permits using standard coils to
accurately meet load and comfort requirements. Multiple face
areas are offered in each cabinet size to allow more selection
flexibility.
A standard coil can be selected manually or through the Daikin
SelectTools for Contractor Coils selection program to deliver the
specified leaving air dry and wet bulb temperatures for virtually
any condition. SelectTools offers designers easy and accurate coil
selection for optimal performance.
Figure 14: Daikin HI-F5 fin
Steam Coils
Steam coils are available with two-row and two-fin spacing
options for sizing flexibility. Steam coils are tube-in-tube
design with directionally orificed inner tubes for jet distribution.
A specially designed coil casing automatically provides the
proper pitch for positive condensate removal.
Figure 17: Steam coils circuitings
Cooling Coils
Evaporator Coils
Options
Coil Section Options
A factory-mounted valve package is offered for heating coils
located in the heat section of the unit and for all chilled water
coils. The valve package consists of a modulating control
valve, piping, and a spring return type valve actuator. During
a power failure, these valves open to provide full flow through
the coil. Complete control of the valves can be provided by the
available MicroTech III controller.
A field-installed coil vestibule is available and is recommended
when piping must enter the side of the unit. It is required on
many coil arrangements to facilitate piping through the curb.
Face and bypass dampers may also be provided for coil
capacity control and freeze protection. Dampers are available
for all chilled water, hot water, and steam coils positioned in the
heat/cool sections of the unit.
Figure 21: Valve package
Electrical Options
Units are completely wired and tested at the factory, with
control wiring routed in an accessible, protective wire
raceway at the base of the unit.
Wiring complies with NEC requirements and all applicable
UL standards.
For ease of use, wiring and electrical components are
number coded and labeled according to the electrical
diagram.
Units have a 115 V convenience receptacle. (unit
powered or field powered)
Supply and return air fan motors, compressor motors,
and condenser fan motor branch circuits have individual
short circuit protection.
A single point power connection with power block or
disconnect switch is standard.
A unit-mounted disconnect includes a service handle on
the exterior of the control panel door.
Electrical power feeds inside the perimeter roof curb
through factory provided knockouts in the bottom of the
main control panel.
Phase-failure/under-voltage protection is available to
protect three phase motors. Not available on size 708.
www.DaikinApplied.com 17
Ultraviolet Lights
Factory-installed ultraviolet lights are available on the
downstream side of all cooling coils and above the unit drain
pan.
All ultraviolet lights are pre-engineered and factory installed for
ease of use and proper placement for maximum effectiveness.
The ultraviolet lamps irradiate the coil and drain pan surfaces
with light in the 245 nanometer wavelength of the light
spectrum (UV-C). UV-C light has proven effective in killing
most bacteria, molds, and viruses in both laboratory and
practical application. This complete package of equipment and
ultraviolet lights includes Intertek Services Inc. (ETL) safety
agency certification.
Figure 22: Ultraviolet light
Intelligent Equipment
Intelligent Equipment (IE) from Daikin
Applied is a secure, cloud-based controls
solution that enables delivery of equipment
and/or system information to customers via
web or mobile devices.
A power measurement module and
communications gateway installed on Daikin equipment
enables the unit to be directly connected to the Internet via
wireless (cellular, WI-FI) or local area network (LAN), providing
management, monitoring control analysis and decision-making
functionality for Daikin rooftop systems and the facility.
Features
Remote monitoring and control of Daikin rooftop units
Remote servicing capabilities
Integration to the Energy Star Portfolio Manager
Advanced data analytics including equipment
performance, financial performance and building Comfort
Index metrix based on ASHRAE Standard 55-2010
Dynamic user dashboards with photo-realistic graphics
and responsive-design interface optimized for users'
mobile devices, tablets or PCs
Secure, role-based user access
Benefits
Informed decision-making
Features
Benefits
For pennies a day, UVGI can improve IAQ by destroying
mold, fungi, and bacteria on coil and drain pan surfaces.
Clean coil surfaces maintain peak heat transfer for near
new performance and lower energy costs.
Reduced coil and drain pan maintenance requirements
and costs.
Satisfies GSA federal facilities standard requirements for
UVGI lights to be incorporated downstream of all cooling
coils and above all drain pans to control airborne and
surface microbial growth and transfer.
Technician Dashboard
www.DaikinApplied.com 19
Unit Controls
Integrated MicroTech III DDC controls with unitmounted
user interface featuring a 5-line, 22 character English
display for fast equipment diagnostics and adjustments.
Features
Benefits
Allows you to access the user interface for each unit from
one location, inside the building.
Users need to learn one format because the remote user
interface is nearly identical to the unit-mounted version.
No additional field commissioning is required for the
remote user interface.
Figure 25: Remote User Interface
Unit #1 MCB
Unit #2 MCB
Unit #3 MCB
CE+
CE-
CE+
CE-
CE+
CE-
CE+
CE-
BLK
WHT
BLK
WHT
BLK
WHT
BLK
WHT
Daisy-chain up to 8 units to a
single remote interface
Airfoil Fans
hp2 = hp1
density2
density1
)( )
rpm2
rpm1
Expansion Modules
Communication Module
An optional communication module provides the means
to factory or field configure MicroTech III unit controls for
interoperability with an independent BAS. Communication
modules are available to support industry recognized
communication protocols including BACnet MS/TP, BACnet/IP
and LonWorks.
Keypad/Display
All MicroTech III unit controllers include a push/pull navigation
wheel and display. The display is a supertwist nematic type
with highly visible black characters on a yellow background.
The 5-line by 22-character format allows for easy to
understand plain English display messages. All operating
conditions, system alarms, control parameters and schedules
can be monitored from the keypad/display. If the correct
password has been entered, any adjustable parameter or
schedule can be modified from the keypad.
Building
automation
system of
your choice
Internal Schedule
www.DaikinApplied.com 23
Calibrate
Change Algorithm
The PI function is also used to adjust set points instead of
controlling variable speed drives or actuators directly. For
example, in zone control applications, the PI loop automatically
changes the discharge temperature set point (cooling or
heating) as the Control Temperature deviates from the zone set
point. Another PI loop then controls the economizer actuator or
heating valve actuator using the current discharge temperature
set point. Unlike a typical master-submaster reset strategy,
this cascade control continuously adjusts the discharge set
point, even if the Control Temperatures deviation from set point
remains constant. This means that the units cooling or heating
output is set according to the actual load, not just the current
zone temperature. The tightest possible zone temperature
control results because proportional droop (load dependent
offset) is eliminated.
www.DaikinApplied.com 25
Control Temperature
The Control Temperature makes the heat/cool changeover
decision. It determines whether cooling or heating is enabled;
the discharge temperature then determines whether cooling or
heating is actually supplied. At the keypad, the operator can
choose the source of the Control Temperature from among the
following selections.
Space temperature sensor
Return temperature sensor
Outside air temperature sensor (modulating heat only)
Network communication
The operator enters separate cool and heat enable set points
and deadbands that the Control Temperature is compared with
(see Figure 30). When the Control Temperature is greater than
or equal to the cooling set point plus DB/2, cooling is enabled.
When the Control Temperature is less than or equal to the heat
set point minus DB/2, heating is enabled. If desired, these set
points and differentials can be set so that there is a dead band
in which both cooling and heating are disabled. The controllers
software prevents simultaneous cooling and heating.
Figure 30: Control Temperature Logic
Space temperature
Return temperature
Outdoor air temperature
Supply airflow (VAV, cooling set point only)
External 010 VDC or 020 mA signal
Network communication
For all temperature reset methods, the minimum and maximum
cooling and heating set points are keypad programmable along
with the corresponding minimum and maximum space, return
or outdoor air temperature parameters. For the supply airflow
method, the discharge set point will be reset as the supply fan
modulates between 30% adjustable and 100% adjustable. For
the external method, the discharge set point will be reset as
the voltage or current signal varies over its entire range. For
units in a BAS network, the discharge set points are reset via
the communication signal.
Control Temperature
The Control Temperature is the representative zone
temperature. When compared with the zone set points, the
Control Temperature determines whether the unit supplies
heating, cooling, or neither. It also determines the amount of
cooling or heating required to satisfy the load. Its source can
be selected at the keypad from among the following selections:
Zone temperature sensor
Return temperature sensor
www.DaikinApplied.com 27
RAF cfm
Building exhaust
16000 (100%)
14000 (100%)
2000
14000 (88%)
12000 (80%)
2000
12000 (75%)
10000 (71%)
2000
10000 (63%)
8000 (57%)
2000
8000 (50%)
6000 (43%)
2000
Outdoor air
volume (%)
Outdoor air
temp. (F)
Mixed air
temp. (F)
10,000
2,000
20
95
79
8,000
2,000
25
70
73.8
6,000
2,000
33.3
40
63.3
4,000
2,000
50
37.5
Application Considerations
General
Units are intended for use in normal heating, ventilating and
air conditioning applications. Consult your local Daikin Applied
sales representative for applications involving operation at
high ambient temperatures, high altitudes, non-cataloged
voltages and for applications requiring modified or special
control sequences. Consult your local Daikin Applied sales
representative for job specific unit selections that fall outside
of the range of the catalog tables, such as 100% outside air
applications.
For proper operation, units should be rigged in accordance with
instructions stated in IM 485. Fire dampers, if required, must
be installed in the ductwork according to local or state codes.
No space is allowed for these dampers in the unit. Follow
factory check, test and start procedures explicitly to achieve
satisfactory start-up and operation (see IM 485).
Application Considerations
Curb Installation
The roof curb is field assembled and must be installed level
(within 1/16 in per foot side to side). A sub-base has to be
constructed by the contractor in applications involving pitched
roofs. Gaskets are furnished and must be installed between the
unit and curb. For proper installation, follow NRCA guidelines.
Typical curb installation is illustrated in Section Options and
LocationsRDS 708B on page 79. In applications requiring
post and rail installation, an I-beam securely mounted on
multiple posts should support the unit on each side.
Applications in geographic areas that are subjected to seismic
or hurricane conditions must meet code requirements for
fastening the unit to the curb and the curb to the building
structure.
Unit Location
The structural engineer must verify that the roof has adequate
strength and ability to minimize deflection. Take extreme
caution when using a wooden roof structure.
Acoustical Considerations
Locate the unit fresh air intakes away from building flue stacks
or exhaust ventilators to reduce possible reintroduction of
contaminated air to the system. Unit condenser coils should be
located to avoid contact with any heated exhaust air.
Split Units
Units may sometimes have to be split into multiple pieces to
accommodate shipping limitations or jobsite lifting limitations.
Units exceeding 52 feet in length may need to be split for
shipping purposes. Units exceeding the rating of an available
crane or helicopter may also need to be split for rigging
purposes. Unit can be split between the supply fan and heat
section. Contact your local Daikin sales representative for more
details.
Application Considerations
Some basic guidelines for good acoustical performance are:
Always provide proper structural support under all areas
of the unit.
Always locate the units center of gravity close to a main
support to minimize roof deflection. Maintaining a roof
deflection under 1/3 in minimizes vibration-induced noise.
Use a concrete deck or pad when a unit has to be located
over an occupied space where good acoustics are
essential.
Only the supply and return air ducts should penetrate the
acoustical material and decking within the curb perimeter;
seal the openings once the duct is installed.
Dont overlook the return air path. Never leave a clear
line of sight into a return or exhaust fan; always include
some duct work (acoustically lined tee) at the return inlet.
Ductwork
A well-designed duct system is required to allow the rooftop
equipment to provide rated performance and to minimize
system resistance and sound generation. Duct connections to
and from units should allow straight, smooth airflow transitions.
Avoid any abrupt change in duct size and sharp turns in the
fan discharge. Avoid turns opposed to wheel rotation since
they generate air turbulence and result in unwanted sound.
If 90 turns are necessary, use turning vanes. Refer to the
2003 ASHRAE Applications Handbook, Chapter 47 for specific
guidelines relevant to rooftop equipment.
Figure 31: Optimal fan selection line
Return Duct
The return path is the most often overlooked. A section of
return duct is required to avoid a line of sight to the return air
opening and to provide attenuation of return air sound. Install
an insulated tee with a maximum duct velocity of 1000 to 1200
feet per minute. Extend the duct 15 feet to provide adequate
attenuation.
Supply Duct
Insulate supply air ductwork for at least the first 20 feet from
the unit. Consider using round or oval ductwork since it
significantly reduces low frequency breakout noise near the
equipment. If rectangular duct is used, keep the aspect ratio of
the duct as low as possible. The large flat surfaces associated
with high aspect ratios increase low frequency breakout to
the space and can generate noise, such as oil canning. The
maximum recommended supply duct velocity is 1800 to 2000
feet per minute.
Application Considerations
Vibration Isolation
Make duct attachments to the unit with a flexible connection.
www.DaikinApplied.com 31
Application Considerations
Exhaust fans are very different than return fans and cannot
maintain proper building pressure and ventilation control as
return ESP increases.
The EAF is normally off during non-economizer operation.
During these minimum outdoor air conditions, the system
essentially acts like a supply fan only system.
When the exhaust fan cycles off, there is no device
available to maintain a positive pressure for relief, the
mixed air plenum pressure dramatically changes, and
minimum ventilation air control and space pressure are
lost.
An exhaust fans performance weaknesses diminish as return
ESP decreases. Properly selected and controlled propeller
exhaust fans can successfully operate and save energy at
reduced return ESP designs.
At system operating conditions where a single fan can
be used successfully, it generally is more efficient than
operating series fans under the same total load. When
the exhaust fan turns off, the supply fan handles both the
supply and return duct loads more efficiently.
At the relatively high cfm, low static pressure conditions of
exhaust/return application, exhaust fans can be selected
closer to their peak design efficiency than can full return
fans. This allows them to run more efficiently throughout
their operating range.
Therefore, when return duct losses dont dictate using a return
air fan, exhaust fans are an efficient alternative.
Filters
General
Routinely replace filters to minimize filter loading. As filters get
dirty, the filter pressure drop increases, causing a decrease in
airflow. Depending on fan type, forward curved or airfoil, this
airflow change can be significant. The effect of filter loading is
the most critical when using 65% and 95% efficient filters.
When making a fan selection, include a pressure drop
component in the system total static pressure for filters since
they get dirty. Generally, select a value midway between clean
and dirty filter ratings. If a minimum airflow is critical, the fan
selection should be made using the higher, dirty filter pressure
drop value. Following these recommendations should limit
airflow fluctuation as the filters load.
Final Filters
The application of final filters (filters downstream of the fan)
places special requirements on unit selection. When final filters
are employed, cooling coils must be located in the drawthrough position so that the filters will not be in a saturated air
stream. Also, final filters applications for a unit with gas heat
requires the filters to be rated for 500F. Instruct maintenance
personnel to use properly rated replacement filters.
Application Considerations
Fan Isolation
All Daikin RoofPak systems feature internally isolated fans.
All supply and return air fans are statically and dynamically
balanced in the factory and mounted on rubber-in-shear
(RIS) or 2-in deflection spring isolators. Flexible isolation is
provided as standard between the fan outlet and the discharge
bulkhead to prevent hard contact and vibration transmission.
Spring isolated fan assemblies also are available with seismic
restraints.
The choice of 2-in deflection spring isolation or RIS isolation
depends on an analysis of the roof structure and whether or
not an isolation curb is being provided. When using an isolation
curb, consult with the curb manufacturer before selecting
spring isolation in the rooftop unit. Doubling or stacking spring
isolation can generate a resonant vibration.
www.DaikinApplied.com 33
Application Considerations
Figure 36: Blow-through vs. draw-through performance
Altitude Adjustments
Fan curve performance is based on 70F air temperature
and sea level elevation. Selections at any other conditions
require the following adjustment for air densities listed in Table
6. Higher elevations generally require more rpm to provide a
given static pressure but less bhp due to the decrease in air
density.
1. Assume 32,000 cfm is required at 3.11" TSP. The
elevation is 5000 ft and 70F average air temperature is
selected. A 40" DWDI airfoil fan is selected.
2. The density adjustment factor for 5000 ft and 70F is 0.83.
1000
2000
3000
4000
5000
6000
7000
8000
-20
1.20
1.16
1.12
1.08
1.04
1.00
0.97
0.93
0.89
1.15
1.10
1.08
1.02
0.99
0.95
0.92
0.88
0.85
20
1.11
1.06
1.02
.098
0.95
0.92
0.88
0.85
0.82
40
1.06
1.02
0.98
0.94
0.91
0.88
0.84
0.81
0.78
60
1.02
0.98
0.94
0.91
0.88
0.85
0.81
0.79
0.76
Example:
70
1.00
0.96
0.93
0.89
0.86
0.83
0.80
0.77
0.74
80
0.98
0.94
0.91
0.88
0.84
0.81
0.78
0.75
0.72
100
0.94
0.91
0.88
0.84
0.81
0.78
0.75
0.72
0.70
120
0.92
0.88
0.85
0.81
0.78
0.76
0.72
0.70
0.67
140
0.89
0.85
0.82
0.79
0.76
0.73
0.70
0.78
0.65
Altitude (feet)
Furnace Performance
Gas heat performance data is based on standard 70F air
temperature and zero feet altitude (sea level). For altitudes of
2000 feet and higher, the gas burner may be derated 4% for
every 1000 feet of altitude. However, if the design ambient is
cold enough then the effect of colder temperatures and higher
altitudes may be offset.
Example:
A 1000 MBh furnace at an altitude of 3000 feet and 70F
ambient is derated (0.04 3 = 0.12). At 1000 MBh input (1000
0.12 MBh), the actual input is 1000 120 = 880 MBh at 3000
feet. If ambient is 10F then no derate is required.
NOTE: Above 6000 feet, consult factory
Application Considerations
www.DaikinApplied.com 35
Application Considerations
An optional non-averaging freezestat equipment protection control
can be provided, located downstream of the heating coil. If a
potential freezing condition is sensed, a sequence is initiated by
the unit control system, closing outdoor air dampers, opening the
heating valve and de-energizing the fan. The freezestat setting
should be some increment higher than freezing to provide an
added margin of protection. The use of a freezestat control may
cause nuisance trips. It cannot prevent freeze-up in the event of
power failure or equipment malfunction.
Freeze protection control strategies must be designed to keep
unit cabinet temperatures from exceeding 150F during a unit
shutdown. Temperatures in excess of 150F may exceed the
design limits of motors, electrical components, gaskets, etc.
potentially leading to premature failure of components.
Unit Wiring
All units require three phase, 60 Hz, 208, 230, 460 or 575 volt
power or three phase, 50 Hz, 400 volt power. Units do not
operate satisfactorily at 10% of rated voltage, at the power
connections to the units. All units include branch circuit, short
circuit protection and are available with one or multiple power
blocks or non-fused disconnect switches. Each unit is provided
with a 115-volt convenience outlet circuit. Per the NEC, this
circuit must be fed independent of the main unit power supply.
All wiring must be installed in accordance with the National
Electric Code (NEC) and local codes.
Winter Shipment
Flat bed shipment in winter can expose units to harsh road
chemicals. Since equipment size and configuration precludes
covering during transit, wash units free of these chemicals as
soon as possible to help prevent corrosion.
Application Considerations
Field-Installed Actuators
Install an actuator to meet the design torque requirement.
For vane actuators, this requirement is based on the effective
wheel diameter and design rpm of the fan. Use the following
equation and table to size actuators:
Torque (ft-lb) = (D) (design rpm / 1000)
Table 6: Effective wheel diameters
Fan description
15" x 15", DWDI
20", DWDI
24", DWDI
27", DWDI
30", SWSI
30", DWDI
33", DWDI
36", DWDI
40", SWSI
40", DWDI
44", SWSI
49", SWSI
D value
7.5
3.8
8.3
13.3
9.8
20.3
29.8
42.2
31.0
64.3
45.4
70.0
Unit size
708B
800C
802C
047C
077C
10
22
22
34
48
19
19
33
45
19
27
10
10
19
27
33
45
20
34
10
22*
22
48
67
19
22
22
33
41
* The RDS 800 with 15" ft FC return fan has an 19 sq ft outside air louver opening.
www.DaikinApplied.com 37
Unit Selection
Example 1
A constant volume system with chilled water, gas heat,
economizer with return fan, and 65% efficient filtration is
required to meet the following criteria:
Supply air capacity = 26,000 cfm
Return air capacity = 20,800 cfm
Maximum face velocity = 600 fpm
Supply duct = 2.00-in wg
Return duct = 0.50-in wg
Altitude = Sea level
Summer design:
Ambient air temperature = 95F
Mixed air temperature = 80F/67F
Entering water temperature = 45F
Leaving water temperature = 55F
Total cooling load = 640,000 Btu/hr
Sensible cooling load = 510,000 Btu/hr
Winter design:
Entering air temperature = 60F
Total heating load = 700,000 Btu/hr
Air temperature rise = 20F
Electrical design: 460 V/60 Hz/3 phase
Unit Selection
Unit Selection
Gas Heat
When selecting a gas furnace, the system heating load,
minimum airflow and maximum temperature rise constraints
are needed. See Figure 43 on page 51 for furnace model
size selection. Enter the graph at 206,000 cfm and move
up vertically to the intersection of 700 MBh output. In this
example, the intersection of Minimum cfm and MBh Output
occurs between model lines. Therefore, the larger model size,
Model 790, should be selected for adequate heating. For all
heat exchangers, there exists a maximum temperature rise.
This limitation is determined by the heat exchanger surface
area to airflow ratio. See Table 21 on page 52 for verification
of the temperature rise capability of the furnace selected.
Also, use this table when specifying baffle position based on
minimum airflow design. Refer to Altitude Adjustments on page
34.
NOTE: In VAV applications, consider range of airflow
modulation when selecting furnace model and baffle
position. The maximum temperature rise cannot be
exceeded at either maximum or minimum airflows.
www.DaikinApplied.com 39
Steam Heat
Steam design:
Unit Selection
Enter Table 8, at 10 psig and 852 lb/hr. The correct valve size
is 1-1/2 in For other operating conditions, use the Selection
program for accurate selection or contact your Daikin Applied
sales representative.
Steam traps are field furnished and mounted. Refer to
Application Considerations on page 29 of this catalog or
Daikin Steam Coil Catalog 413 for piping recommendations.
Table 8: Steam valve selection chart
Valve size
(in.)
10 psig
15 psig
25 psig
196260
301380
391480
571650
261380
381560
481700
651940
381600
561870
7011090
9401470
601950
8711390
10911750
14712350
9511330
13911940
17512450
23513290
13312020
19412950
24513716
Temperature (F)
Latent heat
218.5
966.1
227.1
960.6
10
239.4
952.6
15
249.7
945.7
25
266.8
934.0
Unit Selection
For the constant volume, blow-through unit in Example 1, a
DWDI, forward curve or airfoil type fan can be selected. See
Application Considerations on page 29 for fan configuration
considerations. A fan type selection comparison for Example 1
is conducted as follows:
The optimal fan size for an airfoil fan without vanes is 30"
(from Figure 59 on page 68). Corresponding fan motor
characteristics are: Fan rpm = 1450 Brake horsepower = 27
Make the final selection by comparing energy savings to first
cost as follows:
Payback = savings / cost
where:
Savings = (bhp2 bhp1) (0.75 kW/hp / motor eff.) $/kwh
hr/yr, and cost = (fan and motor cost)1 (fan and motor cost)2
Example 2
A constant air volume system with electric heat at 50 Hz.
Applicable design constraints in Example 1 are used in
Example 2 with the following parameters.
Winter design:
Total heating load . . . . . . . . . . . . . . . . . . . . . . . . 480,000 Btu/h
Electrical Design: . . . . . . . . . . . . . . . . . . . 380 V/50 Hz/3 phase
www.DaikinApplied.com 41
Unit Selection
Example 3
FLA = (kW l000) / (1.732 V)
= (149.7 1000) / (1.732 380)
= 227.5 amps
Selecting Motors at 50 Hz
Ind. airflow = airflow (in FH / total FH)
= 40,000 (30/126) = 9,523 cfm
= 40,000 (33/126) = 10,476 cfm
1. Add capacities together and multiply by two for
staggered configuration.
380
400
415
O.D.P.
0.85
0.80
0.75
T.E.F.C.
0.80
0.75
0.70
For the RAH O77CL without F&BP and the RAH O77CS with
F&BP, Table 16 on page 49 provides additional header
pressure drops. These values are added to the water pressure
drop provided by the coil selection program to account for
the presence of a continuous header. In the given example,
an additional 6.5 feet of water is added resulting in a water
pressure drop of 19 feet of water through the coil.
Example:
RAH O77CL chilled water valve and piping selection
Coil type = 5 WL
Water flow rate = 160 gpm
Determine valve size selection for the given chilled water coil
by entering Figure 41 on page 49 at 160 gpm and moving
vertically up past the minimum pressure drop line to the
nearest curve. Select a 2" valve with a pressure drop of 19.5
feet of water under design conditions. For proper temperature
control, maintain adequate pressure drop through the valve.
To determine the pressure drop through the valve piping, first
reference Table 15 on page 47 for the assigned index number
of the given valve. Then enter Figure 41 on page 49 at the
designated index number and water flow rate. Following vertically
down from the gpm curve, locate the corresponding pressure
drop. For this example, the chilled water valve piping pressure
drop is 8.0 feet of water. Therefore, the total valve and piping
pressure drop for the given chilled water coil is 27.5 feet of water.
Physical Data
Physical Data
Unit size
708B
800C
802C
Length (in)
114279
62538
84566
Height (in)
51.0
55.5
55.5
Width (in)
67.5
94.0
94.0
Cabinet Dimensions
Supply Fans
Type: Forward curved
Qtydiameter (in)
115 6
215 6
124
Qtydiameter (in)
115 9
215 15
Qtydiameter (in)
115 15
2,0008,000
4,00016,000
8,00020,000
Motor hp range
17.5
120
125
124
8,00020,000
Motor hp range
125
Type: Airfoil
Qtydiameter (in)
116
120
2,0008,000
4,00016,000
Motor hp range
110
125
Return Fans
Type: Forward curved
Qtydiameter (in)
115 151
215 15
2,0007,200
3,00014,400
Motor hp range
15
110
Qtydiameter (in)
116
130
130
Qtydiameter (in)
140
2,0007,200
3,00014,400
6,00018,000
Motor hp range
15
110
110
Type: Airfoil
13.91
50.0
50.0
Qtysize (in)
420 25 2
1016 20 2
1016 25 2
1016 20 2
1016 25 2
20.82
Qtysize (in)
620 25 2
6.01
24.0
24.0
Qtysize (in)
124 24 12
112 24 12
424 24 12
412 24 12
424 24 12
412 24 12
12.02
Qtysize (in)
224 24 12
212 24 12
8.01
24.0
24.0
Qtysize (in)
224 24 12
424 24 12
412 24 12
424 24 12
412 24 12
14.02
Qtysize (in)
224 24 12
312 24 12
250, 312, 400, 500, 625, 800, 812, 988, 1000, 1250
200, 250, 320, 400, 500, 640, 650, 790, 800, 1000
20, 40, 60, 80, 100, 120, 140, 160, 180, 200, 220, 240
Electric3
1. Filter area for RDS 708B units with a 15" 6" supply fan.
2. Filter area for RDS 708B units with a 15" 9", 15" 15" or 16" supply fan.
3. Gas, oil and electric heat selection is limited by the minimum airflow requirements.
www.DaikinApplied.com 43
Physical Data
Table 12: RDS 708B, 800C, and 802Ccontractor coil1 data
Unit size
Data
708BS
708BL
800CY
802CY
Without
With
Without
With
Without
With
Without
With
12-39
12-30
12-39
12-30
12-36
12-30
12-36
12-30
36
36
48
48
79
79
79
79
25.0
20.0
25.0
20.0
19.5
19.5
19.5
19.5
9.8
7.5
13.0
10.0
19.8
16.5
19.8
16.5
1.9
2.5
3.3
3.3
4,750
6,250
8,225
8,225
Typerows
5/8
5/8
5MH2
5MH2
5WH3, 4, 5, 6, 8, 10
5WH3, 4, 5, 6, 8, 10
5WL3, 4, 5, 6, 8, 10
5WL3, 4, 5, 6, 8, 10
5MS2
5MS2
5WS4, 6, 8, 10
5WS4, 6, 8, 10
5WM5, 6, 8, 10
5WM5, 6, 8, 10
5WD8
5WD8
Evaporator coils
Diameter (in)
Typerows
5/8
5/8
SEN2, 3, 4, 5, 6, 8
SEN2, 3, 4, 5, 6, 8
SER6
SER6
SEF2, 3, 4, 5, 6, 8
SEF2, 3, 4, 5, 6, 8
SEJ3, 4,6, 8
SEJ3, 4,6, 8
SEK4, 8
SEK4, 8
Typerows
5/8
5/8
SWB1, 2
5WB1
5WQ1
5WQ1
5WH1, 2
5WH1
SWS2
5MH24
5MS24
Steam coils
Diameter (in)
Typerows
5/8
5/8
5JA1, 2
5JA1, 2
5GA1, 2
5GA1, 2
8JA1
8JA1
8GA1
8GA1
Physical Data
Table 13: RDS 708B, 800C, and 802Cunit coil data
Data
Unit size
800CL
802CL
5WH3, 4, 5, 6C
5WH3, 4, 5, 6C
5WL3, 4, 5, 6C
5WL3, 4, 5, 6C
5WS4, 6C
5WS4, 6C
8, 10, 12
8, 10, 12
FH FL (in.)
48 78
48 78
26.0
26.0
16,900
16,900
1, 1-1/4, 1-1/2, 2
1, 1-1/4, 1-1/2, 2
Typerowsfin geometry
5EN3, 4, 5C
5EJ3, 4, 5C
8, 10, 12
8, 10, 12
FH FL (in.)
48 82
48 82
27.3
27.3
17,750
17,750
Evaporator coils
Compressor circuits/split
1/100
2/50-50
5WH1H
5WH1H
5WS2C
5WS2C
FH FL (in.)heat only
39 75
3975
20.3
20.3
FH FL (in.)heat/cool
39 78
39 78
21.1
21.1
1, 1-1/4, 1-1/2, 2
1, 1-1/4, 1-1/2, 2
Typerowsfin geometry
5JA1H
5JA1H
6, 12
6, 12
FH FL (in.)heat only
39 75
39 75
Steam coils
20.3
20.3
FH FL (in.)heat/cool
39 78
39 78
21.1
21.1
1, 1-1/4, 1-1/2, 2
1, 1-1/4, 1-1/2, 2
1. Unit coils are HI-F5 fin design and have opposite drive end connections except to the heat only section.
2. Valve package available in cooling only and heating only sections.
3. For coils with factory valve package, supply and return connections are the size of the valve with female threading.
www.DaikinApplied.com 45
Physical Data
Table 14: RAH 047C and 077Ccomponent data
Unit size
Data
Length (in.)
Cabinet
047CS
047CL
047CY
077CS
077CL
077CY
96552
96576
96504
96624
96696
96-600
Height (in.)
73.0
Width (in.)
99.0
97.0
99.0
Throwaway
Throwaway filters
(standard)
Area (ft2)
73.9
116.1
Qtysize (in.)
716 20 2
2116 25 2
1116 20 2
3316 25 2
Area (ft2)
73.9
116.1
Qtysize (in.)
716 20 2
2116 25 2
1116 20 2
3316 25 2
Area (ft2)
40.0
56.0
Qtysize (in.)
412 24 2
824 24 2
412 24 2
1224 24 2
Area (ft2)
48.0
64.0
Qtysize (in.)
812 24 2
824 24 2
1624 24 2
Area (ft2)
80.0
Qtysize (in.)
812 24 2
1624 24 2
Area (ft2)
40.0
56.0
Qtysize (in.)
412 24 12
824 24 12
412 24 12
1224 24 12
Area (ft2)
48.0
64.0
Qtysize (in.)
812 24 12
824 24 12
1624 24 12
Area (ft2)
80.0
Qtysize (in.)
812 24 12
1624 24 12
Diameter (inch)
27, 30, 33
33, 36, 40
30,000
50,000
Motor hp range
350
30% pleated
Throwaway filters
(optional)
575
Airfoil
Diameter (inch)
40, 44
44, 49
30,000
50,000
Motor hp range
350
575
Airfoil
Return fans
Diameter (inch)
40
44
27,000
45,000
Motor hp range
230
560
Propeller
Diameter (inch)
Exhaust fans
Quantity
36 Inch
12 Per Unit
Motor hp
Electric
Gas furnace
23 Per Unit
5 HP Each
Airflow range(cfm)
11,00030,000
22,00050,00
Input (MBh)
250 312 400 500 625 800 812 988 100 1250*
200 250 320 400 500 640 650 790 800 1000
500 640 650 650 790 800 1000 1100 1400 1500 2000*
* Furnace size availability is limited by the minimum airflow per Table 23 on page 46.
Physical Data
Table 15: RAH 047C and 077Ccoil data
Unit size
Data
047CS
wo/ F&BP
047CL
w/ F&BP2
wo/ F&BP
077CS
w/ F&BP2
Rows
Evaporator
coils
wo/ F&BP
077CL
w/ F&BP2
wo/ F&BP
w/ F&BP2
3, 4, 5, 6
8, 10, 12,
Fin material
Aluminum, copper
FH FW (in.)
66 87.5
(2) 39 87.5
90 87.5
(2) 63 87.5
Face area
(sq ft)
40.1
47.4
54.7
76.6
Max. cfm
26,000
30,800
35, 500
49,800
2, 2, 3
2, 2, 3
2, 2, 3
2, 2, 3
2, 2, 3
63 83
(2) 63 83
(2) 54 83
5WH3, 4, 5, 6, 8
1, 2, 2
1, 2, 2
1, 1, 2, 3
5WL3, 4, 5, 6, 8
Typerows
Valve package
(in.)
1, 2, 2
1, 2, 2, 3
1, 2, 2, 3
5WS4, 6, 8
2, 2, 3
1, 2, 2, 3
1, 2, 2, 3
5WM4, 5, 6, 8
2, 2, 3
Chilled water
coils
1, 2, 2, 3
2, 2, 3
5WD4, 8
2, 2, 3
2, 2, 3
2, 2, 3
8, 10, 12
Aluminum, copper
66 83
48 83
(2) 39 83
(2) 39 83
90 83
Face area
(sq ft)
38.0
27.7
45.0
45.01
51.9
36.3
72.6
62.3
24,700
18,000
29,200
29,200
33,700
23,600
47,200
40,500
Bypass Area
(sq ft)
9.2
10.4
14.4
18.4
Max. bypass
cfm
23,000
25,900
36,000
46,100
1, 1, 2,
2, 3
1, 1, 2,
2, 3
1, 2, 2, 3
1, 2, 2, 3
1, 1, 2,
2, 3
1, 2, 2, 3
5WH1
Typerows
Valve package
(in.)
5WS2
1, 1, 2,
2, 3
Aluminum, copper
FH FW (in.)
57 75
39 75
57 75
81 75
54 75
81 75
Face area
(sq ft)
29.7
20.3
29.7
42.2
28.1
42.2
Bypass area
(sq ft)
9.2
14.4
Max. bypass
cfm
23,000
36,000
1, 1, 2,
2, 3
1, 1, 2,
2, 3
1, 2, 2, 3
1, 2, 2, 3
Rows
Valve package
(in.)
Steam coils
1, 2, 2, 3
9
1, 2
6, 12
Fin material
Aluminum, copper
FH FW (in.)
57 75
39 75
57 75
81 75
54 75
81 75
Face area
(sq ft)
29.7
20.3
29.7
42.2
28.1
42.2
Bypass area
(sq ft)
9.2
14.4
Max. bypass
cfm
23,000
36,000
www.DaikinApplied.com 47
Figure 40: Unit hot water valve and piping pressure drop
Header
height (in.)
077CS
with
F&BP
63
077CL
without
F&BP
(2) 63
Coil type
5WH
5WL
5WS
5WM
5WD
GPM
PD
GPM
PD
GPM
PD
GPM
PD
GPM
PD
21
0.10
31
0.22
41
0.40
62
0.70
83
1.00
41
0.39
62
0.89
83
1.61
124
283
165
4.05
83
1.57
124
3.62
165
6.50
248
11.43
331
16.36
21
0.10
31
0.22
41
0.40
62
0.70
83
1.00
41
0.39
62
0.89
83
1.61
124
2.83
165
4.05
83
1.57
124
3.62
165
6.50
248
11.43
331
16.36
www.DaikinApplied.com 49
5WH
5WL
5WS
5WM
5WD
Valve size
(in.)
Unit size
047CS
047CL
077CS
077CL
w/o F&BP
w/ F&BP
w/o F&BP
w/ F&BP
w/o F&BP
w/ F&BP
w/o F&BP
1.25
3820
w/ F&BP
1.50
3510
2230
8810
7250
3760
1820
6070
2.00
2380
1430
4130
3320
2020
760
1910
2280
2.50
2140
3070
2610
1680
540
1350
1820
3.00
1580
1190
1640
1.25
4510
1.50
3750
1860
8460
3490
5740
2.00
2620
780
3150
2420
1750
830
1810
2220
2.50
2380
550
1980
1640
1260
500
1250
1490
3.00
1670
1370
1310
420
1090
1300
1.50
2420
8460
3410
2.00
1540
710
3150
2420
1670
830
1810
2130
2.50
1190
370
1980
1640
1330
500
1250
1400
3.00
1100
290
1670
1370
1230
420
1090
1210
1.50
2420
8460
3410
2.00
1540
710
3150
2420
1670
830
1810
2130
2.50
1190
370
1980
1640
1330
500
1250
1400
3.00
1100
290
1670
1370
1230
420
1090
1210
1.50
2420
3410
2.00
1460
710
3100
2560
1670
830
1810
2130
2.50
1110
370
1950
1560
1330
500
1250
1400
3.00
1030
290
1620
1290
1230
420
1090
1210
Figure 42: Chilled water valve piping pressure drop Index number (obtained from Table 17)
Gas Heat
RDS 800C and 802C, RAH 047C and 077C
Figure 43: Gas heat capacity
Regulator
200
250
320
400
500
650
Minimum pressure
790
Maximum pressure
High pressure
800
1000
1100
1400
1500
2000
2.010.0
2.010.0
2.010.0
2.010.0
2.010.0
2.010.0
2.010.0
2.010.0
2.010.0
2.010.0
2.010.0
2.010.0
250
320
400
500
650
790
800
1000
1100
1400
1500
2000
250
312
400
500
625
812
1000
1000
1250
1375
1750
1875
2500
Standard burner
6.00
6.00
7.00
7.00
7.00
7.00
7.50
7.50
9.00
7.00
8.00
8.00
9.00
20:1 burner
4.50
5.50
6.00
5.00
5.50
7.00
6.50
6.50
6.50
5.00
5.00
5.00
6.00
0.75
0.75
0.75
1.00
1.00
1.25
1.25
1.25
1.25
1.50
1.50
1.50
2.00
23 psi
0.75
0.75
0.75
1.00
1.00
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.50
510 psi
0.75
0.75
0.75
1.00
1.00
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
www.DaikinApplied.com 51
Nominal
airflow
(cfm)
200
250
320
400
500
790
015C
7000
26.3
32.9
42.1
52.7
65.8
85.6
020C
8000
23.0
28.8
36.9
46.1
57.6
74.9
025C
10000
18.4
23.0
29.5
36.9
46.1
030C
12000
15.4
19.2
24.6
30.7
036C
14000
13.2
16.5
21.1
040C
16000
11.5
14.4
045C
16000
11.5
050C
20000
060C
800
1000
1100
1400
1500
2000
92.2
59.9
73.7
38.4
49.9
60.7
61.4
26.3
32.9
42.8
52.0
52.7
18.4
23.0
28.8
37.4
45.5
46.1
57.6
14.4
18.4
23.0
28.8
37.4
45.5
46.1
57.6
9.2
11.5
14.7
18.4
23.0
30.0
36.4
36.9
46.1
24000
7.7
9.6
12.3
15.4
19.2
25.0
30.3
30.7
38.4
070C
28000
6.6
8.2
10.5
13.2
16.5
21.4
26.0
26.3
32.9
075C
30000
6.1
7.7
9.8
12.3
15.4
20.0
24.3
24.6
30.7
080C
32000
14.4
18.7
22.8
23.0
28.8
31.7
40.3
43.2
57.6
090C
36000
12.8
16.6
20.2
20.5
25.6
28.2
35.8
38.4
51.2
105C
40000
11.5
15.0
18.2
18.4
23.0
25.3
32.3
34.6
46.1
115C
46000
10.0
13.0
15.8
16.0
20.0
22.0
28.1
30.1
40.1
125C
48000
9.6
12.5
15.2
15.4
19.2
21.1
26.9
28.8
38.4
135C
50000
9.2
12.0
14.6
14.7
18.4
20.3
25.8
27.6
36.9
Baffle
position
A
B
200
250
320
400
500
650
790
800
80
61
100
61
100
100
61
100
1000
61
2300
3800
2950
6000
4600
5970
12000
7340
15000
62
42
78
35
63
73
52
76
50
3000
5500
3800
10500
7400
82000
14000
9800
18500
Note: When selecting baffle position, consider the minimum reduced airflow on VAV units.
250
320
400
500
650
790
800
1000
1100
1400
1500
46
57
73
61
100
100
61
100
61
100
61
100
2000
61
4,000
4,000
4,000
6,000
4,600
5,970
12,000
7,340
15,000
10,100
21,000
13,770
30,000
13
16
21
26
29
33
41
41
42
46
46
51
14,000
14,000
14,000
14,000
16,000
18,000
18,000
18,000
22,000
22,000
28,000
36,000
10
13
17
19
27
33
33
33
38
49
44
22,000
22,000
22,000
22,000
24,000
22,000
22,000
22,000
28,000
34,000
28,000
42,000
23
24
28
25
34
32
26,000
30,000
26,000
36,000
30,000
40,000
Note: When selecting baffle position, consider the minimum reduced airflow on variable air volume units.
Electric Heat
RDS 800C and 802C
Table 23: 208 V electric heat air temperature rise (F)*
Electric heater model number
20
Airflow (cfm)
40
60
80
100
120
102
154
204
255
306
6,000
7.8
15.6
23.5
31.2
39.0
46.8
7,000
6.7
13.4
20.2
26.7
33.4
40.1
8,000
5.9
11.7
17.6
23.4
29.2
35.1
9,000
5.2
10.4
15.7
20.8
26.0
31.2
10,000
4.7
9.4
14.1
18.7
23.4
28.1
11,000
4.3
8.5
12.8
17.0
21.3
25.5
12,000
3.9
7.8
11.8
15.6
19.5
23.4
13,000
3.6
7.2
10.9
14.4
18.0
21.6
14,000
3.4
6.7
10.1
13.4
16.7
20.1
15,000
3.1
6.2
9.4
12.5
15.6
18.7
16,000
2.9
5.8
8.8
11.7
14.6
17.5
Table 24: 230 V, 460 V, 575 V electric heat air temperature rise (F)*
Electric heater model number
Airflow
(cfm)
20
40
60
80
100
120
63
125
188
249
312
374
6,000
9.6
19.1
28.7
38.1
47.7
57.2
7,000
8.2
16.3
24.6
32.7
40.9
8,000
7.2
14.3
21.6
28.6
9,000
6.4
12.7
19.2
10,000
5.7
11.4
11,000
5.2
12,000
140
160
180
200**
220**
240**
439
499
564
624
689
748
49.0
57.5
35.8
42.9
50.3
57.2
25.4
31.8
38.1
44.7
50.9
57.5
17.2
22.9
28.6
34.3
40.2
45.8
51.7
57.2
10.4
15.7
20.8
26.0
31.2
36.6
41.6
47.0
52.0
57.5
4.8
9.5
14.4
19.1
23.8
28.6
33.5
38.1
43.1
47.7
52.7
57.2
13,000
4.4
8.8
13.3
17.6
22.0
26.4
31.0
35.2
39.8
44.0
48.7
52.8
14,000
4.1
8.2
12.3
16.3
20.4
24.5
28.7
32.7
37.0
40.9
45.2
49.0
15,000
3.8
7.6
11.5
15.3
19.1
22.9
26.8
30.5
34.5
38.1
42.2
45.8
16,000
3.6
7.2
10.8
14.3
17.9
21.5
25.2
28.6
32.3
35.8
39.5
42.9
* Maximum temperature rise allowed is 60F with temperature not exceeding 140F
** Electric heater temperature available at 460 or 575 volts only.
www.DaikinApplied.com 53
40
60
80
100
120
160
153.9
204.1
255.0
306.1
408.2
14,000
6.7
10.1
13.4
16.7
20.0
26.1
15,000
6.3
9.4
12.5
15.7
18.8
25.0
16,000
5.8
8.8
11.7
14.6
17.6
23.4
17,000
5.5
8.3
11.0
13.7
16.6
22,1
18,000
5.2
7.8
10.4
13.0
15.6
20.8
19,000
4.9
7.4
9.9
12.3
14.8
19.8
20,000
4.7
7.0
9.4
11.7
14.0
18.7
21,000
4.5
6.7
8.9
11.1
13.4
17.8
22,000
4.3
6.4
8.5
10.6
12.8
17.0
23,000
4.1
6.1
8.1
10.1
12.2
16.3
24,000
3.9
5.9
7.8
9.7
11.7
15.6
25,000
3.7
5.6
7.5
9.3
11.2
15.0
26,000
3.6
5.4
7.2
9.0
10.8
14,4
27.000
3.4
5.2
6.9
8.7
10.4
13.9
28,000
3.3
5.0
6.7
8.4
10.0
13.5
29,000
3.2
4.8
6.5
8.1
9.7
13.0
30,000
3.1
4.7
6.3
7.8
9.4
12.5
Table 26: RAH 077, 208 V electric heat air temperature rise (F)
Electric heater model number
Airflow (cfm)*
80
100
120
255.0
306.1
22,000
8.5
10.6
12.8
24,000
7.8
9.7
11.7
26,000
7.2
9.0
10.8
28,000
6.7
8.4
10.0
30,000
6.3
7.8
9.4
32,000
5.8
7.3
8.8
34,000
5.5
6.9
8.3
36,000
5.2
6.5
7.8
38,000
4.9
6.1
7.4
40,000
4.7
5.8
7.0
42,000
4.5
5.5
6.7
44,000
4.3
5.3
6.4
46,000
4.1
5.1
6.1
48,000
3.9
4.9
5.8
50,000
3.7
4.7
5.6
*22,000 cfm is the minimum airflow required for unit size 077C with electric heat.
*14,000 cfm is the minimum airflow required for unit size 047C with electric heat
40
60
80
100
120
160
200
240
188.1
249.5
311.9
374.3
499.0
623.8
748.5
14,000
8.2
12.3
16.3
20.4
24.5
32.7
40.8
49.0
15,000
7.7
11.5
15.3
19.1
23.0
30.6
38.2
46.0
16,000
7.2
10.8
14.3
17.9
21.5
28.6
35.8
42.9
17,000
6.8
10.2
13.6
16.9
20.4
27.5
33.7
40.8
18,000
6.4
9.6
12.7
15.9
19.2
25.4
31.8
38.4
19,000
6.0
9.1
12.0
15.1
18.1
24.0
30.2
36.2
20,000
5.7
8.6
11.4
14.3
17.2
22.8
28.6
34.3
21,000
5.4
8.2
10.7
13.6
16.4
21.4
27.2
32.8
22,000
5.2
7.8
10.4
13.0
15.6
20.8
26.0
31.2
23,000
5.0
7.5
10.0
12.4
15.0
19.9
24.8
30.0
24,000
4.8
7.2
9.5
11.9
14.4
19.0
23.8
28.8
25,000
4.6
6.9
9.2
11.4
13.8
18.4
22.9
27.6
26,000
4.4
6.6
8.8
11.0
13.2
17.6
22.0
26.4
27.000
4.2
6.4
8.5
10.6
12.8
11.0
21.2
25.6
28,000
4.0
6.2
8.2
10.2
12.4
16.4
20.4
24.8
29,000
3.9
6.0
7.8
9.9
12.0
15.8
19.7
24.0
30,000
3.8
5.8
7.6
9.5
11.6
15.2
19.0
23.2
240
280
320
* 14,000 cfm is the minimum airflow required for unit size 047C with electric heat.
Table 28: RAH O77C, 230,460,575 Velectric heat air temperature rise (F)
Electric heater model number
Airflow (cfm)*
80
100
120
160
200
311.9
374.3
499.0
623.8
748.5
873.3
998.0
22,000
10.4
13.0
15.6
20.8
26.0
31.2
36.4
41.6
24,000
9.5
11.9
14.4
19.0
23.8
28.8
33.4
38.1
26,000
8.8
11.0
13.2
17.6
22.0
26.4
30.8
35.2
28,000
8.2
10.2
12.4
16.4
20.4
24.8
28.6
32.7
30,000
7.6
9.5
11.6
15.2
19.0
23.2
26.7
30.5
32,000
7.2
8.9
10.7
14.3
17.9
21.5
25.0
28.6
34,000
6.7
8.4
10.1
13.5
16.8
20.2
23.6
26.9
36,000
6.3
7.9
9.5
12.6
15.9
19.1
22.2
25.2
38,000
6.0
7.5
9.0
12.0
15.0
18.0
21.1
24.0
40,000
5.7
7.1
8.6
11.4
14.2
17.2
20.0
22.8
42,000
5.4
6.8
8.2
10.9
13.6
16.3
19.1
21.8
44,000
5.2
6.5
7.8
10.4
13.0
15.6
18.2
20.8
46,000
5.0
6.2
7.5
10.0
12.4
15.0
17.4
20.0
48,000
4.8
5.9
7.2
9.6
11.8
14.4
16.7
19.2
50,000
4.6
5.7
6.9
9.2
11.4
13.7
16.0
18.3
*22,000 cfm is the minimum airflow required for unit size 077C with electric heat.
www.DaikinApplied.com 55
Outdoor/
return air
Filters
15" 6"
supply fan
Filters
15" 9" /
15" 15"
supply fans
Face and
bypass
dampers
Discharge or
return
dampers
Discharge
plenum
Airflow (cfm)
2,000
3,000
4,000
5,000
6,000
7,000
8,000
0.01
0.01
0.02
0.02
0.03
0.05
0.06
0.01
0.03
0.06
0.09
0.13
0.17
0.22
0100% economizer
0.01
0.01
0.02
0.04
0.05
0.07
0.10
0.01
0.02
0.03
0.05
0.07
0.09
0.12
Throwaway
0.05
0.07
0.10
30% Pleated
0.05
0.08
0.11
Cleanable
0.02
0.03
0.05
0.12
0.21
0.34
0.09
0.14
0.21
65% cartridge
0.18
0.39
0.66
95% cartridge
0.21
0.40
0.64
Throwaway
0.06
0.08
0.10
0.12
0.15
30% pleated
0.07
0.09
0.11
0.14
0.16
Cleanable
0.03
0.04
0.05
0.06
0.08
0.12
0.16
0.21
0.27
0.34
0.10
0.13
0.17
0.21
0.26
65% cartridge
0.19
0.27
0.39
0.52
0.66
95% cartridge
0.26
0.37
0.50
0.64
0.79
0.01
0.02
0.03
0.01
0.02
0.02
0.07
0.17
0.29
0.16
0.26
0.37
0.13
0.29
0.51
0.07
0.15
0.26
0.41
0.58
0.03
0.07
0.12
0.19
0.28
0.38
0.49
0.14
0.34
0.59
0.11
0.24
0.43
0.67
0.97
0.07
0.15
0.26
0.41
0.59
0.80
1.05
0.03
0.06
0.11
0.18
0.25
0.34
0.45
Note: Pressure drop through coils can be found in the SelectTools for Contractor Coils selection program.
www.DaikinApplied.com 57
Component
4,000
6,000
8,000
10,000
12,000
14,000
16,000
18,000
0.02
0.03
0.06
0.09
0.13
0.18
0.23
0.28
0.01
0.01
0.02
0.03
0.05
0.06
0.08
0.10
0100% economizer
0.01
0.03
0.05
0.08
0.12
0.17
0.23
0.29
Throwaway
0.02
0.03
0.05
0.07
0.09
0.12
0.14
0.17
30% pleated
0.02
0.04
0.07
0.09
0.12
0.14
0.18
0.21
Prefilter
0.06
0.10
0.16
0.22
0.28
0.35
0.42
0.50
65% cartridge
0.05
0.11
0.19
0.27
0.39
0.52
0.66
0.83
95% cartridge
0.11
0.21
0.33
0.48
0.64
0.83
1.03
1.25
0.01
0.02
0.04
Discharge1
0.02
0.05
0.08
0.13
0.18
0.25
0.33
0.37
Outdoor/return air
Filters
Damper options
Discharge plenum
(deduct)2
Return1
0.01
0.02
0.04
0.06
0.08
0.11
0.14
0.16
0.06
0.13
0.22
0.02
0.04
0.07
0.12
0.17
0.21
0.28
0.03
0.07
0.11
0.18
0.26
0.35
0.46
0.08
0.11
0.17
0.25
0.34
0.45
0.58
0.01
0.02
0.04
0.05
0.07
0.09
0.11
1. Discharge and return air dampers available on the RDS 800C only.
2. Discharge plenum pressure drop incorporated into supply fan curves; deduct pressure drop from total when not provided.
3. Pressure drop through coils are found in the SelectTools for Contractor Coils selection program.
Table 31: RDS 800C and 802Cfurnace pressure drops (in wg)
Airflow
(cfm)
500
650
790
800
1000
PD
PD
PD
PD
PD
PD
4,000
0.06
5,000
0.09
0.07
6,000
0.13
0.10
0.08
7,000
0.18
0.14
0.11
8,000
0.24
0.17
0.14
0.14
9,000
0.30
0.22
0.18
0.18
10,000
0.37
0.27
0.22
0.22
12,000
0.53
0.39
0.32
0.32
0.32
14,000
0.25
0.54
0.44
0.44
0.44
16,000
0.31
0.28
0.57
0.57
0.57
0.57
18,000
0.39
0.35
0.72
20,000
0.48
0.43
0.89
22,000
0.52
24,000
Outdoor/
return air
option1, 2
Filter options
Plenum
(deduct)3
Plenum
options
Heating
options
Airflow (cfm)
14,000
16,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
0.06
0.08
0.10
0.12
0.15
0.18
0.21
0.24
0.28
0.01
0.02
0.02
0.03
0.03
0.04
0.05
0.05
0.06
0.08
0.10
0.13
0.16
0.19
0.23
0.27
0.31
0.36
0.21
0.25
0.29
0.33
0.38
0.43
0.48
0.54
0.59
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
2" throwaway
0.07
0.08
0.10
0.11
0.13
30% pleated
0.08
0.10
0.12
0.14
0.16
0.18
0.20
0.25
0.27
0.17
0.20
0.21
C.28
0.32
0.37
0.41
0.13
0.15
0.18
0.21
0.25
0.28
0.32
0.35
0.39
0.27
0.34
0.41
0.49
0.57
0.66
0.76
0.20
0.25
0.31
0.36
0.43
0.49
0.56
0.63
0.71
0.38
0.46
0.55
0.64
0.74
0.84
0.95
0.29
0.35
0.42
0.49
0.56
0.64
0.72
0.81
0.89
(0.17)
(0.22)
(0.28)
(0.34)
(0.42)
(0.50)
(0.58)
(0.67)
(0.77)
(0.14)
(0.19)
(0.24)
(0.30)
(0.36)
(0.43)
(0.50)
(0.58)
(0.66)
(0.13)
(0.17)
(0.21)
(0.26)
(0.32)
(0.38)
(0.44)
(0.51)
(0.59)
0.02
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.12
0.15
0.19
0.22
0.26
0.30
0.35
0.39
0.44
0.24
0.30
0.37
0.44
0.52
0.60
0.69
0.78
0.88
0.10
0.12
0.18
0.18
0.21
0.24
0.27
0.31
0.35
018
0.20
1.24
0.73
0.33
0.38
0.43
0.48
0.54
0.19
0.24
0.30
0.35
0.41
0.48
0.55
0.62
0.70
Electric heat
0.07
0.10
0.12
0.15
0.18
0.22
0.25
0.29
0.34
Gas heat
Cooling4
Face and
bypass6
See Table 34: Furnace pressure drops (in wg)RAH 047C and 077C on page 61.
Cooling diffuser5
0.04
0.05
0.06
0.08
0.10
0.11
0.13
0.15
0.18
0.04
0.05
0.07
0.08
0.10
0.11
0.14
0.16
0.18
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.06
0.07
0.25
0.32
0.41
0.50
0.61
0.72
0.85
0.98
1.12
0.29
0.37
0.47
0.56
0.69
0.82
0.97
1.11
1.27
Notes:
1. Pressure drop through hood and damper is based on 30% of listed airflow.
2. Pressure drop through the economizer assumes that all of the air will be passing through the return air dampers.
3. If a discharge plenum is not used with a DWDI supply fan, subtract this static pressure factor from the total static pressure drop.
4. Pressure drop through cooling coils can be found in the Daikin MS-85 selection program output or Coil Catalog 411.
5. A cooling diffuser is provided on blow-through units with cooling, hot water or steam heating.
6. Base design pressure drop across face and bypass dampers on the position creating the greatest resistance.
www.DaikinApplied.com 59
Component
Outdoor/return air
options1, 2
Filter options
Plenum (deduct)3
Plenum options
Heating options
18,000
22,000
26,000
30,000
34,000
38,000
42,000
46,000
50,000
0.05
0.08
0.11
0.14
0.18
0.23
0.28
0.34
0.40
0.01
0.02
0.03
0.03
0.04
0.06
0.07
0.08
0.09
0.06
0.10
0.15
0.20
0.26
0.32
0.39
0.46
0.54
0.16
0.22
0.29
0.36
0.44
0.52
0.61
0.70
0.80
0.03
0.05
0.05
0.06
0.07
0.09
0.10
0.11
0.12
2" Throwaway
0.15
0.07
0.09
0.11
0.13
30% Pleated
0.06
0.08
0.11
0.13
0.15
0.18
0.21
0.24
0.27
0.15
0.20
0.24
0.31
0.37
0.12
0.16
0.21
0.25
0.31
0.36
0.09
0.12
0.15
0.18
0.22
0.26
0.30
0.34
0.39
0.24
0.33
0.43
0.55
0.68
0.19
0.27
0.35
0.44
0.54
0.65
0.13
0.18
0.24
0.31
0.38
0.45
0.53
0.62
0.71
0.33
0.45
0.57
0.71
0.85
0.27
0.37
0.47
0.58
0.70
0.83
0.19
0.26
0.34
0.42
0.50
0.59
0.69
0.79
0.89
(0,12)
(0.19)
(0.26)
(0.35)
(0.44)
(0.56)
(0.68)
(0.81)
(0.96)
0.11)
(0.16)
(0.22)
(0.30)
(0.38)
(0.47)
(0.58)
(0.69)
(0.82)
(0.09)
(0.14)
(0.20)
(0.26)
(0.33)
(0.42)
(0.51)
(0.61)
(0.72)
0.02
0.02
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.10
0.14
0.19
0.24
0.30
0.36
0.43
0.50
0.57
0.20
0.28
0.38
0.48
0.59
0.72
0.85
1.00
1.15
0.07
0.11
0.14
0.18
0.23
0.28
0.33
0.39
0.46
0.15
0.21
0.29
0.37
0.46
0.56
0.67
0.79
0.91
0.12
0.17
0.23
0.29
0.36
0.43
0.51
0.60
0.69
Electric heat
0.07
0.10
0.14
0.19
0.24
0.30
0.37
0.45
0.53
Gas heat
Cooling4
See Table 34: Furnace pressure drops (in wg)RAH 047C and 077C on page 61.
Cooling diffuser5
0.04
0.05
0.07
0.10
0.13
0.16
0.19
0.23
0.28
0.04
0.06
0.08
0.10
0.13
0.17
0.20
0.24
0.29
0.01
0.02
0.03
0.04
0.05
0.06
0.08
0.09
0.10
0.15
0.25
0.35
0.46
0.59
0.74
0.90
1.08
1.28
0.18
0.29
0.40
0.53
0.67
0.82
1.09
1.17
1.28
Notes:
1. Pressure drop through hood and damper is based on 30% of listed airflow.
2. Pressure drop through the economizer assumes that all of the air will be passing through the return air dampers.
3. If a discharge plenum is not used with a DWDI supply fan, subtract this static pressure factor from the total static pressure drop.
4. Pressure drop through cooling coils can be found in the Daikin MS-85 selection program output or Coil Catalog 411.
5. A cooling diffuser is provided on blow-through units with cooling, hot water or steam heating.
6. Base design pressure drop across face and bypass dampers on the position creating the greatest resistance.
500
650
790
800
1000
1100
1400
1500
2000
PD
PD
PD
PD
PD
PD
PD
PD
PD
PD
4,000
0.06
6,000
0.13
0.13
0.10
0.08
8,000
0.24
0.24
0.18
0.14
0.14
10,000
0.37
0.37
0.28
0.22
0.22
0.13
12,000
0.53
0.53
0.40
0.32
0.32
0.32
0.19
14,000
0.25
0.25
0.54
0.44
0.44
0.44
0.26
0.16
16,000
0.33
0.33
0.27
0.57
0.57
0.57
0.57
0.34
0.20
18,000
0.41
0.41
0.35
0.39
0.39
0.39
0.72
0.43
0.26
20,000
0.51
0.51
0.43
0.48
0.48
0.48
0.89
0.53
0.32
22,000
0.25
0.25
0.52
0.36
0.36
0.36
0.58
0.44
0.64
0.39
24,000
0.30
0.30
0.25
0.43
0.43
0.43
0.69
0.53
0.76
0.46
26,000
0.35
0.35
0.30
0.31
0.50
0.31
0.81
0.62
0.89
0.54
28,000
0.41
0.41
0.35
0.36
0.59
0.36
0.59
0.72
0.72
0.38
30,000
0.47
0.47
0.40
0.41
0.41
0.41
0.67
0.40
0.83
0.44
32,000
0.45
0.46
0.46
0.46
0.76
0.46
0.94
0.50
0.72
34,000
0.51
0.52
0.52
0.52
0.86
0.52
0.72
0.56
0.82
36,000
0.57
0.59
0.59
0.59
0.59
0.58
0.81
0.63
0.93
38,000
0.64
0.65
0.65
0.65
0.65
0.65
0.90
0.70
0.85
40,000
0.71
0.73
0.73
0.73
0.73
0.72
0.72
0.78
0.95
42,000
0.78
0.80
0.80
0.80
0.80
0.79
0.79
0.86
1.05
46,000
0.94
0.96
0.96
0.96
0.96
0.95
0.95
1.03
0.86
50,000
1.11
1.13
1.13
1.13
1.13
1.12
1.12
1.22
1.03
NOTE: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops
cannot exceed 5.0 in).
www.DaikinApplied.com 61
Fan Performance
Fan Performance
Do not select
Figure 47: RDS 708B supply fan, 15"9" forward curved fan
Do not select
Fan Performance
Figure 48: RDS 708B supply fan, 15"15" forward curved fan without vanes
Do not select
Figure 49: RDS 708B supply fan, 15"15" forward curved fan with vanes
Do not select
www.DaikinApplied.com 63
Fan Performance
Figure 50: RDS 708B supply fan, 16" airfoil fan without vanes
Do not select
Figure 51: RDS 708B supply fan, 16" airfoil fan with vanes
Do not select
Fan Performance
Figure 52: RDS 800C supply fan, (2) 15"6" forward curved
Do not select
Figure 53: RDS 800C supply fan, (2) 15"15" forward curved
Do not select
www.DaikinApplied.com 65
Fan Performance
Figure 54: RDS 800C supply fan, 20" airfoil
Do not select
NOTE: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops
cannot exceed 5.0 in).
Figure 55: RDS 802C supply fan, 24" forward curved fan
Do not select
NOTE: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops
cannot exceed 5.0 in).
CAT 218-3 ROOFPAK APPLIED AIR HANDLERS 66 www.DaikinApplied.com
Fan Performance
Figure 56: RDS 802C supply fan, 24" backward curved fan
Do not select
NOTE: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops
cannot exceed 5.0 in).
Figure 57: RAH 047C, DWDI fan, 27" forward curved Class II
Do not select
NOTE: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops
cannot exceed 5.0 in).
www.DaikinApplied.com 67
Fan Performance
Figure 58: RAH 047C, DWDI fan, 27" airfoil
Do not select
NOTE: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops
cannot exceed 5.0 in).
Figure 59: RAH 047C, DWDI fan, 30" airfoil
Do not select
NOTE: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops
cannot exceed 5.0 in).
CAT 218-3 ROOFPAK APPLIED AIR HANDLERS 68 www.DaikinApplied.com
Fan Performance
Figure 60: RAH 047C, DWDI fan, 33" airfoil
Do not select
NOTE: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops
cannot exceed 5.0 in).
Figure 61: RAH 077C DWDI fan, 33" airfoil
Do not select
NOTE: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops
cannot exceed 5.0 in).
www.DaikinApplied.com 69
Fan Performance
Figure 62: RAH 077C, DWDI fan, 36" airfoil
Do not select
NOTE: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops
cannot exceed 5.0 in).
Figure 63: RAH 077C, DWDI fan, 40" airfoil
Do not select
NOTE: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops
cannot exceed 5.0 in).
CAT 218-3 ROOFPAK APPLIED AIR HANDLERS 70 www.DaikinApplied.com
Fan Performance
Do not select
NOTE: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops
cannot exceed 5.0 in).
Figure 65: RAH 047C, SWSI fan, 44" airfoil
Do not select
NOTE: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops
cannot exceed 5.0 in).
www.DaikinApplied.com 71
Fan Performance
Figure 66: RAH 077C, SWSI fan, 44" airfoil
Do not select
NOTE: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops
cannot exceed 5.0 in).
Figure 67: RAH 077C, SWSI fan, 49" airfoil
Do not select
NOTE: Maximum allowable static pressure at fan bulkhead is 5.0 in (i.e., ESP plus blow-through component pressure drops
cannot exceed 5.0 in).
CAT 218-3 ROOFPAK APPLIED AIR HANDLERS 72 www.DaikinApplied.com
Fan Performance
Do not select
Figure 69: RAH 047C and 077C (2) 36" propeller exhaust fan
Do not select
www.DaikinApplied.com 73
Fan Performance
Figure 70: RAH 077C (3) 36" propeller exhaust fan
Do not select
Fan Performance
Return Fans
Figure 71: RDS 708B 15"15" forward curved return fan without vanes
Do not select
Figure 72: RDS 708B 15"15" forward curved return fan with vanes
Do not select
www.DaikinApplied.com 75
Fan Performance
Figure 73: RDS 708B 16" airfoil fan without vanes
Do not select
Do not select
Fan Performance
Figure 75: RDS 800C (2) 15" x 15" forward curved return fan
Do not select
Class II Fan Required Class II
*Fan curve applicable for bottom return. Back return corrections are listed below.
4,000
6,000
8,000
10,000
12,000
14,000
Back
return SP
(in wg)
0.05
0.12
0.21
0.33
0.48
0.65
Figure 76: RDS 800C and 802C, 30" airfoil return fan (bottom return*)
Do not select
www.DaikinApplied.com 77
Fan Performance
Figure 77: RDS 802C, 40" airfoil return fan
Do not select
Do not select
Do not select
Dimensional Data
Dimensional Data
www.DaikinApplied.com 79
Dimensional Data
Figure 82: Typical basic unit
Fan Size
15"6"
10.23
27.94
17.0
15"9"
13.94
26.19
17.0
15"15"
19.75
23.25
17.0
16"
24.75
20.75
22.8
Dimensional Data
63.5
45.0
62.0
Cabinet Height
50.88
www.DaikinApplied.com 81
Door Opening
A
42.0
45.0
Dimensional Data
Discharge plenum
50.0
20.0
2.13
1.63
10.38
17.0
0.75
21.44
13.94
17.0
0.75
19.69
19.75
17.0
0.75
16.75
24.75
22.8
5.62
14.28
Dimensional Data
Contractor Coils
Contractor coils are available in direct expansion, chilled
water, steam and hot water type and are located in the
Heat/ Cool sections, positions D and I.
Contractor coils are available with or without factoryinstalled face and bypass dampers less actuator.
www.DaikinApplied.com 83
Electric Heat
Electric heating coils are located in the Blow-through
Heat section, position G only.
Gas Heat
A gas heating furnace is located in the Blow-through Heat
section, position G only.
Final Filters
Final filters are not available with a drain pan only or any
option with a cooling coil located in the Blow-through
Heat/ Cool section, position I.
General
When any section is located in position H (Blank Access
section), I (Blow-through Heat/Cool section) or J (Final
Filter section), a heating or blank section must be placed
in position G to provide proper airflow diffusion for the
sections that follow the supply air fan.
Dimensional Data
Dimensional Data
www.DaikinApplied.com 85
Dimensional Data
Return Fan
None
24
82
6.8
1.5
(2) 15" FC
24
82
6.8
1.5
30" AF
30
76
6.8
4.5
40" AF
36
78
14.8
3.5
Return Fan
None
24
82
6.8
1.5
(2) 15" FC
24
82
6.8
1.5
30" AF
30
76
6.8
4.5
40" AF
36
78
14.8
3.5
Dimensional Data
Blank Access and Drain Pan Only Section DetailRDS 800C and 802C
Figure 97: Cross section detail and access door detailRDS 800C and RDS 802C
www.DaikinApplied.com 87
Dimensional Data
Dimensional Data
Figure 102: Large face area coilsRAH 047C
www.DaikinApplied.com 89
Dimensional Data
Cooling Coils
Cooling Coils are available in either direct expansion or
chilled water type and can be located in the Heat/Cool
sections.
Chilled water cooling coils are available with or without
factory-installed, three-way modulating control valves as
well as face and bypass dampers and actuator.
Factory-wired control of cooling coils is limited to one
cooling coil section per unit.
Electric Heat
Electric heating coils can be located in the Blow-through
Heat section, position G only on units with a DWDI supply
fan.
Gas Heat
A gas heating furnace can be located in the Blow-through
Heat section, position G only on units with a DWDI supply
fan. Factory-wired control of cooling coils is limited to one
heating section per unit.
Final Filters
If final filters are installed, a Discharge Plenum section is
required in position K.
Final filters are not available on units with a SWSI supply
fan.
Final filters are not available on units with a blow-through
cooling coil in the Heat/Cool section, position I.
General
When any selection is located in position H (Blank access
section), I (Blow-through Heat/Cool Section), or J (Final
Filter Section), a heating or blank section must be placed
in position G to provide proper airflow diffusion for the
sections that follow the supply fan.
Dimensional Data
www.DaikinApplied.com 91
Dimensional Data
Figure 106: Large face area coilsRAH 077C
Dimensional Data
Figure 108: Heat coil piping vestibule detailRAH 047C and 077C
Dimension (in.)
RAH 047C
64.1
RAH 077C
88.1
Blank Access and Drain Pan Only Section DetailsRAH 047C and RAH 077C
Figure 109: Cross section detailRAH 047C and 077C
Dimension (in.)
RAH 047C
67.7
96.0
91.8
95.0
61.0
73.0
61.0
RAH 077C
91.7
96.0
91.8
95.0
85.0
97.0
85.0
www.DaikinApplied.com 93
Dimensional Data
SWSI Wheel
Diameter
Supply Air
Opening B
44
38
49
46
077C
077 CS
See Figure 115
077 CL
Dimensions (in.)
RAH 047C
38
28
RAH 077C
62
See tables
077 CY
Cooling
Coil Type*
Cooling
Coil Size
(sq ft)
Chilled
Water (CW)
36.3
Direct
Expansion
(DX)
Chilled
Water (CW)
51.9
Supply Air
Opening B
38
54.7
62.3
72.6
Direct
Expansion
(DX)
72.6
None
46
46
Dimensional Data
www.DaikinApplied.com 95
Recommended Clearances
Recommended Clearances
Service Clearance
Allow recommended service clearances shown in Figure 117, Figure 118, Figure 119, and Figure 120. Provide a roof walkway
along two sides of the unit for service and access to most controls. Contact your Daikin sales representative for service
requirements less than those recommended.
Figure 117: Service clearancesRDS 708B
Legend:
A = Return Air Section
B = Filter Section
C = Combination Coil Section
D = Heat Section
E = Supply Fan Section
F = Discharge Plenum Section
Legend:
A = Return Air Section
B = Filter Section
C = Combination Coil Section
D = Heat Section
E = Supply Fan Section
F = Discharge Plenum Section
Legend:
A = Return Air Section
B = Filter Section
C = Combination Coil Section
D = Heat Section
E = Supply Fan Section
F = Discharge Plenum Section
Recommended Clearances
Overhead Clearance
Unit(s) surrounded by screens or solid walls must have
no overhead obstructions over any part of the unit.
Ventilation Clearance
Unit(s) surrounded by a screen or a fence:
www.DaikinApplied.com 97
Gas Piping
Gas Piping
Item
Description
FM/ETL/UL
FM/ETL-C
IRI
4002000 MBh
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Pilot cock
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Pilot orifice
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
10
Test cock
Standard
Standard
Standard
Standard
Standard
11
Standard
12
Combination redundant
valve and pressure
regulator
Standard
Combination redundant
valve and pressure
regulator
Standard
13
Vent to atmosphere
valve, N/O
Standard
14
Combination redundant
valve and pressure
regulator
Standard
Combination redundant
valve and pressure
regulator
15
Standard
Combination redundant
valve and pressure
regulator
Standard
Combination redundant
valve and pressure
regulator
Standard
Standard
17
Standard
Standard
Standard
Standard
Standard
18
Optional
Optional
Optional
Optional
Optional
19
Optional
Optional
Optional
Optional
Optional
20
Combustion air
butterfly valve
Standard
Standard
Standard
Standard
Standard
21
Standard
Standard
Standard
Standard
Standard
22
Modulating operator
Standard
Standard
Standard
Standard
Standard
16
Electrical Data
Electrical Data
Table 36: Supply, exhaust and return fan motors, RPS 015C to 135C
HP
1
1.5
7.5
10
15
20
25
30
40
50
60
75
Fan Motor
Efficiency
High ODP
High TEFC
Premium ODP
Premium TEFC
High ODP
High TEFC
Premium ODP
Premium TEFC
High ODP
High TEFC
Premium ODP
Premium TEFC
High ODP
High TEFC
Premium ODP
Premium TEFC
High ODP
High TEFC
Premium ODP
Premium TEFC
High ODP
High TEFC
Premium ODP
Premium TEFC
High ODP
High TEFC
Premium ODP
Premium TEFC
High ODP
High TEFC
Premium ODP
Premium TEFC
High ODP
High TEFC
Premium ODP
Premium TEFC
High ODP
High TEFC
Premium ODP
Premium TEFC
High ODP
High TEFC
Premium ODP
Premium TEFC
High ODP
High TEFC
Premium ODP
Premium TEFC
High ODP
High TEFC
Premium ODP
Premium TEFC
High ODP
High TEFC
Premium ODP
Premium TEFC
High ODP
High TEFC
Premium ODP
Premium TEFC
208/60/3
FLA
3.9
4
3.3
4.5
6.2
4.8
7.1
7
6.1
9.9
9.6
9.3
9.4
16.1
15.2
15.7
15
25
24.8
22.3
22
33
29.5
29
28.5
44.8
43.7
43.4
42.4
61
60
57
56
74
73
70
68.4
86.5
87
83.3
84
117
114
110
106
140
136
137
131
154
160
189
195
230/60/3
LRA
26
27
27
39
39
40.3
47
50.6
43.2
79
81
74
80
106
126
110
124
137
175.3
185
177
290
228
247
209
368
310
271
282
342
465
373
403
427
416
438
431
560
448
514
566
660
590
730
734
832
840
877
897
991
1125
1240
1240
FLA
2.8
2.8
3
3
4.2
4.2
4.2
4.2
5.6
5.6
5.8
5.6
9
8.2
8.2
8.2
14
13.4
13.6
13
21.6
20.4
20
20
28
28.4
25.8
25
40.6
38.8
37.8
37
50
48
49
48
62
60
61
61
75
72
72.4
69
102
95
96
94
124
118
120
118
144
140
140
140
176
172
170
168
460/60/31
LRA
20
21
19.2
28
32
32
25
40
42
48
37.6
44
64.6
77.2
64
71
94
102.4
96
96
148.4
145.2
122
141
180
200
192
182
301
272
233.6
246
350
320
322
350
382
380
380
376
460
460
448
428
630
544
630
650
770
744
752
778
872
1022
912
1200
1108
1132
1044
1186
FLA
1.4
1.4
1.5
1.5
2.1
2.1
2.1
2.1
2.8
2.8
2.9
2.8
4.5
4.1
4.1
4.1
7
6.7
6.8
6.5
10.8
10.2
10
10
14
14.2
12.9
12.5
20.3
19.4
18.9
18.5
25
24
24.5
24
31
30
30.5
30.5
37.5
36
36.2
34.5
51
47.5
48
47
62
59
60
59
72
70
70
70
88
86
85
84
575/60/3
LRA
10.5
10.5
15
14
16
16
14
20
21
24
26.5
22
32.3
38.6
32
35.5
47
51.2
48
48
74.2
72.6
80
70.5
94
100
106
91
150.5
136
117
123
175
160
160.8
175
191
190
190
188
230
230
224
214
315
272
315
325
385
372
376
389
442
511
456
600
553
566
553
593
FLA
1.15
1.2
1.1
1.3
1.7
1.7
1.7
1.7
2.2
2.2
2.1
2.2
3.4
3.4
3.1
3.3
5.3
5.4
5.2
5.2
8.2
8.2
7.4
8
11
11.4
10.3
10
16.2
15.5
14.1
14
20
19.1
18.9
18.8
24.3
24.2
24.2
22.8
30
28.6
29.8
27.6
40
38
38
37
49.2
48
47.5
46
57.4
56
56
54
71
68
65.5
66
LRA
9
9
7.7
10
12.8
12.8
14
16
16.8
17
15
17
26.1
30.9
25.6
29
38
39
38.4
38
49
58
52
56
72
80
76.6
67
120
109
94
89
135
123
130
138
151
152
125
148
177
184
179
178
251
214
245
213
303
266
332
237
355
409
345
403
505
447
444
504
1. 380/50/3 applications, 460/60/3 motors are used. Derate nameplate by 0.85 to obtain actual horsepower.
Electrical Data
Table 37: Electric heat, RDS 800C and 802C
Model
208/60/3
240/60/3
480/60/3
600/60/3
kW
FLA
Steps1
Stages2
kW
FLA
Steps1
Stages2
kW
FLA
Steps1
Stages2
kW
FLA
Steps1
Stage2
20
14.4
41.4
19.8
47.6
19.8
23.8
19.8
19.0
40
29.9
83.0
39.8
95.7
39.8
47.8
39.8
38.3
60
45.1
124.9
60.0
144.3
60.0
72.2
60.0
57.7
80
59.8
166.0
79.6
191.5
79.6
94.7
79.6
76.6
100
74.7
207.4
99.5
239.3
99.5
19.7
99.5
95.7
120
89.7
249.3
119.4
287.2
119.4
143.6
119.4
114.9
140
139.1
167.3
139.1
133.8
160
159.2
191.5
159.2
153.2
180
179.1
215.4
179.1
172.3
200
199.0
239.4
199.0
191.5
220
218.7
263.0
218.7
210.4
240
238.6
287.2
238.8
229.6
208/60/3
240/60/3
480/60/3
600/60/3
kW
FLA
Stages
kW
FLA
Stages
kW
FLA
Stages
kW
FLA
Stages
40
29.9
83.0
39.8
95.7
39.8
47.9
39.8
38.3
60
45.1
124.9
60.0
144.3
60.0
72.2
60.0
57.7
80
59.8
166.0
79.6
191.5
79.6
95.7
79.6
76.6
100
74.7
207.4
99.5
239.4
99.5
119.7
99.5
95.7
120
89.7
249.3
119.4
287.2
119.4
143.6
119.4
114.9
160
119.7
332.0
159.2
383.0
159.2
191.5
159.2
153.2
200
199.0
239.4
199.0
191.5
240
238.8
287.2
238.8
229.8
208/60/3
240/60/3
480/60/3
600/60/3
kW
FLA
Stages
kW
FLA
Stages
kW
FLA
Stages
kW
FLA
Stages
80
59.8
166.0
79.6
191.5
79.6
95.7
79.6
76.6
100
74.7
207.4
99.5
239.4
99.5
119.7
99.5
95.7
120
89.7
249.3
119.4
287.2
119.4
143.6
119.4
114.9
160
159.2
191.5
159.2
153.2
200
199.0
239.4
199.0
191.5
240
238.8
287.2
238.8
229.8
280
278.6
335.1
278.6
268.1
320
318.4
383.0
318.4
306.4
Electrical Data
Ampacity
No. of power
wires per
phase
No. of
conduits
Wire gauge
Insulation
rating (0C)
30
10
60
40
60
55
60
70
60
85
60
95
60
130
75
150
1/0
75
175
2/0
75
200
3/0
75
230
4/0
75
255
250
75
285
300
75
310
350
75
335
400
75
380
500
75
400
3/0
75
460
4/0
75
510
250
75
570
300
75
620
350
75
670
400
75
760
500
75
765
250
75
855
300
75
Heater is > 50 kW
930
350
75
a. 60 Hertz
Nameplate 208 V: Min 187 V, Max. 229 V
www.DaikinApplied.com 101
Unit Weights
Unit Weights
Blenders
Filter optionsblow-through section
(final filters, 95% cartridge)2
Heat/cool section1
Electric heat
708B
881
265
309
155
220
767
395
63
112
85
113
378
155
165
193
212
311
339
211
253
311
339
48
82
124
144
135
90
Unit size
800C
893
488
633
286
1003
1125
1180
9
19
146
154
540
548
625
794
345
375
556
350
385
48
82
124
144
185
214
266
540
144
45
102
111
126
143
802C
1180
599
744
286
1121
1125
1444
9
19
146
154
540
548
625
794
539
569
385
512
48
82
124
144
185
214
266
540
144
45
102
111
126
143
565
664
668
696
769
777
811
819
841
849
565
664
668
696
769
777
811
819
841
849
Unit Weights
Plenum options
Power package/MicroTech control
Blank section
Insulation liners
Roof curbs
708B
265
23
23
150
265
30
270
320
400
450
Unit size
800C
964
1041
1155
1237
515
49
58
300
262
309
405
512
24
802C
964
1041
1155
1237
515
300
262
309
405
512
24
See page 99
1. A basic RDS 708B unit consists of filter section without media, coil section without coil, and supply fan section without fan or motor. A basic RDS 800C and 802C unit consists of angular filter
section with 2" throwaway filters and a supply fan section without fan or motor.
2. Final filter option includes liners in final filter and discharge plenum sections.
www.DaikinApplied.com 103
Unit Weights
Weight Formula
5/8" Coils
Additional Weights:
1" Coils
4. Cross supports:
36
48
5/8" steam
1" steam
Fin
height
Face
area
1 row
2 row
3 row
4 row
5 row
6 row
8 row
10 row
1 row
2 row
1 row
12
3.0
16
23
32
39
46
54
70
84
21
33
48
18
4.5
21
32
42
53
64
75
96
116
28
44
61
24
6.0
26
40
53
68
81
95
124
148
37
57
74
30
7.5
32
49
66
83
99
116
150
179
44
69
86
36
9.0
54
84
99
12
4.0
22
31
39
51
61
71
90
109
27
42
59
18
6.0
26
41
54
69
82
96
124
149
36
56
74
24
8.0
32
50
68
85
103
122
158
189
45
72
90
30
10.0
39
61
82
104
126
148
191
229
54
87
104
36
12.0
43
70
96
122
148
174
226
269
65
104
120
36
5/8" steam
1" steam
Fin
height
Face
area
1 row
2 row
3 row
4 row
5 row
6 row
8 row
10 row
1 row
2 row
12
6.6
44
58
72
86
99
113
141
167
46
62
87
18
9.9
55
76
96
117
138
158
199
240
58
81
108
24
13.2
66
93
120
148
175
202
258
312
70
102
130
30
16.5
77
111
146
179
214
248
316
385
81
123
152
36
19.8
88
128
160
211
251
293
374
458
93
142
173
42
23.0
99
146
174
242
290
338
433
530
105
161
195
1 row
Note:
1. Coil weight based on 8 fpi.
2. Correcting for actual weight of 75", 78" or 82" unit code is not significant
Unit Weights
Table 44: Component unit weights (lbs.)RAH 047C to 077C
Components
Unit configuration
Blenders
Filter optionsdraw-through
section
047CS
1475
524
746
435
1589
1144
628
632
525
785
1125
1385
047CL
1475
524
746
435
1589
1144
628
632
525
785
1125
1385
4
57
538
67
550
1083
1509
919
942
868
965
1452
1068
1367
629
44
71
82
124
144
185
214
266
310
404
452
49
72
85
140
170
235
300
330
390
510
570
4
57
538
67
550
1083
1509
919
942
868
965
1452
1068
1367
629
44
71
82
124
144
185
214
266
310
404
452
49
72
85
140
170
235
300
330
390
510
570
Unit size
047CY
077CS
1475
1732
524
973
746
1235
435
967
1589
2239
1144
2161
628
727
632
731
525
785
891
1151
1125
1385
1581
1841
Included in basic unit weight
4
6
57
69
538
589
1100
67
83
550
605
1120
1083
1296
1509
1760
2275
919
942
868
965
1452
989
1719
1760
1068
1367
1484
2540
629
1143
44
71
82
82
124
124
144
144
185
185
214
214
266
266
310
310
404
404
452
452
620
680
49
72
85
85
140
140
170
170
235
235
300
300
330
330
390
390
510
510
570
570
850
910
077CL
1732
973
1235
967
2239
2161
727
731
891
1151
1581
1841
077CY
1732
973
1235
967
2239
2161
727
731
891
1151
1581
1841
6
69
589
1100
83
605
1120
1296
1760
2275
989
1719
1760
1484
2540
1143
82
124
144
185
214
266
310
404
452
620
680
85
140
170
235
300
330
390
510
570
850
910
6
69
589
1100
83
605
1120
1296
1760
2275
989
1719
1760
1484
2540
1143
82
124
144
185
214
266
310
404
452
620
680
85
140
170
235
300
330
390
510
570
850
910
Unit Weights
Components
Electric heat
Gas furnace
Plenum options
Roof curbswithout
blank compartment (out of airstream)
40 kW
60 kW
80 kW
100 kW
120 kW
160 kW
200 kW
240 kW
280 kW
320 kW
200 MBh
250 MBh
320 MBh
400 MBh
500 MBh
640 MBh
650 MBh
790 MBh
800 MBh
1000 MBh
1100 MBh
1400 MBh
1500 MBh
2000 MBh
4 ft lined
Discharge plenum4 ft
Discharge plenum6 ft
Burglar barsdischarge
Burglar barsreturn
Isolation dampersdischarge
Isolation dampersreturn
Main control panel
24" section, unlined
48" section, unlined
72" section, unlined
2", 1.5 lb insulation with linersweight
per ft of unit length, excluding blank
compartment.
8 feet
10 feet
12 feet
14 feet
16 feet
18 feet
20 feet
22 feet
24 feet
26 feet
28 feet
30 feet
32 feet
34 feet
36 feet
38 feet
40 feet
42 feet
44 feet
46 feet
48 feet
50 feet
52 feet
54 feet
Unit size
047CY
077CS
852
860
863
1035
869
1041
875
1046
886
1058
910
1087
922
1099
1111
1123
893
893
941
946
1002
1132
1002
1132
1086
1230
1086
1230
1151
1301
1151
1301
1496
1496
1718
1733
233
536
600
53
69
73
114
85
106
112
172
410
470
341
387
574
651
915
1038
047CS
852
860
863
869
875
886
910
922
893
893
941
946
1002
1002
1086
1086
1151
1151
536
53
73
85
112
410
341
574
915
047CL
852
860
863
869
875
886
910
922
893
893
941
946
1002
1002
1086
1086
1151
1151
536
53
73
85
112
410
341
574
915
25
25
25
435
469
550
584
618
652
686
720
801
835
870
903
937
971
1053
1087
1121
1155
1189
1223
1304
1338
435
469
550
584
618
652
686
720
801
835
870
903
937
971
1053
1087
1121
1155
1189
1223
1304
1338
435
469
550
584
618
652
686
720
801
835
870
903
937
971
1053
1087
1121
1155
1189
1223
1304
1338
077CL
1035
1041
1046
1058
1087
1099
1111
1123
1132
1132
1230
1230
1301
1301
1496
1496
1718
1733
233
600
987
81
114
125
172
470
387
651
1038
077CY
1035
1041
1046
1058
1087
1099
1111
1123
1132
1132
1230
1230
1301
1301
1496
1496
1718
1733
233
600
987
81
114
125
172
470
387
651
1038
30
30
30
455
489
523
604
638
672
706
740
774
808
889
924
958
992
1026
1060
1141
1175
1209
1243
1277
1311
1392
1427
455
489
523
604
638
672
706
740
774
808
889
924
958
992
1026
1060
1141
1175
1209
1243
1277
1311
1392
1427
455
489
523
604
638
672
706
740
774
808
889
924
958
992
1026
1060
1141
1175
1209
1243
1277
1311
1392
1427
Unit Weights
14 feet
16 feet
18 feet
20 feet
22 feet
24 feet
26 feet
28 feet
30 feet
32 feet
34 feet
36 feet
38 feet
40 feet
42 feet
44 feet
46 feet
48 feet
50 feet
52 feet
54 feet
56 feet
58 feet
60 feet
047CS
584
618
699
733
767
801
835
869
950
985
1019
1053
1087
1121
1203
1237
1271
1305
1339
1373
1454
1488
047CL
584
618
699
733
767
801
835
869
950
985
1019
1053
1087
1121
1203
1237
1271
1305
1339
1373
1454
1488
Unit size
047CY
077CS
584
604
618
638
699
672
733
706
767
787
801
821
835
855
869
889
950
923
985
957
1019
1039
1053
1073
1087
1107
1121
1141
1203
1175
1237
1209
1271
1291
1305
1325
1339
1358
1373
1392
1454
1426
1488
1460
1541
1575
077CL
604
638
672
706
787
821
855
889
923
957
1039
1073
1107
1141
1175
1209
1291
1325
1358
1392
1426
1460
1541
1575
077CY
604
638
672
706
787
821
855
889
923
957
1039
1073
1107
1141
1175
1209
1291
1325
1358
1392
1426
1460
1541
1575
1. RAH basic unit includes fan section less fan and motor plus an angular filter section.
2. Final filter option includes liners in final filter and discharge plenum sections.
www.DaikinApplied.com 107
Unit Weights
Table 45: Coil section unit weight (lbs.)RAH 047C to 077C
Unit size
Components
Heat/cool section
Heat section
Evaporator coils
aluminum fins
Evaporator coils
copper fins
047CS
047CL
077CS
077CL
w/o F&BP
w/ F&BP
w/o F&BP
w/ F&BP
w/o F&BP
w/ F&BP
w/o F&BP
628
628
705
705
w/ F&BP
969
969
1092
1356
1356
4 ftunlined
574
574
574
574
3 row8 FPI
370
1001
487
1374
3 row10 FPI
395
1030
520
1411
3 row12 FPI
419
1059
553
1448
4 row8 FPI
445
1135
588
1495
4 row10 FPI
478
1151
632
1558
4 row12 FPI
510
1166
676
1621
5 row8 FPI
518
1176
689
1637
5 row10 FPI
559
1224
744
1715
5 row12 FPI
600
1272
799
1793
6 row8 FPI
595
1269
793
1786
6 row10 FPI
644
1327
859
1880
6 row12 FPI
693
1385
925
1974
3 row8 FPI
591
1262
788
1776
3 row10 FPI
671
1356
897
1928
3 row12 FPI
750
1450
1005
2080
4 row8 FPI
739
1437
989
2058
4 row10 FPI
845
1562
1134
2261
4 row12 FPI
951
1687
1278
2463
5 row8 FPI
886
1611
1191
2340
5 row10 FPI
1019
1768
1372
2594
5 row12 FPI
1151
1924
1553
2847
6 row8 FPI
1036
1791
1395
2630
6 row10 FPI
1196
1979
1612
2934
6 row12 FPI
1355
2167
1829
3238
3 row8 FPI
351
423
950
1117
462
576
1302
1370
3 row10 FPI
374
440
978
1145
493
598
1337
1401
3 row12 FPI
397
456
1005
1172
525
620
1372
1431
4 row8 FPI
422
474
1078
1245
558
643
1417
1469
4 row10 FPI
453
497
1093
1260
600
672
1477
1520
4 row12 FPI
483
519
1107
1274
641
702
1536
1571
5 row8 FPI
491
525
1116
1283
654
710
1552
1584
5 row10 FPI
530
553
1162
1329
706
747
1625
1648
5 row12 FPI
569
581
1208
1375
758
783
1699
1711
6 row8 FPI
564
578
1205
1372
752
779
1693
1706
6 row10 FPI
610
612
1260
1427
815
823
1782
1782
6 row12 FPI
657
646
1315
1482
878
867
1871
1858
8 row8 FPI
722
693
1542
1709
963
927
2167
2112
8 row10 FPI
781
736
1613
1780
1043
983
2281
2210
8 row12 FPI
841
780
1683
1850
1123
1039
1395
2308
Unit Weights
047CS
047CL
077CS
077CL
w/o F&BP
w/ F&BP
w/o F&BP
w/ F&BP
w/o F&BP
w/ F&BP
w/o F&BP
w/ F&BP
3 row8 FPI
560
575
1198
1365
748
776
1683
1697
3 row10 FPI
636
631
1287
1454
851
848
1827
1821
3 row12 FPI
711
685
1377
1544
954
920
1971
1945
4 row8 FPI
700
677
1364
1631
938
909
1951
1927
4 row10 FPI
801
751
1483
1650
1076
1006
2143
2092
4 row12 FPI
901
824
1602
1769
1213
1101
2334
2256
5 row8 FPI
840
779
1529
1696
1130
1043
2218
2156
5 row10 FPI
966
871
1678
1845
1302
1163
2459
2363
5 row12 FPI
1091
962
1827
1994
1474
1284
2698
2569
6 row8 FPI
982
883
1700
1867
1324
1179
2493
2392
6 row10 FPI
1133
993
1879
2046
1529
1323
2781
2639
6 row12 FPI
1284
1103
2057
2224
1735
1467
3069
2887
8 row8 FPI
1257
1083
2176
2343
1694
1438
3191
2991
8 row10 FPI
1451
1224
2405
2572
1958
1622
3559
3307
8 row12 FPI
1644
1365
2633
2800
2221
1807
3928
3624
1 row
235
328
235
386
443
286
2 row
311
380
311
393
515
393
1 row
306
398
306
387
544
387
2 row
453
521
453
594
716
594
1 row6 FPI
228
323
228
276
437
276
1 row12 FPI
251
339
251
309
459
309
2 row6 FPI
302
373
302
382
507
382
1 row6 FPI
252
347
252
311
471
311
1 row12 FPI
368
456
368
476
625
476
2 row6 FPI
351
422
651
451
577
451
Chilled water
126
126
126
126
126
126
126
126
Hot water
138
138
138
138
Steam
103
103
103
103
2 ftlined
120
120
120
120
4 ftlined
183
183
183
183
183
183
183
183
Steam coil
aluminum fins
Steam coils
copper fins
Valve package
Heat coil piping vestibule
Basic unit
1475
Economizer 1589
2" throw-away filter 95% final filters, std. flow
1083
DWDI supply fan, 33" airfoil
1452
Return fan, 40" airfoil
629
SAF motor20 hp open drip proof
214
RAF motor10 hp open drip proof
144
Discharge plenum
536
Burglar bars, discharge
53
Heat section
574
Hot water coil, Al fins2 row
311
Hot water valve package
138
Heat/Cool section
969
Chilled water coil, AI fins, F&BP5 row, 10 fpi
1329
Chilled water valve package
126
MicroTech control
410
Liners (section length 25 lb/ft)*
650
Roof curb34 feet
971
*Liner weight
Section
Length (ft)
Economizer 6
Filter 2
Supply Fan
8
Heat 4
Heat/Cool 6
26
Weight (lbs)
150
50
200
100
150
650
www.DaikinApplied.com 109
General
A. Furnish and install, as shown on plans, Daikin
RoofPak Applied Rooftop Air Handling Unit(s)
model RDS 708. Unit performance and electrical
characteristics shall be per the job schedule.
B. Each unit shall be specifically designed for outdoor
rooftop application and include a weatherproof
cabinet. Units shall be of a modular design to
provide maximum design flexibility. Each unit shall
be completely factory assembled and shipped in one
piece.
C. All units shall have decals and tags to indicate
caution areas and aid unit service. Unit nameplates
shall be fixed to the main control panel door.
Electrical wiring diagrams shall be attached to
the control panels. Installation, operating and
maintenance bulletins and start-up forms shall be
supplied with each unit.
D. The unit shall undergo a complete factory run test
prior to shipment and factory test sheets shall
be available upon request. The factory test shall
include final balancing of the supply [and return]
fan assemblies, [a unit electrical system operations
checkout,] and a final unit inspection.
E. The complete unit(s) shall be ETL and ETL-Canada
listed by Intertek Testing Services, Inc. Units shall
conform to bi-national standard ANSI/UL Standard
1995/CSA Standard C22.2 No. 236. Unit(s) shall
be accepted for use in the City of New York by the
Department of Building, MEA #368-93-E Vol. II.
F. Unit supply fan and coil performance shall be AHRI
certified.
C. Exterior surfaces shall be constructed of prepainted galvanized steel for aesthetics and long
term durability. Paint finish to include a base primer
with a high quality, polyester resin topcoat of a
neutral beige color. Finished surface to withstand a
minimum 750-hour salt spray test in accordance with
ASTM B117 standard for salt spray resistance.
D. Service doors shall be provided on both sides of each
section in order to provide user access to all unit
components. Service doors shall be constructed of
19 gauge galvanized steel. All service doors shall be
mounted on multiple, stainless steel hinges and shall
be secured by a latch system that is operated by a
single, flush mounted handle. Removable panels, or
doors secured by multiple, mechanical fasteners are
not acceptable.
E. The unit base frame shall be constructed of 8 &
18-gauge galvanized steel. The unit base shall
overhang the roof curb for positive water runoff and
shall have a formed recess that seats on the roof
curb gasket to provide a positive, weather tight seal.
Lifting brackets shall be provided on the unit base
with lifting holes to accept cable or chain hooks.
Fan Sections
A. All fan assemblies shall be statically and dynamically
balanced at the factory, including a final trim
balance, prior to shipment.
B. All fan assemblies shall employ solid steel fan
shafts. Heavy-duty pillow block type, self-aligning,
grease-lubricated ball bearings shall be used.
Bearings shall be sized to provide an L-50 life at
200,000 hours.
C. The entire fan assembly shall be isolated from the
fan bulkhead and mounted on [rubber-in-shear
isolators] [spring isolators] [spring isolators with
seismic restraints].
D. [Fixed] [Adjustable] pitch V-belt drives with matching
belts shall be provided. V-belt drives shall be
selected at [the manufacturers standard service
factor] [1.5 times fan brake horsepower].
E. Fan motors shall be heavy-duty 1800 rpm [open
drip-proof (ODP)] [totally enclosed TEFC] type with
grease-lubricated ball bearings. [Motors shall be
premium efficiency.] Motors shall be mounted on an
adjustable base that provides for proper alignment
and belt tension adjustment.
Electrical
A. [The air handler shall have no power control wiring.
All unit wiring shall be the responsibility of the
control contractor.
B. [Each unit shall come complete with an integral,
weatherproof control panel. Wiring shall comply
with NEC requirements and with all applicable UL
standards. All electrical components shall be UL
recognized, where applicable.]
1. To provide for easy identification, all wiring and
electrical components provided with unit shall be
numbered, color-coded and labeled according to
the electrical diagram provided with the unit.
2. The main unit control panel shall be completely
factory wired and contained in a weatherproof
enclosure. The main unit control panel shall
be provided with dead front covers over all line
voltage components. A terminal board shall be
provided for low voltage control wiring.
3. Branch circuit fusing, 115V control circuit
transformer with fuse, system switches, high
temperature sensor and 115V service receptacle
shall also be provided. The 115V service
receptacle shall require a separate power source.
4. Knockouts shall be provided in the bottom of the
main control panels for field wiring entrance.
5. Supply [and return] fan motors shall have
individual fuses, contactors and external, line
break overload protection.
6. [A factory installed and wired marine light, with
switch and receptacle, shall be provided in the
supply [and return] fan section.]
7. All receptacles will have ground fault protection.
8. A single point power connection shall power
the entire unit except the receptacle and light
circuit. [Separate 115-volt power is required
for the lights and receptacle to allow power
to these components while the main power is
disconnected for service.]
a. [A terminal block shall be provided for the 3
phase power connection.]
b. A single non-fused disconnect switch shall be
provided for disconnecting electrical power at
the unit. Disconnect switch shall be mounted
internal to the control panel and operated
by an externally mounted handle. Externally
mounted handle to prohibit opening of the
control panel door without the use of a service
tool.
www.DaikinApplied.com 111
Filter Sections
Draw-through Filters
A. Unit shall be provided with a draw-through filter
section. The filter section shall be supplied complete
with the filter rack as an integral part of the unit. The
draw-through filter section shall be provided with
[panel] [cartridge] filters.
B. 2" thick AmericanAirFilter [30% efficient, MERV 8]
[85% efficient, MERV 13] pleated panel filters shall
be provided. Filters shall be frame mounted and
shall slide into galvanized steel racks contained
within the unit. Filters shall be installed in an angular
arrangement to maximize filter area and minimize
filter face velocity. Filters shall be accessible from
both sides of the filter section.
C. [12" deep [60-65%] [90-95%] efficient, UL Std. 900,
Class 1, AmericanAirFilter cartridge filters shall be
provided. 2" panel, 30% efficient pre-filters shall
be included. Cartridge filters shall consist of filter
media permanently attached to a metal frame and
shall slide into a gasketed, extruded aluminum rack
contained within the unit. The filter rack shall have
secondary gasketed, hinged end panels to insure
proper sealing. Filters shall be accessible from both
sides of the filter section.]
D. [[30% efficient pleated] [60-65% efficient cartridge]
[90-95% efficient cartridge] filters shall be provided
with INTERSEPT antimicrobial treatment.]
www.DaikinApplied.com 113
Additional Sections
A. [No additiopnal sections are required.]
B. [A blank heat section shall be installed [downstream]
[upstream] [and upstream] of the supply air fan.]
C. [The unit shall be provided with factory installed
access sections located [upstream] [downstream]
[upstream and downstream] of the supply air fan.
Access sections shall have hinged access doors on
both sides of the section and shall have the same
construction features as the rest of the unit.]
D. [A supply air discharge plenum shall be provided.
The plenum section shall have a [bottom] [side]
[front] discharge opening.
Roof Curb
A. [No roof curb is required.]
B. [The installing contractor shall provide the roof curb.]
C. [The manufacturer shall provide a prefabricated
12-gauge galvanized steel, mounting curb, designed
and manufactured by the unit manufacturer, shall be
provided for field assembly on the roof decking prior
to unit shipment.]
1. The roof curb shall be a full perimeter type with
complete perimeter support of the air handling
unit. The curb shall be a minimum of 16" high and
include a nominal 2" x 4" wood nailing strip.
2. Gasket shall be provided for field mounting
between the unit base and roof curb.
General
A. Furnish and install, as shown on plans, Daikin
RoofPak Applied Rooftop Air Handling Unit(s) model
RDS 800C, 802C, 047C or 077C. Unit performance
and electrical characteristics shall be per the job
schedule.
B. Each unit shall be specifically designed for outdoor
rooftop application and include a weatherproof
cabinet. Units shall be of a modular design to
provide maximum design flexibility. Each unit shall
be [completely factory assembled and shipped in
one piece.] [shipped in multiple sections to facilitate
job site rigging] and configured as shown on the
drawings.
C. All units shall have decals and tags to indicate
caution areas and aid unit service. Unit nameplates
shall be fixed to the main control panel door.
Electrical wiring diagrams shall be attached to
the control panels. Installation, operating and
maintenance bulletins and start-up forms shall be
supplied with each unit.
D. The unit shall undergo a complete factory run test
prior to shipment. The factory test shall include final
balancing of the supply [and return] fan assemblies,
and a final unit inspection. [The following is also
required.]
1. [a unit electrical [and control] system operations
checkout]
2. [test and adjustment of the gas furnace]
E. The complete unit(s) shall be ETL and ETL-Canada
listed by Intertek Testing Services, Inc. Units shall
conform to International standard ANSI/UL Standard
1995/CSA Standard C22.2 No. 236. Unit(s) shall
be accepted for use in the City of New York by the
Department of Building, MEA #368-93-E Vol. II.
F. The furnace shall be ETL Canada/ [FM [IRI]
approved.
G. Unit supply fan and coil performance shall be ARI
certified.
www.DaikinApplied.com 115
Fan Sections
A. All fan assemblies shall be statically and dynamically
balanced at the factory, including a final trim balance
prior to shipment.
B. All fan assemblies shall employ solid steel fan
shafts. Heavy-duty pillow block type, self-aligning,
grease lubricated ball bearings shall be used.
Bearings shall be sized to provide an L-50 life at
200,000 hours.
C. The entire fan assembly shall be isolated from the
fan bulkhead and mounted on [rubber-in-shear
isolators] [spring isolators] [spring isolators with
seismic restraints].
D. [Fixed] [Adjustable] pitch V-belt drives with matching
belts shall be provided. V-belt drives shall be
selected at [the manufacturer's standard service
factor] [1.5 times fan brake horsepower].
E. Fan motors shall be heavy-duty 1800 rpm [open
drip-proof (ODP)] [totally enclosed TEFC] type
with grease-lubricated ball bearings. [Motors shall
be high efficiency and meet applicable EPACT
requirements.] [Motors shall be premium efficiency.]
Motors shall be mounted on an adjustable base
that provides for proper alignment and belt tension
adjustment.
www.DaikinApplied.com 117
Electrical
A. Unit wiring shall comply with NEC requirements
and with all applicable UL standards. All electrical
components shall be UL recognized where
applicable. All wiring and electrical components
provided with unit shall be number and color coded
and labeled according to the electrical diagram
provided for easy identification.
1. The unit shall be provided with a factory wired
weatherproof control panel. Unit shall have a
[single] [dual] point power terminal block for main
power connection. A terminal board shall be
provided for low voltage control wiring.
2. Branch short circuit protection, 115-volt control
circuit transformer and fuse, system switches,
high temperature sensor, [and a 115-volt
receptacle with a separate electrical connection
shall also be provided with unit]. [A factory
installed and wired 115 volt power supply shall
be provided for the GFI receptacle. The power
supply shall be wired to the line side of the
disconnect so the receptacle is powered when
the main unit disconnect is off. This option
shall include a weather proof transformer and
disconnect for the 115 volt GFI. The 115 volt GFI
electrical circuit shall complete with primary fused
short circuit protection.]
3. Supply and return fan motors shall have
contactors and external overload protection.
Knockouts shall be provided in the bottom of the
main control panels for field wiring entrance. All
115600 voltage wire shall be protected from
damage by raceways or conduit.
Coil Sections
A. [No coil sections are required.]
B. The coil section shall include hinged access doors
on both sides of the section. The doors also provide
access for [field installed control valves] [factoryinstalled control valves.
C. Cooling coil sections shall include [painted
galvanized] [stainless] steel, positively sloped drain
pan shall be provided.
1. The drain pan shall have a minimum slope of 1/8"
per foot to provide positive draining.
2. The drain pan shall extend beyond the leaving
side of the coil and underneath the cooling coil
connections.
3. The drain pan shall be connected to a threaded
drain connection extending through the unit base.
D. The coil section shall be located as follows.
1. [draw-through configuration]
2. [blow-through configuration including a diffuser
and sufficient space between the fan and coil to
allow even air flow across the coil.]
3. [Cooling coils shall be mounted in the blowthrough position to minimize leaving air
temperature from the unit, and maximize sensible
heat ratio, after motor heat is considered. A
draw-through alternative must meet the required
unit leaving air temperature after fan and fan
motor heat is added to the scheduled, cooling
coil, leaving air temperature. The submittal must
clearly show cooling coil leaving air temperature,
fan and fan motor heat temperature rise, and unit
leaving air temperature.]
E. Field piping must be able to enter through the floor
of the unit. [A field assembled, piping vestibule shall
be provided.]
1. [Coils can be removed through the access doors,
RDS 800802 only.]
2. Any coil piping vestibule shall be 16" deep and
include sufficient space to allow piping access
to the heating coil and be shipped loose and
knocked down for field assembly. The vestibule
shall be constructed of the same materials as the
unit casing.
Heat Sections
A. [No heat is required.]
B. [Steam or hot water heat is specified above.]
C. [Electric heat is required.]
1. Staged electric heating coils shall be factory
installed in the unit heat section. Heating coils
shall be constructed of a low watt density,
high nickel-chromium alloy resistance wire,
mechanically stacked and heli-arc welded to
corrosion resistant terminals.
2. A corrosion resistant heavy gauge rack shall
support the elements.
3. Safety controls shall include automatic reset high
limit control for each heater element with manual
reset backup line break protection in each heater
element branch circuit (Note: Manual reset not
provided when ETL-Canada label is provided).
4. Heating element branch circuits shall be
individually fused to maximum of 48 Amps per
NEC requirements. The electric heat section shall
be positioned downstream of the supply air fan.
5. [The electric heat elements shall be controlled by
the factory-installed main unit control system]
www.DaikinApplied.com 119
8. [The gas burner shall be controlled by the factoryinstalled main unit control system]
9. The burner shall be fired, tested and adjusted at
the factory. Final adjustments shall be made in
the field at initial start-up by a qualified service
technician to verify that installation and operation
of the burner is according to specifications.
Filter Sections
Draw-through Filters
A. Unit shall be provided with a draw-through filter
section. The filter section shall be supplied complete
with the filter rack as an integral part of the unit. The
draw-through filter section shall be provided with
[panel] [cartridge] filters.
B. 2" thick AmericanAirFilter [30% efficient, MERV 8]
[85% efficient, MERV 13] pleated panel filters shall
be provided. Filters shall be frame mounted and
shall slide into galvanized steel racks contained
within the unit. Filters shall be installed in an angular
arrangement to maximize filter area and minimize
filter face velocity. Filters shall be accessible from
both sides of the filter section.
C. [12" deep [60-65%] [90-95%] efficient, UL Std. 900,
Class 1, AmericanAirFilter cartridge filters shall be
provided. 2" panel, 30% MERV 8 efficient pre-filters
shall be included. Cartridge filters shall consist of
filter media permanently attached to a metal frame
and shall slide into a gasketed, extruded aluminum
rack contained within the unit. The filter rack shall
have secondary gasketed, hinged end panels to
insure proper sealing. Filters shall be accessible
from both sides of the filter section.]
D. [[30% efficient pleated] [60-65% efficient cartridge]
[90-95% efficient cartridge] filters shall be provided
with INTERSEPT antimicrobial treatment.]
www.DaikinApplied.com 121
Additional Sections
63
125
250
500
7dB
9dB
ILR w/ mylar
6dB
Octave band
63
125
7dB
9dB
ILR w/ mylar
6dB
500
www.DaikinApplied.com 123
Roof Curb
A. [No roof curb is required.]
B. [Roof curb is to be supplied by the installing
contractor.]
C. [The rooftop manufacturer shall supply a
prefabricated 12-gauge galvanized steel, mounting
curb, designed and manufactured by the unit
manufacturer, shall be provided for field assembly
on the roof decking prior to unit shipment.]
1. The roof curb shall be a full perimeter type with
complete perimeter support of the air handling
unit. The curb shall be a minimum of 16" high and
include a nominal 2" 4" wood nailing strip.
2. Gasket shall be provided for field mounting
between the unit base and roof curb.
Controls
A. Each unit shall be equipped with a complete
MicroTech III microprocessor based control system.
The unit control system shall include all required
temperature and pressure sensors, input/output
boards, main microprocessor and operator interface.
The unit control system shall perform all unit control
functions including scheduling,], unit diagnostics and
safeties. Control sequences shall include [constant
air volume, zone temperature control (CAV-ZTC)]
[constant air volume, discharge temperature control
(CAV-DTC)] [variable air volume, cooling only
discharge temperature control (VAV-DTC)] [variable
air volume, cooling/modulating heating discharge
temperature control (VAV-DTC)] [duct static pressure
control], [supply/return air fan tracking control] and
[building static pressure control. All boards shall
be individually replaceable for ease of service. All
microprocessors, boards, and sensors shall be
factory mounted, wired and tested.
B. The microprocessor shall be a stand-alone DDC
controller not dependent on communications with
any on-site or remote PC or master control panel.
The microprocessor shall maintain existing set
points and operate stand alone if the unit loses
either direct connect or network communications.
The microprocessor memory shall be protected
from voltage fluctuations as well as any extended
power failures. All factory and user set schedules
and control points shall be maintained in nonvolatile
memory. No settings shall be lost, even during
extended power shutdowns.
C. An optional [BACnet IP] [BACnet MS/TP]
[LonWorks] communication module shall be
provided for direct interface to the BAS network.
D. All digital inputs and outputs shall be protected
against damage from transients or wrong voltages.
The status of each input and output can be read on
the display. All field wiring shall be terminated at a
separate, clearly marked terminal strip.
E. The microprocessor memory shall be protected
from all voltage fluctuations as well as any extended
power failures. The microprocessor shall maintain
existing set points and operate stand alone if the
rooftop loses either direct connect or network
communications.
F. The microprocessor shall have a built-in time
schedule. The schedule shall be programmable from
the unit keypad interface. The schedule shall be
maintained in nonvolatile memory to insure that it is
not lost during a power failure. There shall be one
start/stop per day and a separate holiday schedule.
The controller shall accept up to ten holidays each
with up to a 5-day duration. Each unit shall also
have the ability to accept a time schedule via BAS
network communications.
Part 3: Execution
3.01 Installation
A. Install in accordance with manufacturers
instructions.
www.DaikinApplied.com 125