Manual On Boiler Tube Failure
Manual On Boiler Tube Failure
Manual On Boiler Tube Failure
INTRODUCTION
A countrys production of electricity is a basic indicator of its size & level of
developments. Although a few countries export electric power, mostly generation
is for domestic consumption.
In 1983 the first electric supply undertaking was established in India by a
company, which constructed a small generating station in the city of Surat in
Gujrat. This was perhaps one of the earliest electric supply companies anywhere in
the world. This undertaking got as far as lighting the main streets of the city by arc
lamps, but unfortunately in the next year disastrous floods of the river Tapi
submerged its generating plant. In the year 1896 an undertaking started operation
at Calcutta. Thus the beginning of electric supply industry in India was mainly due
to private company effort.
According to reports (1998)
The total installed capacity
89,166.87MW
Thermal power
55,969.48MW = 62.76%
Hydro
21,891.08MW = 24.55%
Nuclear
2,225.00MW = 2.49%
9,081.31MW = 10.18%
100%
called utilization factor). In India the average utilization factor is about 46% .So as
such there exists a room for improving the availability. This would probably off
set the gap in present demand & supply more economically.
The forced shut down of a boiler due to failure of components severely
affects the progress through non-availability of power which is the basic need for
growth in national economy. Some of the outages are due to tube failures in
pressure parts most of which can be minimized by proper care and preventive steps
of its causes.
The actual cost of repairing failed tubes is less than the cost of generation
loss due to outage, so it becomes imperative to repair & bring the unit quickly into
service. Also, it is equally important to identify the cause of failure so as to take
corrective action and preventive measures so that the failure does not recur. Tube
failure is most significant causes of bringing down the plant availability in utility
fossil-fired boilers. Shutdown of a 200MW unit on account of tube failure will
cause a loss of several lakhs rupees, even when the shutdown is only for three
days. Further, during outage of boiler, if the secondary damages due to the tube
failure is not detected additional failure during start up or afterwards can occur,
thus prolonging shutdown & increasing the generation loss.
1. Forced / unplanned / planned outages in power plant amount to 15%.
2. Forced / unplanned / planned outages resulting out of boiler are 60% or more of
the above (1).
3. Outages due to boiler tube leakage are 75% or more of the above (2).
Water Walls
Almost all-modern power boilers are equipped with water walls. In large
boilers water walls completely occur in the interior surface of the furnace
providing practically complete elimination of exposed refractory surface. Water
walls serve as means of heating and evaporating the feed water supplied to the
boiler from economiser. Water walls usually consist of large number of vertical
tubes arranged tangentially or approximately. They are connected at the top and
bottom of headers. These tubes receive water from the boiler drum by means of
down comers connected between drum and water wall lower header. In boiler the
water walls absorb approximately 50% of heat released by combustion of fuel in
the furnace. Heat so absorbed is used in evaporation of all or a relatively large
percentage of water supplied to the boiler. The mixture of steam and water is
discharged from top of water wall tubes into the upper wall header and then passes
through riser tubes to the steam drum.
b)
Super- Heaters
SH are meant to raise the steam temperature above the saturation
temperature by absorbing heat from flue gas. By increasing the temperature of the
medium (steam) the useful energy that can be recovered increases thus efficiency
of the cycle is improved. So in modern Boilers SH are widely used to increase
cycle efficiency economically. The maximum temperature to which steam can be
heated is dictated by the metallurgy & economy in initial cost and maintenance
cost. Present trend is to limit the steam temperature value to 540 oC both in SH as
well as reheater. SH also eliminates the formation of condensate during
transporting of steam in pipelines and inside the early stages of turbines, which is
harmful to the turbine blades and pipelines.
Water Walls
Reheater
RH is used to raise the temperature of cold steam from which, part of the
energy has been extracted in H.P.T. This is another method of increasing the
cycle. The efficiency increases with number of stages of reheating. Reheating
requires additional equipment (i.e.) heating surface, boiler turbine connecting
piping, safety equipment like safety valve, NRV, isolating valve, steam temperature
regulating equipment , instruments etc. Because of these additional investment,
complexity in operation and reduced availability of such system offsets the gain in
efficiency of the system gets minimised. Hence single RH can be economically
applied only for capacity above 100 MW & two RH for capacity above 500MW.
The limit is also dictated by the predicted fuel price over the period of operation.
Types of SH & RH
These heating surfaces can be classified into convection and radiant type
according to heat transfer process.
Even though the surfaces get heat by both radiation and convection, the ratio
between them varies according to the location and temperature of flue gases at that
location. The Reheater and SH placed above furnace which can view the flame is
called Radiant type .The other surfaces are called as convection type. Radiant
surfaces are located at high temperature region.
They are widely pitched to reduce the velocity of gas and bridging the
surface by the ash . They are arranged inline with least longitudinal pitch. They are
called platen SH. The SH and RH can be arranged either horizontally or allowed to
hung vertically. The vertical arrangements are simpler in supporting and allows for
expansion . This arrangement is pendent type. Horizontal SH needs supporting of
tubes at multi points to avoid sagging . Expansion movement should also be
permitted with advantage of draining.
The SH which is placed at lower flue gas temperature region is called as
Low Temperature Super heater (LTSH). The SH & RH can also arranged as ceiling
or wall and they are termed as ceiling superheater or wall SH etc. accordingly.
Arrangements of SH and RH
Generally the heating surface can be arranged in line or staggered. Staggered
arrangement requires fewer surfaces for the same duty but draft loss will be more.
Also on load cleaning of surfaces, will not be effective. Hence In line or staggered
arrangement is selected based on fuel fouling characteristic, operating cost of draft
loss and cost of tube material used at location.
The surface can be designed to place in such way that the flow direction of
flue gas and steam is in line parallel or opposite. Counter flow arrangement has
advantages of minimum surface area requirement but the metal temperature at the
leaving section is high compared to parallel flow. Counter flow arrangement is
used in most cases except in final section where the metal temperature limitations
call for parallel flow.
Economiser
The function of an economiser in a steam-generating unit is to absorb heat
from the flue gases & add this as sensible heat to the feed water before the water
enters the evaporative circuit of the boiler.
Earlier the economisers were introduced mainly to recover the heat available
in flue gas that leaves the boiler. Provision of this additional heating surface
increased the efficiency of steam generation, thus saving in fuel consumption. So
the name economiser was christened. In the modern boiler (used for power
generation) feed water heaters are used to increased the efficiency of the unit &
feed water temperature. So the relative size of economiser is less than earlier unit.
This is a good proposition as the heat available in boiler exit flue gas can be
economically recovered using air heater, which is essential, for pulverized fuel
fired boiler.
Location & Arrangements
It is usual to locate economiser ahead of Air Heaters & following the
primary SH or RH in the gas stream. Hence it will generally be contained in the
same casing as the primary SH or RH tubes.
Counter flow arrangement is normally selected so that heating surface
requirement is kept minimum for the same temperature drop in the flue gas.
Economiser coils are designed for horizontal placement, which facilitate draining
of the coil & favours the arrangement in the second pass of boiler. Water flow is
from bottom to top so that any steam formed during heat transfer can move along
with water & prevent the lock up steam, which will cause overheating, & failure of
economizer tube.
steel, giving rise to extensive porosity. All cast ingots contains a small proportion
of cavities but these have little significance & are welded up by a pressure welding
process during rolling or forging. It is necessary to remove most of the gases whilst
the steel is still molten.
Effects of Alloying
The effects of alloying elements are numerous. a list of a few of the more
important effects is given below.
1) To alter the transformation temperatures and time.
2) To modify the room temperature & Elevated temperature strength of given
structures by
a) Stiffening the crystals.
b) Introducing complex precipitates, which tend to harden the steel.
3) To modify the type of oxide film formed on the surface of the steel & there by
affects its corrosion resistance.
Alloying elements can be broadly classified into two groups
a) Austenite Stabilizers: Which have the effects of extending the temperature
range over which austenite is formed. Such elements are carbon, manganese,
nickel, copper & cobalt.
b) Ferrite Stabilizers: Which have the effect of extending the temperature range
over which alpha & delta ferrite are formed. This consequently reduces
temperature range over which austentile is formed. Such elements are Silicon
Chromium, Molybdenum, Tungsten, and Titanium & Niobium.
Some of these elements for example chromium, molybdenum & vanadium
also form carbides, which replace or modify the iron carbide in the structure.
Additions of the austenite stablising elements reduce temperature at which
the austenite to ferrite change occurs and will consequently facilitate the formation
of martensite with slower rates of cooling that are necessary with plain carbon
steels. This also means that for a given cooling rate, larger cross- sections can be
fully hardened uniformly throughout their section.
A) Chromium
Chromium, although in itself a ferrite & carbide former, has a side effect of
making the structural changes very sluggish. This suppresses the austenite to ferrite
change in heat treatment easily . It is therefore extensively used in steels to be
hardened & tempered. A further important property of chromium particularly
marked when present in quantities above about 5% is to improve resistance to
corrosion & oxidation.
Resistance to corrosion & oxidation of steel depends on the film of oxide
formed on its surface . In carbon & many low alloy steels, this oxide film offers
little or no resistance to atmospheric corrosion. At elevated temperature i.e. upto
575 degree C these steels have good resistance to oxidation in air or flue gases but
above this, the rate of oxidation increase rapidly. The presence of chromium,
however, in excesses of about 5% promotes the formation of a more protective
oxide film . Although 5% is insufficient to obtain useful resistance to atmospheric
& aqueous corrosion, it is enough to improve the oxidation resistance up to about
600c. Further increasing the chromium content produces a more resistant oxide
film & at 13% satisfactory resistance to mild corrosion media such as wet steam is
achieved. Application of this type of steel is steam turbine blades, propeller &
pump shafts, impellers & water turbine runners. Increasing the chromium content
above 13% produces improved resistance to more corrosive media & at 28%
chromium, satisfactory oxidation resistance at 1100 degree C can be obtained.
B) Nickel
In order to be able to utilize the good corrosion resisting properties of
these high chromium steels and at the same time attain satisfactory engineering
C) Carbon
Carbon is not generally regarded as an alloying element because steel
would not be steel without carbon. Nevertheless, it is appropriate in a discussion of
alloying elements to note the specific effects of carbon on the properties of steel.
In general, an increase in carbon content produces higher ultimate strength
and hardness but lowers ductility and toughness of steel alloys. The curves in
figure indicate the general effect of carbon on the mechanical properties of hot
rolled carbon steel.
Carbon also increases air hardening tendencies and weld hardness,
especially in the presence of chromium in low alloy steel for high temperature
applications. The carbon content is usually restricted to a maximum of about
0.15% in order to assure optimum ductility for welding, expanding, and bending
operations. To minimize intergranular corrosion caused by carbide precipitation,
the carbon content of austenitic (18-8 type) alloys is limited in commercial
specification to a maximum of 0.08%, or even less, i.e. 0.03% in the extremely
low- carbon grades used in certain corrosion- resistant applications.
In plain carbon steels in the normalised condition, the resistance to creep at
temperature below 440C appears to increase with carbon content upto 0.4%
carbon. At higher temperature there is but little variation of creep properties with
carbon content.
An increase in carbon content lessens the thermal and electrical
conductivities of steel and increases its hardness on quenching.
C) Silicon
Silicon contributes greatly to the production of sound steel because of its
deoxidizing and degasifying properties. When added in amounts up to 2.5%, the
ultimate strength of the steel is increased without loss in ductility. Silicon in excess
of 2.5% causes brittleness, and amounts higher than 5% make the steel
nonmalleable.
Resistance to oxidation and surface stability of steel is increased by the
addition of silicon. These desirable effects partially compensate for the tendency of
silicon to lower the creep properties of steel. Silicon increases the electrical
resistivity of steel and decreases hysteresis losses. Silicon steels are, therefore,
widely used in electrical apparatus.
E) Manganese
Manganese is an excellent deoxidizer and sulfur neutralizer, and improves
the mechanical properties of steel, notably the ratio of yield strength to tensile
strength at normal temperatures. As an alloying element, manganese serves as an
inexpensive means of preventing red shortness (brittleness, now more commonly
known as hot shortness). It improves rolling properties, hardenability, and
resistance to wear. However, manganese increases the crack sensitivity of
weldments particularly with steels of higher carbon content.
Unlike silicon, manganese benefits the creep properties of steel. It does not
appear to have any specific influence on the resistance to oxidation or corrosion of
steel.
F) Titanium and Columbium (Niobium)
These are potent carbide-forming elements. Titanium is also a good
deoxidizer and denitrider. These elements are most effective in the chromiumnickel austenitic alloys (18-8 type) where they react more readily with carbon than
does chromium. This allows the chromium to remain in solid solution and in the
Chapter - 2
BOILER TUBE FAILURE MECHANISMS
Identification
1)
particular temperature. If the tube metal temperature increases beyond this point,
creep will occur and the tube will eventually fail by stress rupture.
Superheaters and reheaters can experience interruptions and/or reductions in
steam flow that can increase tube metal temperatures that lead to stress rupture
failures.
With ferritic steel, a "fish mouth" or longitudinal rupture, with a thin edge
fracture is most likely. With other tube materials, still other appearances are
possible. The causes for this type of failure are the following
(Fig. 2.3).
Abnormal coolant flow from a blockage in the tube
Blockage due to debris in the tube
Blockage due to scale in the tube
Blockage due to condensate in the tube following an incomplete boil out
Excessive combustion gas temperatures
High temperatures from over-firing during start-up.
2)
could have a thick-edged, "fish mouth", longitudinal crack. The area around the
fracture may have an alligator hide appearance, with significant oxide scale
penetration. The root causes for high temperature, longer term failure such as
these are the following
High heat flux into a section of the boiler that could have used a higher grade of
steel
Excessive hot gas flow through an area that is plugged
Excessive heat absorption from an adjacent lug, or other welded attachment
Partial pluggage from blockage or internal scale
3)
magnet, while the other does not. The weld crack will be circumferential at the
weld, over on the side that responds to the magnet; the ferritic side. The cause of
failure relate the stress of the two metals expanding differently
And the following
Stress from internal steam pressure
Stress from the vertical weight on the weld
Stress from the constraints of how the tube is supported or attached
Internal thermal gradients, which add up to the total stress. The higher the
value, the sooner the weld fails.
4.
Caustic
5.
affects generating tubes in sub critical boilers operating above 124.11 bar or 1800
psig. Lower pressure units can also experience hydrogen damage, but it becomes
more uncommon as the operating pressure is reduced.
Hydrogen damage will occur whenever acidic conditions exist in the boiler
Clean tubes are far less susceptible to hydrogen damage than heavily
deposited tubes. Certain types of adherent and nonporous deposits appear to
promote localized hydrogen attack more readily.
The failures remove a chunk of tube, almost like a window that has been
placed in the tube. The failure has a thick edge fracture that removes the heavy
deposit that lead to the failure. The failure's root cause is
(Fig. 2.5)
Boiler water chemistry that has turned acidic, rather than its normally caustic
level. Hydrogen damage will not occur under alkaline conditions.
In-leakage of condenser water which tends to be acidic
Contamination from a chemical cleaning procedure
Higher heat flux which helps to form the deposit in the first place. Note
that if the deposit is not there to begin with, the excursion to low pH by itself
will not cause hydrogen damage.
The dirtier the boiler water, the sooner failures could occur.
Hydrogen damage seldom causes any significant wastage of the tube wall,
making it difficult to detect using ultrasonic devices. Sometimes hardened dense
oxide plugs of magnetite dispersed with copper form directly over hydrogen
damaged areas.
6.
depending on how the stress is oriented. Typically the chemical attack is on the
inside of the tube and works its way out through the growing crack. Far less
commonly, the chemical attack exists on the outside (fire side) and works its way
inward. The root cause is the coupling of more than one factor working on the
same location
Contaminants can come from boiler steam drum carry over
containing flue gases can experience acid corrosion. Certain acidic salts (ferrous
sulfate for example) can hydrolyze in moist environment to produce low pH
conditions that will attack carbon steel.
Sulfur trioxide (SO3), present in the cooler flue gas areas, can react with
water vapour to produce sulfuric acid. If the temperature is below the dew point,
sulfuric acid condenses along metal surfaces and corrodes the metal.
Water
wall ductile rupture will go length wise down the tube. The surface of the tube will
typically have a hard dark slag deposit. The causes are
A zone of combustion where there is too little oxygen
High level of chloride or sulfides in the fuel being burned
10.
failure can form at the toe of the weld. This fracture is circumferential, running at
right angles to the weld. The root cause is
The vibration of the tube, caused by the steady flow of exhaust gases
Along with a lug location that induces a rigid point that will concentrate the
force into a short distance.
11.
laterally across the tube which results in a thick edge fracture. The fatigue is
caused by
Sudden cooling of the tube metal, either from within or externally
Rapid change in the feed water temperatures to the economiser, i.e.
maloperation of the pre-boiler system
12.
parallel surface cracks, however this time the corrosive environment adds to the
deterioration by forcing an oxide wedge into the cracks, further leveraging the
fracture. The thick edge fracture will be coated with an oxide layer. Pits can often
be found on the inside surface of the cracks. The causes have two key ingredients,
corrosion and stress
There is either induced stress from the way the tube connects to another
pressure part or, there is induced stress from the way the tube is tied to a
structural support,
There is residual stress left over from fabrication
Internal pits from dissolved oxygen or acidic corrosion from the pre-boiler
circuit aggravate the cracking process in the water cooled tubes.
External corrosion in steam cooled units aggravates the cyclic flexing where
the tube enters the header.
13.
When accumulations need to be removed with force, it is possible that tubes will
be gouged, or dented. This point of stress will be a weak link that eventually gives
way. Some of the most common causes are
Hammering on a tube or its supporting lug
Chiseling at fused material
Poking and vacuuming ash/dust/debris out of tight spaces
Aqua-blasting
14.
surface, but in time the chemical contamination will act on the most sensitive
locations and result in such mechanisms as hydrogen damage, stress corrosion
cracking, caustic corrosion, corrosion fatigue, etc. The causes are
Mal operation or mechanical malfunctions of the pre-boiler water treatment
system.
Insufficient neutralization of boiler wash chemicals prior to returning a unit
to service.
15.
if the defect is a flaw, the failure may appear as a fatigue failure. In either case,
the cause is Poor QA on the part of the manufacturer
Material fabrication
Storage
Installation
16.
internal scale build-up, and resultant corrosion, or corrosion fatigue failure. If the
defect is with the integrity of the weld itself, the failures often appear as a brittle
failure, where stress is concentrated in a small area. Causes again relate to quality
control
The procedure
Weld material used
Preparation of the tube ends before the first pass
17.
Steam/Condensate Erosion
When a failure is allowed to continue for several hours or days, the result
can amount to more time and energy needed to make repairs. The root cause is
Decision making in how quickly a unit is brought off-line once a failure is
found
Insufficient documentation to justify the economics of not waiting to bring
the unit off-line to attend to the tube failure.
18.
possible failure modes, and some tubing problems do not necessarily reduce
availability by virtue of a tube failure, as in the example shown below. The
spalling of the indigenous oxide on superheater, reheater tubes and steam piping is
referred to as exfoliation. With exfoliation, the tube wastage is from the inside out,
and the damaged component is in the turbine's internals. The root cause is not
known, however, consider the following
Bottling-up of stream in the tube when the unit trips, resulting in forced
migration of steam into the black oxide scale layer within the tube.
Difference in the coefficient in expansion between the internal magnetite
layer and the tube metal, resulting in spalling of scale when the unit cycles
Quenching of the tube internals when the unit is in a start-up mode.
Chapter 3
ii)
iii)
iv)
v)
Deficiencies in maintenance.
Stages of an analysis
Although the sequence is subject to variation depending on the nature of specific
boiler tube failures, the principal stages that comprise the investigation and
analysis of a failure are as follows:
i)
ii)
iii)
Non-destructive inspection
iv)
v)
'thick-lip' rupture. There was a tightly adhering 'black-scale' on the outer surface of
the tube. Boiler quality carbon steel, conforming to the specification B.S. 36021962 grade Hot Finished Seamless 27, was used as the material of construction
for the economiser tube.
Metrological measurement of the tube had established considerable amount
of 'thinning and bulging" out of the wall of the subject tube.
Microstructural examination of the specimen selected judiciously from the
extreme edge of the rupture covering the external surface revealed "inter
crystalline penetration of oxide scales (oxide-rooting) to an appreciable depth
from the external surface of the tube (Fig. 2).
It also exhibited considerable decarborization of the material, Microstructure
in and around the rupture area of the tube represented globular carbides indicating
"spherodization" of the carbide constitute of pearlite within and at the boundary of
the ferrite grains (Fig. 3). Further, the microstructure away from the ruptured zone
illustrated a ferrite-pearlite structure which is normal of this type of steel (Fig. 4).
In the present case, the economiser tube was placed horizontally. Sometimes
"Steam Blanket" preferentially might be formed inside the tube wall. This in turn,
might have deteriorated the heat transfer characteristics of the subject tube
material, and caused localized 'over heating'.
The tube had failed as a result of prolonged localized overheating. Due to
'overheating' and consequential 'oxidation' and spheroidization the material could
not withstand the working stress, and failure occurred. This type of failure can be
minimized by improving upon the tube layout design. The economiser tube may
be changed into a vertical position instead of horizontal as in the present case to
avoid possible formation of steam-blanket in the pipe wall.
For the
one of the pronounced ribs. There was no evidence of corrosion or fitting on the
bore of tube.
Microstructural analysis of the samples selected from the vicinity of crack
and away from it revealed almost identical structures, i.e. fine dispersion of alloy
carbides particles in a matrix of ferrite (Fig. 10). This illustrated that the tube was
not overheated as the microstructure was quite agreeable to this class of material as
developed in commercial production of the tubes.
To substantiate the case of failure, metrological measurements in regard to
the well thickness at different locations of the tube in the vicinity of crack and at its
sound portion as well as the roundness error on the inside diameter at the sound
portion were done. The observations showed heterogeneity in measured values.
The roundness error on the inside diameter of the round region of the cracked tube
was in the order of 0.60 mm. This is represented graphically in Fig.11.
Development of ribs on the bore surface of the tube during tube production
might have a contributory effect towards the failure of this nature during services.
In addition to above causes, leakages/ruptures of boiler tubes in the power plants
can occur due to (a) embrittlement arising out of hydrogen damage, (b) water side
corrosion by feed water, (d) fire side corrosion resulting from combustion of fossil
fuel, (d) abrasives erosion of superheater tubes results from impact by particles of
fly ash entrained in the flue gases, (e) stress corrosion cracking of the tubes where
feed or condensate can collect.
Remarks
The foregoing illustrations have discussed many causes related to failure. Many
failures in steam systems involve more than one failures process the so called
multiple mode failures. Certainly many types of failures were not discussed and
no attempt could be made to illustrate all the types of failures possible. The causes
that promote failures can indeed be many and complex and attempt has been made
to illustrate and discuss some of the more common failures and the related causes.
Usually the most spectacular or dramatic failures are carefully studied while
little emphasis is placed on the common failures. Many analyses of plant or
operational failures usually add upto high separational costs due to time loss
resulting from make-shift maintenance or repairs in order to continue operation.
Thus metallurgical analysis of such failures is all the more important.
Chapter - 4
In the present
chapter, based on experience, it has been tried to show how improper water
conditioning can cause tube failures.
NEED FOR WATER CONDITIONING
1. The main need is to protect the internals from corrosion which cause ultimate
failure. There are several types of corrosion possible, like
i)
Dissolved O2 pitting
ii)
Stress corrosion
iii)
Ductile corrosion
iv)
H2 embrittlement etc.
There are three zones, where same water is conditioned differently. They are
a) Feed System
b) Drum
c) Steam and Condensate
Particulars
PH
Cond.
Silica
PH
Cond.
Silica
7.0
0.5
Nil
Nil
7.0
0.5
Nil
Nil
Feed
8.8 9.0
Upto 4.0
Nil
Nil
8.9 9.0
Upto 2.5
Nil
Nil
Drum
9.5 9.9
Upto 100
Nil
9.3 9.5
Upto 25
Nil
Steam
8.8 9.0
Upto 4.0
Nil
0.02
8.9 9.0
Upto 2.5
Nil
0.02
Condensate
8.5-8.7
Upto4.0
Nil
Nil
8.5 8.7
Upto 2.5
Nil
Nil
Make up
Scale :
Type of
Dosing
Volatile
Chemical Dosed
Place of Dosing
Ultimate Effect
Ammonia
Morpholine
Cyclohexyl amine
Hydrazine hydrate
inhibited or treated
hydrazine
To increase pH
2.
Volatile
To scavange oxygen
&
To increase pH
3.
Nonvolatile
Tri-sodium Phosphate
Sodium Hydroxide
4.
Nonvolatile
Drum
To increase pH to
maintain residual
phosphate.
To decrease pH, to
maintain residual
phosphate
Possible Impurities
Hardness, Silica
Effect or Dosing
Very slow increase in pH
Rapid increase in conductivity.
Injection of silica in System/
Phosphate
Unstable pH condition
Increase in conductivity
Foaming action in drum,
Free sodium hydroxide in Steam
Normal Reaction
Simple addition
NH4OH + H2O NH4OH H2O
Hydrazine
Phosphate
Remarks on effect
Caustic corrosion
N2H4 + O2 = N2 + 2H2O
Effect
High pH &
Conductivity
(Dilution)
Oxygen Scavenging
2N2H4 = N2 + H2 + 2NH3
Hydrogen in steam
Stress corrosion
None
None
Caustic attack carry
over foaming causing
starvation
When we analyse the remarks on last column following points are raised on
tube failure:
a) Caustic attack
b) Hydrogen attack
Caustic Attack
Although the pH of the media is high and safe for most of the tubes, yet
excess of it may cause soap-bubble effect at a particular point leading to carryover
and or volatile caustic carryover from drum and improper distribution of heat flux
at any point due to the same.
The caustic attack due to sodium hydroxide is very much deteriorating than
due to ammonia. Whereas, excess of ammonia may give raise to a possible
formation of nitric acid as :
NH3 + 202 = HNO3 + H2O
The possibility is very less due to the presence of excess hydrazine hydrate,
which takes care of any oxygen available in the system.
The caustic attack due to the presence of excess sodium hydroxide is very
much harmful due to the phenomenon known as steam blanketing, resulting static
or slow moving slug of steam generation causing rupture in the tube due to
irregular heat transfer.
Hydrogen Attack
This is very serious, sometimes we find unnecessary increase in hydrogen
level in steam, this leads to corrosion as per per-oxide theory.
The H2 released combines immediately with free O2 to from hydrogen peroxide (H2O2). This reacts with Fe(OH)2 and forms Fe(OH)3.
2.
Corrosion products formed in the feed water system are kept within specified
limits;
3.
4.
Hydraulic test water, superheater fill water, and desuperheater spray water are
free of solids. It is preferable to use DM water for these operations.
2.
Drum internal and drum water level controls are maintained in good working
order.
3.
maintained. This oxide (magnetite Fe 3O4) is normal product that forms on steel
exposed to boiler water. It protects the surface from corrosion. The magnetite
coating is damaged most often by boiler water salt that becomes corrosive when
concentrated. Graph 1 show the relative corrosion rate of carbon steel as acid and
alkaline concentrations varies in the boiler water.
In the pH range from low acid to low-alkaline concentrations the oxides on
boiler tubes are fully protective. When the pH is excessively high or low, the
protective oxide is consumed by the corrosive action of the acid or alkaline salts in
the water.
sometimes will not remove them. Arbitrary replacement of tubes, in the general
areas where metal attack exists, becomes necessary. Generally, hydrogen damage
is difficult to detect using non-destructive means. Ultrasonic thickness checks may
pinpoint some damaged areas, but positive identification of all failure prone tube is
not possible.
HIGH-pH DAMAGE
Ductile failures caused by a gouging type of corrosion usually occur when
the concentration of hydroxide salts such as sodium hydroxide in the boiler water
is too high. Ultrasonic tube-wall thickness checks can detect tubes with metal loss.
Proper boiler water treatment can minimize further corrosion.
5. Consider a partial flow condensate polisher for cycling units. Its use together
with that of the pre-boiler systems recycles line, permits removal of both
erosion products and oxygen from the feed water during steam-generator startup operations.
Importance of Water Analysis
A comprehensive water analysis program should be maintained to assure
that feed water and boiler water chemistry are held within prescribed limits, and
conduct water tests as per programmed schedule, for pH, oxygen, silica, copper
and total iron, and total solids.
The gas side corrosion occurs in oil fired boilers.
High temperature
corrosion occurs due to the presence in oil of sodium and vanadium, the oxides of
which form flux with the protective oxide of the material, thereby causing further
attack on the material by the gas. This can be prevented by using low vanadium
content oil or by employing certain additives like MgO powder in the oil. The
MgO powder can be sprayed through a separate nozzle into the furnace or
magnesium wires can be burnt in the furnace. Low temperature or dew point
corrosion occurs in oil fired boilers in the air heaters or economizers if the flue gas
temperature approaches the dew point temperature. Sulphur in the oil transforms
to SO3 in the furnace and then to sulphuric acid with the water vapour in the flue
gas at low temperatures and causes corrosion. Low temperature corrosion can be
avoided by controlling the inlet temperature of the feed water to the economizer, or
counter flow existing in economizer with respect to gas is made as reversed or
parallel flow of water, which gets higher temperature at low temperature gas end
and helps preventing low temperature corrosion.
Minimizing Pitting of Boiler Tubes
Excessive dissolved oxygen in the boiler water and excessive temperature
during chemical cleaning can cause severe local attack pitting. Crevices, like those
overheating failures by insulating the tube from the cooling effect of the steam.
Such failures usually occur as creep blisters at the low spot in pendant surfaces.
But deposits also have caused failures on vertical tubes.
Occasionally, they
partially or totally block steam flow in a particular circuit. Solids carried by the
steam into the turbine also can be damaging.
Boiler manufacturers help limit solids carry over by paying considerable
attention to the design of drum components. To avoid solids contamination from
operational point of view three factors are of particular importance.
1.
2.
3.
The third and most important operating factor is to keep solids contained in
the boiler feed water from entering the superheater. Steam drum internals
reduce the mechanical carry over of moisture content upto 0.1%. Vapors
Sufficient care during rolling of tubes and correct material selection can
avoid failures due to such defects.
b)
c)
d)
e)
b)
c)
d)
e)
f)
g)
Frequency and method of cleaning water side and fire side surfaces of tubes.
-o0o-
REPAIR GUIDELINES
Introduction
All plant personnel should bear in mind the legal formalities involved in the
repair of boiler pressure parts. The responsible parties, before making repairs or
alterations of a pressure part, must notify the legally responsible inspection agency
and obtain approval before starting the work. The responsible inspection agency
may be the boiler insurance carrier or state or municipal inspection agency. In
some cases, it may be a federal agency. The responsible parties must follow this
procedure even though a pressure part fails during the manufacturer's warranty
period. The boiler manufacturer may recommend a repair procedure, but it must
be approved by the responsible inspection agency. Generally, the manufacturer's
recommendation will be accepted, but the inspection agency still has the legal
responsibility for approval.
Welding Repair or Low Carbon Steel Tubes
Cut out a damaged tube at least 50 mm (2') on each side of the defective
area. The minimum replacement tube length should be not less than 152 mm (6').
Do not use backing rings to weld any heat-absorbing tubes carrying water or a
mixture of steam and water. Without a backing ring, make the first pass of the
weld using gas tungsten arc or oxyacetylene. The weld passes may be completed
by either process, or by shielding metal arc. If access is difficult, use window
welds for repair work. The first pass of a window weld must be made by gas
tungsten arc of oxyacetylene (Fig. 1).
Fit-up of the weld joints is important. Although it is difficult to obtain
accurate cuts on furnace tubes, it is important to get the existing tube ends squared
and correctly chamfered and to cut the replacement tube to the correct length. Use
a tube-end scarfing tool when possible. Allow for shrink in welding. Remember
that the weld metal and parent metal are melted in the welding process and the
molten metal shrinks as it solidifies.
A butt weld in a tube will shorten the total length about 1.6 mm (1/16").
Use a clamp or guide lug to hold one end of the replacement tube in
alignment while the first weld is made.
Do not tack weld both ends of the replacement tube, particularly if the
existing tubes are rigidly supported.
As a general rule, first complete the weld at the lower end of the
replacement tube.
Do not start welding the upper end of the replacement tube until both the
replacement and existing tubes have cooled to ambient temperature.
Alloy Tube Repairs
If a damaged alloy tube must be replaced, it is always preferable to weld the
replacement tube to an existing tube end of the same alloy and the same wall
thickness.
material diagram and locate shop welds used to join the damaged length to tubes of
different material or different wall thickness. If at all possible, make the cuts to
remove the damaged tube at least 152 mm (6") from the shop weld, thus leaving a
"Safe end".
If necessary to cut out a shop weld joining tubes of different material and/or
wall thickness, pay special attention since all qualified but-welding procedures
require the two tube ends to have the same internal diameter (ID) as the weld root.
In some cases, the thicker wall tube may be bored to match the ID of the
thinner wall tube
But the thicker wall tube may be bored only if the strength of the tube, after
reducing the wall thickness, is at least equal to the strength of the thinner
wall tube at the same operating temperature.
A ferritic alloy tube must not be bored to match a thinner wall austenitic
alloy tube.
The only satisfactory method is to use a connector of austenitic alloy tube
having the same wall thickness as the ferritic alloy tube.
One end of the connector is bored to match the wall thickness of the existing
austenitic alloy tube.
Shrinkage in welding alloy tubes is similar to that for carbon steel tubes.
Allowance must be made for expansion from preheating which will close the root
gap slightly.
For shielded metal arc welding with a backing ring, it is essential that the root
gap opening be sufficient to assure full penetration and fusion with the backing
ring during the first pass.
For gas tungsten arc welding, a zero root gap opening is permitted.
There must be no pressure exerted between the two tubes.
It is advisable to allow enough clearance to avoid actual contact at the root
gap opening after the two tubes are preheated.
3.
As the heated area swells, the internal deposit cracks off and the tube metal
temperature returns to normal.
The process may be repeated several times before the blister ruptures.
Commonly, a large number of tubes are blistered and not noticed until one of
the blisters cracks open. To avoid a massive tube replacement job, particularly
where replacement tubes are not immediately available, work the blisters down to
the original tube radius. Follow these general guidelines :
Remove the damaged tube, then carefully cut away enough of the bar or fin
to allow chamfering the tube end for welding around the sides of the replacement
tube joint
After the tube welds are completed, weld the bar or fin to the replacement
tube.
If the gas between bar or fin is too great for easy bridging, insert a low
carbon steel welding rod for a fin is too great for easy bridging, insert a low
carbon steel welding rod for a filler.
The spaces in the bars or fins, at the tube joints, are built up with deposited
weld metal.
Be sure no cracks exist in the these deposits before making the final weld to
the tubes.
Chapter 5
3. Flame impingement
4. Secondary burning of fuel.
5. Other causes.
Choking with foreign materials
Foreign materials like mill scales, weld slag, sand, electrodes bits, rust products,
chips, small tools, nuts etc. Which collect at the bends or weld joints where the
internal cross section is restricted will cause choking of tubes. These materials
enter the tube during various stages of manufacture, shipping and / or erection.
Choking of tube with foreign materials will impede the flow fully or partially &
cause overheating.
Precautions can be taken to mitigate tube choking at various stages of
manufacture, shipping, storage & erection. By using TIG root welding for all
SH coils at shop & site, the problem of choking can be minimised by
eliminating the construction at the weld joints due to excessive weld penetration
to check the blocking of tube with foreign material an instrument called
contract flow meter (developed by CE research lab UK, & manufactured by
Land Pyrometers LTD, UK) can be used. This meter can be used during the
commissioning of new boiler to ensure that there is not blockage of & in the
case of operating boiler, it can be used during overheating.
Starvation due to improper circulation:Insufficient circulation in the water walls may lead to departure from onset of
nucleate boiling & may lead to overheating. Which in turn will result in tube
failures. Where the failure are traced to improper circulation, the same can be
improved in the region of water wall by providing additional downcorners /
spider tubes to the existing downcomers.
Starvation due to insufficient flow:Starvation can occurs in SH tubes due to an insufficient flow resulting in
overheating. This is generally observed in the binder tubes of the platen SH.
These binder coils have a number of bends & are longer in length than the other
coils in the platen. The flow through these binder coils is, therefore, inadequate.
The prolong overheating in such tubes results in creep failure.
Such failures can be avoided by replacing the long binder tubes with shorter
tubes, which in turn increases internal flow, & prevents overheating.
Overheating can also be avoided by allowing cooler steam through the wrapper
tubes of platen to better cooling of the tube materials.
The materials of the bottom portion of the outermost coils of platen can also be
replaced by stainless steel to enhance their life since the bottom most portion
faces direct radiation from the furnace.
Flame Impingement
Water wall failures occurs mostly near the burners. This is due to the flame
impingement from burners, which get distorted in service. To avoid such
failures new burner nozzles such as honeycomb types, which resist distortion,
are now used.
Additional peep holes can also be provided for better monitoring of the flame &
observation of the burner tip.
Arrangements could be made to supply mellowing air to bring down air
temperature wherever necessary so that the combustion front can be kept away
from the burner nozzles.
Secondary burning of fuel:In certain cases oil from the oil gun may flash on to the tubes & then burning
takes place which results in overheating the tubes. Even in coal fired boilers, the
unburnt fuel particles may catch fire at the top of the furnace or in the second
pass causing secondary combustion, explosion, or overheating of the tubes. This
can be avoided by proper control of the atomisation of oil, coal particle size &
the firing rate.
Excessive air
Excess air plays an important role in the heat absorption pattern of various
zones of the boiler. Too much of excess air leads to cooler furnace & higher
heat absorption rates in convective paths. Too little of excess air leads to higher
furnance temperature resulting in higher radiation, heat absorption & slagging
problems.
In oil fired boilers too much of excess air is favourable to the formation of SO3
due to the increased availability of O2 thereby promoting a higher rate of low
temp. corrosion. To avoid such failure O2 content in flue gases should be
measured periodically during operation & adjustments made to achieve design
values as closely as possible. Further, to avoid overheating the flue gas
temperature in different zones should be closely monitored & kept within the
design limits.
Internal Deposits
Inferior quality of feed water leads to internal deposits of salts & silica in the
water wall tube. This internal deposit will cause overheating of water wall
tubes leading to failure. To avoid this, the feed water of boiler water quality
should be maintained within the allowable limits as per the international
standards.
The carryover of salts by steam can cause deposits in the tubes with consequent
overheating & failure. To avoid this, the salts, content in the drum water should
be maintained as per the standard operation with high water levels in drum
could lead to carryover of water drops & dissolved solids leading to internal
tube deposits in SH tubes. These deposits hinder heat transfer & lead to increase
in metal temperature & consequent tube failure. Hence it is necessary to restrict
the drum WATER LEVEL TO THE prescribed limits under all operating
conditions.
Other causes
Mal-operation can sometimes leads to overheating & results in tube failure.
When high-pressure heaters are out of service, the convection SH O/L
temperature can shoot up leading to overheating of tubes. This can be avoided
by suitable control of the excess air & the boiler load. During hot restart if the
flow of auxiliary steam from the drum tap off point is high it will result in a
reduced flow through the SH which in turn will lead to overheating.
EROSION
Erosion is a second major cause of tube failure. The tube wall thickness gets
reduced due to erosion & when the thickness is not sufficient to withstand the
operating pressure and temperature of the tube, the tube will fail.
Erosion of SH & economiser tube may be due to following reasons
i)
ii)
-- 55.5 to 56.5%
Alumina
-- 27.3 to 27.9%
Unburnt carbon
-- 4.4 to 6.2%
FeO
-- 5.3 to 6.7%
Lime
-- 1.37 to 2.16%
Sulphates
-- 0.5 to 0.68%
The flue gas erosion in the horizontal SH & economiser can be prevented by
providing baffles. The flue gas erosion in the bands of the convection SH in the
horizontal pass can be prevented by increasing the height of refractory lining of the
ash hoppers in front of the coils.
Erosion due to steam or water
Whenever there is a tube failure the water or steam from the faulty tube
escapes in the form of a high velocity jet & when it impinges on the adjacent tube
they get eroded. If the boiler is not shutdown immediately after detection of the
failure & allowed operating for a protected period the damage due to steam or
water erosion will be considerable.
Additionally, sometimes leakage from the soot blowers or wall blowers
causes erosion of water wall, SH or economiser tubes. In some boiler, vertical bar
type soot blowers have caused tube failures in the horizontal SH & RH & to
overcome this the sort blowers should be moved from the ceiling to the sidewalls.
Corrosion
This can be mainly grouped into two types
1) External corrosion due to depositing of chemicals.
2) Internal corrosion taking place inside the tube due to impurities in steam and
water.
such that dew point problems already rarely encountered. Condensation problem
further down stream where lower temperature exists may corrode air heater,
precipitator, hoppers, fans, ducts & stacks. As the sulpher content is more in the
fuel oil & also as the flue gas temperature will be low during starting usually the
air preheaters will be experiencing the cold corrosion problems. To overcome this
problem, steam coiled Air preheater should be kept in service till flue gas
temperature rises above 300C.
Remedy
All the deposits, which cause corrosion of the above types, are easily soluble
in water & will be loose also. This deposit can be cleaned by normal operation of
soot blowers. When this method is not totally effective, water washing during
outage is recommended. It is very important to schedule water washing so that the
tube surfaces can be dried out immediately after cleaning, as otherwise corrosion
will occur. A good approach is to water just before returning a boiler to service. If
this is not possible, fire at a low rate until tubes are dry.
Design Improvements
In coal fired boilers most major corrosion problems are caused by coal ash
with in a specific temp. range certain coal produce liquid ash compounds that are
very corrosive to all conventional boiler materials. This temp. range normally
extend from about 1000F to 1200F essentially restricts attack to the SH & RH .
Engineers weigh carefully the four major factors that influence the severity
of coal ash corrosion viz. Ash properties, ash deposition rate, tube external
temperature, & tube chromium content, before finalizing the design of SH & RH
surfaces. If the high temp. Corrosion occurs inspite of design efforts, the option for
correcting the problems are limited; for example the following remedial measures
may be resorted to.
Hydrogen damage.
ii)
iii)
Corrosion fatigue.
iv)
Stress corrosion.
v)
Steam blanketting.
vi)
Oxidation.
vii) Pitting.
viii) Galvanic attack.
ix)
i)
Caustic embrittlement.
Hydrogen Damage
This induces brittle fracture & will occur beneath a relatively dense deposit
when boiler water pH is too low. The accepted thereby of this type of attacks is that
the hydrogen atoms are produced between the deposit and the tube surface. They in
turn react with cementite a hard brittle iron compound at the grain boundaries of
the tube material to form molecular methane gas, which removes carbon from
metal weakening it by creating fissures in its grain structure.
The pressure of the gas that is formed literally blows the material apart. This
damage is most common where condenser leakage occurs in units cooled by sea
water. Some metal loss may be caused by corrosion mechanism, but the tube
which failure would occur.
ii)
compounds usually strong alkalies, such as sodium hydroxide between the tube
walls & a relatively porous deposit. (60-90 % porosity compared to theoretically
dense magnetite). The term caustic gouging is sometimes used to describe this
form of corrosion, which is characterised by rapid attack & subsequent tube
failure.
iii)
Corrosion Fatigue
Material that undergoes cyclic strain may suffer fatigue failure. The strain
v)
Steam Blanketting: Steam blanketting phenomenon occurs in tubes, which are slightly inclined,
for example flow started slag screen tubes since the steam flow in some what
restricted resulting in obstruction for heat transfer. In such environment if the feed
water possesses caustic soda, it may give rise to general wasting of the crown of
the tube or the formation of grooves at the water line.
vi)
Oxidation
Oxidation of low alloy ferritic steels operating at temp. above about 450C
is a natural phenomenon in the boiler water side environment. All materials used in
high temp. SH & RH tubing are subjected to oxidation, although at different rates.
Problems arise when oxide scale on the tubes internal surface become so thick that
differential expansion between the oxide and the parent metal results in spalling of
the oxide from the metal surface a process called exfoliation. The loose flakes
are hard & brittle & generally range from the size of a match HEAD to that of a
quarter. Loose scale can clog tubes at bends causing their failure by overheating.
Pitting
This is mainly due to the difference in effective electrode potential between
adjacent areas of the metal surface. This can result due to the following reasons.
1. Differential heat treatment resulting in localised difference in stress
concentration.
2. Surface
irregularities
such
as
scratches
&
cuts
developing
during
manufacturing.
3. Different concentration in dissolved compounds. The effect of individual factor
depends upon their relative magnitude & most of them are independent.
Galvanic Attack
The corrosion of the less noble member of a pair of metal which are joined
together is called Galvanic corrosion or Dissimilar metal corrosion. The
effects of galvanic corrosion are often serious especially in sea water power station
as feed water conditions are conductive, since at temperature that occurs in the
high pressure boiler tubing, are very high Galvanic attack will be more severe in
these areas.
Caustic embrittlement
This is due to the caustic ALKALINITY formed in the drum & the scale of
this caustic soda reacts with the metal & may result in cracking at welding joints
where the welding is weak
Material Defects
Some of the tube failures in the boiler may be due to the usage of the
defective raw materials. Though different quality control measurement are adopted
in various stages of the manufacturing, defective materials may find there way in
rare cases and cause failure. High quality of the materials can be ensured by
selecting tubes, which have undergone ultrasonic tests, & by resorting to strict
quality control inspection procedure. Successful waterside corrosion control
requires careful selection of the material used throughout the steam cycle
including the feed water heaters & condensers.
Manufacturing defects
Tube failure may occur due to the defect in the manufacturing process, such
as weld defect, & improper heat treatment. Mix up of material sometimes lead to
failure because of the wrong usage of materials.
Creep and fatigue are very important factors while designing the thermal
power plant equipment. Metals undergoing high temperature will also be subject
both creep and fatigue.
Creep
When metal stressed at sufficiently high temperature it will continue to
deform with time although at a relatively low rate. This process is known as
creep and is of major importance in selecting metals for service in power plant.
This is because at temperature much above 350C (660F) steels are subjected to
this phenomenon. The figure illustrated that the creep process can be viewed in
three stages. The primary stage in which the initially high rate of strain remain
constant over a period of time, the second stage in which strain rate remain
constant over a period of time, and the tertiary stage in which strain rate increases
continuously and which culminates in rupture.
This behaviour may be explained in terms of a balance between the effect of
straining which are to be strengthen the material and increase its resistance to
further deformation and effect of heating which are to be soften the material and
decrease resistance to deformation. Thus strain hardening predominates initially
until the strain rate falls to level at which the opposing influence are in balance
accompanied by continuous deformation until the tertiary stage is reached, where
loss of strength leads to fracture.
Fatigue
Metals undergoing high temperature service may also be subjected to
fatigue. This process is one in which failure may arise exposer to many cycle of
alternating stress, with or without super imposition of mean stress. This type of
failure is comparatively rare in power plant. The predominant failure is creep not
fatigue.
The form of the stress cycle such as square, triangular or sinusoidal wave
has no effect on the fatigue life.
ii)
iii)
iv)
Stress gradient has strong effect on fatigue life. Higher stress gradient, lesser
is fatigue life.
v)
4. Then take the sample of tube of unfractured zone and fractured zone. Then with
the help of grinder, grind it to remove rust and scale & then polish it to get
scratch free surface. The polishing method is known as buffing.
For which Diamond paste & metsesfluid (lubricant) is used & after that
apply etching agent (nitol or picrol) for 30sec & then clean the surface by acetone.
Then watch the prepared sample under microscope.
Analysis to Find out Cause of Failure
The metallurgist can conclude the cause of failure by studying the
microstructure of the material of both, fractured & unfractured zone.
The normal microstructure of the material consist of ferrite & pearlite, with
the dispersed grain boundaries. In case of failure the microstructure of the material
changes & depending upon the change of microstructure, metallurgist can conclude
the cause of failure.
1. Corrosion
Due to corrosion the normal structure of the material which consists of
ferrite & pearlite will change from ferrite to ferritic & spheroidisition of carbides
occur along the grain boundaries.
2. Erosion
Due to erosion the normal structure will change from pearlite to pearritic &
spheroidisition of carbides occur along the grain boundaries.
3. Creeps
Due to creep the grain growth occurs along the boundaries which weakness
the material strength & due to which the voids are formed along the boundaries &
in case of prolonged period these voids combine & fracture takes place.
Remedial Measures
The corrosion in general is resulting due to the oxygen present in feed water
& the pH value of feed water. Oxygen may be carried over into boiler through
make up water leaks, etc. Even the minute quantity of O2 is capable of causing
sever corrosion in the boiler working at high pressure. Since the O2 content
carried over the steam will go on increasing as the pressure of the boiler increases.
The table below shows how the O2 content carried over to steam increases as
the pressure increases.
Boiler pressure kg/cm2
12.6
42
70
140