Substation Automation Products

MicroSCADA Pro SYS 600C


The compact system

Power automation with industrial design

The compact system, SYS 600C provides proven


MicroSCADA Pro functionality for real-time monitoring
and control of primary and secondary equipment. Robust
and compact, it offers an ideal solution for harsh and
demanding environments in both transmission and
distribution substations. Depend on it whenever real-time
process information as well as state-of-the-art monitoring
and control capabilities are crucial.
The MicroSCADA Pro SYS 600C does not contain moving or
otherwise vulnerable parts. With high scalability and modern
architecture, it is easy to adapt and expand: You can enjoy its
ease of use as a communication gateway, as a control system
HMI or communication server in both industrial and electrical
utility applications.
Pre-configured from the factory
The SYS 600C is delivered from the factory with tested and
pre-installed software, containing an order-specific configuration. With the help of the ready-to-use library of symbols and
control dialogs, the SYS 600C requires only minimal engineering before installation and commissioning. In addition,
copy and paste functions allow, for instance, easy system
extension. This way, the MicroSCADA Pro SYS 600C ensures
efficient engineering and system integration.
Right actions at the right time
The operator interface of the MicroSCADA Pro SYS 600C
enables you to easily and safely interact with the process, via
protection and control IEDs (intelligent electronic device), RTUs
or other types of sensors. As a result, your MicroSCADA Pro
SYS 600C will effectively help you take the right actions and
achieve the maximum power system availability.

The high availability can be further secured by using redundant SYS 600C computers, redundant power supplies, as
well as by the support for redundant communication.
IEC 61850 compliant
The MicroSCADA Pro SYS 600C is compliant with the
IEC 61850 standard for substation automation including
Edition 2. This means that it can operate together with
IEC 61850-compliant IEDs, tools and systems, which
simplifies system engineering. With IEC 61850 support, the
MicroSCADA Pro SYS 600C creates seamless communication
and connectivity opportunities for its users.
Seamless integration and connectivity
The MicroSCADA Pro SYS 600C ensures optimized control
and reliable operation of your switchyard through the seamless
integration and connectivity between different devices and systems. SYS 600C also supports an extensive range of standard
and de facto standard communication protocols and interfaces.
Cyber security
A large number of cyber security features contained in
MicroSCADA Pro SYS 600C protect systems from abuse
and vandalism. Features include, for example:
user authentication
flexible user authorization
session expiration
communication encryption
event logging
reporting
MicrosSCADA Pro-based systems can also be be equipped
with industry-standard malware and intrusion protection solu-

tions, like virus protection and application whitelisting. Cyber


security is considered during the whole lifecycle of products
starting from the requirements and development phases and
throughout the operation phase. New cyber security features
are designed to meet and exceed requirements from standards such as IEC 62351, IEEE 1686 and NERC-C.
Application areas
Communication Gateway
The MicroSCADA Pro SYS 600C provides a scalable communication gateway solution, including support for a hot standby
configuration. The communication gateway functionality
provides mapping of data and signals between the various substation equipment and upper level system. It features a wide
selection of communication protocols and interfaces and is
thus open for any master system (SCADA or DCS systems). It
further offers versatile connection to IEDs through both standard and de facto standard communication protocols.
Control system HMI
The MicroSCADA Pro SYS 600C is also designed to be used
as a complete control system HMI to enable smooth monitoring
and control of the connected process in both transmission and
distribution substations. One SYS 600C computer is capable
of accommodating both a full fledged control system HMI and
a communication gateway, including hot standby configuration.
Communication Server
In SCADA applications, MicroSCADA Pro SYS 600C offers
an excellent solid state front-end solution with support for
hot standby configuration. The large number of master
communication protocols enables easy connection to RTUs,
gateways and other process interface units.

Hardware characteristics

CPU

Intel Core 2 Duo 2.2 GHz

Memory

2GB DDR2 memory

Storage device

30/60 GB SSD

Expansion slot

3 x PCI v2.3 slots

Serial port

16 x RS232 serial ports at rear panel

LAN port

6 x Gigabit Ethernet (RJ45 or LC) at rear panel


1 x Gigabit Ethernet at front panel (RJ45)

USB

2 x USB 2.0 at rear panel


1 x USB 2.0 at front panel
1 x USB 2.0 internal

Power supply

88132 VAC/45160VDC
176264 VAC/200370 VDC option
Redundant power supply is optional
Alarm contact

Dimensions

3U height, 19 rack mountable


438W x 130H x 312D mm
(excluding rack mount accessories)

Temperature

Operating temperature -30C +65C (-22F 149F)


Maximum continuous CPU burden 50% of lowest/
highest operating temperature
Storage temperature -40C +75C (-40F 167 F)

Humidity

5% 95% (+40C) non-condensing

Protection class

IP40

SYS 600C EMI/EMS and environmental type test report

STANDARD COMPLIANCE

IEC61850-3

IEEE Std 1613-2003

Environmental

TYPE TEST

DESCRIPTION

SEVERITY LEVEL

IEC 61000-4-2-2001

Electrostatic discharge

Level 4 - 8KV contact/15KV Air

IEC 61000-4-3-2006

Radiated RF succeptibility

Level 3 -18V/m, 6 directions

IEC 61000-4-4-2004

Fast transient (burst immunity)

Level 4 - 4KV 5KHz power supply line/2KV


5KHz signal line

IEC 61000-4-5-2005

Surge immunity

Level 4 4KV line-to-earth/2KV line-to-line

IEC 61000-4-6-2006

Conducted RF immunity

Level 3 - 10Vrms

IEC 61000-4-8-2001

Magnetic field immunity

Level 5 - 100A/m 5min/1000A/m 1s

IEC 61000-4-10-1993

Damped magnetic immunity

Level 4 - 30A/m

IEC 61000-4-12-1995

Damped oscillatory burst

Level 3 - 2.5KV common/differential 1.25KV


for Substation

IEC 61000-4-16-2002

Conducted RF immunity

Level 3 - 15Hz ~ 150KHz

IEC 61000-4-29-2000

Voltage dips and interrupts

30% 120ms/ 70% 10ms 100% 3ms (cycle 3)

CISPR22-2008

Conducted and radiated


emissions

Class A

FCC 15

Conducted and radiated


emissions

Class A

EN55022A

Conducted and radiated


emissions

Class A

IEC 60255-5

Insulation resitance
measurement

500VDC, 1min, 999Mohm>100Mohm

IEC 60255-27

Protective bonding resistance

25Amps, 1min, 0.021ohm<0.1ohm

IEEE C37.90.1

EFT

Level 4 - 4KV 5KHz all ports

IEEE C37.90.3

ESD

Level 4 - 8KV contact/15KV air

IEEE C37.90.1

Oscillatory wave

Level 3 - 2.5KV common/differential 1.25KV


for substation

IEEE C37.90

Dielectric strength

2000Vrms

IEEE C37.90

Impulse voltage

5000V

IEC 60870-2-1-1995

DC voltage ranges

-20% ~ +15%

IEC 60870-2-1-1995

Voltage ripple of DC

Level VR3 - 5%

IEEE C37.90

Non-operational temperature
range

-40C ~ +75C

IEEE C37.90

Operational temperature range

-30C (start up)~+65C

IEC 60068-2-1

Cold temperature

-30C start up for 16 hours

IEC 60068-2-2

Dry heat temperature

+65C start up for 16 hours

IEC 60068-2-30

Humidity (damp heat, cyclic)

Test Db 6 cycles +25C/+55C 93%/95%


(1 cycle=24hrs)

IEC 60068-2-3

Humidity (damp heat, steady


state)

95% (non-condensing) 40C 2d

IEC 60870-2-2-1996

Vibration

10-200-500-200-10Hz(1g/1.5g) X/Y/Z axes

IEC 60870-2-2-1996

Shock

10g 11ms X/Y/Z axes

IEC 60068-2-29-1987

Bump (packed)

10g, repeat 1000 times X/Y/Z axes

IEC 60068-2-29-1987

Bump (unpacked)

10g, repeat 1000 times X/Y/Z axes

Application example

Main control center

Remote
access

Office access

SYS 600C
Redundant communication gateway
with integrated control system HMI

SYS 600C

SYS 600C

Communication gateway

Communication gateway

Communication gateway and


control system HMI
SYS 600C

SYS 600C

SYS 600C

Technology summary:
Power distribution monitoring
Process displays with network coloring, zooming, panning
and de-cluttering
Event, alarm and blocking lists
Trends
Extensive reporting facilities
- e.g. measurement, outage and energy reports
- availability statistics and indices, such as SAIFI (System average

interruption frequency index), CAIFI (Customer average interruption

frequency index), SAIDI (System average interruption duration

index) and CAIDI (Customer average interruption duration index)
Power-quality monitoring
Language support including several simultaneous operator-specific
languages
Uploading and analysis of disturbance record files
Setting of relay parameters
System platform and architecture
System supervision
High performance and availability
Process data mirroring for hierarchical systems
Redundant hot standby system capability
Remote workstations also web-based
Operating systems
- Windows Server 2008 R2 (64-bit)
- Windows 7 (32-bit)

Cyber security
To answer to requirements from IEC 62351, IEEE 1686, NERC-CIP
and more
User authentication, authorization and session expiration based
on roles
Event logging and reporting
Communication encryption such as DNP 3.0 Secure Authentication,
VPN
Malware and intrusion protection
Product hardening, patch management and incident-handling
processes
Communication and interfaces
Solution libraries for efficient integration with protection and control
IEDs
Master protocols: IEC 61850, IEC 60870-5-101/103/104,
IEC 61107, DNP 3.0 TCP/serial, Modbus TCP/RTU, LON, SPA,
ANSI X3.28, I35/P214, RP570/1, ADLP180, etc.
Slave protocols: IEC 60870-5-101/104, DNP 3.0 TCP/serial,
Modbus RTU, RP570/1, ADLP180, F4F, etc
Ethernet redundancy according to IEC 62439/PRP
Open interfaces: OPC, ODBC, Application programming interfaces
for application and communication extensions
GPS time synchronization

ABB Oy
Substation Automation Products
P.O. Box 699
FI-65101 VAASA, Finland
Tel. +358 10 22 11
www.abb.com/substationautomation

1MRS 756833 D Copyright 2012 ABB. All rights reserved. Imageneering 12/2012