ESR 1056 Titen Head
ESR 1056 Titen Head
ESR 1056 Titen Head
ESR-1056
Reissued March 1, 2012
This report is subject to renewal in two years.
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
1000
Copyright 2012
Page 1 of 6
Page 2 of 6
1.0
where:
Ps
Pt
Vs
Vt
4.0 INSTALLATION
4.1 General:
Titen HD screw anchors shall be installed by drilling a pilot
hole into the substrate using a handheld electro-pneumatic
rotary hammer drill with a carbide-tipped drill bit
conforming to ANSI B212.15-1994. The pilot hole shall
have the same diameter as the nominal diameter of the
anchor. The hole is drilled to the specified embedment
depth plus 1/2 inch (12.7 mm). Dust and debris in the hole
shall be removed by using oil-free compressed air. The
Titen HD screw anchor shall be installed into the hole to
the required embedment using a socket wrench or
powered impact wrench.
4.1.1 Installation in Fully Grouted CMU Masonry:
Anchors installed in the face of fully grouted CMU
construction shall be limited to the face shell of the CMU
unit (center web and grouted cores) and the horizontal
mortared bed joints, as indicated by the shaded areas in
Figure 2. Anchors installed in a T-joint, the mortared head
joint, or the end webs of a CMU unit, as indicated in the
non-shaded areas in Figure 2, are outside the scope of this
report.
For anchors installed in the top of fully grouted concrete
masonry (CMU grouted cores and CMU webs), anchor
location shall comply with the minimum edge and end
distances noted in Tables 4A and 4B and shown in Figure
3. Anchors installed in the mortared head joint are outside
the scope of this report.
4.2 Installation
Required):
with
Special
Inspection
(When
only.
Anchors
that
support
fire-resistance-rated
construction or gravity loadbearing structural
elements are within a fire-resistance-rated
envelope or a fire-resistance-rated membrane, are
protected by approved fire-resistance-rated
materials, or have been evaluated for resistance
to fire exposure in accordance with recognized
standards.
Anchors
are
used
to
support
nonstructural
elements.
5.7 Cracked Masonry: Since an ICC-ES acceptance
criteria for evaluating the performance of screw
anchors in cracked masonry is unavailable at this
time, the use of anchors is limited to installation in
uncracked masonry. Cracking occurs when ft > fr due
to service loads or deformations.
Page 3 of 6
Edge Distance
Spacing
Critical,
ccrit
Minimum,
cmin
Critical,
scrit
Minimum,
smin
Tension
Shear
2 /4
12
480
870
3 /2
12
690
1,385
4 /2
12
10
1,060
2,085
12
12
1,600
3,000
/8
/2
/8
/4
/8
/2
/8
/4
5 /2
For SI: 1 inch = 25.4 mm, 1 psi = 6.89 kPa, 1 lbf = 4.48 N.
1
Anchors shall be installed a minimum of 1 /4 inches from vertical head joints and T-joints. Refer to Figure 2 for permitted and prohibited anchor
installation locations.
2
The drill bit diameter shall be equal to the nominal diameter of the anchor. Anchor installation shall comply with Section 4.0 of this report.
3
Embedment depth is measured from the outside face of the masonry.
4
Critical and minimum edge distances, ccrit and cmin, respectively, shall comply with this table. Refer to Figure 2. Critical and minimum spacing, scrit
and smin, respectively, shall comply with this table. Critical and minimum edge and spacing distances are valid for anchors resisting tension or
shear loads. Refer to Table 2 for allowable tension and shear load reduction factors for anchors installed between critical and minimum edge
distances, and to Table 3 for anchors installed between critical and minimum spacing.
5
Tabulated loads are for anchors installed in fully grouted masonry wall construction, consisting of Grade N, Type II, lightweight, medium-weight,
or normal-weight, closed-end, concrete masonry units (CMUs) conforming to ASTM C 90. Masonry shall be fully grouted with coarse grout
having a minimum compressive strength of 2,000 psi, and complying with IBC Section 2103.12 (2009 and 2006 IBC) or 2103.10 (2003 and 2000
IBC) or IRC Section R609.1.1 as applicable. Mortar shall be Type M or S in compliance with IBC Section 2103.8 (2009 and 2006 IBC or 2103.7
(2003 and 2000 IBC) or IRC Section R607, as applicable. The specified compressive strength of masonry, fm, at 28 days shall be a minimum of
1,500 psi.
6
Tabulated allowable loads are based on a safety factor of 5.0 and are based on special inspection being provided during anchor installation.
Special inspection requirements shall comply with Section 4.2 of this report.
7
For wind or earthquake loading conditions, allowable loads may be adjusted in accordance with Section 5.3.
Page 4 of 6
TABLE 1BUBC ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW ANCHORS INSTALLED IN THE
1
FACE OF FULLY GROUTED CMU MASONRY CONSTRUCTION
ALLOWABLE LOADS BASED ON ANCHORS INSTALLED AT
DISTANCES CRITICAL EDGE DISTANCE, ccrit, AND
5,6,7
SPACING, scrit
(lbf)
Edge Distance
Spacing
Tension
Installed with
7
Special Inspection
Installed without
8
Special Inspection
Shear
2 /4
12
600
300
1,085
3 /2
12
860
430
1,730
4 /2
12
10
1,325
665
2,605
5 /2
12
12
2,000
1,000
3,750
/8
/2
/8
/4
/8
/2
/8
/4
For SI: 1 inch = 25.4 mm, 1 psi = 6.89 kPa, 1 lbf = 4.48 N.
1
Anchors shall be installed a minimum of 1 /4 inches from vertical head joints and T-joints. Refer to Figure 2 for permitted and prohibited anchor
installation locations.
2
The drill bit diameter shall be equal to the nominal diameter of the anchor. Anchor installation shall comply with Section 4.0 of this report.
3
Embedment depth is measured from the outside face of the masonry.
4
Critical and minimum edge distances, ccrit and cmin, respectively, shall comply with this table. Refer to Figure 2. Critical and minimum spacing,
scrit and smin, respectively, shall comply with this table. Critical and minimum edge and spacing distances are valid for anchors resisting tension or
shear loads. Refer to Table 2 for allowable tension and shear load reduction factors for anchors installed between critical and minimum edge
distances, and to Table 3 for anchors installed between critical and minimum spacing.
5
Tabulated loads are for anchors installed in fully grouted masonry wall construction, consisting of Grade N, Type II, lightweight, medium-weight,
or normal-weight, closed-end, concrete masonry units (CMUs) conforming to UBC Standard 21-4. Masonry shall be fully grouted with coarse
grout having a minimum compressive strength of 2,000 psi, and complying with UBC Section 2103.4. Mortar shall be Type M or S in compliance
with UBC Section 2103.3 and UBC Standard 21-15. The specified compressive strength of masonry, fm, at 28 days shall be a minimum of 1,500
psi.
6
For wind or earthquake loading conditions, allowable loads may be adjusted in accordance with Section 5.4.
7
These allowable tension loads are based on a factor of safety of 4.0 and special inspection being provided during anchor installation. Special
inspection requirements shall comply with Section 4.2 of this report.
8
These reduced allowable tension loads are applicable for anchors installed without special inspection and are based on a factor of safety of 8.0.
9
These allowable shear loads are based on a factor of safety of 4.0 and anchor installation with or without special inspection.
Page 5 of 6
TABLE 2LOAD REDUCTION FACTORS FOR TITEN HD SCREW ANCHORS INSTALLED BETWEEN CRITICAL
1,2,3
AND MINIMUM EDGE DISTANCES (Anchors Installed in the Face of Grout-filled CMU Masonry)
LOAD REDUCTION FACTORS FOR ANCHORS INSTALLED AT:
ANCHOR DIAMETER
(in)
MINIMUM
EMBEDMENT
DEPTH
(in)
Tension Load
Towards
an Edge
Away from
an Edge
Parallel to
an Edge
1.0
1.0
0.58
0.89
0.77
2 /4
3 /2
1.0
1.0
0.38
0.79
0.48
4 /2
1.0
0.83
0.30
0.58
0.46
5 /2
1.0
0.66
0.21
0.38
0.44
/8
/2
/8
/4
The load reduction factors in this table are applicable to the allowable loads shown in Tables 1A and 1B.
Reduction factors are cumulative. Multiple reduction factors for more than one spacing or edge distance are calculated separately and
multiplied.
3
Load reduction factors for anchors loaded in tension or shear with edge distances between critical and minimum are obtained by linear
interpolation.
2
TABLE 3LOAD REDUCTION FACTORS FOR TITEN HD SCREW ANCHORS INSTALLED BETWEEN CRITICAL
1,2,3
AND MINIMUM SPACING (Anchors Installed in the Face of Grout-filled CMU Masonry)
LOAD REDUCTION FACTORS FOR ANCHORS INSTALLED AT:
MINIMUM
EMBEDMENT
DEPTH
(in)
ANCHOR
DIAMETER
(in)
Tension Load
Shear Load
2 /4
1.0
0.87
0.62
3 /2
1.0
0.69
0.62
4 /2
1.0
0.59
0.62
1.0
0.50
0.62
/8
/2
/8
/4
5 /2
The load reduction factors in this table are applicable to the allowable loads shown in Tables 1A and 1B.
Reduction factors are cumulative. Multiple reduction factors for more than one spacing or edge distance are calculated separately and
multiplied.
3
Load reduction factors for anchors loaded in tension or shear with spacing between critical and minimum are obtained by linear interpolation.
2
TABLE 4AIBC AND IRC ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW ANCHORS
1
INSTALLED IN TOP OF GROUT-FILLED CMU MASONRY
2
3,4,5
Shear
Minimum Edge
Distance
Minimum End
Distance
Minimum
Spacing
Tension
Parallel
to Edge of
Masonry Wall
Perpendicular
to Edge of
Masonry Wall
4 /2
1 /4
570
585
160
1 /4
10
10
570
675
160
/2
/8
/2
/8
4 /2
(lbf)
For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N, 1 psi = 6.89 kPa.
1
The allowable tension and shear loads in Table 4A are applicable when anchors are installed in structures regulated by the IRC or IBC.
Minimum edge and end distances are measured from the anchor centerline to the edge and end of the CMU masonry wall, respectively.
Refer to Figure 3. Minimum spacing is measured from center-to-center of two anchors. Anchors installed in the mortared head joint are outside
the scope of this report.
3
The allowable loads in Table 4A are for anchors resisting dead, live, wind, and earthquake load applications. For short-term loading due to
wind and earthquake forces, the allowable loads may be adjusted in accordance with Section 5.3.
4
Tabulated loads are for anchors installed in fully grouted masonry wall construction consisting of Grade N, Type II, lightweight, mediumweight, or normal-weight concrete masonry units (CMUs) conforming to ASTM C 90. Allowable minimum nominal dimensions of the CMU shall
be 8 inches wide by 8 inches high by 16 inches long (8"8"16"). Masonry wall construction shall be fully grouted with coarse grout having a
minimum compressive strength of 2,000 psi, and complying with IBC Section 2103.12 (2009 and 2006 IBC) or 2103.10 (2003 and 2000 IBC)
or IRC Section R609.1.1, as applicable. Mortar shall be Type M or S in compliance with IBC Section 2103.8 (2009 or 2006 IBC) or 2103.7
(2003 and 2000 IBC) or IRC Section R607.1, as applicable, and have a minimum compressive strength of 1,500 psi. The specified
compressive strength of masonry, fm, at 28 days shall be a minimum of 1,500 psi.
5
Allowable tension and shear loads are based on a safety factor of 5.0, and are based on anchor installations with special inspection. Refer to
Section 4.2 of this report for special inspection requirements.
2
Page 6 of 6
TABLE 4BUBC ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW ANCHORS
1
INSTALLED IN TOP OF GROUT-FILLED CMU MASONRY
2
DRILL
MIN.
BIT
EMBED.
DIA.
(in)
(in)
3,4
Tension
Minimum
Edge
Distance
(lbf)
Shear
Installed
with
Special
6
Inspection
Installed without
Special
7
Inspection
Parallel
to Edge of
Masonry
Perpendicular to
Edge of Masonry
4 /2
1 /4
715
355
730
200
10
10
715
355
845
200
/2
/8
/2
/8
4 /2
1 /4
For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N, 1 psi = 6.89 kPa.
1
The allowable tension and shear loads in Table 4B are applicable for anchors installed in structures regulated by the UBC.
Minimum edge and end distances are measured from the anchor centerline to the edge and end of the CMU masonry wall, respectively.
Refer to Figure 3. Minimum spacing is measured from center-to-center of two anchors. Anchors installed in the mortared head joint are outside
the scope of this report.
3
The allowable loads in Table 4B are for anchors resisting dead, live, wind, and earthquake load applications. For short-term loading due to
wind and earthquake forces, the allowable loads may be adjusted in accordance with Section 5.4.
4
Tabulated loads are for anchors installed in fully grouted masonry wall construction consisting of Grade N, Type II, lightweight, mediumweight, or normal-weight concrete masonry units (CMUs) conforming to UBC Standard 21-4. Allowable minimum nominal dimensions of the
CMU shall be 8 inches wide by 8 inches high by 16 inches long (8"8"16"). Masonry shall be fully grouted with coarse grout having a
minimum compressive strength of 2,000 psi, and complying with UBC Section 2103.4. Mortar shall be Type M or S in compliance with UBC
Section 2103.3 and UBC Standard 21-15. The specified compressive strength of masonry, fm, at 28 days shall be a minimum of 1,500 psi.
5
Allowable shear loads are based on a safety factor of 4.0. Special inspection for anchor installation is not required.
6
Allowable tension loads in the column entitled Installed with Special Inspection are based on a safety factor of 4.0. Special inspection shall
be provided during anchor installation, and shall comply with the requirements described in Section 4.2 of this report.
7
Allowable tension loads in the column entitled Installed without Special Inspection are based on a safety factor of 8.0. Special inspection for
anchor installation is not required for anchors assigned these reduced allowable tension loads.
2