Ehv Instrument Transformers

This document provides specifications for an outdoor oil cooled current transformer. It has 5 cores with ratings of 800-1600/1-1,200-400-800-1600/1-1-1 Amps and can withstand short circuit currents up to 40 kA for 1 second. Additional key specifications include a rated voltage of 220 kV, impulse withstand voltage of 1050 kV, and accuracy class of 0.2 for one core and PS for the others. The current transformer has a ring type primary made of copper with a cross sectional area of 1000-1250 sq mm depending on the extended current rating.

Uploaded by

Tejaswi Shukla
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
131 views3 pages

Ehv Instrument Transformers

This document provides specifications for an outdoor oil cooled current transformer. It has 5 cores with ratings of 800-1600/1-1,200-400-800-1600/1-1-1 Amps and can withstand short circuit currents up to 40 kA for 1 second. Additional key specifications include a rated voltage of 220 kV, impulse withstand voltage of 1050 kV, and accuracy class of 0.2 for one core and PS for the others. The current transformer has a ring type primary made of copper with a cross sectional area of 1000-1250 sq mm depending on the extended current rating.

Uploaded by

Tejaswi Shukla
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

EHV INSTRUMENT TRANSFORMER

CURRENT TRANSFORMERS
As per Make List
1. Name & country of the Manufacturer
2. Manufacturers type designation

Outdoor Oil cooled ,


Hermetically sealed , Live
Tank Type Current
Transformer

3. Standard applicable

IEC 44-1/ IS 2705

4. Rated frequency (Hz)

50 Hz

5. Rated Voltage (KV)

220 kV

6. i) Rated continuous normal current (A)

200-400-800-1600 Amps

ii) Rated thermal current (A)


7. Short time current withstand of 1 sec. (kA)

120% of the Rated Primary


current continuous
40 KA for 1 second

8. Dynamic current withstand (kA peak)

100 kA P

9. 1.2 /50 micro second impulse withstand


Voltage (kV peak).
10. 250/2500 micro second switching withstand
Voltage (kV peak dry and wet)

1050 kV

11. One minute dry & wet power frequency


Withstand voltage (kV rms)

460kV

12. No. of cores per CT

13. Transformation Ratio

800-1600/1-1,200-400-8001600/1-1-1 Amps
800-1600 for Core 1 & 2 and
,200-400-800-1600 for Core
IV & V

14. Number of secondary turns

15. Rated output (VA) at different taps.

20 VA for Core III

16. Accuracy class

0.2 For Core III , PS for Core


I,II,IV & V

17. Knee-point voltage (volts) at the different taps.

800-1600 V for Core I & II


And 400-800-1600-3200 V for
Core IV & V

18. Secondary data


a) Secondary resistance at different taps.

b) Oversize factor and transient error under


Reclosing duty condition

1/2/4/8 Ohms for Core IV & V


And 4/8 Ohms for Core I & II
Not applicable

19. Maximum exciting current at For Core I ,II, III


& IV

a) 100% kpv (mA)

For Core I , II & IV & V


60/30 mA, 240/120/60/30mA

b) 25% kpv (mA)

60/30 mA,

c) 20% kpv (mA)

30/20/10 mA

d) 10% kpv (mA)

25/15/5 mA

240/120/60/30mA

20. Instrument security factor


at different ratios

< 5 for Core III

21. Radio interference(max)


Voltage at 1.1xUm/3 (microvolts)
For frequency between 0.5 MHz to 2.0 MHz

1000 Microvolts, max

22. Whether auxiliary CT/reactor provided for


Metering winding

No.

23. Corona extinction voltage (kV rms)

156 kV rms , min

24. Partial discharge level (pico coulombs)

Less than 10 P.C

25. Total creepage distance (mm)

25 mm / kV (6125mm) Min

26.

a) No. of primary turns.

b) Material and cross section of primary.

Material :- Copper
C/s area :- 1000 Sq mm
For CT having 120 %
extended current &
C/s area :- 1250 Sq mm
For CT having 150 %
extended current &

c) Whether bar type or ring type primary

Ring Type

27. Whether CT is suitable for transportation


horizontally.
28. Composite error at rated burden and at :a) 20% rated current
b) 120% rated current

29. Composite error at 25% rated burden and at:a) 20% rated current
b) 120% rated current

30. Quality of oil per CT (litres)


31. Whether
- Spark gap/surge
Arrester provided at the
Primary
- Power factor measurement terminal
provided
32. Standard to which oil conforms generally

Yes

Within Limits as per :- IEC


44-1
Within Limits as per :- IEC
44-1

Within Limits as per :- IEC


44-1
Within Limits as per :- IEC
44-1
250 Litres

No..
Yes .
IS 335

33. Whether current transformers are hermetically


sealed.
34. Total weight (Kg.)

Yes

35. Transport weight (Kg.)

1100 Kgs

36. Temperature risen over an


Ambient temp. of 50C (C)

50 Deg C

37. Whether CT characteristic


Curves enclosed
38. Type Test Report enclosed
39. OGA drawing enclosed

Yes , enclosed

1000 Kgs

Yes
Yes