KNX - Communication
KNX - Communication
KNX Association
Table of Contents
1
2
3
4
5
6
Flags ..................................................................................................................9
7
8
9
10
11
12
12.1
12.2
12.3
Cable Length between TP1 Power Supply Unit and TP1 Bus Device ...............24
Cable Lengths between two TP 1 Bus Devices ................................................25
Total Cable Length per TP 1 Line Segment .....................................................25
Communication_E1212a
KNX Association
2/25
Definition
The following terms are used as synonyms in KNX literature:
Physical address and individual address
Communication object and group object
The terms individual address and group objects are commonly used In the KNX
training documentation as well as in ETS.
After the installation and in the case of S-mode compatible products, a KNX system is not
ready for operation until sensors and actuators have been loaded with application
Communication_E1212a
KNX Association
3/25
When the lower rocker is pressed, the same process occurs except that the value is set
to 0 this time and the output relay of the actuator is thereby opened.
The respective elements of the KNX system are explained in more detail on the following
pages.
Communication_E1212a
KNX Association
4/25
2 Individual address
An individual address must be unique within a KNX installation. The individual address is
configured as described above. It has the following format: Area [4 bit] - Line [4 bit] Bus
device [1 byte]. The bus device is normally prepared for the acceptance of its individual
address by pressing a programming button on the bus device. The programming LED is
lit during this process. The individual address is also used for the following purposes after
the commissioning stage:
Diagnosis, error rectification, modification of the installation by reprogramming
Addressing of the interface objects using commissioning tools or other devices.
Important: The individual address has no significance during normal operation of
the installation.
Communication_E1212a
KNX Association
5/25
3 Group Address
Communication_E1212a
KNX Association
6/25
Communication_E1212a
KNX Association
7/25
4 Group object
KNX group objects are memory locations in bus devices. The size of these objects can be
between 1 bit and 14 bytes. The size of the group objects is dependent on its function.
As only two states (0 and 1) are required for switching, 1 bit group objects are used. The
data involved in text transmission is more comprehensive and therefore group objects
with a maximum size of 14 bytes are used.
The ETS only allows to link objects with the same size using group addresses. Several
group addresses can be assigned to one group object, but only one is the sending group
address.
An object value is sent on the bus in the following way:
a) If the upper left rocker is pressed for example, the two-fold switch sensor writes a 1
to its group object with the number 0. As the communication and transmit flag are set
for this object, this device will send a telegram on the bus with the information Group
address 1/1/1, write value, 1.
b) All the bus devices throughout the KNX installation that also have the group address
1/1/1 will then write 1 in their own group object.
c) In our example, the 1 is written in group object no. 0 of the actuator.
d) The application software of the actuator establishes that the value in this group object
has changed and executes the switching process.
Communication_E1212a
KNX Association
8/25
4.1 Flags
Each group object has flags which are used to set the following properties:
Communication
READ
WRITE
TRANSMIT
UPDATE
READ ON INIT
A telegram is transmitted when the object value (at the sensor) has been
modified.
The group object will generate a response only when receiving a read request.
The device independently sends Read value commands for the initialisation of
the group object after return of current (only available on certain masks)
After return of current the device does not initialise the value of the assigned
group object via Read Value commands
Please note: The default flags should only be changed in exceptional circumstances.
For further information you can consult the topic Flags in the chapter Project Design of
the basic course documentation or the chapter Flags in the advanced course
documentation.
Communication_E1212a
KNX Association
9/25
Communication_E1212a
KNX Association
10/25
Communication_E1212a
KNX Association
11/25
Communication_E1212a
KNX Association
12/25
Communication_E1212a
KNX Association
13/25
Communication_E1212a
KNX Association
14/25
Communication_E1212a
KNX Association
15/25
With the Scaling, a brightness value between 1 (minimum) and 255 (maximum) is set
directly.
Depending on the manufacturers application, it may be possible to switch on (1 value
255) or off (value = 0) a connected device using this DPT.
The DPT has a size of 1 byte.
Communication_E1212a
KNX Association
16/25
Communication_E1212a
KNX Association
17/25
Communication_E1212a
KNX Association
18/25
Communication_E1212a
KNX Association
19/25
The data is transmitted symmetrically over the pair of cores. Bus devices evaluate the
difference in voltage between the two cores.
As radiated noise affects both cores with the same polarity, it has no influence on the
difference in the signal voltage.
Communication_E1212a
KNX Association
20/25
Communication_E1212a
KNX Association
21/25
Communication_E1212a
KNX Association
22/25
Communication_E1212a
KNX Association
23/25
Figure 19: Cable Length between TP1 power supply unit and TP1 bus device
12.1 Cable Length between TP1 Power Supply Unit and TP1 Bus Device
The bus device only transmits a half wave (shown in the picture as a negative half wave
at the positive core).
The choke as part of the power supply unit produces - together with the transformers of
the bus devices - the positive equalisation pulse.
As the choke has a major part in the forming of the equalisation pulse, the bus devices
may be installed up to 350 m cable length away from the choke (power supply unit).
Communication_E1212a
KNX Association
24/25
Communication_E1212a
KNX Association
25/25