G2 Study Notes
G2 Study Notes
G2 Study Notes
Pressure Drop
PRESSURE DROP = working pressure differential b/t the gas meter outlet to the appliance
regulator inlet
Maximum allowable pressure drops
Natural Gas
Supply pressure of <7 w.c.
Supply pressure of 7 w.c. to 14 w.c.
Supply pressure of >14 w.c.
Propane
Supply pressure of <14 w.c.
Supply pressure of >14 w.c.
7) check manometer to see if the pressure reading decreases (if decreases => there is a
leak)
High Pressure Test gauges
-requirements for pressure gauges are in code book
Purging of Gas
-all purging requirements are in the code book
-purging hoses w/ Dead Man's hoses are recommended
Valves
-typical valves on gas systems = 1/4 turn valves
-allows for opening and closing rapidly
-typical locations: utility gas meter; upstream of a new run but downstream of manifold; at the
drop to the gas appliance
-break points:
-break/weak point of valve is to be installed on same side of the appliances
-only valves stamped w/ #3.16 are for outdoor use
Pipe Sizing
Tables
-for systems w/ a supply pressure of <=2PSIG: tables include an allowance for a reasonable # of
fittings
-for systems w/ pressures >2PSIG: each fitting must be sized according to its equivalent length
of straight feet
Information requirements
1) Relative density of the gas (N.G. or Propane)
2) supply pressure
3) allowable pressure drop
4) total gas (BTU/hr) input for each appliance
5) length of piping
-BTU/hr is a heating value for an appliance
-CFH (cubic feet per hour; BTUs/1000) is a measurement of gas flow for an appliance
Different Types
I) One pressure zone:
1) Determine LMR
(gas meter outlet/regulator to appliance that is furthest away)
2) Determine total input of all appliances and convert to CFH
3) Determine gas type, material type, pressure, pressure drop
4) Select appropriate table
5) Using LMR, determine pipe sizes using the appliance CFHs they supply
II) Two pressure zones:
1) Calculate pipe sizes for all pipe in the first pressure zone (using the appropriate table)
2) Calculate pipe sizes for all pipe in the second pressure zone
III) Pressures greater than 2PSIG:
-these tables don't include fittings
-only include fittings which change the direction of the gas flow on the
longest-measured run
FIND THIS OUT
IV) Point Load Method:
1) Size the manifold using the LMR which includes tubing downstream of the manifold
2) Size the tubing: LMR is the length of each individual run of tubing
Transformer
= used to change or transform voltage from one value to another
-don't work w/ DC (only w/ AC)
-rated by the amount of power the 2ndary winding can handle
-VA = volt amps (how much current a transformer can handle [the 2ndary side])
-if the gas valve is humming: the problem might be a low 2ndary voltage on transformer (would
have to be replaced)
Motors
-operation based upon principle of electromagnetism
Electrical Wire Insulation
-application determines type of insulation:
NMD
= non-metallic dry (in locations not exposed to moisture)
NMW
= non-metallic wet (can be used in damp locations)
unsheathed conductors
= only to be used in liquid-tight conduit
BX cable
= armoured cable (when running wire in steal stud/joist applications)
TEK
= watertight BX cable
Electrical Conductors
-gauge is measured in AWG (american wire gauge)
-the high the number, then thinner it is
-max. fuse sizes:
14AWG
= 15A
12AWG
= 20A
10AWG
= 30A
-if a circuit is fused any higher, it may overheat and cause a fire
-as length of conductor increases
= resistance increases
-as diameter of conductor increases = resistance decreases
-as resistance through conductor increases = voltage drop along conductor increases
*so the larger the wire the less voltage drop there will be
Electrical Building Service
-voltage into a residential panel = 240/1/60 (240V, single phase, 60HZ)
-4 wires are fed to a panel:
-two hot wires
-one neutral wire
-one ground wire
-fuses and circuit breakers:
-purpose = protect circuit conductors
-fuses are one-time only
-time delay fuses are used for intermittent high loads (e.g. motor circuits)
LRA = lock rotor amps
= the amps required for something to start up
RLA = running load amps
= the amps required for something to run
GFCI
-used in wet locations
-senses current flow to ground: GFCI will open circuit when current to ground exceeds rating
-senses minute current to ground (5mA)
Bonding Electrical Circuits
Bonding Conductor = a conductor which connects non-current carrying parts of electrical
equipment, raceways, enclosures, etc. to the system's grounding conductor
-meant to avoid build up of electrical charge in something (like a gas line)
Grounding condutor = a permanent + continuous conductive path to the earth:
Wiring Diagrams
Pictorial diagrams: show where wires and components are physically located
Connection diagrams: show where wires are connected
(used for initial wiring and tracing wiring)
Ladder or schematic diagrams: shows how the circuit works and what components do
(switches on left, load on right)
Switches
Switching Action
Pole:
Throw:
Symbols
2) High Limit
Type:
Senses:
Action:
Controls:
Flame Rectification
(measured in mA)
-converts AC to DC w/ use of flame rectification
-current from spark igniter travels through the flame -> to the ground -> to the control module
*the control module detects a DC voltage, which proves that the flame is lit
-when occupant load increases => relative humidity w/in building increases
-actions that affect building systems:
-cooking and food prep.
-smoking
-contaminants generated by occupants (CO, perspiration, breathing, exercise)
-bathing
Mechanical Impact:
-all equipment and appliances in the building
-water heaters
-dryers
-motors
-fireplaces
-wood stoves
-air cleaners
-central vacs
-refridgerators
-lighting
-natural draft appliances
-air changers (HRVs, ERVs)
-impact from mechanical equip. can be severe: gas tech.s must take combustion and
ventilation air into account
External Environment:
-building location matters:
-if home is in path of strong prevailing winds = cooling effect in the winter
-shade trees can have same effect in summer
-exposure to solar radiation can have same effect in summer and winter
Minimizing negative impact:
-above factors will impact on quantity and quality of:
-heat
-moisture
-air flow
-heat/moisture will always flow from area of high concentration to low concentration
-buildings are constructed to keep conditioned area from escaping to the outside
= helps keep energy costs to a minimum
= helps keep occupant comfort at a maximum
-need appropriate amount of moisture
-enough moisture for benefit of occupants, furniture, and building construction
-too much moisture = moulds and mildew
*reasons for excess moisture:
-new construction materials
-open sump pits
-poor air barriers
-too little moisture will cause:
-wood to dry and crack
-make air dry and might lead to respiratory illnesses
-exfiltration: movement of air from inside to outside
-infiltration: movement of air from outside to inside
Source
showers
plants
cooking
seasonal storage
drying firewood
wet basement
construction moisture
-warm air holds more water vapour than cold air (takes more water vapour to saturate the same amount
of air
*so: relative humidity decreases when air is heated (e.g. by a furnace)
(b/c amt of water is the same, but air molecules are further spaced apart)
-cold air = molecules are more dense
-heated air = molecules less dense = more room for water vapour
-methods of decreasing relative humidity
-A/C dehumidifies conditioned air
-increase air flow through building
-use HRV to exhaust warm moist air + bring in cooler, drier air
-in winter, if vapour barrier is continuous, then relative humidity should stay the same
Ventilation
-ventilation air: fresh air required by all building occupants
= introduction of outside air to replace exhausted air or to dilute indoor air
-older houses made of looser construction satisfied ventilation req.s w/out any specific measures
(fresh air entered house through cracks in building envelope)
-newer houses are tighter = so they require a specific amount of air to be introduced by
mechanical ventilation
-ventilation also the best way to remove odours from a house
Heat Recovery Ventilators
-HRVs = mechanical heat exchangers
-warm moist air exhausted from inside of building is cycled out while cooler, dry, fresh air is
cycled in
-heat exchanger in the HRV transfers heat from inside exhausting air to the cooler incoming air
(reduces cost of supplying ventilation air and re-heating it in the furnace
-usually have two speeds:
1) low speed for continuous ventil.
2) high speed for exhausting inside air when it is outside of comfort range
*this speed controlled by humidistat
-if humidity level climbs above comfort range, high speed option will become energized
-can have their own dedicated ductwork, or can be hooked into return air side of furnace ducting
Filtration
-regular filters: purposes is to protect, furnace components, heat exchangers, and A/C coils from effect
of heavy particle pollution
= arrestance
-dust spot efficiency = measurement of filter's efficiency at picking particles of dust at various size
ranges
-filters clean air w/ three methods:
1) Impingement:
-dust particles strike filter media and are stopped
2) Straining:
-dust particles stopped if they are larger than space between the fibres
3) Electrostatic Precipitation:
-dust particles given an electrical charge which is opposite to that of the filter material
= dust particles are attracted to filter media
Building Pressure
-air flows from area of high pressure to low pressure
-when air is heated in winter by furnace = it will expand
= will put building under positive pressure
-air will flow through openings and cracks
-building under negative pressure: cause outside air to be drawn into structure
-a building can experience both positive and negative pressure at the same time
e.g. mechanical ventil. system may be oversupplying one area of the house, while lack of
make-up air in basement can cause a negative pressure
-several means by which building pressure is changed:
1) Stack Effect:
-warm air rises in a building, finding its way through cracks in the building envelope
-may cause negative pressure in basement and starve gas-fired appliances located in the
area
2) Mechanical or Natural Ventilation Effect:
-exhausting building air can lead to negative pressure w/in building
-air will enter building to equalize the pressure: it will do this through path of least
resistance
= in many cases: venting system of appliances: will disrupt these appliances from
venting properly
*mechanical ventilation = most common cause of negative pressure in a house
3) Duct Effect:
-improperly designed or installed HVAC systems can cause air to leak out of ducts and
short cycle
= can lead to poor occupant comfort and removal of combustion air from
appliance rooms
4) Wind Effect:
-positive pressure building up on windward side
-negative pressure building up on leeward side
5) Flue Effect:
-venting systems are usually easiest way for air to enter and exit a building
Spillage
-natural draft systems can be susceptible to spillage of flue gases into house
-most common cause of spillage = negative pressure in building created by mechanical exhaust systems
*caused by downdraft down chimney
-causes of downdraft:
1) improper vent locations
2) negative air pressure condition w/in house
3) strong prevailing winds
-causes of spillage:
1) blocked vent
2) down draft
3) negative pressure in house
Combustion Air Sizing
-gas tech. must consider several things when installing a gas-fired appliance:
1) BTU input
2) Construction type: tight or loose
3) method of venting flue products: draft controlled or no draft controlled
-for inputs greater than 400 000 BTU: appliances must use outside air for combustion and ventilation
Components
1) Orifice: THE RESTRICTING ELEMENT
-controls the volume of gas entering the chamber
2) Spring: THE LOADING ELEMENT; OPENING FORCE
*two jobs:
1) sets working pressure
2) opening force = overcomes pressure on gas side to open seat
-can adjust in order to set different working pressures
3) Diaphragm: THE MEASURING ELEMENT
-separates the bottom part from the top
4) Vent: allows gas to escape in case of overpressure downstream of the regulator
-allows top of the diaphragm to breath
-all regulator vents have to be facing down
Functions:
-allow for displacement of air above measuring element (diaphragm) so it can
operate
-allows gas to escape in case of diaphragm rupture or downstream overpressure
-allow for installation of a leak-limiting orifice in some regulators
5) Leak Limiting Orifices:
-vent limiting orifice:
-normally a #78 drill size
-will allow one cubic foot of gas per hour to pass
6) Surge Limiting Device:
(for when too much gas enters the regulator)
-used in special applications that require regulator to be slow opening
-position of the ball restricts flow of air from top of chamber
-static pressure = lock-up pressure = shut-off pressure
= the regulator shuts off at this pressure
-the pressure under which downstream pressure will stabilize after the burner shuts
down
(should not exceed 20% of operating pressure)
Terminology
Service regulator: regulator at end of utility's pipeline that reduces supply pressure to working
pressure
(may also describe second stage regulator in a propane system)
Appliance regulator: reduces building line pressure to the manifold pressure of the appliance
System regulator / low-pressure regulator / zone regulator: the regulator b/t the service and the
appliance regulator
First stage regulator / high-pressure regulator: reduces tank pressure down to supply line
pressure on a propane system (0-375 PSIG down to 10PSIG)
Second stage regulator / medium pressure regulator: reduces supply line pressure to building
line pressure
Twin stage regulator: regulator that combines a first stage and second stage in one
-example where system regulators are handy:
-if need 300' of gas pipe to feed 3m BTUs at 14 w.c. => requires 4 pipe
*but at 5PSIG => requires only 1.5 pipe
= so run pipe at 5PSIG and introduce a service regulator just upstream of the appliances
Two Stage Propane Regulators
-required on all permanent installations
-max. first stage pressure = 10PSIG
-first stage regulator eliminates fluctuating supply pressure (b/c pressure in the tank
changes w/ temperature)
-allows for small supply lines b/t tank and building
Creeping regulator = gas being passed at regulator valve seat when leak test being done w/
manometer
Converting Natural Gas to L.P.G Regulator
1) change orifice
2) change spring
3) set manifold pressure
4) change rating plate
Gas Meters
Types:
1) Bellows:
2) Rotary-type:
3) Orifice-type:
4) Turbine:
Meter Construction:
-castings can be made from: tin, pressed steel, cast iron, aluminum
-interior parts are often synthetic or plastic
-bellows meters don't require lubrication
-some rotary meters require lube
Domestic Bellows Meter:
-outlets come in different sizes:
1 outlet
= 225 000 BTU output max
1.25 outlet = 400 000 BTU output max
1.5 outlet
= 800 000 BTU output max
-anything above 800 000BTU = need a new meter
-max. allowable pressure drop = 1/2 w.c.
1) positive displacement meter
-measures actual volume of gas
-force that operates the meter = diff. b/t the pressure of the gas at the meter inlet and the
pressure at the outlet acting upon the diaphragms or chambers
Propane Containers
Standard set by:
Cylinder
Transport Canada
Tank
Boiler and Pressure Vessels Act
(TSSA)
Re-inspection:
Capacity:
Pounds of water
US water gallons
375 PSIG
250PSIG
3) weak ammonia solution (containing water) is diverted to the top of the ABSORBER
COILS
4) any small amount of weak ammonia solution that enters vapour pipe flows
into ammonia pipe via gravity (it is lower)
IN CONDENSER
5) ammonia in CONDENSER is cooled into a liquid
6) ammonia liquid enters evaporator that contains hydrogen vapour
7) as liquid ammonia contacts the hydrogen => ammonia begins to vapourize
8) ammonia and hydrogen flow down to return pipe
IN ABSORBER
9) hydrogen and ammonia separated in ABSORBER in conjunction w/ weak
ammonia solution present in the weak ammonia pipe
10) ammonia vapour attracted into the ammonia hydroxide solution in ABSORBER
11) hydrogen rises into EVAPORATOR
N.G.
1
2
8
11.9%
L.P.G.
3
4
18.5
13.9%
DIP TUBE
(tank will allow small drips of cold water to replace the hot water)
= a little water drips down dip tube
-so unitrol only on intermittently
*result = cold at bottom, warm throughout
Instantaneous Water Heaters
-cannot run out of hot water at their designed flow rate
-require sufficient water supply for proper operation
-important components:
PUMP
PUMP CONTROL CONTROL SWITCH
T AND P
LIMIT CONTROL
DIP TUBE
-outdoor air
*are mounted:
-in wells
-directly to metal pipes
-according to manuf.'s recommendations
-fluid flow controlled by pressure bypass valve or shunt pump
-max. allowable velocity of fluid in supply and return lines less than 2 = 4ft/sec.
-min. size and type of water heater recommended for a combo. system
= 40 gallon high recovery gas-fired water heater
= 40 gallon high efficiency gas-fired water heater
Circulating Pumps
Purpose
= to overcome resistance in system caused by pipings and fittings, etc.
Head pressure = ability of the pump to overcome resistance
-how to size pump?
= use head pressure and water flow rate
BTU (output)
1.1 x Temp. rise
3) Fan switch
-automatically turns blower off and on
-delays blower fan operation to heat the heat exchanger and prevent nuisance drafts
-delays blower fan termination to cool heat exchanger and dissipate heat
-switch is temp. controlled or time delayed
4) Limit switch
-normally closed safety switch
-when detects overheat situation = will open and de-energize main gas valve
-can be in combo w/ fan limit switch
Temp. Range
170 to 250 degrees F
Pressure
<= 30PSI
30PSI to 150PSI
150PSI to 500PSI
-boilers used to supply water for commercial and industrial heating usually operate at 250
degrees F
Properties of Water
Latent heat = change of state but no change in temp.
Sensible heat = change in temp. but no change in state
ABVs (Automatic Bypass Valves)
*purpose = bring up temp. in the return line
*dumps some hot water in return line so its not too cold when it enters boiler
= most important valve in a heating system
Boiler Types
1) Steel Tube Boilers (Verticle Steel Boilers)
2) Copper-Fin Tube Boilers (Water Tube Boilers
3) Cast-Iron Section Boiler
1) Steel Tube/Verticle Steel
= Fire Tube Boilers
-fire is inside tubes and the water is outside the tubes, but around it
-take a long time to reach operating temp. + pressure upon initial startup
*but can deliver large quantities of steam or water for extended period of time
-sometimes have several fire passes:
e.g. First pass through a Morrison Tube, then second pass into fire tube
-turbulators = installed in fire tubes to turbulate flue gases (provide additional
3) Total BTUs
Air supply requirements for > 400 000 BTUs
-if one appliance has no draft control and another does => determine them separately and add
together
Air Changers
HRVs
(Heat Recovery Ventilator)
ERVs
(Energy Recovery Ventilator)
C2
C3
C4
-sling psychrometer measures air temp. using two thermometers: a wet bulb and a dry bulb
*as psychrometer is rotated quickly in air, moisture is evaporated from wet bulb
-when the temperature stabilizes on the two thermometers, readings are taken
-the readings are then compared to tables supplied w/ the device
A/C
Cooling coils
-measuring pressure drop across coil
*one way of checking system
= measured using a magnehelic gauge or manometer