Monitor Design IMO SOLAS Helideck
Monitor Design IMO SOLAS Helideck
Monitor Design IMO SOLAS Helideck
4 ALBERT EMBANKMENT
LONDON SE1 7SR
Telephone: +44 (0)20 7735 7611
Fax: +44 (0)20 7587 3210
MSC.1/Circ.1431
31 May 2012
GUIDELINES FOR THE APPROVAL OF HELICOPTER FACILITY
FOAM FIRE-FIGHTING APPLIANCES
1
The Maritime Safety Committee, at its ninetieth session (16 to 25 May 2012), having
considered a proposal by the Sub-Committee on Fire Protection, at its fifty-fifth session,
approved the Guidelines for the approval of helicopter facility foam fire-fighting appliances,
as set out in the annex.
2
Member Governments are invited to apply the annexed Guidelines when approving
helicopter facility foam fire-fighting appliances in accordance with SOLAS regulation II-2/18,
the 2009 MODU Code and the Recommendation on helicopter landing areas on ro-ro passenger
ships (MSC/Circ.895) on or after 21 May 2013 and bring them to the attention of ship designers,
shipowners, equipment manufacturers, test laboratories and other parties concerned.
***
I:\CIRC\MSC\01\1431.doc
MSC.1/Circ.1431
Annex, page 1
ANNEX
GUIDELINES FOR THE APPROVAL OF HELICOPTER
FACILITY FOAM FIRE-FIGHTING APPLIANCES
Application
These Guidelines apply to foam fire-fighting appliances for the protection of helicopter facilities in
accordance with SOLAS regulations II-2/18.5.1.3 to 5.1.5, chapter 9 of the Code for the
Construction and Equipment of Mobile Offshore Drilling Units, 2009 (2009 MODU Code) and the
Recommendation on helicopter landing areas on ro-ro passenger ships (MSC/Circ.895).
2
Definitions
2.1
D-value means the largest dimension of the helicopter used for assessment of the
helideck when its rotors are turning. It establishes the required area of foam application.
2.2
Deck integrated foam nozzles are foam nozzles recessed into or edge mounted on the
helideck.
2.3
Foam-making branch pipes are air-aspirating nozzles in tube shape for producing and
discharging foam, usually in straight stream only.
2.4
Helicopter landing area is an area on a ship designated for occasional or emergency
landing of helicopters, for example as referred to in SOLAS regulation II-2/18.2.2 and not
designed for routine helicopter operations.
2.5
Helideck is a purpose-built helicopter landing platform or other deck area including all
structure, fire-fighting appliances and other equipment necessary for the safe operation of
helicopters, as referred to in SOLAS regulations II-2/3.26 and 18.5 and the 2009 MODU Code
(chapter 1, paragraph 1.3.27).
2.6
Hose reel foam station is a hose reel fitted with a foam-making branch pipe and
non-collapsible hose, together with fixed foam proportioner and fixed foam concentrate tank,
mounted on a common frame.
2.7
Monitor foam station is a foam monitor, either self-inducing, or together with separate
fixed foam proportioner, and fixed foam concentrate tank, mounted on a common frame.
2.8
Obstacle free sector is the take-off and approach sector which totally encompasses the
safe landing area and extends over a sector of at least 210, within which only specified
obstacles are permitted.
2.9
Limited obstacle sector is a 150 sector outside the take-off and approach sector that
extends outward from a helideck where objects of limited height are permitted.
2.10
Winching area is a pick-up area provided for the transfer by helicopter of personnel or
stores to or from the ship, while the helicopter hovers above the deck, for example as referred to
in SOLAS regulation III/28.
3
3.1
The system should be capable of manual release, and may be arranged for automatic
release.
I:\CIRC\MSC\01\1431.doc
MSC.1/Circ.1431
Annex, page 2
3.2
For helidecks the foam system should contain at least two fixed foam monitors or deck
integrated foam nozzles. In addition, at least two hose reels fitted with a foam-making branch
pipe and non-collapsible hose sufficient to reach any part of the helideck should be provided.
The minimum foam system discharge rate should be determined by multiplying the D-value area
by 6 l/min/m2. The minimum foam system discharge rate for deck integrated foam nozzle
systems should be determined by multiplying the overall helideck area by 6 l/min/m2. Each
monitor should be capable of supplying at least 50 per cent of the minimum foam system
discharge rate, but not less than 500 l/min. The minimum discharge rate of each hose reel
should be at least 400 l/min. The quantity of foam concentrate should be adequate to allow
operation of all connected discharge devices for at least 5 min.
3.3
Where foam monitors are installed, the distance from the monitor to the farthest
extremity of the protected area should be not more than 75 per cent of the monitor throw in still
air conditions.
3.4
For helicopter landing areas, at least two portable foam applicators or two hose reel
foam stations should be provided, each capable of discharging a minimum foam solution
discharge rate, in accordance with the following table.
Category Helicopter overall length
(D- value)
H1
H2
H3
Minimum foam
solution discharge
rate (l/min)
up to but not including 15 m
250
from 15 m up to but not including 24 m
500
from 24 m up to but not including 35 m
800
The quantity of foam concentrate should be adequate to allow operation of all connected
discharge devices for at least 10 min. For tankers fitted with a deck foam system, the
Administration may consider an alternative arrangement, taking into account the type of foam
concentrate to be used.
3.5
3.6
Manual release stations capable of starting necessary pumps and opening required
valves, including the fire main system, if used for water supply, should be located at each
monitor and hose reel. In addition, a central manual release station should be provided at a
protected location. The foam system should be designed to discharge foam with nominal flow
and at design pressure from any connected discharge devices within 30 s of activation.
3.7
Activation of any manual release station should initiate the flow of foam solution to all
connected hose reels, monitors, and deck integrated foam nozzles.
3.8
The system and its components should be designed to withstand ambient temperature
changes, vibration, humidity, shock impact and corrosion normally encountered on the open
deck, and should be manufactured and tested to the satisfaction of the Administration.
3.9
A minimum nozzle throw of at least 15 m should be provided with all hose reels and
monitors discharging foam simultaneously. The discharge pressure, flow rate, and discharge
pattern of deck integrated foam nozzles should be to the satisfaction of the Administration,
based on tests that demonstrate the nozzle's capability to extinguish fires involving the largest
size helicopter for which the helideck is designed.
I:\CIRC\MSC\01\1431.doc
MSC.1/Circ.1431
Annex, page 3
3.10
Monitors, foam-making branch pipes, deck integrated foam nozzles and couplings
should be constructed of brass, bronze or stainless steel. Piping, fittings and related
components, except gaskets, should be designed to withstand 925C.
3.11
The foam concentrate should be demonstrated effective for extinguishing aviation fuel
spill fires and should conform to performance standards not inferior to those acceptable to the
Organization*. Where the foam storage tank is on the exposed deck, freeze protected foam
concentrates should be used, if appropriate, for the area of operation.
3.12
Any equipment installed within the take-off and approach obstacle free sector should
not exceed a height of 0.25 m. Any equipment installed in the limited obstacle sector should not
exceed the height permitted for objects in this area.
3.13
All manual release stations, monitor foam stations, hose reel foam stations, hose reels
and monitors should be provided with a means of access that does not require travel across the
helideck or helicopter landing area.
3.14
Oscillating monitors, if used, should be preset to discharge foam in a spray pattern and
have a means of disengaging the oscillating mechanism to allow rapid conversion to manual
operation.
3.15
If a foam monitor with flow rate up to 1,000 l/min is installed, it should be equipped with
an air-aspirating nozzle. If a deck integrated nozzle system is installed, then the additionally
installed hose reel should be equipped with an air-aspirating handline nozzles (foam branch
pipes). Use of non air-aspirating foam nozzles (on both: monitors and the additional hose reel) is
permitted only where foam monitors with a flow rate above 1,000 l/min are installed. If only
portable foam applicators or hose reel stations are provided, these should be equipped with an
air-aspirating handline nozzles (foam branchpipes).
___________
Refer to the International Civil Aviation Organization Airport Services Manual, part 1, Rescue and Fire-Fighting,
chapter 8, Extinguishing Agent Characteristics, paragraph 8.1.5, foam Specifications table 8-1, level "B", or to
the Revised Guidelines for the performance and testing criteria, and surveys of foam concentrates for fixed
fire-extinguishing systems (MSC.1/Circ.1312).
I:\CIRC\MSC\01\1431.doc