Leroy Somer Alternator Datasheet LSA 47.2 - 4 Pole

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

3782 en - 10.

2004 / b

Alternators
LSA 47.2 - 4 Pole
Electrical and mechanical data

LSA 47.2 - 4 Pole


SPECIALLY ADAPTED FOR APPLICATIONS
The LSA 47.2 alternator is designed to be suitable for typical generator applications, such as: stand-by,
prime power, cogeneration, marine, rental, telecommunications, etc.
COMPLIANT WITH INTERNATIONAL STANDARDS
The LSA 47.2 alternator conforms to the main international standards and regulations:
IEC 60034, NEMA MG 1.22, ISO 8528, CSA, CSA/UL, marine regulations, etc.
It can be integrated into a CE marked generator-set.
The LSA 47.2 is designed, manufactured and marketed in an ISO 9001 environment.
TOP OF THE RANGE ELECTRICAL PERFORMANCE
- Class H insulation.
- Standard 12-wire re-connectable winding, 2/3 pitch, type no. 6 (the LSA 47.2 L9 is available in two versions: 6-wire and 12-wire).
- Voltage range: 220 V - 240 V and 380 V - 415 V (440 V) - 50 Hz / 208 V - 240 V and 380 V - 480 V - 60 Hz.
- High efficiency and motor starting capacity.
- Other voltages are possible with optional adapted windings:
- 50 Hz: 440 V (no. 7), 500 V (no. 9), 600 V (no. 22 or 23), 690 V (no. 10 or 52)
- 60 Hz: 380 V and 416 V (no. 8), 600 V (no. 9).
- Total harmonic content < 2%.
- R 791 interference suppression conforming to standard EN 55011 group 1 class B standard for European zone (CE marking).
EXCITATION AND REGULATION SYSTEM SUITED TO THE APPLICATION

Excitation system
Voltage
regulator

Regulation options

SHUNT
PMG

Current transformer
for paralleling

Mains paralleling

R 726

3-phase sensing

R 731

R 734

Remote voltage
potentiometer

12 wire
only

AREP

R 230

Std

R 448

optional

Std

Std

mains paralleling

Voltage regulator accuracy +/- 0.5%.


PROTECTION SYSTEM SUITED TO THE ENVIRONMENT
- The LSA 47. 2 is IP 23.
- Standard winding protection for clean environments with relative humidity 95 %, including indoor marine environments.
Options:
Filters on air inlet and air outlet (IP 44).
Winding protections for harsh environments and relative humidity greater than 95%.
Space heaters.
Thermal protection for winding.
REINFORCED MECHANICAL STRUCTURE USING FINITE ELEMENT MODELLING
- Standard direction of rotation : clockwise when looking at the drive end view (engine side).
Running unit anti-clockwise: a derate of 5% must be applied.
- Compact and rigid assembly to better withstand generator-set vibrations.
- Steel frame.
- Cast iron flanges and shields.
- Two bearing and single bearing versions designed to be suitable for engines on the market.
- Half-key balancing.
- Greased for life bearings (regreasable bearings optional)
ACCESSIBLE TERMINAL BOX PROPORTIONED FOR OPTIONAL EQUIPMENT
- Easy access to the voltage regulator and to the connections.
- Possible clusion of accessories for paralleling, protection and measurement.
- 8-way terminal block for voltage reconnection.

Copyright 2004 : MOTEURS LEROY-SOMER


Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments, improve the design or change conditions of utilization.
Their description cannot, in any case, engage LEROY-SOMER liability. The values indicated are typical values.

LSA 47.2 - 4 Pole


Common data
H
2/3 (N 6 or N 6S)
12 (N 6) / 6 (N 6S)
IP 23
1000 m
2250 min-1
3
0,9 m /s (50Hz) / 1,1 (60Hz)

Insulation class
Winding pitch
Terminals
Drip proof
Altitude
Overspeed
Air ow

Excitation system
A.V.R. model
Voltage regulation (*)
Sustained short-circuit current
Total harmonic TGH / THC (**)
Waveform : NEMA = TIF (**)
Wave form : I.E.C. = THF(**)

SHUNT (12 wire)


A R E P or PMG
R 230
R 448
0,5 %
0,5 %
300% (3 IN) : 10s
at no load < 1,5 % - on load < 2 %
< 50
<2%

(*) Steady state duty. (**) Total harmonic content line to line, at no load or full rated linear and balanced load.

Ratings 50 Hz - 1500 min.-1


kVA / kW - Power factor = 0,8

6 wire

12 wire

Duty
Class/TK
Phase
Y

YY
47.2 VS2

Continuous duty 40C


H / 125 K
3 ph.

Continuous duty / 40C


F / 105 K
3 ph.

Stand-by/ 40C
H / 150 K
3 ph.

Stand-by / 27C
H / 163 K
3 ph.

380V

400V

415V

380V

400V

415V

380V

400V

415V

380V

400V

415V

220V

230V

240V

220V

230V

240V

220V

230V

240V

220V

230V

240V

200V

200V

200V

200V

kVA

365

330

405

420

kW

292

264

324

336

47.2 S4

kVA

410

370

430

450

kW

328

296

344

360

47.2 S5

kVA

455

405

471

500

kW

364

324

377

400

47.2 M7

kVA

500

465

545

570

kW

400

372

436

456

47.2 M8

kVA

550

500

575

600

kW

440

400

460

480

47.2 L9

kVA

600

535

630

660

kW

480

428

504

528

47.2 L9*

380V

400V

415V

380V

400V

415V

380V

400V

415V

380V

400V

415V

220V

230V

240V

220V

230V

240V

220V

230V

240V

220V

230V

240V

kVA

600

535

630

660

kW

480

428

504

528

Stand-by / 40 C
H / 150 K
3 ph.

Stand-by / 27 C
H / 163 K
3 ph.

Ratings 60 Hz - 1800 min.-1


kVA / kW - PF = 0,8

6 wire

12 wire

Duty
Class / T K
Phase
Y

YY
47.2 VS2 kVA

H / 125 K
3 ph.
380V

416V

220V

240V

Continuous duty 40C


F / 105 K
3 ph.

440V

480V

380V

416V

220V

240V

440V

480V

380V

416V

220V

240V

440V

480V

380V

416V

220V

240V

440V

480V

208V

220V

240V

208V

220V

240V

208V

220V

240V

208V

220V

240V

424

454

456

456

394

410

410

410

451

483

500

511

469

500

518

530

kW

339

363

365

365

315

328

328

328

361

386

400

409

375

400

414

424

47.2 S4

kVA

450

480

500

512

396

442

442

465

475

513

533

550

500

530

550

581

kW

360

384

400

410

317

354

354

372

380

410

426

440

400

424

440

465

47.2 S5

kVA

475

510

531

570

441

473

493

518

503

543

566

592

527

562

585

625

kW

380

408

425

456

353

378

394

414

402

434

453

474

422

450

468

500

47.2 M7

kVA

562

610

625

625

523

566

581

590

600

651

669

680

625

668

690

700

kW

450

488

500

500

418

453

465

472

480

521

535

554

500

534

552

560

47.2 M8

kVA

562

610

630

690

523

566

587

632

600

651

672

729

625

671

705

750

kW

450

488

504

552

418

453

470

506

480

521

538

583

500

537

564

600

47.2 L9

kVA

602

661

685

750

556

609

634

675

643

707

734

780

667

728

763

825

kW

482

529

548

600

445

487

507

540

514

566

587

624

534

582

610

660

380V

416V

440V

480V

380V

416V

440V

480V

380V

416V

440V

480V

380V

416V

440V

480V

220V

240V

220V

240V

220V

240V

220V

240V

kVA

602

661

685

750

556

609

634

675

643

707

734

780

667

728

763

825

kW

482

529

548

600

445

487

507

540

514

566

587

624

534

582

610

660

47.2 L9*

* AREP excitation only

LSA 47.2 - 4 Pole


Efficiencies 50 Hz - P.F. : 1 / P.F. : 0,8
LSA 47.2 M7

LSA 47.2 VS 2
96%

97%

95.4
95.5

95

96

92.6

96.1

95

93.3 P.F. : 0,8

93.8

93.8

93

96.2

95.8

94

P.F. : 1

96.2

P.F. : 1

95.3

95.1

94

93

94.5

94.9

94.8

94.3

P.F. : 0,8

93.5

93

92

92.8

91.7

91
50

92

100

150

200

250

300

350

400

100 150

450 kVA

200

250

300

400

450

500

550 kVA

LSA 47.2 M8

LSA 47.2 S4
97%

97%

96.1 P.F. : 1

95.9

96

P.F. : 1

95.9

94.1

93.1

93.8

96

95

94.4

94.9

94.2

94

P.F. : 0,8

96.3

96.1

95

94.5

94.4

94

96

95.8

95.5

95

93

350

94.1
P.F. : 0,8

93.6

93

92.4

92

92
50

100

150

200

250

300

350

400

100

450 kVA

LSA 47.2 S5

300

97%

96

95.7
94.5

94

95.6

93.8

94

93.5
93.6

P.F. : 0,8

95,1

95,1

95

94.4

96.4

96

P.F. : 1

500

600 kVA

LSA 47.2 L9 (6 w.)


96.5

96.1

95.8

96
95

400

LSA 47.2 L9 (12 w.)

97%

93

200

96.3 96.2
P.F. : 1
96.2 96.1
94.7

95

94.4

94.5
94.3
P.F. : 0,8

94.2
93.5

93

92.8

92

92
50

100

150

200

250

300

350

400

450

500 kVA

100

200

300

400

500

600

700 kVA

Reactances Class H / 400 V - Time constants (ms)


VS2

S4

S5

M7

M8

L9

L9 (6f)

Kcc

Short-circuit ratio

0,38

0,37

0,33

0,41

0,32

0,37

0,38

Xd

Direct axis synchro.reactance unsaturated

336

322

357

307

360

330

325

Xq

Quadra. axis synchr.reactance unsaturated

201

193

214

184

216

198

195

Open circuit time constant

1738

1855

1855

1930

1958

1997

1997

Xd

Direct axis transient reactance saturated

19,3

17,3

19,2

15,9

18,3

16,5

16,2

Td

Short-Circuit transient time constant

100

100

100

100

100

100

100

X"d

Direct axis subtransient reactance saturated

13,5

12,1

13,5

11,1

12,9

11,4

11,6

Tdo

T"d

Subtransient time constant

10

10

10

10

10

10

10

X"q

Quadra. axis subtransient reactance saturated

18,4

16,3

18

14,7

17

15

15,2

Xo

Zero sequence reactance unsaturated

0,9

0,9

0,9

0,7

0,6

0,9

0,2

X2

Negative sequence reactance saturated

16

14,2

15,8

13

15

13,2

13,4

Ta

Armature time constant

15

15

15

15

15

15

15

Other data - Class H / 400 V


io (A)

No load excitation current

0,9

0,9

0,9

0,9

0,9

ic (A)

Full load excitation current

3,8

3,5

3,8

3,6

3,7

3,7

3,7

uc (V)

Full load excitation voltage

39

35

38

36

37

36

36

Recovery time (U = 20 % trans.)

500

500

500

500

500

500

500

ms

kVA

Motor start. (U = 20% sust.) or (U = 50% trans.) SHUNT

722

928

928

1073

1159

1258

1258

kVA

Motor start. (U = 20% sust.) or (U = 50% trans.) AREP

805

1035

1035

1195

1294

1400

1400

Transient dip (rated step load) SHUNT / PF : 0,8 LAG

16,8

15,5

16,7

14,6

16,2

15

14,8

Transient dip (rated step load) AREP / PF : 0,8 LAG

13,7

12,7

13,6

11,9

13,2

12,2

12,1

No load losses

5440

5690

5690

6540

6120

6780

6880

Heat rejection

20780

20470

23780

23040

26020

27490

26720

LSA 47.2 - 4 Pole


Transient voltage variation 400 V - 50 Hz
Load application (SHUNT excitation)
VS 2

S4

Load application (AREP or PMG excitation)

S5

VS 2

25 %

25 %

M7

S4
S5

M8

M7

20

L9
6/12w

M8

% Voltage dip

% Voltage dip

20
15
10
5

L9

15

6/12w

10
5

0
0

100 200 300 400 500 600 700 800 kVA

100 200 300 400 500 600 700 800 kVA

kVA at 0,8 power factor

Load rejection (SHUNT excitation)

kVA at 0,8 power factor

Load rejection (AREP or PMG excitation)


VS 2

S4

S5

S4

VS 2

30%

S5

30%
M7

25

L9
6/12w

20
15

L9

20

6/12w

15

10

10

0
0

M8

25

% Voltage rise

% Voltage rise

M7

M8

100 200 300 400 500 600 700 800 kVA

100 200 300 400 500 600 700 800 kVA

kVA at 0,8 power factor

kVA at 0,8 power factor

Motor starting (SHUNT excitation)

S5
VS 2

S4

Motor starting (AREP or PMG excitation)


M7

35%

M8

30

L9
6/12w

VS 2

M8
L9
6/12w

% Voltage dip

25

20
15

20
15

10

10

S5
M7

30

25

% Voltage dip

S4

35%

0
0

200

400

600

800

kVA Locked rotor

1000

1200 kVA

200

400

600

800

1000

1200

1400 kVA

kVA Locked rotor

1) For a starting P.F. differing from 0,6, the starting kVA must be multiplied by (Sine /0,8)
2) For voltages other than 400V(Y) , 230V() at 50 Hz, then kVA must be multiplied by (400/U)2 or (230/U)2.

LSA 47.2 - 4 Pole


Efficiencies 60 Hz - P.F. :1 / P.F. : 0,8
LSA 47.2 M7

LSA 47.2 VS 2
96%

97%

95.3

95

P.F. : 1

95.2

95

93.4
93.7

93

93.3

92.3

91.7

91

100

200

300

400

500

100

kVA

200

300

95.7

95.6

94.3

93.9

93

P.F. : 0,8
93.8

91.7

91

700 kVA

96.1

95.9

95.6

95

94.4

94.2

94.8

94.7

94

92

600

96 P.F. : 1

96

94.1

94.9

94

500

97%

P.F. : 1

95.6

95

400
LSA 47.2 M8

LSA 47.2 S4
96%

94.4
P.F. : 0,8

94.3

92
90.4

90

94.7

93

P.F. : 0,8
91.1

94.5

95.2

94

93.1

92
91

96

95.9

94.4

94

P.F. : 1

96

96

95.1

93.2

P.F. : 0,8

93
92.6

91.1

92

90
100

200

300

400

500

100

600 kVA

200

LSA 47.2 S5
95.7

96%
95.7

95

400

LSA 47.2 L9 (12 w.)

95

P.F. : 0,8

94.3

96.1
95

94.8

93.7

96.2

P.F. : 1

94.7
94.6

93.1
92.4

92

93.2

93

91.7

92.5

91

800 kVA

96.1

94.9

94.7

94

700

LSA 47.2 L9 (6 w.)

96.2

95.7

93.9

93

600

96.2

96
94.1

500

97%

P.F. : 1
95.6

95.1

94

300

94.6

94.4
P.F. : 0,8

92.6

92
100

200

300

400

500

600

700 kVA

100

200

300

400

500

600

700

800 kVA

Reactances Class H / 480 V - Time constants (ms)


VS2

S4

S5

M7

M8

L9

L9 (6f)

Kcc

Short-circuit ratio

0,36

0,36

0,32

0,40

0,31

0,35

0,36

Xd

Direct axis synchro.reactance unsaturated

349

335

373

319

376

344

338

Xq

Quadra. axis synchr.reactance unsaturated

209

201

223

191

225

206

203

Tdo

Open circuit time constant

1738

1855

1855

1930

1958

1997

1997

Xd

Direct axis transient reactance saturated

20,1

18

20,1

16,5

19,2

17,2

16,9

Td

Short circuit transient time constant

100

100

100

100

100

100

100

X"d

Direct axis subtransient reactance saturated

14,1

12,6

14

11,6

13,4

11,8

12,1

T"d

Subtransient time constant

X"q

Quadra. axis subtransient reactance saturated

10

10

10

10

10

10

10

19,1

16,9

18,8

15,3

17,8

15,6

15,8

Xo

Zero sequence reactance unsaturated

0,1

0,4

0,1

0,1

X2

Negative sequence reactance saturated

16,6

14,8

16,5

13,5

0,9

0,9

0,4

15,6

13,7

Ta

Armature time constant

15

15

15

15

15

14

15

15

Other data - Class H / 480 V


io (A)

No load excitation current

0,9

0,9

0,9

0,9

0,9

ic (A)

Full load excitation current

3,9

3,5

3,9

3,7

3,8

3,7

3,7

uc (V)

Full load excitation voltage

40

35

39

37

38

37

37

ms

Recovery time (U = 20 % trans.)

500

500

500

500

500

500

500

kVA

Motor start. (U = 20% sust.) or (U = 50% trans.) SHUNT

890

1136

1136

1318

1433

1550

1554

kVA

Motor start. (U = 20% sust.) or (U = 50% trans.) AREP

994

1271

1271

1473

1606

1733

1737

Transient dip (rated step load) SHUNT / PF : 0,8 LAG

17,3

16

17,3

15

16,7

15,5

15,3

Transient dip (rated step load) AREP / PF : 0,8 LAG

14,1

13

14,1

12,2

13,6

12,6

12,4

No load losses

8540

8910

8910

10080

9530

10440

10580

Heat rejection

25650

25650

29340

28630

32190

33870

33010

LSA 47.2 - 4 Pole


Transient voltage variation - 480 V - 60 Hz
Load application (SHUNT excitation)

Load application (AREP or PMG excitation)


VS 2

S4

S5

VS 2

25 %

S4

25 %
M7

S5

M8

M7

L9
6/12w.

% Voltage dip

% Voltage dip

20
15
10

20

M8

15

L9
6/12w.

10

0
0

200

400

600

800

1000 kVA

200

kVA at 0,8 power factor

600

800

1000 kVA

kVA at 0,8 power factor

Load rejection (SHUNT excitation)

Load rejection (AREP or PMG excitation)


VS 2

30%

400

S4

S5

VS 2

30%

S4

S5

M8

20

L9
6/12w.

M7

% Voltage rise

% Voltage rise

M7

25

15

25

M8

20

L9
6/12w.

15

10

10

0
0

200

400

600

800

1000 kVA

200

kVA at 0,8 power factor

400

600

800

1000 kVA

kVA at 0,8 power factor

Motor starting (SHUNT excitation)

Motor starting (AREP or PMG excitation)


VS 2

S4

35%

S5

VS 2

35%

M7

M8

30

L9
6/12w.

L9
6/12w.

25

% voltage dip

25

% voltage dip

S5
M7

M8

30

S4

20
15

20
15

10

10

0
0

200

400

600

800

Locked rotor

1000

1200

1400 kVA

200

600

1000

1400

1800 kVA

Locked rotor

1) For a starting P.F. differing from 0,6, the starting kVA must be multiplied by (Sine /0,8)
2) For voltages other than 480V(Y), 277V(), 240V(YY) at 60 Hz, then kVA must be multiplied by (480/U)2 or (277/U)2 or (240/U)2.

LSA 47.2 - 4 Pole


3 phase short-circuit curves at no load and rated speed (star connection Y)
10000

Current (A)

LSA 47.2 VS2

AREP or PMG
1000

Symmetrical
Asymmetrical
100

SHUNT

10
1

10

100

1000

10000

time (ms)

10000

LSA 47.2 S4

AREP or PMG

Current (A)

1000

Symmetrical
Asymmetrical
100

SHUNT

10
1

10

100

1000

10000

time (ms)

10000

LSA 47.2 S5

AREP or PMG

Current (A)

1000

Symmetrical
Asymmetrical
100

SHUNT

10
1

10

Inuence due to connexion.


Curves shown are for star connection (Y).
For other connections, use the following multiplication factors :
- Series delta : Current value x 1,732
- Parallel star : Current value x 2

100

1000

10000

time (ms)

LSA 47.2 - 4 Pole


3 phase short-circuit curves at no load and rated speed (star connection Y)
10000

Current (A)

LSA 47.2 M7

AREP or PMG
1000

Symmetrical
Asymmetrical
100

SHUNT

10
1

10

100

1000

10000

time (ms)

10000

LSA 47.2 M8

AREP or PMG

Current (A)

1000

Symmetrical
Asymmetrical
100

SHUNT

10
1

10

100

1000

10000

time (ms)

10000

LSA 47.2 L9
(6w / 12 w)

AREP or PMG

Current (A)

1000

Symmetrical
Asymmetrical
100

SHUNT

10
1

10

100

1000

10000

time (ms)

Influence due to short-circuit.


Curves are based on a three-phase short-circuit.
For other types of short-circuit, use the following multiplication factors :
3 phase

2 phase L - L.

1 phase L - N.

Instantaneous (Max)

0,87

1,3

Sustained

1,5

2,2

Max sustained duration (AREP/ PMG)

10 sec.

5 sec.

2 sec.

LSA 47.2 - 4 Pole


Single bearing dimensions
L

Y DIA, X Eq.Sp holes on U P.C.D.

LB
Xg

AH
14,5

A.V.R.

740
560

49
17

330
CF

Cable

867

512
0

2 x 13

12

206
62

89,3

355 - 1

235

616

- 0,050

BX - 0,100

N - 0,127

PMG option

AIR INLET

68
180

228

244

28

AIR OUTLET

610
710

Access to rectifiers

530

50

130 90

S DIA, XBG Eq. Sp. holes on M P.C.D.

FRAME DIMENSIONS (mm)


TYPE
L max without PMG
LSA 47.2 VS2
1041

LB
996

Xg
437

Weight(kg)
976

LSA 47.2 S4

1101

1056

471

1113

Flange S.A.E 1

LSA 47.2 S5

1101

1056

471

1113

Flange S.A.E 1/2

LSA 47.2 M7

1201

1156

511

1240

Flange S.A.E 0

LSA 47.2 M8

1201

1156

520

1289

LSA 47.2 L9

1221

1176

545

1372

X
8

Y
11

AH
39,6

S
12

15

CF
15

14

Flex plate dimensions (mm)


S.A.E.
BX
U
11 1/2
352,4
333,38

18

1/2

713

584,2

619,125

12

14

15

22

14

466,7

438,15

14

25,4

713

647,7

679,45

16

14

11

42

18

571,5

542,92

17

15,7

75

XBG
12

111/2

110

M
530,225

Flex plate

115

Flange dimensions (mm)


S.A.E.
P
N
1
713
511,175

COUPLING

Torsional analysis data

120

115

106

75

Xr

Lr

Gravity center : Xr (mm), Rotor length Lr (mm), Weight : M (kg), Moment of inertia : J (kgm2) : (4J = MD2)
Flex plate S.A.E. 11 1/2
Flex plate S.A.E. 14
Flex plate S.A.E. 18
TYPE
Xr
Lr
M
J
Xr
Lr
M
J
Xr
Lr
M
432,5
1029
387
5,99
418,3
1029
387
6,12
408,5
1029
387
LSA 47.2 VS2

6,38

LSA 47.2 S4

470

1089

442

6,90

456

1089

442

7,03

446

1089

442

7,29

LSA 47.2 S5

470

1089

442

6,90

456

1089

442

7,03

446

1089

442

7,29

LSA 47.2 M7

510

1189

495

7,61

496

1189

495

7,74

486

1189

495

LSA 47.2 M8

521

1189

514

8,01

507

1189

514

8,14

497

1189

514

8,40

LSA 47.2 L9

542

1209

547

8,52

528

1209

547

8,65

518

1209

547

8,91

10

LSA 47.2 - 4 Pole


Two bearing dimensions
L

AVR access

LB

740

Xg

560

17

Cable

2 x 13

472

12

90
62

89,3

355 - 1

235

867

14

616

85 m6

552

511,175 - 0,127

713

PMG option

512

355

1 hole M20x42

15

49

22

130

68

AIR OUTLET
205

FRAME DIMENSIONS (mm)


TYPE
LSA 47.2 VS2

130 130

28

AIR INLET

515

50

610
710

130 90

M10 DIA, 12 ep. sp. hole on 530,225 PCD

Diode access

L maxi without PMG


1151

LB
1021

Xg
457

Weight (kg)
996

LSA 47.2 S4

1211

1081

491

1126

LSA 47.2 S5

1211

1081

491

1126

LSA 47.2 M7

1311

1181

531

1253

LSA 47.2 M8

1311

1181

531

1302

LSA 47.2 L9

1331

1201

565

1392

Torsional analysis data

Xr

75

110

115

120

115

106

90

85

130

Lr

Gravity center : Xr (mm), Rotor length Lr (mm), Weight : M (kg), Moment of inertia : J (kgm2) : (4J = MD2)
TYPE
Xr
Lr
M
LSA 47.2 VS2
396,4
1139
368,5

J (kg)
5,79

LSA 47.2 S4

433,2

1199

424

6,70

LSA 47.2 S5

433,2

1199

424

6,70

LSA 47.2 M7

473

1299

476,2

7,41

LSA 47.2 M8

483,5

1299

494,9

7,81

LSA 47.2 L9

504,5

1319

528

8,32

11

LEROY-SOMER 16015 ANGOULME CEDEX - FRANCE


RCS ANGOULME N B 671 820 223
S.A. au capital de 62 779 000

www.leroy-somer.com

You might also like