DIGISTAR Start Option
DIGISTAR Start Option
DIGISTAR Start Option
95
COM-START
DIGISTART
MODE / MEM.
RESET
@ / DATA
STV 2313
ETATS : CODE FIXE
Absence rseau
Moteur hors tension
Acclration
En fonctionnement
Dclration
Coupure rseau
Dmarrage trop long
Thermique thyristors
Absence de phase
Microcoupure
Thermique moteur
Sur puissance
Sous puissance
Dfaut interne
Run
Stop
Rotor bloqu
Thermique dissipateur
Thyristor(s) en court circuit
Thyristor(s) ouvert(s)
Inversion sens de rotation
Nombre de dmarrages limit
Inhibit
Autres dfauts (voir notice)
ES-START
RV-START
10
11
12
CDC - START
7 .2 8 - :
no
A N L G R E F :o f f s I ?
PAR
MODE
RUN
Mem
STOP
RESET
PLEASE CONTACT US AT :
START OPTIONS
Options for DIGISTART STV 2313
Installation
Imprimerie MOTEURS LEROY-SOMER
RC ANGOULEME B 671 820 223
NOTE
LEROY-SOMER reserves the right to modify its product characteristics at any time to
incorporate the latest technological developments. The information contained in this
document may therefore be changed without prior warning.
LEROY-SOMER gives no contractual guarantee whatsoever concerning the information
published in this document and cannot be held responsible for any errors it may contain, nor
for any damage arising from its use.
Other OPTIONS
1 - UR - START
2 - IP20 - START
DIGISTART
IP 20 - START
reference
37
60 and 86
145 to 250
Height
IP 20 - START added to
the
STV 2313
Reference
(mm)
120
140
70
20
65
65
200
220
Weight (kg)
Net
Packed
100
1.2
1.70
100
1.6
2.15
130
1.6
2.15
122
For the user's own safety, the STV 2313 starter must be connected to an approved earth
(B terminal).
Power electronic equipment such as speed controllers, soft starters and inverters cannot be
used as circuit-breaking or isolating devices as specified in standard EN 60204 - 1 (1992),
section 5.
CAUTION
For the safety of personnel and equipment, LEROY-SOMER prohibits the use of the
DIGISTART STV 2313 for hoisting applications.
If an accidental start of the installation represents a risk for personnel or the machinery to be
driven, it is imperative to supply the equipment via an isolating device and a circuit-breaking
device (power contactor) controllable by an external safety system (emergency stop, fault
detector).
The electronic starter is fitted with safety devices which can, in the case of certain faults, stop
the starter and the motor. The motor can itself be jammed by mechanical means. Finally,
voltage fluctuations, and particularly power cuts, can also cause the starter to switch off.
The removal of the cause of the shutdown can lead to restarting, with consequent hazard for
certain machines or installations.
In such cases, it is essential that the user takes appropriate precautions against restarting
when the motor makes an unscheduled stop.
Although this equipment complies with current construction standards, it may cause
interference. The user must then take any necessary steps to eliminate it.
LEROY-SOMER declines all responsibility in the event of the above recommendations
not being observed.
DANGER
IMPORTANT
BEFORE ANY INTERVENTION, WHETHER TO DO WITH THE ELECTRICS OR THE
MECHANICS OF THE INSTALLATION OR MACHINE :
- ensure that the power to the starter has been switched off (fused isolator or circuit-breaker)
and locked manually,
- wait 1 minute before any intervention.
30
FR - START
module
3.4 - Connecting the power supply
3.4.1 - FR - START 86 module
As the FR - START 86 module has no
forced ventilation unit, it is not necessary
to provide an external 230V or 400V power
supply.
3.4.2 - FR - START modules 250 to 900
FR - START modules 250 to 900 have
forced ventilation units. They must therefore
have an external power supply
START OPTIONS
CONTENTS
Pages
CDC - START ............................................................... 6 to 9
RV - START................................................................... 10 to 14
ES - START ................................................................... 15 to 20
FR - START ................................................................... 21 to 29
Function
Supply used
with 230V or
N/L
400V
Supply used with
230V
N/L
Supply used with
400V
N/L
Elect. char.
Single phase
230V, 50/60Hz
Single phase
400V, 50/60Hz
Not used
Volt-free
ST1
FR - START *
thermal
protection
16A
ST2
at 250V
28
FR - START
module
3 - CONNECTION
CDC - START
console
F.V. Resistor
Control circuit
1
1
Input Output
Terminal blocks
for connecting
FR - START
module
to the STV
N/L
ST1
230V 400V
Power supply
V/T2
ST2
Thermal probe *
W/T3
F.V. Transformer
Control circuit
1
1
Input Output
Terminal blocks
for connecting
FR - START
module
to the STV
N/L
230V 400V
FV power supply
V/T2
26
W/T3
ST1
1 - GENERAL INFORMATION
ST2
Thermal probe *
FR - START
module
CDC - START
console
2.3 - Installation
L2
P2
D1
L1
FR-START
CDC - START
7 .2 8 - :
no
A N L G R E F :o f f s I ?
H2 H1
PAR
MODE
RUN
Mem
STOP
RESET
21
44.5
rating
86
250
530
900
Mounting
H1
150
150
200
200
points (mm)
L1
168
168
335
335
D1
10
10
Overall
H2
170
210
320
320
dimensions
P2
100
120
320
320
L2
209
209
370
370
(kg)
10
10
Weight
37
97
4 holes 3.5
146.5
3 - CONNECTION
Power supply : provided by the STV 2313
to which the console is connected.
Remote installation : max. length 5 m.
4 - COMMISSIONING
Refer to the CDC - START manual, ref. 1814.
24
FR - START
module
1 - GENERAL INFORMATION
1.1 - Operating principle
When connected to the DIGISTART
STV 2313 the FR - START module enables
D.C. injection between 2 motor phases
and thus provides access to the following
additional functions.
1.1.1 - Braking before starting
In certain appications the rotor may be
backdriven when the motor is not powered
up. When a start command is given, this function brakes the free wheeling motor to a stop
before commencing the starting phase.
- Maximum braking torque : 2.5 rated torque,
can be adjusted by programming.
- Applications : ventilation units, deep well
pumps, etc.
1.1.2 - Braking during deceleration
In the case of high inertia applications, this
function shortens the natural stopping
time. As soon as the stop command is
given, the STV injects a D.C. current
between 2 motor phases, producing a
braking torque.
- Maximum braking torque : 2.5 rated torque,
can be adjusted by programming.
- Applications : crushers, saws, grinding
machines, etc.
1.1.3 - Motor anti-condensation
Keeps the motor free of condensation
while it is stopped by circulating D.C.
current between 2 phases.
- Start of injection with delay time after
stopping.
- End of injection as soon as the command
is given to restart the motor.
- Adjustable current level.
RV - START
module
1 - GENERAL INFORMATION
1.1 - Operating principle
When connected to the DIGISTART
STV 2313, the RV - START module
provides speed feedback data so that
gradual and repeated starts are possible,
whatever the load on the driven machine.
It is particularly well-suited for equipment
whose load may vary widely from one start
to the next.
Applications :
Starting conveyors, elevators, mixers, ball
mills, pelleting machines, roll mills, etc.
In addition, the RV - START module has a
logic input which is used for setting dual
parameters on the STV if a 2-speed motor
is used.
Open contact on input :
start and protect speed 1.
Closed contact on input :
start and protect speed 2.
The following three types of speed feedback can be chosen for the RV - START
module :
Power supply :
230V (- 20% + 5%) 50/60 Hz 5%.
or
400V (- 15% + 10%) 50/60 Hz 5%.
Consumption : 10 VA.
RV - START
195
170
60
Weight : 1 kg.
22
11
ES - START
module
RV - START
module
Ref.
EA1
0V
}
}
}
}
Description
4-20mA or 0-10V analogue
input
CTP1
CTP2
CTP3
CTP4
SA1
0V
SA2
EL1
0V
EL2
SL1
SL1
SL2
SL2
Functions / Characteristics
The type of signal is selected by
programming
The ES - START module is supplied with
terminals 3 and 7 linked together.
- For 1 PTC probe (or 1 set) : connect
between terminals 3 and 7, having
removed the link between them.
- For several probes (or several sets) :
wire them in series between terminals
3, 4, 5, 6 and 7.
The type of output signal is selected by
programming.
Use volt-free contacts according to the
intended use.
20
3
+ -
* If the circuit is open between terminals 3 and 7, the display will indicate "FAULT PTC
SENSORS".
4 - COMMISSIONING
Function
Elect. char.
Power supply Single phase
N/L - 230V
for
230V - 50/60Hz
Single phase
N/L - 400V RV-START
400V - 50/60Hz
Note : If the module is supplied with 230V,
the plastic plug must be removed from the
230V terminal.
IMPORTANT : The STV 2313 and the RV
- START module must have the same
power supply and they must be
powered up simultaneously.
Do not forget to connect the power
supply earth wire to the B terminal.
3.4.2 - Cable diameter
Use twisted cable, diameter 1.5mm2.
13
ES - START
module
ES - START
module
2 - MECHANICAL INSTALLATION
3 - CONNECTION
2.3 - Installation
The fixing holes inside the casing of the
ES - START module are designed so that
it can be installed via the back plate (flat)
or via the side plate. As the connection
block is across the whole width of the module, access is easier if it is installed flat.
85
CONTENTS
ES - START
module
power supply
N/L 230 400
Input
Output
Pages
1 - GENERAL INFORMATION
1.1 - Operating principle ................................................. 16 - 17
1.2 - General description ................................................
17
1.3 - General characteristics............................................ 17
1.4 - Dimensions and weight...........................................
17
2 - MECHANICAL INSTALLATION
2.1 - Inspection on receipt...............................................
2.2 - Installation precautions ...........................................
2.3 - Installation...............................................................
18
18
18
3 - CONNECTION
3.1 - General recommendations .....................................
3.2 - Location of terminal blocks......................................
3.3 - Connecting the ES - START module to the STV ....
3.4 - Connecting the power supply .................................
3.5 - Connecting the Inputs / Outputs .............................
18
18
19
19
20
4 - COMMISSIONING
4.1 - Access to parameter setting....................................
4.2 - Setting the parameters of the DIGISTART..............
20
20
30
170
Back
Side
1
Earth terminal
18
Input connection
terminals
15
ES - START
module
1 - GENERAL INFORMATION
1.1 - Operating principle
When connected to the DIGISTART
STV 2313 the ES - START module provides
access to the following Inputs / Outputs :
1.1.1 - Two logic inputs
Volt-free contact input assigned to the
management of external trips and / or multisetting of the STV.
External trips
Tripping and disabling of the STV when
the contact connected to the input is open.
Management by the STV of external safety
devices (PTO temperature probes, pressure
sensors, limit switches, etc).
Multi-setting
Ability to use 2 sets of preset parameters
by closing a contact on one of the logic
inputs, or 4 sets of preset parameters by
combining 2 contacts on the 2 logic inputs.
Applications :
- Cascaded starting of several motors of
differing powers or requiring different starting parameters.
- Starting and protection of a 2-speed
motor :
parameter set 1 : low speed,
parameter set 2 : high speed.
- Machines which generally start without
load but which may occasionally start
under load.
Parameter set 1 : no-load start.
Parameter set 2 : start under load.
16
ES - START
module
Selection
Parameter 1
Parameter 2
195
EL1
EL2
Selection
Parameter 1
Parameter 2
Parameter 3
Parameter 4
170
60
Weight : 1 kg.
17
RV - START
module
3.5 - Connecting the inputs
3.5.1 - Description of the terminal block
This has 9 screw terminals which will take multicore cables up to 2.5 mm2 diameter.
3.5.2 - Description of the terminals
No.
1
2
3
4
5
6
7
8
9
Ref.
Bk (E)
Br (+)
BI (-)
CT1
CT2
0V
CA
2V1
2V2
Description
Inductive sensor black wire
Inductive sensor brown wire
Inductive sensor blue wire
Input for A.C. or D.C. tachometer
Functions/Characteristics
Connection of a 3-wire PNP or
programmable inductive sensor.
ES - START
module
3.3 - Connecting the ES - START
module to the STV 2313
3.3.1 - STV with no options :
- Use the screened cable (34-pin) supplied
for this purpose.
- Switch off the power supply to the basic
STV to which the option is to be connected.
- Remove the cover of the basic STV
control module.
Signal between :
20V and 220V D.C. or A.C.
4-20mA signal
+ -
4 - COMMISSIONING
Ref.
Function
Elect. char.
Single phase
230V
N/L - 230V Power supply
for
50/60Hz
ES - START Single phase
400V
N/L - 400V
50/60Hz
Note : If the module is supplied with 230V,
the plastic plug must be removed from the
230V terminal.
IMPORTANT : The STV 2313 and the ES
- START module must have the same
power supply and they must be
powered up simultaneously.
Do not forget to connect the power
supply earth wire to the B terminal.
3.4.2 - Cable diameter
Use twisted cable, diameter 1.5mm2.
14
19
RV - START
module
FR - START
module
2 - MECHANICAL INSTALLATION
3 - CONNECTION
2.3 - Installation
The fixing holes inside the casing of the
RV - START module are designed so that
it can be installed via the back plate (flat) or
via the side plate. As the connection block is
across the whole width of the module, access is easier if it is installed flat.
85
CONTENTS
Pages
1. GENERAL INFORMATION
1.1 - Operating principle ......................................................................
22
1.2 - General description .....................................................................
23
1.3 - General characteristics ...............................................................
23
1.4 - Dimension and weights ............................................................... 23 - 24
2. MECHANICAL INSTALLATION
2.1 - Inspection on receipt ...................................................................
2.2 - Installation precautions ...............................................................
2.3 - Mounting .....................................................................................
25
25
25
RV - START
module
power supply
N/L 230 400
Input
Output
30
3. CONNECTION
3.1 - Location of terminal blocks..........................................................
3.2 - Connecting the FR - START control board to the STV 2313.......
3.3 - Connecting the power terminals between the FR - START
and the STV.........................................................................................
3.4 - Connecting the power supply.......................................................
27
28
4. COMMISSIONING
4.1 - Access to parameter setting .......................................................
4.2 - Setting the parameters of the DIGISTART..................................
29
29
26
27
170
Back
Side
1
Earth terminal
12
Input connection
terminals
21
RV - START
module
FR - START
module
Pages
1 - GENERAL INFORMATION
1.1 - Operating principle .........................................................
1.2 - General description.........................................................
1.3 - General characteristics...................................................
1.4 - Dimensions and weight ..................................................
2 - MECHANICAL INSTALLATION
2.1 - Inspection on receipt.......................................................
2.2 - Installation precautions...................................................
2.3 - Installation.......................................................................
3 - CONNECTION
3.1 - General recommendations.............................................
3.2 - Location of terminal blocks.............................................
3.3 - Connecting the RV - START module to the STV 2313...
3.4 - Connecting the power supply.........................................
3.5 - Connecting the inputs.....................................................
CONTENTS
11
11
11
11
Example : FR - START 14 - 86
- FR - START : D.C. injection option module.
- 14 : supply voltage code
14 : 208 V to 500 V.
16 : 500 V to 690 V.
12
12
12
30
FR - START size
86
145
86
211
250
365
250
530
700
530
900
900
Control supply
Voltage
No
Frequency
supply
50/60 Hz 5%
Maximum current
12
12
13
13
14
60
Consumption
0VA
20VA
40VA
Operating conditions
0C to 40C
Protection index
IP 00
4 - COMMISSIONING
4.1 - Access to parameter setting...........................................
4.2 - Setting the parameters of the DIGISTART.....................
14
14
L2
P2
L1
FR-START
H2
H1
D1
10
23
CDC - START
console
FR - START
module
2 - MECHANICAL INSTALLATION
165
5
15
20
CDC - START
113
INITIALISATION
OF SOFTSTARTER
85
PAR
MODE
RUN
Mem
STOP
RESET
2 - MECHANICAL INSTALLATION
2.1 - Inspection on receipt
2.3 - Mounting
A set of fixing feet for mounting is supplied
with the FR - START 86 and 250 ratings.
Slide the foot into the groove provided for it
in the heat sink. It may be necessary to
use a centre punch in order to keep it in
place and make handling easier when
mounting the FR - START in the cubicle.
Note : For the 250 rating, locate the longest fixing feet on the ventilation unit side.
21 117 117
Centre
punch
25
CDC - START
console
FR - START
module
CONTENTS
1 - GENERAL INFORMATION
1.1 - Operating principle ..........................................
1.2 - General description .........................................
1.3 - Dimensions and weight ...................................
7
7
8
2 - MECHANICAL INSTALLATION
2.1 - Inspection on receipt...........................................
2.2 - Installation precautions ...................................
2.3 - Installation .......................................................
8
8
9
3 - CONNECTION ........................................................
4 - COMMISSIONING ..................................................
2
+ -
FR - START
rating
86
250
530
900
Diameter
(mm2)
16
50
120
2 x 120
Length
(mm)
500
700
1000
1000
27
FR - START
module
START OPTIONS
4 - COMMISSIONING
PREFACE
4.1 - Access to parameter setting
This manual describes how to install and connect the main options for the STV 2313
electronic starter.
Electronic starter
Communication (option)
COM-START CDC-START
RS 485
serial link
MODBUS
protocol
COM-START
Standard extensions
STV 2313
Removable
console
CDC - START
7 .2 8 - :
no
A N L G R E F :o f f s I?
DIGISTART
MODE / MEM.
PAR
MODE
RUN
FR-START
RESET
ES-START RV-START
@ / DATA
ES-START
Mem
STV 2313
STOP
RESET
FR-START
ETATS : CODE FIXE
Coupure r seau
D marrage trop long
Thermique thyristors
Absence de phase
Microcoupure
Thermique moteur
Sur puissance
Sous puissance
D faut interne
Run
Stop
Rotor bloqu
Thermique dissipateur
Thyristor(s) en court circuit
Thyristor(s) ouvert(s)
Inversion sens de rotation
Nombre de d marrages limit
Inhibit
Autres d fauts (voir notice)
10
11
RV-START
Absence r seau
Moteur hors tension
Acc l ration
En fonctionnement
D c l ration
ES-START
FR - START
86
12
170
170
155
150
140
140
Gearboxes
parallel shaft
Options
D.C.
tachometer
COMPABLOC 2000
helical bevel
ORTHOBLOC 2000
Induction motor
FR - START
250
300
270
265
260
530
820
FR - START
A.C
tachometer
285
FR - START
300
765
735
690
660
900
0.1 to 10
1400
1300
1245
1220
1200
Note :
- The maximum current is the D.C. current measured in the V and W phases of the FR - START.
- The currents shown in the above tables are defined for 1 braking operation every 10 min.
For more severe operating cycles please consult LEROY-SOMER.
planetary gears
Brake
PLANIBLOC 2000
29
Other OPTIONS
3 - COM - START
The MODBUS network interface used with starters in the DIGISTART STV 2313 range,
extends the communication capabilities of the basic product, using the settings mode to
configure and control the DIGISTART, and the read mode to access all the DIGISTART's data.
MODBUS
NETWORK
INTERFACE
Modbus
network
DIGISTART
Read
Set parameters
Start/Stop
MODE / MEM.
RESET
@ / DATA
STV 2313
ETATS : CODE FIXE
CDC - START
Absence rseau
Moteur hors tension
Acclration
En fonctionnement
Dclration
Coupure rseau
Dmarrage trop long
Thermique thyristors
Absence de phase
Microcoupure
Thermique moteur
Sur puissance
Sous puissance
Dfaut interne
Run
Stop
Rotor bloqu
Thermique dissipateur
Thyristor(s) en court circuit
Thyristor(s) ouvert(s)
Inversion sens de rotation
Nombre de dmarrages limit
Inhibit
Autres dfauts (voir notice)
7 .2 8 - :
no
A N L G R E F :o f f s I ?
PAR
10
11
12
MODE
RUN
Mem
Read
Start/Stop
STOP
RESET
Read
Set parameters
Start/Stop
A short description of the MODBUS protocol, and the mounting and connection instructions
are given in the installation manual supplied with COM - START units, or on request.
4 - DER - START
The DER - START kit is designed to enable
connection of a bypass contactor to the
DIGISTART STV 2313 thyristor terminals
(365 to 900 ratings). System losses are
thus decreased while maintaining all
monitoring, protection and recording of the
DIGISTART STV 2313 faults.
DIGISTART
DER - START
reference
31