Intelligent Addressable BMS and Networking Interfaces
Single Mode Lon to Fibre Optic Adaptor
CFSFL01 - Single Mode Lon to Fibre Optic Adaptor
Overview
Benefits
The single mode Lon to fiber optic adapter
(CFSFL01) allows connection the of Cooper
system network (LonWorks) devices through
optical fiber, and to allow both point to point or
multi drop topology.
Simple to install
Easy to use
Extends Cooper panel
network
Fast response
Using only single mode fiber optic, the
(CFSFL01) adapter allows extension of the
Cooper system network LonWorks to a
maximum distance of 15km with a transmission
speed of up to 78Kbit/s or 1.25Mbit/s.
Connection is made using SC type fibre optic
connectors. In comparison with conventional
twisted pair cable, the fibre optic usage in a
LonWorks network has many advantages; it is
reliable and fast in long distance network
transmission even in difficult industrial
environments (with transients, surges or
electromagnetic interference etc.) without
requiring any additional transient protection.
Single Mode Lon to Fibre Optic Adaptor - CFSFL01
Dimensions
4mm
Technical Specification
36mm
5mm
12mm
Code
CFSFL01
Description
Single Mode Lon to Fibre Optic Adaptor
Specification
90mm
115.5mm
10mm
100mm
52mm
Operating Voltage
100mm
20mm
135mm
24V dc
Communication Protocol
LonWorks
LonWorks Connectors
Screw terminal block
LonWorks Rate
78 Kbps / 1.25 Mbps
Bit Error Rate
10e-9
Wavelength
1310nm
Fiber Type
Single mode fiber
Fibre Diameter
9/125 micron
Fibre Connector
SC type (optional ST type)
Link Distance
15km
Environmental
Operating Temperature
-30C to +70C
Humidity (Non Condensing)
20 to 90% RH
Physical
Dimensions (H x W x D)
Typical System Architecture
CFSFL01
Single-Mode
Fiber
Lon-Fiber
ADAPTOR
CFSFL01
LonWorks
NODE
Control Panel
&
Network Card
Fiber Optic Star Topology Link
LonWorks
NODE
Single-Mode Fiber
Single-Mode Fiber
CFSFL02
Terminals
SC type
connectors
TXD RXD POW
Lon-Fiber
ADAPTOR
LonWorks
Single-Mode Fiber
LonWorks
Single-Mode Fiber
LonWorks
CFSFL02
Lon-Fiber
ADAPTOR
1. Ensure that the power supply is switched off
during installation.
2. Take care when inserting the fibre optic
connector to avoid damage. Note that the
"RX" connector in the local modules port
should connect to the "TX" connector in the
far end modules port and vice versa.
3. LonA connects to Net_A of the LonWorks
Bus (network card), LonB connects Net_B.
Mechanical Layout and Connections
LonWorks
Lon-Fiber
ADAPTOR
Installation
CFSFL02
LonWorks
NODE
LonWorks
NODE
LonWorks
NODE
Control Panel
&
Network Card
Control Panel
&
Network Card
Control Panel
&
Network Card
Fiber
OUT
TX
Fiber
IN
RX
TX
RX
GND
LonA
LonB
DC24V
Control Panel
&
Network Card
Lon-Fiber
ADAPTOR
LonWorks
LonWorks
NODE
LonWorks
Fiber Optic Point to Point Link
36mm x 116 mm x 135mm
+
-
LonWorks Fiber Optical Adaptor
GND
LONA
LONB
10
9
8
7
6
5
4
3
2
1
+
Unused
Unused
Unused
Unused
Unused
GND
LONA
LONB
Network Screen Connecttion
Net_A of Network Card
Net_B of Network Card
Fiber Transmitting
Fiber Receiving
Network Screen
Net_A
Net_B
LED Indication
POW
TXD
RXD
Power On Indication
Fibre Port Transmitting Data
Fibre Port Receiving Data
on
Flashing
Flashing
Power On
Working
Working
Product Codes
Code
CFSFL01
Description
Single Mode Lon to Fibre Optic Adaptor
Descriptions represent only particulars of the goods to which they apply and do not form part of any contract. The company reserves the right to change specification without prior notification or public announcement.
Cooper Lighting and Safety Ltd, Wheatley Hall Road, Doncaster, South Yorkshire, DN2 4NB. UK.
T: +44 (0) 1302 303350 l F: +44 (0) 1302 303332 l E: [email protected] l W: www.cooperfire.com