5-7-9-11 kVA

GB

005 DRWNETRT-XX

Installation and operating manual

WARRANTY CERTIFICATE AND CONDITIONS


This SOCOMEC UPS appliance is guaranteed against possible defects of manufacture and materials, for a period of 12 months from
the date of purchase (local warranty conditions are applicable in addition to the general conditions). The present warranty certificate
should NOT be mailed, but kept by the customer together with the proof of purchase document, for use in the event of a claim being
made for repairs or replacement under warranty.
The warranty period runs from the date on which the new product was purchased by the end user at the showroom of an official
resaler (the reference data is that indicated on the proof-of-purchase document).
The warranty is offered on carry-in terms: components and labour for repairs supplied free of charge, and in the case of a replacement, the product to be returned to SOCOMEC UPS or to authorized service centres, at the customers own risk and expense.
To claim service under warranty, the user must abide by the following rules:
The product is to be returned only in the original packing. Any damage occurring in transit to a product not in its original packing
will not be covered by the warranty;
The product must be accompanied by proof of purchase: a document (delivery note, invoice, counter receipt) indicating the date
of the purchase, which must also indicate the essential identification data for the product (model, serial numer). The sender must
also attach the acceptance number issued to authorize the return of the product, together with a detailed description of the defect
encountered. If any of these elements is missing, the warranty will be invalidated. The authorization number is issued by service
centres over the telephone, after being informed of the malfunction in respect of which a claim is submitted;
Should it be impossible to furnish proof of purchase, the serial number and date of manufacture will be used to calculate the
probable expiry date of the warranty; this could result in a reduction of the original warranty period.
The warranty on the product does not cover damage occasioned by thoughtlessness (improper use: wrong input power, explosions,
excessive humidity, temperature, poor ventilation, etc.), tampering or any unauthorized repair work.
During the warranty period, SOCOMEC UPS remains at liberty to decide whether the product should be repaired, or whether to
replace defective parts with new parts, or with used parts that are equivalent to new parts in terms of functionality and performance.
In the case of batteries, warranty is valid only if the battery has been recharged periodically in accordance with the manufacturers
directions. Accordingly, it is advisable to check, following purchase, that the date of the next recharge indicated on the packing
has not expired.
Optionals.
A 12-month carry-in warranty is offered on optionals.
Software products.
Software products are guaranteed for 90 days. The software is guaranteed to work substantially as indicated in the manual accompanying the product. Hardware media or accessories (e.g. diskettes, cables, etc.) used with appliances are guaranteed free of
material or manufacturing defects under normal conditions of use for a period of 12 months from the date of purchase.
On no account will SOCOMEC UPS ackowledge liability for damages (including loss of income, interruption of business activity, loss
of information or other economic losses, of whatever magnitude) deriving from the use of the product.
The present conditions are regulated by the laws of Italy. Disputes shall be submitted to the jurisdiction of the Vicenza Law
Courts.

SOCOMEC UPS retains the full and exclusive ownership rights over this document. Only a personal right to utilize the document for
the application indicated by SOCOMEC UPS is granted to the recipient of such document. All reproduction, modification, dissemination of this document whether in part or whole and by any manner are expressly prohibited except upon Socomecs express
prior written consent.
This document is not a specification. SOCOMEC UPS reserves the right to make any changes to data without prior notice.

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

TABLE OF CONTENTS
1. SAFETY STANDARDS 4
1.1 Important  4
1.2 Description of the symbols used on the labels applied to the unit 5

ENGLISH

2. INSTALLATION 6
2.1 Environmental requirements for installation 6
2.2 Electrical requirements  6
2.3 Vertical installation 7
2.4 Horizontal installation on rack 9
3. REAR VIEW 13
4. CONNECTIONS  14
4.1 Connection terminal strips  14
4.2 Connection of UPS 15
5. CONNECTION OF BATTERY EXTENSION 16
5.1 Safety warnings  16
5.2 Connection of battery extension 16
6. CONNECTION OF BY-PASS AND SINGLE UPS 18
6.1 Installation of BY-PASS and single UPS 18
6.2 Connection of BY-PASS to single UPS 19
7. CONNECTION OF BY-PASS AND UPS IN PARALLEL  23
7.1 Vertical installation of BY-PASS and UPS in parallel 23
7.2 Rack installation of BY-PASS and UPS in parallel 24
7.3 Connection of BY-PASS and UPS in parallel 25
7.4 Connection of BY-PASS to UPS in parallel 27
8. MIMIC PANEL 28
9. OPERATING MODES  29
9.1 Basic settings 29
9.2 Operation in BY-PASS mode for maintenance purposes - single UPS 30
9.3 Operation in BY-PASS mode - UPS in parallel for maintenance purposes  32
10. COMMUNICATION 33
10.1 Communication solutions 33
10.2 RS232 interface  33
10.3 Integrated WEB/SNMP card 33
10.4 Use of warning relay interface 33
11. MAINTENANCE 36
11.1 Minor troubleshooting 36
12. TECHNICAL SPECIFICATIONS  37

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

1. SAFETY STANDARDS
1.1 Important
This manual should be kept carefully in a safe place near the UPS, so that it can be consulted by the operator at any time for any
information that may be needed regarding correct use of the unit. Read the manual carefully before connecting the unit to the a.c.
mains supply and to the downstream appliances. Before the UPS NETYS RT is put into commission, the user must be perfectly
familiar with its operation, with the position of all the controls and with the technical and functional characteristics of the unit, so as
to ensure there will be no risk to any persons or to the appliance itself.
The electrical installation must be entrusted EXCLUSIVELY to a skilled engineer, following the instructions provided
exactly.
Before being started up, the unit must be equipotentially bonded, in accordance with current safety regulations. The earth
wire of the UPS must then be connected to an efficient earth system.
If the earth connection is not made, the appliances connected to the UPS will not be equipotentially bonded. In this situation,
the manufacturer declines all liability for any damage or accidents that could derive from failure to observe the requirements.
Should a power outage occur (UPS in stand-alone mode), do not disconnect the power cord from the mains, as this will
break the earth connection to bonded appliances.
All subsequent maintenance operations must be entrusted only to authorized service engineers. The UPS generates high
internal voltages that could be hazardous for a maintenance operative not in possession of the appropriate skills and training for
this type of work.
If a hazard situation should arise at any moment when the UPS is in use, isolate the unit from the power supply (by operating
a switch at the upstream PDU if possible) and switch the appliance off completely by running the shutdown procedure.
The UPS houses a source of electrical energy, namely its batteries. The output of the UPS may be under power even
when the appliance is not connected to the a.c. mains supply.
Never force, break or attempt to open the batteries. These batteries are sealed, maintenance-free components containing substances that are harmful to health and a source of environmental pollution. If liquid can be seen leaking from the
battery, or a white powdery residue is noticeable, do not switch the UPS on.
Avoid exposing the UPS to contact with water or any liquids generally. Do not allow foreign objects to come into contact
with the materials.
If the appliance is to be scrapped, it must be entrusted exclusively to a specialist waste disposal company. These companies
will split up and dispose of the various components in accordance with statutory regulations in the country of purchase.
Use the UPS in accordance with the technical specifications indicated in this manual (chapter 11).
Avoid connecting the output neutral to earth. The UPS does not alter the function of mains neutral in any way; if neutral needs to
be modifed downstream of the UPS, an isolation transformer must be used.
To meet the operating requirements for the Emergency Switch Device (ESD), a specific RJ11 input with remote ESD/EPO function
is available.
In the event that the equipment has no automatic backfeed protection contactor device, make certain that:
- the user/installer attaches warning labels to all mains isolating switches located remotely from the area where the UPS is sited, in
order to inform service personnel that the circuit is connected to a UPS.
- an external isolating device is installed, as indicated in figure 1-1.
The product you have selected, given the specified conditions of use, capacity and performance limits, is designed exclusively for
commercial and industrial service. The use of the product in critical applications could require compliance with statutory regulations and standards, or with specific local bylaws, or adaptation to SOCOMEC UPS recommendations. For this type of use, in any
event, it is advisable to contact SOCOMEC UPS beforehand for confirmation regarding the capacity of products to meet required
levels of safety, performance and reliability. The expression critical applications covers, in particular, life support systems, medical
applications, commercial transport, nuclear facilities or any other systems where failure of the product might on occasion cause
serious damage to persons or property.
WARNING!
This is a product for commercial and industrial application in the second environment installation restrictions or
additional measures may be needed to prevent disturbances.

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

2. SAFETY

1-1
External power
distribution unit
Q

UPS.

Legend.
B Contactor solenoid.
Q Mains input thermal-magnetic switch
T Two-pole contactor 90 A AC1; coil voltage: according to the Mains input.

085 DRWNETRT-XX

1.2 Description of the symbols used on the labels applied to the unit
All the precautions and the warnings on the labels and plates on the inside and outside of the equipment should be respected.
DANGER! HIGH VOLTAGE (BLACK/YELLOW)

GROUND TERMINAL

READ THE USER MANUAL BEFORE USING THE UNIT

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

ENGLISH

ISOLATE THE UPS BEFORE WORKING ON THIS


CIRCUIT.

2. INSTALLATION
2.1 Environmental requirements for installation
Consult the following check list when installing the UPS:
NETYS RT units are designed for use in enclosed environments.
Position the UPS on a flat and stable surface in a properly ventilated room, well away from heat sources and avoiding direct exposure to sunlight.
Ambient temperature should be maintained between 0 C and 40 C, and relative humidity below 90% (without condensation);
the optimum temperature in terms of maximizing battery life is 15-20 C.
Check that the UPS will not be installed in a dust-laden environment.
Be certain that a clearance of at least 20 cm is left on all sides of the unit to ensure adequate ventilation and provide access to the
rear panel.
Take care not to stand the UPS or any other heavy object on cables.
Check that the operating voltage and frequency settings are correct for the mains power supply at the installation site. Details for
the UPS will be found on the data plate affixed to the rear panel.
When making the RS232 serial connection, use only the cables and accessories supplied or specified by the manufacturer.
When the UPS is first used, it is advisable to leave the battery on charge for a minimum of 8 hours.

PRECAUTIONS IN THE EVENT OF DAMAGE


DO NOT OVERTURN THE BATTERIES.
Packing materials that have been broken, punctured or torn in such a way as to reveal the contents must be kept
separate in a secure area, and inspected by skilled staff. Any packing considered unsuitable for shipment of the
contents must be set aside immediately and kept secure, and the sender or recipient contacted.

2.2 Electrical requirements


The installation and the system must comply with pertinent national statutory regulations.
The fixed power distribution unit must include protection and isolation for the utility supply and the back-up supply. In the event that
a residual current device is installed on the UPS input line (optional), this must be located upstream of the power distribution unit.
The following table indicates the sizing of input protection devices that will ensure correct installation.

WARNING!
Use type B four-pole selective (S) RCDs Any leakage currents at the loads will be added to that of the UPS, so that
current peaks can occur during transients (loss and restoration of mains supply), although these will be of very
short duration. Where loads generate high leakage current, make certain the rating of the RCD is suitably matched.
In any event, always conduct a preliminary test for current leakage to eart

Electrical requirements
UPS

Thermal-magnetic switch
oninput

Recommended selective
RCDon input

Minimum cable section

5 kVA

40 C

0,1 A type B

6 mm2

7 kVA

40 C

0,1 A type B

8 mm2

9 kVA

63 D

0,1 A type B

10 mm2

11 kVA

63 D

0,1 A type B

10 mm2

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

2. INSTALLATION

2.3 Vertical installation

ENGLISH

103 DRWNETRT-XX

102 DRWNETRT-XX

2.3.1 UPS Installation

031 DRWNETRT-XX

115 DRWNETRT-XX

059 DRWNETRT-XX

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

2. INSTALLATION

065 DRWNETRT-XX

068 DRWNETRT-XX

2.3.2 UPS installation with multiple battery


extensions

069 DRWNETRT-XX

059 DRWNETRT-XX

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

033 DRWNETRT-XX

2. INSTALLATION

2.4 Horizontal installation on rack

126 DRWNETRT-XX

122 DRWNETRT-XX

125 DRWNETRT-XX

124 DRWNETRT-XX

127 DRWNETRT-XX

123 DRWNETRT-XX

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

ENGLISH

121 DRWNETRT-XX

2.4.1 Rotation of mimic pannel

2. INSTALLATION

129 DRWNETRT-XX

128 DRWNETRT-XX

2.4.2 Fitting rack brackets

10

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

2. INSTALLATION

045 DRWNETRT-XX

064 DRWNETRT-XX

067 DRWNETRT-XX

ENGLISH

2.4.3 Rotation of battery extension panel

1
2

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

11

2. INSTALLATION

2.4.4 Fixing to rack


1. Adapt the length of the tracks to fit the rack.
2. Secure the wing nuts.
3. Fix the track to the rack.
4. Slot in the UPS and tighten the screws.

066 DRWNETRT-XX

MAX 100 kg

12

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

061 DRWNETRT-XX

060 DRWNETRT-XX

MAX 100 kg

3. REAR VIEW

COM. SLOT

MINI COM. SLOT

RS232

100

EPO

PARALLEL

Network

COM. SLOT

10

SW

PARALLEL

EPO

L
I

RS232

ENGLISH

B
B

INPUT 230Vac 50/60Hz

111 DRWNETRT-XX

INPUT

230Vac 50/60Hz

5 kVA
7 kVA

131 DRWNETRT-XX

OUTPUT 230Vac 50/60Hz

OUTPUT

230Vac 50/60Hz

INPUT
BREAKER
230Vac 40A

EXTERNAL BATTERY CONNECTOR


240Vdc 32A(9KVA)/40A(11KVA)

DO NOT DISCONNECT
BATTERY CABLE UNDER LOAD

SMART SLOT

CAUTION:

SW

EXTERNAL BATTERY CONNECTOR


192Vdc 21.5A(5KVA)/30A(7KVA)

NOT DISCONNECT BATTERY


CAUTION:DO
CABLE UNDER LOAD.

INPUT
BREAKER
230Vac 63A

9 kVA
11 kVA

Legend
A EPO (Emergency Power Off)
B Fan
C Battery extension socket
D Output terminals
E Input terminals
F Input switch
G RJ45 LAN ethernet connector
H Parallel D connector
I

RS232 serial connector (JBUS protocol)

L Slot for optional communication cards


3-1

The external contact MUST be dedicated and voltage-free, so as not to cause


permanent damage to the UPS.

123456

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

070 DRWNETRT-XX

If requested, the UPS can also be switched off utilizing a remote external EPO contact. The
command is acknowledged when the contact is made and held for 3 seconds (default), as
in figure 3-1.

13

4. CONNECTIONS
Connection to the mains power supply and to the load(s) must be made using cables of suitable cross section, in accordance with
current standards.
If not already provided, install a PDU panel allowing isolation of the mains supply upstream of the UPS. The panel must be equipped
with an automatic switch rated high enough to handle the current draw on full load, and with a residual current device.

4.1 Connection terminal strips

RS232

PARALLEL

COM. SLOT

100

Network

10

EPO

MINI COM. SLOT

SW

COM. SLOT

PARALLEL

EPO

RS232

INPUT
BREAKER
230Vac 63A

N
N

INPUT 230Vac 50/60Hz

OUTPUT 230Vac 50/60Hz

OUTPUT

230Vac 50/60Hz

INPUT
BREAKER
230Vac 40A

OUT 230 V~

L
N

INPUT

230Vac 50/60Hz

5 kVA
7 kVA

14

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

IN 230 V~

111 DRWNETRT-XX

IN 230 V~

131 DRWNETRT-XX

SMART SLOT

EXTERNAL BATTERY CONNECTOR


240Vdc 32A(9KVA)/40A(11KVA)

DO NOT DISCONNECT
BATTERY CABLE UNDER LOAD

CAUTION:

SW

EXTERNAL BATTERY CONNECTOR


192Vdc 21.5A(5KVA)/30A(7KVA)

NOT DISCONNECT BATTERY


CAUTION:DO
CABLE UNDER LOAD.

OUT 230 V~

9 kVA
11 kVA

4. CONNECTION

4.2 Connection of UPS


4.2-2

ENGLISH

4.2-1

UPS
Mains

Output

UPS

6
8
10
10

5 kVA
7 kVA
9 kVA
11 kVA

(mm2)

6
8
10
10

118 DRWNETRT-XX

(mm2)

108 DRWNETRT-XX

4.2-4

097 DRWNETRT-XX

4.2-3

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

15

5. CONNECTION OF BATTERY EXTENSION


5.1 Safety warnings
Before connecting the battery extension, check that it is fully compatible with the model of UPS in use.
The use of battery extensions not supplied by the manufacturer is inadvisable.
WARNING!
There is a risk of explosion if battery modules are replaced with others of incorrect type.
Depleted batteries are considered as toxic waste. When battery replacement becomes necessary, release all depleted batteries
only to certified and licensed waste disposal companies. In accordance with local bylaws, it is absolutely forbidden to dispose of
batteries together with other industrial waste or household refuse.
WARNING!
It is extremely dangerous to touch any part of the battery storage unit.

5.2 Connection of battery extension

WARNING!
Before commencing any operation, make certain that:
the voltages of the UPS battery and of the battery extension are the same,
5 kVA: 192 VDC (NRT-B7000)
7 kVA: 192 VDC (NRT-B7000)
9 kVA: 240 VDC (NRT-B11000)
11 kVA: 240 VDC (NRT-B11000)
the UPS has been shut down completely and all isolation switches are OFF;
switches upstream of the UPS are OFF.

When connecting the UPS to the battery extension, use only the cable provided with the equipment.

Any wiring error that results in the polarity of the battery being inverted can cause permanent damage to the
equipment.

Set the switch on the back of the battery extension module to the OFF position.
Connect the battery extension module to the UPS.
Set the switch on the back of the battery extension module to the ON position.

16

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

INPUT 230Vac 50/60Hz


L

ENGLISH
240Vdc
BATTERY CONNECTOR

230Vac 50/60Hz

INPUT

OUTPUT 230Vac 50/60Hz

096 DRWNETRT-XX
INPUT
BREAKER
230Vac 63A

EXTERNAL BATTERY CONNECTOR


240Vdc 32A(9KVA)/40A(11KVA)

DO NOT DISCONNECT
BATTERY CABLE UNDER LOAD

CAUTION:

SW

SMART SLOT

EXTERNAL BATTERY CONNECTOR


192Vdc 21.5A(5KVA)/30A(7KVA)

NOT DISCONNECT BATTERY


CAUTION:DO
CABLE UNDER LOAD.

OUTPUT

230Vac 50/60Hz

INPUT
BREAKER
230Vac 40A

095 DRWNETRT-XX

COM. SLOT

100

Network

10

RS232
PARALLEL
EPO

DO NOT DISCONNECT
BATTERY CABLE UNDER LOAD.

SMART SLOT

OUTPUT

230Vac 50/60Hz

INPUT
BREAKER
230Vac 40A

COM. SLOT

Connection of
multiple batteries

CAUTION:
DANGER:
RISK OF ELCTRIC SHOCK.
DO NOT TOUCH UNINSULATED
BATTERY TERMINAL.

CAUTION:
RISK OF ELCTRIC SHOCK.BATTERY
SUPPLY CIRCUIT IS GROUNDED.
REFER TO INSTRUCTION MANUAL
BEFORE WORKING ON BATTERIES.

SW

EXTERNAL BATTERY CONNECTOR


192Vdc 21.5A(5KVA)/30A(7KVA)

DO NOT DISCONNECT BATTERY


CAUTION:CABLE
UNDER LOAD.

9 kVA
11 kVA
5 kVA
7 kVA

MINI COM. SLOT

SW

BREAKER
300Vdc 50A

COM. SLOT

RS232
PARALLEL
EPO

RS232
PARALLEL
EPO

ON-OFF
switch
ON-OFF
switch

094 DRWNETRT-XX

5. CONNECTION OF BATTERY EXTENSION

INPUT

230Vac 50/60Hz

17

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

240Vdc
BATTERY CONNECTOR

6. CONNECTION OF BY-PASS AND SINGLE UPS


6.1 Installation of BY-PASS and single UPS
TO CONNECT WITH WIRES:LOOSEN SCREWS MARKED BY
200-240Vac
50/60Hz

TO UPS PARALLEL PORT

N
L
TO UPS OUTPUT

200-240Vac
50/60Hz

N
TO UPS INPUT

N
L
AC OUTPUT

N
AC INPUT

10

100

Network

PARALLEL

EXTERNAL BATTERY CONNECTOR


192Vdc 21.5A(5KVA)/30A(7KVA)

EPO

COM. SLOT

SW

NOT DISCONNECTBATTERY
CAUTION:DO
CABLE UNDER LOAD.

INPUT
BREAKER
230Vac
40A
OUTPUT

INPUT

230Vac 50/60Hz

230Vac 50/60Hz

112 DRWNETRT-XX

RS232

MINI COM. SLOT

072 DRWNETRT-XX

6.1.1 Fixing the BY-PASS to the UPS

18

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

6. CONNECTION OF BY-PASS AND SINGLE UPS

6.2 Connection of BY-PASS to single UPS

073 DRWNETRT-XX

ENGLISH

6.2.1 Fixing the BY-PASS to the UPS

6.2.2 Signal connections between BY-PASS and UPS

OUTPUT

230 Vac 50/60 Hz

55

INPUT

UPS

BYPASS

UPS

BYPASS

230 Vac 50/60 Hz

300

UPS OUTPUT

UPS INPUT

117 DRWNETRT-XX

55

POWER
SUPPLY
LOAD

092 DRWNETRT-XX

40

BYPASS
55

BYPASS

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

19

6. CONNECTION OF BY-PASS AND SINGLE UPS

074 DRWNETRT-XX

6.2.3 Connection of cables to the UPS terminal strips

20

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

076 DRWNETRT-XX

075 DRWNETRT-XX

6. CONNECTION OF BY-PASS AND SINGLE UPS

077 DRWNETRT-XX

ENGLISH

6.2.4 Connection of cables to the BY-PASS terminal strips

UPS output

079 DRWNETRT-XX

078 DRWNETRT-XX

UPS input

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

21

6. CONNECTION OF BY-PASS AND SINGLE UPS

080 DRWNETRT-XX

6.2.5 Connection of cables to the BY-PASS input and output terminal strips

UPS input

081 DRWNETRT-XX

UPS output

UPS output

22

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

UPS input

7. CONNECTION OF BY-PASS AND UPS IN PARALLEL


7.1 Vertical installation of BY-PASS and UPS in parallel

120 DRWNETRT-XX

ENGLISH

7.1.1 Assembly of BY-PASS and UPS for vertical installation

132 DRWNETRT-XX

7.1.2 Fixing BY-PASS to UPS for vertical installation

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

23

7. CONNECTION OF BY-PASS AND UPS IN PARALLEL

7.2 Rack installation of BY-PASS and UPS in parallel

133 DRWNETRT-XX

7.2.1 Fixing brackets for rack installation

109 DRWNETRT-XX

7.2.2 Fitting BY-PASS to rack

24

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

7. CONNECTION OF BY-PASS AND UPS IN PARALLEL

7.3 Connection of BY-PASS and UPS in parallel


7.3.1 Connection of BY-PASS to 2 UPSs
7.3.1-2

ENGLISH

7.3.1-1

083 DRWNETRT-XX

input UPS 2

7.3.1-3

087 DRWNETRT-XX

output UPS 2

7.3.1-4

088 DRWNETRT-XX

input UPS 1

086 DRWNETRT-XX

output UPS 1

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

25

7. CONNECTION OF BY-PASS AND UPS IN PARALLEL

7.3.2 Connection of BY-PASS to line and load


7.3.2-1

7.3.2-2

LINE

084 DRWNETRT-XX

082 DRWNETRT-XX

LOAD

089 DRWNETRT-XX

7.3.2-3

26

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

BREAKER 300VDC 50A

BREAKER 300VDC 50A

EPO

AC INPUT 230Vac 50/60 Hz

BREAKER 300VDC 50A

BREAKER 300VDC 50A

COM. SLOT
COM. SLOT

OUTPUT

UPS1 BREAKER
230Vac 63A

TO UP
PARALLEL

INPUT

BATTERY
CONNECTOR
192Vdc

BATTERY
CONNECTOR
192Vdc

BATTERY
CONNECTOR
192Vdc

CAUTION:

CAUTION:

BATTERY
CONNECTOR
192Vdc

CAUTION:

CAUTION:

S1
LLEL

UPS OUTPUT
LINE BREAKER
230Vac 63A

ENGLISH
L

AC INPUT 230Vac 50/60 Hz

BYPASS BREAKER
230Vac 63A

RS232
EL
EPO

PA
RS232
EL
PA

OUTPUT

UPS2 BREAKER
230Vac 63A

INPUT

100

Network

10

MINI COM. SLOT

SW

EXTERNAL BATTERY CONNECTOR


192Vdc 21.5A(5KVA)/30A(7KVA)

NOT DISCONN
CAUTION:DO
CABLE UNDER LO

100
Network

10

MINI COM. SLOT

SW

EXTERNAL BATTERY CONNECTOR


192Vdc 21.5A(5KVA)/30A(7KVA)

NOT DISCON
CAUTION:DO
CABLE UNDER LO

TO UPS1
230Vac
50/60Hz

TO UPS2
230Vac
50/60Hz

L
N

INP

TO UPS1 INPUT

230

230Vac

TO UPS1 OUTPUT

TO UPS2 OUTPUT

230Vac 50/60Hz

INPUT
BREAKER
230Vac
40A
OUTPUT

230Vac 50/60Hz

INPUT
BREAKER
230Vac
40A
OUTPUT

093 DRWNETRT-XX

7. CONNECTION OF BY-PASS AND UPS IN PARALLEL

7.4 Connection of BY-PASS to UPS in parallel

27

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

8. MIMIC PANEL
The mimic panel on the front of the UPS provides all essential information on the operating status of the appliance.

Legend

A Display.
B Red symbol lit.

C

Fault.
2 colour LEDs:
Green - Normal.
Red - Overload.

D Green LED lit.


Normal operation (inverter in-line).
B

E Power-on, Enter and Buzzer override button.


G Scroll button - DOWN
H Off button
I

Green LED:
Lit - Mains healthy
Blink - Mains low but not loss.

3 colour LEDs:
Green - Stand-alone mode (battery power)
Yellow - Battery low.
Red - Battery needs replacing.

M Yellow LED:
Lit - Operation in by-pass mode

(Bypass voltage healthy).
Blink - Operation in by-pa ss mode

(Bypass voltage Out of range)

28

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

L
I

110 DRWNETRT-XX

F Scroll button - UP

9. OPERATING MODES
9.1 Basic settings

4 sec

ENGLISH

9.1-4

143 DRWNETRT-XX

9.1-1

144 DRWNETRT-XX

9.1-2

146 DRWNETRT-XX

Digit password 1234 using the


scroll buttons.
Press ENTER to confirm.

100 DRWNETRT-XX

9.1-3

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

29

TO UPS PARALLEL PORT

BREAKER 300VDC 50A

BREAKER 300VDC 50A

COM. SLOT

NORMAL

TEST

BATTERY
CONNECTOR
192Vdc

CAUTION:

BYPASS

BY-PASS selector
NORMAL - TEST - BYPASS
BATTERY
CONNECTOR
192Vdc

CAUTION:

N
L
TO UPS OUTPUT

200-240Vac
50/60Hz

UPS
ON-OFF switch
50/60Hz

OUTPUT

PUT
AKER

TO CONNECT WITH WIRES:LOOSEN SCREWS MARKED BY

TO

100

Network

10

MINI COM. SLOT

SW

EXTERNAL BATTERY CONNECTOR


192Vdc 21.5A(5KVA)/30A(7KVA)

NOT DISCONN
CAUTION:DO
CABLE UNDER LO

N
AC INPUT

INPUT

230Vac 50/60Hz

Vac

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

30

RS232
PAR
EPO

113 DRWNETRT-XX

9. OPERATING MODES

9.2 Operation in BY-PASS mode for maintenance purposes - single UPS

INPUT

230Vac 50/60Hz

BYPASS

NORMAL

TEST

TO CONNECT WITH WIRES:LOOSEN SCREWS MARKED BY

SMART SLOT

230Vac 50/60Hz

OUTPUT

INPUT
BREAKER
230Vac 40A

090 DRWNETRT-XX
L

114 DRWNETRT-XX
L

TEST

SW

EXTERNAL BATTERY CONNECTOR


192Vdc 21.5A(5KVA)/30A(7KVA)

INPUT

230Vac 50/60Hz

BYPASS

105 DRWNETRT-XX

NORMAL

TEST

BYPASS

31

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

9.2.2 Restoring normal operation of UPS

ENGLISH
100 DRWNETRT-XX
005 DRWNETRT-XX

BYPASS

SMART SLOT

OUTPUT

230Vac 50/60Hz

INPUT
BREAKER
230Vac 40A

TO CONNECT WITH WIRES:LOOSEN SCREWS MARKED BY

SW

EXTERNAL BATTERY CONNECTOR


192Vdc 21.5A(5KVA)/30A(7KVA)

DO NOT DISCONNECT BATTERY


CAUTION:CABLE
UNDER LOAD.

TO CONNECT WITH WIRES:LOOSEN SCREWS MARKED BY

NORMAL

9.2.2-3
NOT DISCONNECT BATTERY
CAUTION:DO
CABLE UNDER LOAD.

101 DRWNETRT-XX

TEST

BYPASS

UPS is by-passed but still


switched on
091 DRWNETRT-XX

NORMAL

TEST

BYPASS

BYPASS

230Vac 50/60Hz

INPUT
BREAKER
230Vac 40A

UPS is operational.

Wait for the UPS to synchronize


and detect the external by-pass.

9.2.2-6

9.2.2-5

9.2.2-4

NORMAL

TEST

TEST

SMART SLOT

100
Network

10

BATTERY

OFF

NORMAL

NORMAL

1 2
ON
SW

EXTERNAL BATTERY CONNECTOR


192Vdc 21.5A(5KVA)/30A(7KVA)

NOT DISCONNECT
CAUTION: DO
CABLE UNDER LOAD.

COM. SLOT

short

ON

OFF

RS232
EPO

PARALLEL

RS232
PARALLEL
EPO

9.2.1-6
9.2.1-5
9.2.1-4

9.2.1-3
9.2.1-2
9.2.1-1

Carry out maintenance on the


UPS in safety.
short

9.2.2-2
9.2.2-1

119 DRWNETRT-XX

RS232
PARALLEL
REPO

116 DRWNETRT-XX

9. OPERATING MODES

9.2.1 Activation of by-pass mode for UPS maintenance purposes


SNMP SLOT

COM. SLOT

AC INPUT 230Vac 50/60 Hz


N

AC INPUT 230Vac 50/60 Hz

OUTPUT

OUTPUT

100

Network

10

MINI COM. SLOT

SW

100
Network

10

MINI COM. SLOT

NOT DISCONN
CAUTION:DO
CABLE UNDER LO

EXTERNAL BATTERY CONNECTOR


192Vdc 21.5A(5KVA)/30A(7KVA)

INPUT

UPS2 BREAKER
230Vac 63A

TO UP
PARALLEL

INPUT

UPS1 BREAKER
230Vac 63A

S1
LLEL

UPS OUTPUT
LINE BREAKER
230Vac 63A

BATTERY
CONNECTOR
192Vdc

CAUTION:

CAUTION:
BATTERY
CONNECTOR
192Vdc

SW

EXTERNAL BATTERY CONNECTOR


192Vdc 21.5A(5KVA)/30A(7KVA)

NOT DISCON
CAUTION:DO
CABLE UNDER LO

TO UPS1
230Vac
50/60Hz

TO UPS2
230Vac
50/60Hz

TO UPS1 OUTPUT

TO UPS2 OUTPUT

230Vac 50/60Hz

INPUT
BREAKER
230Vac
40A
OUTPUT

230Vac 50/60Hz

INPUT
BREAKER
230Vac
40A
OUTPUT

TO UPS1 INPUT

INP

230Vac

230

4. BY-PASS output: turn off UPS1 and UPS2 by pressing the OFF buttons

BYPASS BREAKER
230Vac 63A

BREAKER 300VDC 50A

BREAKER 300VDC 50A

BATTERY
CONNECTOR
192Vdc

3. To guard against operator error, wire in a detection signal for the BY-PASS switch.

CAUTION:

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

32

BREAKER 300VDC 50A

BREAKER 300VDC 50A

1. The function of the UPS output line breaker is to protect the output from overloads.

C
BATTERY
CONNECTOR
192Vdc

2. Disconnect all cables from the UPS when carrying out maintenance work.

COM. SLOT
COM. SLOT

B
CAUTION:

Notes:

RS232
EL
PA
EPO
RS232
EL
PA
EPO

104 DRWNETRT-XX

9. OPERATING MODES

9.3 Operation in BY-PASS mode - UPS in parallel for maintenance purposes

BYPASS
switch

UPS1
switch

UPS2
switch

UPS output line


breaker

Output UPS1+UPS2

OFF

ON

ON

ON

Output UPS1 (UPS2 off for maintenance)

OFF

ON

OFF

ON

Output UPS2 (UPS1 off for maintenance)

OFF

OFF

ON

ON

BY-PASS Output

ON

OFF

OFF

ON

10. COMMUNICATION
Communication software and accessories are available for monitoring the status of the UPS, with the end in view of optimizing
normal operation and ensuring that shutdown at the end of backup time is managed correctly. Applications allow recording of all
power outages and any depletion of battery power so as to enable the activation of an automatic procedure for closing programs
in ordered sequence and shutting down the system.
NETYS RT no-break systems are equipped with RS232 serial communication interface, and slots for NetVision cards.

ENGLISH

10.1 Communication solutions


UniVision local management software (RS232interface) with local shutdown functions for Windows and Linux systems,
downloadable free of charge from the Socomec website www.socomec.com/univision (CD included with certain models).
Uni Vision Pro network management software (RS232interface) with local/remote shutdown functions on major operating
systems, using Java Shutdown Client.
Web/SNMP manager (Web/SNMP slot card) allowing control via LAN using TCP/IP protocol, and remote shutdown management.
BMS (JBUS protocol), allows the UPS to interface with a Building Management system.

10.2 RS232 interface


This interface is required to run the UniVision local management software and UniVision Pro network management software. Use
the cable provided.

10.3 Integrated WEB/SNMP card


With this card installed, the UPS can be connected directly to a LAN (RJ45 ethernet) and controlled remotely from a WEB browser
using TCP/IP protocol. Reference should be made to the dedicated literature for a full description of the functionalities.

10.4 Use of warning relay interface


This is an optional card (slot-mounted) that will manage 6 indication circuits with isolated contacts carrying information on the status
of the UPS. The maximum voltage that can be applied to the contacts is 24 VDC, and the maximum current 500 mA.
Relay contacts can be set individually for NO (default) or NC operation, and programmed selectively for customized monitoring of
the UPS.
If requested, the UPS can also be switched off utilizing a remote external shutdown contact. The command is acknowledged when
the contact is made and held for 3 seconds (default), whereas the external contact must be made between the common and input
pins.
The external contact MUST be dedicated and voltage-free, so as not to cause permanent damage to the UPS.

The shutdown input can be configured alternatively as a battery test input.

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

33

10. COMMUNICATION

10.4.1 Internal circuit


10.4.1-1

10.4.1-2
Common
R1
R2

R1 General alarm

R3

R2 No mains
R3 Battery low

R4

R4 On by-pass

R5
+5V

R5 Overload

R6

CPU Pin

R6 Overtemperature

GND-R
058 DRWNETRT-XX

Input

GND-R

GND-R
Common
R1
R2
R3
R4
R5
R6
Input
Tx
Rx
GND-C
SW1
SW2

10.4.2 Standard configuration


SW1

SW2

relay contact

OFF

OFF

NO

ON

OFF

NC

GND-R: Relay ground contact


Common: 12~24 V DC
R1

General alarm

R2

No mains

R3

Battery low

R4

On by-pass

R5

Overload

R6

Overtemperature

Input: Remote shutdown or battery test

34

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

063 DRWNETRT-XX

10.4.1-3

10. COMMUNICATION

10.4.3 Customized configuration for relay and/or input contacts


Connect Tx to pin 2, Rx to pin 3 and GND-C to pin 5 of the computers RS232 port.
In Windows, start the Hyper-Terminal application and proceed to open the specified COM port.
Set the following properties: Baud rate: 2400, Data Bits: 8, Parity: None, Stop Bit: 1, Flow Control: None.
Configuration.

1. Press 1 to configure the alarms relative to contacts R1~R6


(Customize Output Relay).
This menu can be used to assign a customized alarm indication to contacts R1~R6.
Having completed the configuration, shift SW2 to the ON
position to activate the settings. The default settings can be
restored by setting SW2 to OFF.
2. Press 2 to configure the input signal.
The input signal can be used either to shut down the UPS or to
test the batteries. The delay preceding shutdown of the UPS
can be set up to 9999 seconds maximum.
3. Press 3 to configure NO or NC operation of each relay.
Shift SW2 to the ON position to activate the settings.
If SW2 is returned to the OFF position, SW1 can be used to
check the NO or NC position of all the relays.
4. Press 0 to end the configuration session. The system will
prompt you to save the new settings.
Press Y to save, N to cancel.

UPS Relay Card


Firmware Version: Relay Card V1.4
[1] . Customize Output Relay
[2] . Configure Input Signal
[3] . Customize Normal Open or Normal Close
[0] . Quit

ENGLISH

Press <Enter> to display the main menu of the relay card.

Please Enter Your Choice >

Customize Output Relay



Relay Selected Event
[1] . Relay 1: Summary Alarm
[2] . Relay 2: Power Fail
[3] . Relay 3: Battery Low
[4] . Relay 4: On by-pass
[5] . Relay 5: Overload
[6] . Relay 6: Overtemperature
[0] . Back to Previous Menu
Please Enter Your Choice >

Customize Output Relay


Relay Selected Event


[1] . Relay 1: Normal Close
[2] . Relay 2: Normal Open
[3] . Relay 3: Normal Close
[4] . Relay 4: Normal Open
[5] . Relay 5: Normal Close
[6] . Relay 6: Normal Open
[0] . Back to Previous Menu
Please Enter Your Choice >

Configure Input Signal


[1] . Act as Shutdown or Test: Shutdown
[2] . Input Signal Confirm 3 Seconds
[3] . Delay Before Shutdown 30 Seconds
[0] . Back to Previous Menu
Please Enter Your Choice >

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

35

11. MAINTENANCE
WARNING!
The UPS generates HAZARDOUS INTERNAL VOLTAGES. All maintenance operations should be carried out by
AUTHORIZED SERVICE ENGINEERS ONLY.
The unit will operate to its maximum capability if kept powered up round the clock (24/7); this ensures that the batteries will always
be properly charged.
If the appliance is to remain idle for any length of time, wait until the batteries are fully charged (connection to mains power supply
for 8 hours continuous) before shutting the UPS down.
Recharge the batteries for a duration of 24 hours at least every 4 weeks during the time the unit remains idle.

11.1 Minor troubleshooting


WARNING!
If problems should persist or reoccur frequently after following the procedures indicated in this section, contact
the SOCOMEC UPS After Sales Service, providing a full description of the current difficulty
Problem

Possible cause

Solution

"UPS not powered up


(no alarm, no LEDs
alight)

The ON/TEST button has not been pressed.

Press the ON/TEST button to switch the UPS on.

Shutdown due to flat battery and no mains


power.

Wait for mains power to be restored

Thermal-magnetic switch on the rear panel


has been tripped.

Reduce the load connected to the UPS, then reset


the thermal-magnetic switch.

Faulty UPS

Contact SOCOMEC UPS After Sales Service if the


solutions indicated above do not solve the problem.

UPS internal batteries not completely


charged.

Recharge the batteries for a minimum of 8 hours.

UPS in overload.

Disconnect non-essential loads.

Depleted batteries.

The batteries will degrade quickly if used fequently,


or in high operating temperatures. Should the batteries have reached the end of their life cycle, contact
SOCOMEC UPS After Sales Service. Batteries must
be replaced even if the "Replace battery" LED is not lit.

Battery charge fault or other causes.

Contact SOCOMEC UPS After Sales Service

"Replace battery" LED


lit.

Batteries flat.

Charge the batteries for a minimum of 8 hours. If the


problem persists, contact SOCOMEC UPS After Sales
Service to have for battery replacement.

Faulty communication
between PC and UPS.

Wrong transmission speed.

Change the transmission speed and test again.

RS232 connection incorrect.

See "Communication" section of this manual.


Reconnect the UPS to the COM1/COM2 port of the PC.

USB connection incorrect.

Reconnect the UPS to the USB port of the PC.

UPS functions in
"Battery Mode" even
though a.c. mains is
connected and healthy.

Mains voltage not registering at UPS input.

Check the input voltage connection.

Thermal-magnetic switch on the rear panel


has been tripped.

Reduce the load connected to the UPS, then reset


the thermal-magnetic switch.

Input voltage too high, too low or distorted.

Have the mains voltage checked by a qualified electrician.

Overtemperature.

Air intake fans and fan cowl may be


obstructed.

Select a well ventilated area in which to position the


UPS, allowing suitable dissipation of heat.

Ambient temperature is higher than 40 C


(104 F).

Position the UPS in a cooler area.

UPS does not guarantee the expected


backup time.

36

"Fault" LED lit and alarm UPS faulty.


signal generated.

Contact SOCOMEC UPS After Sales Service.

"Overload" LED lit, with Overload.


continuous alarm signal.

Disconnect non-essential loads.

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

12. TECHNICAL SPECIFICATIONS

UPS power

NRT-U5000

NRT-U7000

NRT-U9000

NRT-U11000

5000 VA
3500 W

7000 VA
4900 W

9000 VA
6400 W

11000 VA
8000 W

Input

Single-phase 230 V (160-275 V); 50/60 Hz with automatic selection

Input socket

Terminals

Output

Single-phase 230 V nominal 2% (selectable: 200/208/220/240 V); 50/60 Hz

Output sockets

Terminals

Technology

ENGLISH

Models

On-line double conversion (VFI-SS-111)

Online efficiency

up to 92%

Batteries
Type
Typical backup (1)

Maintenance-free sealed lead - life expectancy 3-5 years


10 minutes

7 minutes

10 minutes

7 minutes

Communication
Connection interface

RJ 45 and RS 232 ports and slots for communication cards

Ethernet

WEB / SNMP interface (Optional)

Environment
Dimensions WxDxH
Weight
Reference standards
(1)
(2)

440x670.5x88.7 mm
17,3x26,4x2U
15 kg

440x623x130.6 mm
17,3x24,5x3U

15.5 kg

19.5 kg

20 kg

EN 62040-1-1, EN 62040-2 , EN 62040-3, EN 61000-4-5/C62.41:1991 (Overvoltage)


(2)

With battery module included.


With output cables shorter than 10 m.

5-11 kVA - Ref.: IOMNETRTXX01-GB 00

37

Socomec UPS
worldwide
IN EUROPE
BELGIUM
Schaatsstraat, 30 rue du Patinage
B - 1190 Bruxelles
Tel. +32 (0)2 340 02 34
Fax +32 (0)2 346 16 69
[email protected]

FRANCE
95, rue Pierre Grange
F - 94132 Fontenay-sous-Bois Cedex
Tel. +33 (0)1 45 14 63 90
Fax +33 (0)1 48 77 31 12
[email protected]

GERMANY
Heppenheimerstrae 57
D - 68309 Mannheim
Tel. +49 (0) 621 71 68 40
Fax +49 (0) 621 71 68 44 4
[email protected]

ITALY
Via Leone Tolstoi, 73 - Zivido
20098 San Giuliano Milanese (MI)
Tel. +39 02 98 242 942
Fax +39 02 98 240 723
[email protected]

NETHERLANDS
Bergveste 2F
NL - 3992DE Houten
Tel. +31 (0)30 63 71 504
Fax +31 (0)30 63 72 166
[email protected]

POLAND
Nowowiejska St 21/25
00-665 Warszawa
Tel. +48 (0)22 2345 223
Fax +48 (0)22 2345 223
[email protected]

IN ASIA
CHINA

PORTUGAL

No.1 Yuanda Road Haidian District, Beijing, 100097


Golden Resource Times Shopping Mall
No. 1001 section B the 2nd issue of business building
Tel. +86 10 8889 2202
Fax +86 10 8889 2150
[email protected]

Rua Moinho do Cuco


Bloco A
Lj. Dta. - Paz
2640-566 MAFRA
Tel. +351 261 812 599
Fax +351 261 812 570
[email protected]

INDIA
B1, IInd Floor, Thiru-Vi-Ka-Industrial Estate
Guindy
Chennai 600 032
Tel. +91 44 3921 5400
Fax +91 44 3921 5450 51
[email protected]

RUSSIA
Kutuzovsky pr. 13, 44-45
121248 - Moscow
Tel. +7 495 775 19 85
Fax +7 495 775 19 85
[email protected]

MALAYSIA

SLOVENIA

31 Jalan SS 25/41- Mayang Industrial Park


47301 Petaling Jaya.- Selangor, Malaysia
Tel. +603 7804 1153
Fax +603 7803 8901
[email protected]

Savlje 89
SI - 1000 Ljubljana
Tel. +386 1 5807 860
Fax +386 1 5611 173
[email protected]

SINGAPORE

SPAIN

31 Ubi Road 1, Aztech Building


# 01-00 (Annex) - SG - Singapore 408694
Tel. +65 6745 7555
Fax +65 6458 7377
[email protected]

C/Nord, 22 Pol. Ind. Buvisa


E - 08329 Tei (Barcelona)
Tel. +34 935 407 575
Fax +34 935 407 576
[email protected]

THAILAND

UNITED KINGDOM
Units 7-9 Lakeside Business Park
Broadway Lane - South Cerney
Cirencester - GL7 5XL
Tel. +44 (0)1285 863300
Fax +44 (0)1285 862304
[email protected]

HEAD OFFICE
SOCOMEC GROUP
S.A. SOCOMEC capital 11 102 300 - R.C.S. Strasbourg B 548 500 149
B.P. 60010 - 1, rue de Westhouse - F-67235 Benfeld Cedex
SOCOMEC UPS Strasbourg
11, route de Strasbourg - B.P. 10050 - F-67235 Huttenheim Cedex- FRANCE
Tel. +33 (0)3 88 57 45 45 - Fax +33 (0)3 88 74 07 90
[email protected]
SOCOMEC UPS Isola Vicentina
Via Sila, 1/3 - I - 36033 Isola Vicentina (VI) - ITALY
Tel. +39 0444 598611 - Fax +39 0444 598622
[email protected]

No.9 Soi Vibhavadirangsit 42


Vibhavadirangsit Rd, Ladyao
Chatujak Bangkok 10900
Tel. +66 2 941-1644-7
Fax. +66 2 941-1650
[email protected]

SALES, MARKETING AND


SERVICE MANAGEMENT
SOCOMEC UPS Paris
95, rue Pierre Grange
F-94132 Fontenay-sous-Bois Cedex - FRANCE
Tel. +33 (0)1 45 14 63 90 - Fax +33 (0)1 48 77 31 12
[email protected]

*IOMNETRTXX01-GB 00*
IOMNETRTXX01-GB

www.socomec.com
Non contractual document. 2008, Socomec SA. All rights reserved.