TABLE OF CONTENTS
1. SAFETY STANDARDS 4
1.1 Important 4
1.2 Description of the symbols used on the labels applied to the unit 5
ENGLISH
2. INSTALLATION 6
2.1 Environmental requirements for installation 6
2.2 Electrical requirements 6
2.3 Vertical installation 7
2.4 Horizontal installation on rack 9
3. REAR VIEW 13
4. CONNECTIONS 14
4.1 Connection terminal strips 14
4.2 Connection of UPS 15
5. CONNECTION OF BATTERY EXTENSION 16
5.1 Safety warnings 16
5.2 Connection of battery extension 16
6. CONNECTION OF BY-PASS AND SINGLE UPS 18
6.1 Installation of BY-PASS and single UPS 18
6.2 Connection of BY-PASS to single UPS 19
7. CONNECTION OF BY-PASS AND UPS IN PARALLEL 23
7.1 Vertical installation of BY-PASS and UPS in parallel 23
7.2 Rack installation of BY-PASS and UPS in parallel 24
7.3 Connection of BY-PASS and UPS in parallel 25
7.4 Connection of BY-PASS to UPS in parallel 27
8. MIMIC PANEL 28
9. OPERATING MODES 29
9.1 Basic settings 29
9.2 Operation in BY-PASS mode for maintenance purposes - single UPS 30
9.3 Operation in BY-PASS mode - UPS in parallel for maintenance purposes 32
10. COMMUNICATION 33
10.1 Communication solutions 33
10.2 RS232 interface 33
10.3 Integrated WEB/SNMP card 33
10.4 Use of warning relay interface 33
11. MAINTENANCE 36
11.1 Minor troubleshooting 36
12. TECHNICAL SPECIFICATIONS 37
1. SAFETY STANDARDS
1.1 Important
This manual should be kept carefully in a safe place near the UPS, so that it can be consulted by the operator at any time for any
information that may be needed regarding correct use of the unit. Read the manual carefully before connecting the unit to the a.c.
mains supply and to the downstream appliances. Before the UPS NETYS RT is put into commission, the user must be perfectly
familiar with its operation, with the position of all the controls and with the technical and functional characteristics of the unit, so as
to ensure there will be no risk to any persons or to the appliance itself.
The electrical installation must be entrusted EXCLUSIVELY to a skilled engineer, following the instructions provided
exactly.
Before being started up, the unit must be equipotentially bonded, in accordance with current safety regulations. The earth
wire of the UPS must then be connected to an efficient earth system.
If the earth connection is not made, the appliances connected to the UPS will not be equipotentially bonded. In this situation,
the manufacturer declines all liability for any damage or accidents that could derive from failure to observe the requirements.
Should a power outage occur (UPS in stand-alone mode), do not disconnect the power cord from the mains, as this will
break the earth connection to bonded appliances.
All subsequent maintenance operations must be entrusted only to authorized service engineers. The UPS generates high
internal voltages that could be hazardous for a maintenance operative not in possession of the appropriate skills and training for
this type of work.
If a hazard situation should arise at any moment when the UPS is in use, isolate the unit from the power supply (by operating
a switch at the upstream PDU if possible) and switch the appliance off completely by running the shutdown procedure.
The UPS houses a source of electrical energy, namely its batteries. The output of the UPS may be under power even
when the appliance is not connected to the a.c. mains supply.
Never force, break or attempt to open the batteries. These batteries are sealed, maintenance-free components containing substances that are harmful to health and a source of environmental pollution. If liquid can be seen leaking from the
battery, or a white powdery residue is noticeable, do not switch the UPS on.
Avoid exposing the UPS to contact with water or any liquids generally. Do not allow foreign objects to come into contact
with the materials.
If the appliance is to be scrapped, it must be entrusted exclusively to a specialist waste disposal company. These companies
will split up and dispose of the various components in accordance with statutory regulations in the country of purchase.
Use the UPS in accordance with the technical specifications indicated in this manual (chapter 11).
Avoid connecting the output neutral to earth. The UPS does not alter the function of mains neutral in any way; if neutral needs to
be modifed downstream of the UPS, an isolation transformer must be used.
To meet the operating requirements for the Emergency Switch Device (ESD), a specific RJ11 input with remote ESD/EPO function
is available.
In the event that the equipment has no automatic backfeed protection contactor device, make certain that:
- the user/installer attaches warning labels to all mains isolating switches located remotely from the area where the UPS is sited, in
order to inform service personnel that the circuit is connected to a UPS.
- an external isolating device is installed, as indicated in figure 1-1.
The product you have selected, given the specified conditions of use, capacity and performance limits, is designed exclusively for
commercial and industrial service. The use of the product in critical applications could require compliance with statutory regulations and standards, or with specific local bylaws, or adaptation to SOCOMEC UPS recommendations. For this type of use, in any
event, it is advisable to contact SOCOMEC UPS beforehand for confirmation regarding the capacity of products to meet required
levels of safety, performance and reliability. The expression critical applications covers, in particular, life support systems, medical
applications, commercial transport, nuclear facilities or any other systems where failure of the product might on occasion cause
serious damage to persons or property.
WARNING!
This is a product for commercial and industrial application in the second environment installation restrictions or
additional measures may be needed to prevent disturbances.
2. SAFETY
1-1
External power
distribution unit
Q
UPS.
Legend.
B Contactor solenoid.
Q Mains input thermal-magnetic switch
T Two-pole contactor 90 A AC1; coil voltage: according to the Mains input.
085 DRWNETRT-XX
1.2 Description of the symbols used on the labels applied to the unit
All the precautions and the warnings on the labels and plates on the inside and outside of the equipment should be respected.
DANGER! HIGH VOLTAGE (BLACK/YELLOW)
GROUND TERMINAL
ENGLISH
2. INSTALLATION
2.1 Environmental requirements for installation
Consult the following check list when installing the UPS:
NETYS RT units are designed for use in enclosed environments.
Position the UPS on a flat and stable surface in a properly ventilated room, well away from heat sources and avoiding direct exposure to sunlight.
Ambient temperature should be maintained between 0 C and 40 C, and relative humidity below 90% (without condensation);
the optimum temperature in terms of maximizing battery life is 15-20 C.
Check that the UPS will not be installed in a dust-laden environment.
Be certain that a clearance of at least 20 cm is left on all sides of the unit to ensure adequate ventilation and provide access to the
rear panel.
Take care not to stand the UPS or any other heavy object on cables.
Check that the operating voltage and frequency settings are correct for the mains power supply at the installation site. Details for
the UPS will be found on the data plate affixed to the rear panel.
When making the RS232 serial connection, use only the cables and accessories supplied or specified by the manufacturer.
When the UPS is first used, it is advisable to leave the battery on charge for a minimum of 8 hours.
WARNING!
Use type B four-pole selective (S) RCDs Any leakage currents at the loads will be added to that of the UPS, so that
current peaks can occur during transients (loss and restoration of mains supply), although these will be of very
short duration. Where loads generate high leakage current, make certain the rating of the RCD is suitably matched.
In any event, always conduct a preliminary test for current leakage to eart
Electrical requirements
UPS
Thermal-magnetic switch
oninput
Recommended selective
RCDon input
5 kVA
40 C
0,1 A type B
6 mm2
7 kVA
40 C
0,1 A type B
8 mm2
9 kVA
63 D
0,1 A type B
10 mm2
11 kVA
63 D
0,1 A type B
10 mm2
2. INSTALLATION
ENGLISH
103 DRWNETRT-XX
102 DRWNETRT-XX
031 DRWNETRT-XX
115 DRWNETRT-XX
059 DRWNETRT-XX
2. INSTALLATION
065 DRWNETRT-XX
068 DRWNETRT-XX
069 DRWNETRT-XX
059 DRWNETRT-XX
033 DRWNETRT-XX
2. INSTALLATION
126 DRWNETRT-XX
122 DRWNETRT-XX
125 DRWNETRT-XX
124 DRWNETRT-XX
127 DRWNETRT-XX
123 DRWNETRT-XX
ENGLISH
121 DRWNETRT-XX
2. INSTALLATION
129 DRWNETRT-XX
128 DRWNETRT-XX
10
2. INSTALLATION
045 DRWNETRT-XX
064 DRWNETRT-XX
067 DRWNETRT-XX
ENGLISH
1
2
11
2. INSTALLATION
066 DRWNETRT-XX
MAX 100 kg
12
061 DRWNETRT-XX
060 DRWNETRT-XX
MAX 100 kg
3. REAR VIEW
COM. SLOT
RS232
100
EPO
PARALLEL
Network
COM. SLOT
10
SW
PARALLEL
EPO
L
I
RS232
ENGLISH
B
B
111 DRWNETRT-XX
INPUT
230Vac 50/60Hz
5 kVA
7 kVA
131 DRWNETRT-XX
OUTPUT
230Vac 50/60Hz
INPUT
BREAKER
230Vac 40A
DO NOT DISCONNECT
BATTERY CABLE UNDER LOAD
SMART SLOT
CAUTION:
SW
INPUT
BREAKER
230Vac 63A
9 kVA
11 kVA
Legend
A EPO (Emergency Power Off)
B Fan
C Battery extension socket
D Output terminals
E Input terminals
F Input switch
G RJ45 LAN ethernet connector
H Parallel D connector
I
123456
070 DRWNETRT-XX
If requested, the UPS can also be switched off utilizing a remote external EPO contact. The
command is acknowledged when the contact is made and held for 3 seconds (default), as
in figure 3-1.
13
4. CONNECTIONS
Connection to the mains power supply and to the load(s) must be made using cables of suitable cross section, in accordance with
current standards.
If not already provided, install a PDU panel allowing isolation of the mains supply upstream of the UPS. The panel must be equipped
with an automatic switch rated high enough to handle the current draw on full load, and with a residual current device.
RS232
PARALLEL
COM. SLOT
100
Network
10
EPO
SW
COM. SLOT
PARALLEL
EPO
RS232
INPUT
BREAKER
230Vac 63A
N
N
OUTPUT
230Vac 50/60Hz
INPUT
BREAKER
230Vac 40A
OUT 230 V~
L
N
INPUT
230Vac 50/60Hz
5 kVA
7 kVA
14
IN 230 V~
111 DRWNETRT-XX
IN 230 V~
131 DRWNETRT-XX
SMART SLOT
DO NOT DISCONNECT
BATTERY CABLE UNDER LOAD
CAUTION:
SW
OUT 230 V~
9 kVA
11 kVA
4. CONNECTION
ENGLISH
4.2-1
UPS
Mains
Output
UPS
6
8
10
10
5 kVA
7 kVA
9 kVA
11 kVA
(mm2)
6
8
10
10
118 DRWNETRT-XX
(mm2)
108 DRWNETRT-XX
4.2-4
097 DRWNETRT-XX
4.2-3
15
WARNING!
Before commencing any operation, make certain that:
the voltages of the UPS battery and of the battery extension are the same,
5 kVA: 192 VDC (NRT-B7000)
7 kVA: 192 VDC (NRT-B7000)
9 kVA: 240 VDC (NRT-B11000)
11 kVA: 240 VDC (NRT-B11000)
the UPS has been shut down completely and all isolation switches are OFF;
switches upstream of the UPS are OFF.
When connecting the UPS to the battery extension, use only the cable provided with the equipment.
Any wiring error that results in the polarity of the battery being inverted can cause permanent damage to the
equipment.
Set the switch on the back of the battery extension module to the OFF position.
Connect the battery extension module to the UPS.
Set the switch on the back of the battery extension module to the ON position.
16
ENGLISH
240Vdc
BATTERY CONNECTOR
230Vac 50/60Hz
INPUT
096 DRWNETRT-XX
INPUT
BREAKER
230Vac 63A
DO NOT DISCONNECT
BATTERY CABLE UNDER LOAD
CAUTION:
SW
SMART SLOT
OUTPUT
230Vac 50/60Hz
INPUT
BREAKER
230Vac 40A
095 DRWNETRT-XX
COM. SLOT
100
Network
10
RS232
PARALLEL
EPO
DO NOT DISCONNECT
BATTERY CABLE UNDER LOAD.
SMART SLOT
OUTPUT
230Vac 50/60Hz
INPUT
BREAKER
230Vac 40A
COM. SLOT
Connection of
multiple batteries
CAUTION:
DANGER:
RISK OF ELCTRIC SHOCK.
DO NOT TOUCH UNINSULATED
BATTERY TERMINAL.
CAUTION:
RISK OF ELCTRIC SHOCK.BATTERY
SUPPLY CIRCUIT IS GROUNDED.
REFER TO INSTRUCTION MANUAL
BEFORE WORKING ON BATTERIES.
SW
9 kVA
11 kVA
5 kVA
7 kVA
SW
BREAKER
300Vdc 50A
COM. SLOT
RS232
PARALLEL
EPO
RS232
PARALLEL
EPO
ON-OFF
switch
ON-OFF
switch
094 DRWNETRT-XX
INPUT
230Vac 50/60Hz
17
240Vdc
BATTERY CONNECTOR
N
L
TO UPS OUTPUT
200-240Vac
50/60Hz
N
TO UPS INPUT
N
L
AC OUTPUT
N
AC INPUT
10
100
Network
PARALLEL
EPO
COM. SLOT
SW
NOT DISCONNECTBATTERY
CAUTION:DO
CABLE UNDER LOAD.
INPUT
BREAKER
230Vac
40A
OUTPUT
INPUT
230Vac 50/60Hz
230Vac 50/60Hz
112 DRWNETRT-XX
RS232
072 DRWNETRT-XX
18
073 DRWNETRT-XX
ENGLISH
OUTPUT
55
INPUT
UPS
BYPASS
UPS
BYPASS
300
UPS OUTPUT
UPS INPUT
117 DRWNETRT-XX
55
POWER
SUPPLY
LOAD
092 DRWNETRT-XX
40
BYPASS
55
BYPASS
19
074 DRWNETRT-XX
20
076 DRWNETRT-XX
075 DRWNETRT-XX
077 DRWNETRT-XX
ENGLISH
UPS output
079 DRWNETRT-XX
078 DRWNETRT-XX
UPS input
21
080 DRWNETRT-XX
6.2.5 Connection of cables to the BY-PASS input and output terminal strips
UPS input
081 DRWNETRT-XX
UPS output
UPS output
22
UPS input
120 DRWNETRT-XX
ENGLISH
132 DRWNETRT-XX
23
133 DRWNETRT-XX
109 DRWNETRT-XX
24
ENGLISH
7.3.1-1
083 DRWNETRT-XX
input UPS 2
7.3.1-3
087 DRWNETRT-XX
output UPS 2
7.3.1-4
088 DRWNETRT-XX
input UPS 1
086 DRWNETRT-XX
output UPS 1
25
7.3.2-2
LINE
084 DRWNETRT-XX
082 DRWNETRT-XX
LOAD
089 DRWNETRT-XX
7.3.2-3
26
EPO
COM. SLOT
COM. SLOT
OUTPUT
UPS1 BREAKER
230Vac 63A
TO UP
PARALLEL
INPUT
BATTERY
CONNECTOR
192Vdc
BATTERY
CONNECTOR
192Vdc
BATTERY
CONNECTOR
192Vdc
CAUTION:
CAUTION:
BATTERY
CONNECTOR
192Vdc
CAUTION:
CAUTION:
S1
LLEL
UPS OUTPUT
LINE BREAKER
230Vac 63A
ENGLISH
L
BYPASS BREAKER
230Vac 63A
RS232
EL
EPO
PA
RS232
EL
PA
OUTPUT
UPS2 BREAKER
230Vac 63A
INPUT
100
Network
10
SW
NOT DISCONN
CAUTION:DO
CABLE UNDER LO
100
Network
10
SW
NOT DISCON
CAUTION:DO
CABLE UNDER LO
TO UPS1
230Vac
50/60Hz
TO UPS2
230Vac
50/60Hz
L
N
INP
TO UPS1 INPUT
230
230Vac
TO UPS1 OUTPUT
TO UPS2 OUTPUT
230Vac 50/60Hz
INPUT
BREAKER
230Vac
40A
OUTPUT
230Vac 50/60Hz
INPUT
BREAKER
230Vac
40A
OUTPUT
093 DRWNETRT-XX
27
8. MIMIC PANEL
The mimic panel on the front of the UPS provides all essential information on the operating status of the appliance.
Legend
A Display.
B Red symbol lit.
C
Fault.
2 colour LEDs:
Green - Normal.
Red - Overload.
Green LED:
Lit - Mains healthy
Blink - Mains low but not loss.
3 colour LEDs:
Green - Stand-alone mode (battery power)
Yellow - Battery low.
Red - Battery needs replacing.
M Yellow LED:
Lit - Operation in by-pass mode
(Bypass voltage healthy).
Blink - Operation in by-pa ss mode
(Bypass voltage Out of range)
28
L
I
110 DRWNETRT-XX
F Scroll button - UP
9. OPERATING MODES
9.1 Basic settings
4 sec
ENGLISH
9.1-4
143 DRWNETRT-XX
9.1-1
144 DRWNETRT-XX
9.1-2
146 DRWNETRT-XX
100 DRWNETRT-XX
9.1-3
29
COM. SLOT
NORMAL
TEST
BATTERY
CONNECTOR
192Vdc
CAUTION:
BYPASS
BY-PASS selector
NORMAL - TEST - BYPASS
BATTERY
CONNECTOR
192Vdc
CAUTION:
N
L
TO UPS OUTPUT
200-240Vac
50/60Hz
UPS
ON-OFF switch
50/60Hz
OUTPUT
PUT
AKER
TO
100
Network
10
SW
NOT DISCONN
CAUTION:DO
CABLE UNDER LO
N
AC INPUT
INPUT
230Vac 50/60Hz
Vac
30
RS232
PAR
EPO
113 DRWNETRT-XX
9. OPERATING MODES
INPUT
230Vac 50/60Hz
BYPASS
NORMAL
TEST
SMART SLOT
230Vac 50/60Hz
OUTPUT
INPUT
BREAKER
230Vac 40A
090 DRWNETRT-XX
L
114 DRWNETRT-XX
L
TEST
SW
INPUT
230Vac 50/60Hz
BYPASS
105 DRWNETRT-XX
NORMAL
TEST
BYPASS
31
ENGLISH
100 DRWNETRT-XX
005 DRWNETRT-XX
BYPASS
SMART SLOT
OUTPUT
230Vac 50/60Hz
INPUT
BREAKER
230Vac 40A
SW
NORMAL
9.2.2-3
NOT DISCONNECT BATTERY
CAUTION:DO
CABLE UNDER LOAD.
101 DRWNETRT-XX
TEST
BYPASS
NORMAL
TEST
BYPASS
BYPASS
230Vac 50/60Hz
INPUT
BREAKER
230Vac 40A
UPS is operational.
9.2.2-6
9.2.2-5
9.2.2-4
NORMAL
TEST
TEST
SMART SLOT
100
Network
10
BATTERY
OFF
NORMAL
NORMAL
1 2
ON
SW
NOT DISCONNECT
CAUTION: DO
CABLE UNDER LOAD.
COM. SLOT
short
ON
OFF
RS232
EPO
PARALLEL
RS232
PARALLEL
EPO
9.2.1-6
9.2.1-5
9.2.1-4
9.2.1-3
9.2.1-2
9.2.1-1
9.2.2-2
9.2.2-1
119 DRWNETRT-XX
RS232
PARALLEL
REPO
116 DRWNETRT-XX
9. OPERATING MODES
COM. SLOT
OUTPUT
OUTPUT
100
Network
10
SW
100
Network
10
NOT DISCONN
CAUTION:DO
CABLE UNDER LO
INPUT
UPS2 BREAKER
230Vac 63A
TO UP
PARALLEL
INPUT
UPS1 BREAKER
230Vac 63A
S1
LLEL
UPS OUTPUT
LINE BREAKER
230Vac 63A
BATTERY
CONNECTOR
192Vdc
CAUTION:
CAUTION:
BATTERY
CONNECTOR
192Vdc
SW
NOT DISCON
CAUTION:DO
CABLE UNDER LO
TO UPS1
230Vac
50/60Hz
TO UPS2
230Vac
50/60Hz
TO UPS1 OUTPUT
TO UPS2 OUTPUT
230Vac 50/60Hz
INPUT
BREAKER
230Vac
40A
OUTPUT
230Vac 50/60Hz
INPUT
BREAKER
230Vac
40A
OUTPUT
TO UPS1 INPUT
INP
230Vac
230
4. BY-PASS output: turn off UPS1 and UPS2 by pressing the OFF buttons
BYPASS BREAKER
230Vac 63A
BATTERY
CONNECTOR
192Vdc
3. To guard against operator error, wire in a detection signal for the BY-PASS switch.
CAUTION:
32
1. The function of the UPS output line breaker is to protect the output from overloads.
C
BATTERY
CONNECTOR
192Vdc
2. Disconnect all cables from the UPS when carrying out maintenance work.
COM. SLOT
COM. SLOT
B
CAUTION:
Notes:
RS232
EL
PA
EPO
RS232
EL
PA
EPO
104 DRWNETRT-XX
9. OPERATING MODES
BYPASS
switch
UPS1
switch
UPS2
switch
Output UPS1+UPS2
OFF
ON
ON
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
BY-PASS Output
ON
OFF
OFF
ON
10. COMMUNICATION
Communication software and accessories are available for monitoring the status of the UPS, with the end in view of optimizing
normal operation and ensuring that shutdown at the end of backup time is managed correctly. Applications allow recording of all
power outages and any depletion of battery power so as to enable the activation of an automatic procedure for closing programs
in ordered sequence and shutting down the system.
NETYS RT no-break systems are equipped with RS232 serial communication interface, and slots for NetVision cards.
ENGLISH
33
10. COMMUNICATION
10.4.1-2
Common
R1
R2
R1 General alarm
R3
R2 No mains
R3 Battery low
R4
R4 On by-pass
R5
+5V
R5 Overload
R6
CPU Pin
R6 Overtemperature
GND-R
058 DRWNETRT-XX
Input
GND-R
GND-R
Common
R1
R2
R3
R4
R5
R6
Input
Tx
Rx
GND-C
SW1
SW2
SW2
relay contact
OFF
OFF
NO
ON
OFF
NC
General alarm
R2
No mains
R3
Battery low
R4
On by-pass
R5
Overload
R6
Overtemperature
34
063 DRWNETRT-XX
10.4.1-3
10. COMMUNICATION
ENGLISH
35
11. MAINTENANCE
WARNING!
The UPS generates HAZARDOUS INTERNAL VOLTAGES. All maintenance operations should be carried out by
AUTHORIZED SERVICE ENGINEERS ONLY.
The unit will operate to its maximum capability if kept powered up round the clock (24/7); this ensures that the batteries will always
be properly charged.
If the appliance is to remain idle for any length of time, wait until the batteries are fully charged (connection to mains power supply
for 8 hours continuous) before shutting the UPS down.
Recharge the batteries for a duration of 24 hours at least every 4 weeks during the time the unit remains idle.
Possible cause
Solution
Faulty UPS
UPS in overload.
Depleted batteries.
Batteries flat.
Faulty communication
between PC and UPS.
UPS functions in
"Battery Mode" even
though a.c. mains is
connected and healthy.
Overtemperature.
36
UPS power
NRT-U5000
NRT-U7000
NRT-U9000
NRT-U11000
5000 VA
3500 W
7000 VA
4900 W
9000 VA
6400 W
11000 VA
8000 W
Input
Input socket
Terminals
Output
Output sockets
Terminals
Technology
ENGLISH
Models
Online efficiency
up to 92%
Batteries
Type
Typical backup (1)
7 minutes
10 minutes
7 minutes
Communication
Connection interface
Ethernet
Environment
Dimensions WxDxH
Weight
Reference standards
(1)
(2)
440x670.5x88.7 mm
17,3x26,4x2U
15 kg
440x623x130.6 mm
17,3x24,5x3U
15.5 kg
19.5 kg
20 kg
37
Socomec UPS
worldwide
IN EUROPE
BELGIUM
Schaatsstraat, 30 rue du Patinage
B - 1190 Bruxelles
Tel. +32 (0)2 340 02 34
Fax +32 (0)2 346 16 69
[email protected]
FRANCE
95, rue Pierre Grange
F - 94132 Fontenay-sous-Bois Cedex
Tel. +33 (0)1 45 14 63 90
Fax +33 (0)1 48 77 31 12
[email protected]
GERMANY
Heppenheimerstrae 57
D - 68309 Mannheim
Tel. +49 (0) 621 71 68 40
Fax +49 (0) 621 71 68 44 4
[email protected]
ITALY
Via Leone Tolstoi, 73 - Zivido
20098 San Giuliano Milanese (MI)
Tel. +39 02 98 242 942
Fax +39 02 98 240 723
[email protected]
NETHERLANDS
Bergveste 2F
NL - 3992DE Houten
Tel. +31 (0)30 63 71 504
Fax +31 (0)30 63 72 166
[email protected]
POLAND
Nowowiejska St 21/25
00-665 Warszawa
Tel. +48 (0)22 2345 223
Fax +48 (0)22 2345 223
[email protected]
IN ASIA
CHINA
PORTUGAL
INDIA
B1, IInd Floor, Thiru-Vi-Ka-Industrial Estate
Guindy
Chennai 600 032
Tel. +91 44 3921 5400
Fax +91 44 3921 5450 51
[email protected]
RUSSIA
Kutuzovsky pr. 13, 44-45
121248 - Moscow
Tel. +7 495 775 19 85
Fax +7 495 775 19 85
[email protected]
MALAYSIA
SLOVENIA
Savlje 89
SI - 1000 Ljubljana
Tel. +386 1 5807 860
Fax +386 1 5611 173
[email protected]
SINGAPORE
SPAIN
THAILAND
UNITED KINGDOM
Units 7-9 Lakeside Business Park
Broadway Lane - South Cerney
Cirencester - GL7 5XL
Tel. +44 (0)1285 863300
Fax +44 (0)1285 862304
[email protected]
HEAD OFFICE
SOCOMEC GROUP
S.A. SOCOMEC capital 11 102 300 - R.C.S. Strasbourg B 548 500 149
B.P. 60010 - 1, rue de Westhouse - F-67235 Benfeld Cedex
SOCOMEC UPS Strasbourg
11, route de Strasbourg - B.P. 10050 - F-67235 Huttenheim Cedex- FRANCE
Tel. +33 (0)3 88 57 45 45 - Fax +33 (0)3 88 74 07 90
[email protected]
SOCOMEC UPS Isola Vicentina
Via Sila, 1/3 - I - 36033 Isola Vicentina (VI) - ITALY
Tel. +39 0444 598611 - Fax +39 0444 598622
[email protected]
*IOMNETRTXX01-GB 00*
IOMNETRTXX01-GB
www.socomec.com
Non contractual document. 2008, Socomec SA. All rights reserved.
00
01.2009