C40 Trace Manual English
C40 Trace Manual English
Charge-Diversion
& Load Controller
!
!
!
!
!
!
!
!
!
!
General Precautions
Before using the charge/load controller, read all instructions and cautionary markings on:
(1) the charge/load controller
(2) the batteries and
(3) the photovoltaic panels
CAUTION - To reduce risk of injury, charge only deep cycle lead-acid, lead-antimony, leadcalcium, gel cell, absorbed mat, NiCad or NiFe type rechargeable batteries. Other types of
batteries may burst, causing personal injury and damage.
Do not attempt to repair the C40. Take it to a qualified service center when service or repair
is required. Incorrect re-assembly may result in a risk of electric shock or fire.
To reduce risk of electric shock, disconnect all wiring before attempting any maintenance or
cleaning. Turning off controls will not reduce this risk. Solar modules produce power when
exposed to light - cover them with opaque material before servicing.
WARNING - WORKING IN VICINITY OF A LEAD ACID BATTERY IS
DANGEROUS. BATTERIES GENERATE EXPLOSIVE GASES DURING
NORMAL OPERATION. Provide ventilation to outdoors from the highest
point of the battery compartment.
NEVER charge a frozen battery.
No terminals or lugs are required for hook-up of the DC wiring. Wiring should be rated for
75 C and should be no less than #8 AWG / 8.367mm2 gauge wire for use at 40 amps.
Terminals provided accept up to #2 AWG / 33.6 mm2 gauge stranded copper or aluminum
wire.
Insulate tool handles with tape to reduce the chance of a short circuit occurring. Spark or
short-circuits can cause an explosion.
Tools required to make DC wiring connections: Wire strippers, Phillips screwdriver #2,
Slotted screw driver 5/32" (4.5 mm).
This charge/load controller is intended to be used with a battery supply of 12, 24, or 48volts direct current nominal voltage..
For battery installation and maintenance, read the instructions provided with the batteries
prior to operating.
No DC disconnect switch is provided as an integral part of this unit. DC disconnects may
be required as part of the system installation. Refer to local electrical codes for
requirements.
No overcurrent protection for the battery supply is provided as an integral part of this unit.
Copyright Trace Engineering Co. Inc.
th
5916 195 Street, NE
Arlington, WA 98223 USA
Overcurrent protection for the battery cables must be provided as part of the system
installation. Refer to local electrical codes for requirements.
Although over current protection for the DC output wiring is provided as an integral part of
this unit, additional over current protection of the DC output wiring may be required as part
of the system installation. Refer to local electrical codes for requirements.
GROUNDING INSTRUCTIONS - This charge/load controller should be connected to a
grounded, metal, permanent wiring system. Connections to the grounding system should
comply with all local codes and ordinances.
Personal Precautions
Someone should be within range of your voice or close enough to come to your aid when
you work near batteries.
Have plenty of fresh water and soap nearby in case battery acid contacts skin, clothing, or
eyes.
Wear eye protection and protective clothing. Avoid touching eyes while working near
batteries.
If battery acid contacts skin or clothing, wash immediately with soap and water. If acid
enters an eye, immediately flood the eye with running cold water for at least 15 minutes and
get medical attention immediately.
Baking soda neutralizes spilled lead acid electrolyte. Vinegar neutralizes spilled NiCad
electrolyte. Keep a supply on hand.
NEVER smoke or allow a spark or flame in vicinity of a battery or generator.
Be extra cautious to reduce the possibility of dropping a metal tool onto
batteries, it might short-circuit batteries or other electrical parts that may
cause an explosion. Cover wrench handles with plastic tape or vinyl dipcoating material.
Remove personal metal items such as rings, bracelets, necklaces, and
watches while installing the system. A single battery can produce a shortcircuit current high enough to weld a ring to a battery terminal, causing severe burns.
!
!
!
!
!
!
Operating Modes
The C40 controller can operate as either a photovoltaic charge controller, a diversion
controller, or a DC load controller. The C40 cannot operate as both a charge controller and
a DC load controller at the same time. If both are required in a system, two C40s must be
installed. Use one C40 for each mode desired.
Photovoltaic Charge Control Mode with three-stage regulation and automatic or manual
battery equalization cycle. When this mode is selected, the status LED will indicate either
blinking green or solid green. It will alternate red/green when in equalization mode.
Diversion Control Mode for PV, hydro-electric, wind generator, or mixed source systems
with three-stage regulation and automatic or manual battery equalization cycle. When this
mode is selected the status LED will indicate either blinking green or solid green.
DC Load Control Mode turns off the DC loads when battery voltage is low. When this
mode is selected, the status LED will typically indicate blinking red or solid red.
C40
controller
Pv Array
Battery
If the PV arrays output increases above the 40-amp level due to reflection or edge of
cloud effect, the C40 will continue to operate until the heatsink reaches a safe operating
temperature. This will take several minutes to occur depending upon the ambient
temperature involved. When the heatsink reaches the maximum safe temperature, the C40
will reduce the current, cooling the transistors and the heatsink. This will occur only if the
current flow exceeds the 40-amp level and the C40 is located in a very hot environment.
If the current from the PV array reaches 63 amps, the C40 will turn off to self protect. This
should never occur in a properly designed system. Ten minutes after shutting off to self
protect, the C40 will automatically restart.
The C40 charge controller rapidly cycles the current source on-and-off to control the
charging current and voltage of the battery. This occurs in both the charge control mode
and the diversion control mode. The amount of time the current source is connected to the
battery is varied to control the average current flow. This is often referred to as pulse width
modulation (PWM) and allows the current to be tapered, rather than coarsely turning the
current off and on as with relay type PV array charge controllers.
diversion load to redirect the excess power generated instead of allowing it to flow into the
battery. This prevents damage to the charging source from an over-speed condition which
could occur if the charging source is suddenly disconnected from all loads - as series relay
regulators do. Consult your dealer for load and regulator size recommendations.
When the C40 operates as a diversion regulator, it provides three-stage regulation of
battery voltage, with temperature compensation and automatic or manual equalization.
See the Three-stage Battery Charging section for more information on this process.
PV, HYDRO,
or WIND
Diversion
C40
Battery controller
dump load
Diversion mode requires a separate load dump to regulate the battery. This load must be
able to absorb more power than the charging source is able to produce at its peak output,
or the DC voltage will become unregulated. The dump load must be available for the
diversion of power at all times. Resistive-type heating elements are the best diversion
loads. Special direct current water heating elements are available. Light bulbs and motors
are not recommended as diversion loads because they are unreliable.
When used in diversion mode, ensure that the operating mode jumpers are on the charge
control pins. See the User Configuration Options section of this booklet.
Current draw of the diversion load is very important. Problems may arise from operating
with a load that is too small or too large. A diversion load that is too small will not be able to
absorb all the excess power from the current source once the batteries are full.
Diversion loads in excess of 63 amps are capable of absorbing more power than the C40 is
designed to handle, resulting in an over-current shut down. During this time, the unit will
not regulate electrical flow in the system, and battery damage may result.
A diversion load that draws about 50 amps when connected to the battery is usually
suitable for use with the C40. The load should be sized about 25% larger than the charging
sources maximum output capability.
Battery
C40
controller
DC LOAD
When used in load control mode, ensure that the operating mode jumpers are on the load
control pins. See Configuring the C40 section of this booklet.
The controller delays disconnecting the DC loads for 10 minutes after the voltage drops
below the low voltage disconnect (LVD) setting. Loads are either automatically or manually
reconnected when battery voltage exceeds the low-voltage reconnect (LVR) setting for 10
minutes. The EQUALIZE jumper determines manual or automatic reconnect when the C40
is used as a load controller.
When used as a DC load controller, the settings of the
LVR and LVD are controlled by two rotary knobs on the
circuit board. The scale on the adjustment pots differ
from the scale used for other functions. A decal with
the corrected adjustment scale is included with the C40
and shown at right. Place this scale over the pots
when using the C40 as a load controller. Do not
temperature-compensate these settings. Do not install
the optional battery temperature compensation sensor.
Copyright Trace Engineering Co. Inc.
th
5916 195 Street, NE
Arlington, WA 98223 USA
Features
The C40 features include over-temperature protection, electronic over-current protection,
and automatic battery temperature compensation.
C40
ARRAY/LOAD
CURRENT
RESET AMP-HOURS
PUSH AND HOLD
FOR 10 SECONDS
TO RESET THE
AMP HOUR METER
OR
BATTERY
VOLTAGE
(DVM/C40)
RESETTABLE
AMP-HOURS
STATUS LED
INDICATOR
TOTALIZING
AMP-HOURS
PN 2247
BATTERY FULL
HVD
HVD
HVD
12.0V 24.0V
CSA-C22.2
No 14-M91 SEP 91
COMMERCIAL AND
INDUSTRIAL POWER
SUPPLIES
12.0V 24.0V
LVD
LVD
LVD
48.0V
UL DRAFT 1741
POWER CONDITIONING
UNITS FOR USE IN
RESIDENTIAL
PHOTOVOLTAIC
POWER SYSTEMS
SOLID GREEN
HVD SETTING
0.25V 0.50V 1.00V
0.50V 1.00V 2.00V
0.75V 1.50V 3.00V
48.0V
BATTERY EMPTY
WARNING !!!
REVERSE POLARITY
CONNECTION OF THE BATTERY OR PV ARRAY
WILL SOUND AN INTERNAL BUZZER. FAILURE
TO CORRECT THIS CONDITION WILL RESULT
IN DAMAGE TO THE CONTROLLER.
SOLID RED
LOW VOLTAGE
DISCONNECT
OVER CURRENT OR
OVER TEMPERATURE
EQUALIZE ACTIVATED
Installation
The C40 controller is a state-of-the-art precision electronic instrument. Installation,
environment, mounting, and wiring must be accomplished in accordance with applicable
local and national electrical codes. The instructions that follow are applicable to the typical
installation. For special applications, consult a qualified electrician or your Trace dealer.
Installation procedures will vary according to your specific application.
Mounting
The C40 is designed for indoor mounting. Care should be taken in selecting a location and
when mounting the enclosure. Avoid mounting the C40 in direct sunlight in order to reduce
heating of the enclosure and subsequent high operating temperatures. The enclosure
should be mounted vertically on a wall.
Mounting and enclosure dimensions are shown in the adjacent diagram. Remove the
faceplate on the C40 and locate the upper two screw locations on the wall. The back of the
enclosure is provided with key-holes for mounting. Leave the screw heads backed out
approximately 1/4 inch (6 mm). Place the C40 onto the screws and pull it down into the
keyhole slots. Then insert the two lower screws to lock the enclosure onto the wall.
Provide either strain-relief clamps or conduit to prevent damage to the circuit board and
terminal block from pulling on the wires. The cover should be replaced and retained with
the screws provided (#10-32 x 3/8 SMS).
In severe environments, additional consideration should be taken to minimize exposure to
wet environments. The use of conformal-coated circuit boards, plated terminals, powder
coated metal components, and stainless steel fasteners improves tolerance to hostile
environments.
Caution: It is in your best interests to install the C40 in a dry, protected location away
from sources of high temperature, moisture, and vibration. Exposure to saltwater is
particularly destructive. Corrosion of the circuit board is not covered by the
warranty. If you wouldnt put your television there, dont put the C40 there.
Copyright Trace Engineering Co. Inc.
th
5916 195 Street, NE
Arlington, WA 98223 USA
Do not locate the C40 in a sealed compartment with the batteries. Batteries can generate
hydrogen sulfide gas which is very corrosive to electronic equipment and everything else.
They also generate hydrogen and oxygen. If accumulated, this mixture could be ignited by
an arc caused by the connection of battery cables, a loose terminal, etc. Installation within
a ventilated enclosure with sealed batteries only is acceptable.
Wiring
Be sure to set the voltage selector jumper to the appropriate setting before energizing the
system (see User Configuration Options for instructions). Incorrect settings may result in
damage to the system as the charging regulation will not occur. Torque the terminals to
25 inch-pounds once the wires have been installed. Replace the cover after wiring.
NOTE: Regardless of configuration, only the positive conductor from a PV array or
a DC load may be connected to the terminal marked PV POS/LOAD.
The minimum recommended wire gauge is 8 AWG (13.3 mm2) with a 75 C insulation
rating. The terminals on the C40 will accept up to #2 AWG (33.6mm2) copper or aluminum
wire. No crimp-on terminals or lugs are required. The following table gives the maximum
permissible length allowed for each wire size at 40 amps with 3% voltage drop. Find your
Warning: Due to a printing error (what were we thinking?), the input
terminal on the C40 Rev. #2230D printed circuit board is incorrectly
labeled PV+/WIND+/LOAD+. Never connect a wind generator to this
terminal. Rev.#2230D is not designed to accept the very large current
fluctuations typical of wind generators. Damage to the C40 will result.
PV+/WIND+/LOAD+
8 AWG
6 AWG
4 AWG
3 AWG
2 AWG
12vdc
5.6/1.7m
8.8/2.68m
14/4.26m
17.7/5.38m
22.4/6.83m
24vdc
11.1/3.38m
17.6/5.36m
28/8.53m
35.4/10.79m
44.8/13.66m
48vdc
22.2/6.77m
35.2/10.72m
56/17.06m
70.8/21.58m
89.6/27.31m
system voltage in the left column, and the distance from your power source (feet/meters) to
the C40 (or the distance from the C40 to your load) on the same line, then read the wire
size required at the top of the column. Dont use wire smaller than #8 gauge.
The wiring, overcurrent protection devices (fuses and circuit breakers) and installation
methods used must conform to all local electrical codes requirements.
Wiring should be protected from physical damage with conduit or a strain relief clamp. You
should pull the temperature sensor cable through the conduit first as the connector may not
fit if other wires have been pulled first.
As a minimum, a 60-amp DC rated current limiting fuse in an appropriate fuse holder or
disconnect switch should be provided near the battery for protection from short circuits.
Local electrical codes should be consulted for wire sizing and any additional installation
requirements. The use of breakers or fuses above 60 amps is not recommended. Use
Trace part number CD60DC available from your Trace dealer.
10
Grounding
The C40 is designed to work with both negative ground and ungrounded electrical systems.
The metal chassis of this charge/load controller must be grounded for either system by
connecting it with a copper wire to a grounding electrode such as a ground rod driven into
the earth. If a negative ground system is desired, connect the negative current carrying
conductor to the grounding system at one point in the system. Consult local electrical
codes for more information and any additional requirements.
Pins
Battery Voltage:
Equalize/LVR:
Operating Mode:
48 volts DC
manual Equalization
Charge Control
11
Potentiometer
Test Points
BTS Connection
BATTERY POSITIVE+
GROUND
PV POS/LOAD
PV NEG
BAT NEG
Torque: 25 IN LB
METER
DVM or Remote
Connection
12
If you are using the C40 as a DC load controller, be sure to set the pots as shown in the DC
Load Control section of this manual. The upper knobs settings are reduced by one volt,
resulting in a range of 14.0 to 12.0 VDC (for a 12 volt system). The lower knobs settings
are reduced by two volts, resulting a range of 12.5 to 10.5 VDC (for a 12 volt system).
Equalization
The C40 offers either manual or automatic triggering of the equalization process (the
default setting is manual). Automatic equalization is enabled by moving the jumper located
on right side of the circuit board above the reset switch. When automatic has been
selected, an equalization charge (holding the voltage one volt (for 12 volt systems) above
the BULK setting for 2 hours) will occur every 30 days. During the equalization process the
status LED will indicate equalization by alternately blinking green and red. (Equalization is
not recommended for NiCad batteries and is disabled when the R46 resistor is cut - see the
drawing for location.)
Manual Equalization
Manual equalization of the battery can be enabled by pressing the reset
switch on the right side of the C40 for 10 seconds. The status LED
indicator will begin to alternate between red and green once equalization is
enabled. The equalization process will continue until the batteries have
been held at or above the BULK setting for two hours of accumulated time.
During the equalization process, the battery voltage will be limited to one
volt above the BULK setting for 12 volt systems (for 24V systems, 2 volts
and 48V systems, 4 volts above BULK). Once the battery voltage has
been at or above the BULK setting for a cumulative period of two hours, the C40 will
return to the FLOAT stage of the charging process.
To stop the equalization process, press the reset switch. The status LED will stop
alternating between red and green. If the equalization process was shorter than one hour,
the C40 will continue with a BULK charge cycle and then hold the battery at the BULK
setting for one hour (the absorption stage) before returning to the FLOAT setting.
During the equalization process the status LED will alternate between red and green and
will not provide any other mode/status indication. Large battery banks may need several
equalization cycles to fully stir the electrolyte and charge the cells. These cycles should
follow one another until the battery voltage reaches the upper limit for the full two hours.
Automatic Equalization
The C40 can automatically trigger an equalization charge every 30 days. The status LED
will indicate that the equalization process is occurring. The equalization process will
continue until the voltage has been held above the BULK setting for a cumulative period of
two hours. This might take several days on larger systems with big batteries and small PV
arrays. The battery voltage only needs to exceed the BULK setting for the timer to start
counting - the voltage may not reach the equalization voltage limiting setting of one volt
above the BULK setting (for a 12 volt system).
To enable automatic equalization, the jumper located on the right
side of the circuit board must be moved to the AUTO setting. The
/LVR
default setting of the C40 is for manual equalization. To
permanently disable the automatic equalization system, remove
the equalize jumper.
To manually stop the equalization process, press the reset switch
at the right side of the C40 until the status LED stops alternating
between red and green. If the equalization process was shorter than one hour, the C40 will
continue with a BULK charge cycle and then hold the battery at the BULK setting for one
hour (the absorption stage) before returning to the FLOAT setting.
Once a manual equalization has been triggered, the 30-day period to the next automatic
equalization will be restarted. To prevent automatic equalization, move the equalize jumper
to the manual position.
Copyright Trace Engineering Co. Inc.
th
5916 195 Street, NE
Arlington, WA 98223 USA
13
Temperature Compensation
If a temperature compensation sensor is installed, the charge or diversion control process
will be automatically adjusted for the battery temperature. Set BULK and FLOAT voltage
for a battery at normal room temperature (23 -27C/74 -80F). Actual voltage may vary
above or below these settings due to adjustment for battery temperature.
If no temperature compensation sensor is installed and the batteries will be operating in
very hot or very cold conditions, adjust the BULK and FLOAT settings to allow for the
battery temperature. The recommended adjustments can be found in the table below. The
setting should be lowered for ambiant temperatures above 80F/27C and raised for
ambiant temperature below 75F/23C. If significant seasonal variations are common, you
will have to change the settings several times a year to prevent battery damage and ensure
proper operation.
Do not compensate the settings when using the C40 as a DC Load Controller.
System Voltage
12 VOLT
.030 Volts/C
.020 Volts/C
24 VOLT
.060 Volts/C
.040 Volts/C
48 VOLT
.120Volts/C
.080 Volts/C
14
After two hours at the HVD setting, the unit will reduce the battery charging voltage to the
Float voltage setting. This will usually result in more current being diverted to the diversion
load. The Status LED indicator will flash from one to five times followed by a five-second
pause to indicate battery voltage. Depending upon system voltage and the number of
flashes between pauses, subtract the value shown on the faceplate of the unit from the
HVD (Bulk) setting. When the LED flashes only once between pauses, the battery voltage
is less than the lowest HVD value at the bottom of the chart. For a unit configured for 24
volts, for example, with the HVD (bulk) set at 26 volts and the LED flashing only once
between pauses, the battery voltage will be less than 24.5 volts (26 minus 1.5 = 24.5). This
means that the battery could be seriously discharged. When the LED stops flashing and
lights steadily, the battery voltage is equal to the float charging voltage.
Note: The LED will light green only in Diversion and Charge Control mode, never in
Load Control mode.
Actual Battery
Voltage
Supply or Load
Current (amps)
Resettable amphours
Status LED
C40R
Totalizing Amps:
resets to zero
at battery or
load disconnect
Amp-hour reset &
backlight button. Press
and hold for 20
seconds to reset.
Press and release for
backlight.
These displays include a two-line, 32 character LCD and a status LED indicator.
The DVM display provides the following information:
!
!
!
!
!
!
If the C40 is disconnected from the battery or the DVM cable, the DVM will be reset when it
is powered up. You can press and hold the pushbutton on the front of the DVM to manually
reset the amp-hour meter. Press and release this button to turn the backlight on or off. An
adjustable potentiometer on the back of the DVM enables you to adjust the contrast of the
LCD display. When installing the DVM, be sure to set the jumper on the printed circuit
board over the pin set for the system voltage, either 12, 24, or 48 volts.
Copyright Trace Engineering Co. Inc.
th
5916 195 Street, NE
Arlington, WA 98223 USA
15
16
When battery voltage drops below the FLOAT setting for a cumulative period of one hour, a
new BULK cycle will be triggered. This typically occurs each night. If the battery is full at
the start of the day, it will receive an ABSORPTION charge for one hour and then be held at
the FLOAT setting for the remaining period of the day. Should the battery voltage drop
below the FLOAT setting for a cumulative period of one hour, another BULK and
ABSORPTION cycle will be initiated.
This three stage charging process results in faster charging compared to on-off relay type
or constant voltage solid state regulators. Faster recharging increases the performance of
the system by storing more of the PV arrays limited output. The final FLOAT voltage
setting reduces battery gassing, minimizes watering requirements and ensures complete
battery recharging.
17
WARNING: If the batteries are equipped with HYDROCAPS (catalytic gas recombiner
caps), they should be removed during the equalization process. If hydrocaps are
used, you should disable automatic equalization to prevent possible damage.
Batteries
Batteries come in different sizes, types, amp hour capacity, voltages and chemistries. Here
are a few guidelines that will help in battery selection, and ensure that the batteries are
properly maintained. The best source of the most appropriate settings for the C40 will be
from the manufacturer or supplier of the batteries.
Automotive Batteries
Automotive and truck batteries are designed for high cranking power - not deep cycling.
Don't use them unless no other battery type is available. They simply will not last long in a
cycling application.
Maintenance-Free Batteries
This type of battery is often sold as a RV or marine battery, but is rarely appropriate for use
with a PV system. They typically have an additional reserve of electrolyte, but are vented.
This is not the same as a sealed battery.
Sealed Batteries
Another type of battery construction is the sealed gel cell. They don't use battery caps.
The electrolyte is in the form of a gel rather than a liquid, which allows the batteries to be
mounted in any position. The advantages are no maintenance, long life (800 cycles
claimed) and low self discharge. Absorbed glass mat electrolyte (AGM) batteries are also
acceptable. Their electrolyte is contained in mats between the battery plates. Sealed
Copyright Trace Engineering Co. Inc.
th
5916 195 Street, NE
Arlington, WA 98223 USA
18
batteries reduce the maintenance requirements for the system and are good for remote
applications. They are much more sensitive to the charging process and can be ruined in
as little as a day of overcharging.
Battery Sizing
Batteries are the fuel tank of the system. The larger the batteries, the longer the system
can operate before recharging is necessary. An undersized battery bank results in short
battery life and disappointing system performance. To determine the proper battery bank
size, compute the number of amp-hours that will be used between charging cycles. Once
the required amp-hours are known, size the batteries at approximately twice this amount.
Doubling the expected amp-hour usage ensures that the batteries will not be overly
discharged and will extend battery life. The critical formula is Watts = Volts X Amps. Divide
the wattage of the load by the battery voltage to determine the amperage the load will draw
from the batteries. Multiply the amperage times the hours of operation and the result is,
reasonably enough, amp-hours.
Diversion Loads
Anyone dealing with solar, wind, or hydro power generation systems knows that a critical
component in these systems is the charge/load controller(s).The job of the charge controller
is to see that a battery bank is charged in a controlled manner. Also, protection against
over discharge and overcharging is provided by disconnecting the charging source(s) from
the battery should one of these conditions occur.
A load controller is generally designed to remove a load or loads from the system when an
over discharge or overload situation occurs.
A diversion load controller is designed to monitor battery state, and when the battery is full,
divert the power coming out of the source (Solar, wind, or hydro generator) to a load which
will utilize the excess power. Usually a water heater or some other type of heating element
is present for this purpose.
Systems utilizing solar arrays do not have a requirement for diversion loads since a solar
module can be open circuited without damage. However, even with a solar based system it
is desirable to use excess power to operate DC loads. On the other side of the equation,
when a wind or hydro generator is operating, the diversion load prevents over speeding and
self destruction. Unload the system by suddenly removing the load and the generator will
over speed and potentially fail. The only way to safely deal with this situation is to either
stop the generator, or allow its power output to continue, but divert it away from the
batteries to prevent overcharging. This is the duty of a diversion load controller.
Copyright Trace Engineering Co. Inc.
th
5916 195 Street, NE
Arlington, WA 98223 USA
19
System Voltage
60 Vdc
(48 Vdc system)
30 Vdc
(24 Vdc system)
15 Vdc
(12 Vdc system)
120 VAC
Power
Amperage
500W
25W
30W
2000W
8.6 Amps
4.3 Amps
2.1 Amps
16.7 Amps
A couple of other excellent diversion loads which may be utilized effectively are available
from Alternative Energy Engineering of Redway California.
1. A 12/24 volt DC or 24/48 volt DC water heater element (AEE Part #20909 or #20919
(24/48V))
2. Open air heater with a fan (AEE Part #2091312 (12V, 720W), #2091324 (24V,720W),
#20 91412 (12V,1440W), #2091524 (24V, 1440W), and #2091648 (48V,1440W)).
For more information calll 1(800) 800-0624,or 1(800) 777-6609, or FAX 1(800) 777-6648.
Regardless of the type of diversion load you decide to utilize, make sure that the diversion
load can handle all the power the charging system is capable of putting out. Paralleling
heater elements (whether open air or water heater) will allow more power dissipation. A
good rule of thumb is to not have a combined charging source greater than 80% of the
diversion load controllers current handling ability. For example, if a Trace C40, 40 amp
diversion load controller is being used, do not place a combination of charging sources
which are capable of putting out more than 32 amps (80% of 40 amps) on the load
controllers circuit. Sizing a diversion system this way allows a safety margin for unusual
conditions (High winds, high water flow, etc.). It is not recommended that light bulbs be
used as diversion loads for a couple of reasons.
1) An incandescent light bulb has a substantially lower cold filament resistance than when
it is on. This means it draws more power (up to five times) to start the light when it is cold
than once the filament has warmed up. Even a forty watt lightbulb may have an inrush
amperage at turn-on of 200 amps. This would cause the load controller to shut down.
2) In the event a light bulb load burns out, a smaller-than-necessary load will be present
and the excess energy will have no where to go. When the controller switches to diversion
mode, the other bulbs will probably burn out in succession since they cant handle the
excess current, and very quickly you will have a no load situation.
Copyright Trace Engineering Co. Inc.
th
5916 195 Street, NE
Arlington, WA 98223 USA
20
WarrantyProcedure
Complete the warranty card and mailed it to Trace Engineering within ten (10) days from
the date of purchase. Keep your bill of sale as proof of purchase, should any difficulties
arise concerning the registration of the warranty card.
Warranty registration is tracked by model and serial numbers only, not by owner's name.
Therefore, any correspondence or inquiries made to Trace Engineering must include the
model and serial number of the product in question. Be sure to fill in the model and serial
numbers in the space provided below. Keep this portion of the warranty card in a safe
place for future reference.
Warranty service must be performed only at an authorized Trace Service Center, or at the
Trace Engineering factory. Notify the repair facility before shipping to avoid the possibility
of needless shipment.
UNAUTHORIZED SERVICE PERFORMED ON ANY TRACE PRODUCT WILL VOID THE
EXISTING FACTORY WARRANTY ON THAT PRODUCT.
FACTORY SERVICE: If you wish your Trace Engineering product to be serviced at the
factory, it must be shipped fully insured in the original packaging or equivalent; this warranty
will not cover repairs on products damaged through improper packaging. If possible, avoid
sending products through the mail.
Note: Before returning any equipment to Trace Engineering, call our Warranty Coordinator
and request an Return Merchandise Authorization (RMA) number. Be sure to have the
serial number of the equipment handy.
Ship To:
Trace Engineering Company, Inc.
Attn: Service Department. RMA#
th
5916 195 NE
Arlington, WA 98223
Phone: (360) 435-8826
(Warranty Coordinator)
Be sure to include in the package:
0
0
0
Complete return shipping address (PO Box numbers are not acceptable) and telephone
number where you can be reached during work hours.
A detailed description of any problems experienced, including the make and model
numbers of any other equipment in the system, types and sizes of loads, operating
environment, time of unit operation and temperature.
A copy of your proof of purchase (purchase receipt).
Repaired products will be returned freight C.O.D. unless sufficient return shipment funds
are included with the unit. Products sent to the factory from outside the U.S. MUST include
return freight funds, and sender is fully responsible for all customs documents, duties,
tariffs, and deposits.
Record the model and serial numbers on page one and retain for your files.
21
22
23
24