SCR Battery Charger / Battery Eliminator

Microprocessor Controlled SCR Battery Charger


The La Marche Model A77 Series Battery Charger is engineered for the
demanding requirements of Switchgear, Process Control, Oil Exploration
and other DC power applications.
Powered by Microprocessor Controlled SCR technology, the A77 Series
Battery Charger / Battery Eliminator has 0.25% DC voltage regulation
from no load to full load over the specified input voltage, frequency and
ambient temperature ranges.
These chargers are available in DC output voltages of 24, 48, 130, and 260
VDC with DC output currents from 6 amps and above. Consult factory for
any special input and output requirements not mentioned above.

Unit Shown: A77DE


*

*
1012

The La Marche A77 charger provides value added features such as AC/DC
breakers, easy to read LCD display with text readout alarm LEDs and
form C alarm contacts. Communication options are available to
remotely monitor and control the charger using DNP3, Modbus, IEC
61850 and SNMP protocols. The SNMP option features easier and faster
charger setup and configuration using a web browser.
Designed to meet NEMA PE5 and UL 1012 safety standards.

* Pending

Standard Features

Microprocessor Controlled SCR Technology


A77D - Filtered
A77DE - Battery Eliminator
Automatic AC Voltage Compensation
AC & DC Surge Protection (MOV)
AC & DC Breaker
Temperature Compensation
Adjustable (1-5 mV /cell/C)
Float / Equalize Mode Switch
Digital Float and Equalize Adjustments
Digital Current Limit Adjustment 50 to 110%
0.25% DC Voltage Regulation
SCR Failure Detection
Load Sharing
Master Equalize
Over Temperature Protection
LCD Display
AC Voltage and Frequency
DC Voltage and Current
Alarms
Unit Temperatures

Specifications subject to change without notice


P25-DSA77-1
ECN 20654
12/14

Advanced Data Logging (Micro SD)


LED Indicators

Float / Equalize
AC Failure
Summary Alarm
Charger Failure
Low DC Current
Overload / Current Limit
Low DC Voltage
End of Discharge
High DC Voltage
High DC Voltage Shutdown
Positive & Negative Ground Detection

Remote Annunciation Form C Contacts

AC Failure
Summary Alarm
(See Optional Accessories For Additional Alarm Contacts)

Alarms Latching / Non-Latching


Equalize Timer - adjustable from 1-144 hours with
with five selectable modes of operation (manual,
automatic every 7, 14 or 30 days and equalize after
sensing a low DC voltage)
UL 1012 & CUL (pending)
5 Year Warranty
La Marche Mfg. (A U.S. Company)
106 Bradrock Drive, Des Plaines, IL 60018
Tel: 847.299.1188 Fax: 847.299.3061
[email protected]
www.lamarchemfg.com

Specifications

ELECTRICAL
AC Input Operating Range Voltage

Voltage range: +10, -12% from nominal


Frequency range: 60 Hz 5%
(50Hz Consult Factory)

. Single Phase Voltages:

120, 208, 240, 480 or 600 VAC


(Tap selectable 120/208/240 on units up to
25 amp output. All other units must specify
single input voltage). Consult factory for
other voltages.

. Three Phase Voltages:

.
.

208, 240, 480 or 600 VAC


Consult factory for other voltages.

. DC Output

24, 48, 130, 260 VDC


6 to 500 amps

. Efficiency

Single Phase > 85%


Three Phase > 90%

. Output Filtering (with or without batteries):


24V
A77D
Filtered

48V

240mV (1%) 480mV (1%)

(w/o battery)

130V

260V

2.6V (2%)

5.2V (2%)

A77D
Filtered

30mV

30mV

100mV*

200mV*

A77DE
Eliminator

30mV

30mV

100mV**

200mV

(w/battery)

. DC Voltage Regulation Steady State

Cells

Volt
Float
23-29.5

24-29

11-13L

17-20N

48V

46-57

48-59

22-26L

33-39N

130V

115-140

123-147

53-62L

83-93N

260V

230-280

246-294

106-124L

166-186N

Note: Typical cell ranges are based on the following:


Lead Acid 2.17 vpc Float, 2.33 vpc Equalize
NiCad 1.44 vpc Float, 1.55 vpc Equalize
VRLA 2.25 vpc Float, 2.27 vpc Equalize

Front Display Panel

in the load from 20% to 100%


Recovery Time < 200 mS

Audible Noise
Less than 65dBA at any point 5 feet from any
vertical surface of the unit.
Load Sharing
Identical La Marche A77 units, when
connected in parallel, are capable of sharing
the DC load within 5% for individual unit
outputs greater than 5% of the rated output.

.PROTECTION
Current Walk-in
.

Equalize Lead Acid Ni-Cad

24V

Dynamic Response (On Battery)


Voltage transient < 5% over a step change

Connect to SCADA System


Web Monitoring
Alarm / Notification E-mails

0.25% of setting from no load to full load


over the specified input voltage, frequency
and ambient temperature ranges.

DC Output Voltage Range

A77 Battery Charger is equipped with data


logging capability on an internal Micro-SD
Card. It logs and stores data of Event-Driven
and Time-Interval-Driven Events. The
chargers data-log file does not need
proprietary software to examine the data; it
could be viewed and easily formatted with
many popular spreadsheet programs.

MONITORING
.REMOTE
Form C Alarm Contacts
. With optional Communications Card:

(w/o battery)

* Battery AH = 4x the chargers ampacity


** 30mV filtering available as an option

Data Logging

The output current will gradually


increase after the charger is turned
on, eliminating surges and overshoot.

Current Limit
Electronic Current-Limiting
Control Circuitry provides a
digitally adjustable limit from
50 to 110% of the rated output
current of the charger,
Factory set at 110%.
AC Breaker
Single Phase units are equipped
with a 2-pole circuit breaker
(10KAIC @ up to 240 VAC /
14KAIC 480 / 600 VAC).
Three Phase units are equipped
with a 3-pole circuit breaker.
(10KAIC @ up to 240 VAC
5KAIC 480 / 600 VAC).
DC Breaker
Standard units are equipped with
a 2-pole circuit breaker.
(7.5KAIC @ 24/48VDC
& 5KAIC @ 130 VDC).

Convection Cooled

Overall dimensions and weight are listed on


the last page. When space requirements are
critical, please consult the factory. Case
specifications are subject to change.

. Mounting

Floor, wall or rack mounting is available; see


enclosure specifications on page 4 for details.

. Finish

Pretreated with a seven stage iron phosphate


wash, sealer and deionized rinse. Then coated
with an environmentally safe and durable
ANSI 61 gray Polyester TGIC Minite powder
finish.

STANDARDS

. UL 1012 *
. ABS *
. EN 55011
. NEMA PE5

. FCC Part 15
. IEEE / ANSI C37. 90.1
. IEC 60255-22-3
. IEC 61000-4

* pending

Optional Accessories
01C
01D
01F
01G

2 - Pole High Interrupting Capacity AC Breaker*


65KAIC @ 240 VAC / 35KAIC @ 480 VAC / 18KAIC
@ 600 VAC
2 - Pole High Interrupting Capacity AC Breaker*
100KAIC @ 240 VAC / 65KAIC @ 480 VAC / 25KAIC
@ 600 VAC
3 - Pole High Interrupting Capacity AC Breaker*
65KAIC @ 240 VAC / 35KAIC @ 480 VAC / 18KAIC
@ 600 VAC
3 - Pole High Interrupting Capacity AC Breaker*
100KAIC @ 240 VAC / 65KAIC @ 480 VAC / 25KAIC
@ 600 VAC
* Only available for units with current draws above 8 amps

19T
19U
19V
47C
11F
20Q
217
38D
11L
102
11W
11Y
09C
01V
09W
46R

AC Breaker Trip on HVSD


Adjustable Ground Detection Sensitivity
AC Voltage & Current Metering (1%)
DC Breaker 10KAIC
Special 30mV Filtering
Equalize Fan Control Relay
Reverse Polarity Protection & LED
Copper Ground Bus Bar
Lightning Arrestor
Blocking Diode
External Temperature Probe 24ft
External Temperature Probe 100ft
I.D. Tags - White text on black background
I.D. Tags - Black text on white background
Heat Shrink Wire Markers with Electrical Schematic
Discrete Alarm Relays
Positive Ground
Negative Ground
High DC Volts
Charger Failure

ENVIRONMENTAL
Operating Temperature

.
0 to 50C (32 to 122F)
. Storage Temperature
-40 to 85C (-40 to 185F)
. Relative Humidity
to 95% (non-condensing)
. 0Cooling

ENCLOSURES

. NEMA Type 1
Consult factory for other enclosure ratings.
. Dimensions

Low DC Volts
Low DC Amps
Battery End of Discharge
High Voltage Shutdown

Communication Protocols
21J
21P
21Q
21S
21X

IEC 61850 (Ethernet)


DNP 3.0 (RS232/RS485/Ethernet)
Modbus (RS232/RS485/Ethernet)
Modbus RTU (RS232/RS485)
SNMP & Web Browser (Ethernet)

A77 Charger Chart


Single Phase

Model Number

AC Input Current Draw Amps @ 100% Load


(Recommended Feeder AC Supply Breaker)

DC
Amps

130 Volt Systems

48 Volt Systems

24 Volt Systems

(ABD)120/240/208
A77D(E)-6-24V
A77D(E)-12-24V
A77D(E)-16-24V
A77D(E)-20-24V
A77D(E)-25-24V
A77D(E)-30-24V
A77D(E)-35-24V
A77D(E)-40-24V
A77D(E)-50-24V
A77D(E)-60-24V
A77D(E)-75-24V
A77D(E)-100-24V
A77D(E)-6-48V
A77D(E)-12-48V
A77D(E)-16-48V
A77D(E)-20-48V
A77D(E)-25-48V
A77D(E)-30-48V
A77D(E)-35-48V
A77D(E)-40-48V
A77D(E)-50-48V
A77D(E)-60-48V
A77D(E)-75-48V
A77D(E)-100-48V
A77D(E)-6-130V
A77D(E)-12-130V
A77D(E)-16-130V
A77D(E)-20-130V
A77D(E)-25-130V
A77D(E)-30-130V
A77D(E)-35-130V
A77D(E)-40-130V
A77D(E)-50-130V
A77D(E)-75-130V

Model Number
A77D(E)-75-24V
A77D(E)-100-24V
A77D(E)-125-24V
A77D(E)-150-24V
A77D(E)-200-24V
A77D(E)-250-24V
A77D(E)-300-24V
A77D(E)-400-24V
A77D(E)-50-48V
A77D(E)-75-48V
A77D(E)-100-48V
A77D(E)-125-48V
A77D(E)-150-48V
A77D(E)-200-48V
A77D(E)-250-48V
A77D(E)-300-48V
A77D(E)-400-48V
A77D(E)-25-130V
A77D(E)-30-130V
A77D(E)-35-130V
A77D(E)-40-130V
A77D(E)-50-130V
A77D(E)-75-130V
A77D(E)-100-130V
A77D(E)-125-130V
A77D(E)-150-130V
A77D(E)-200-130V
A77D(E)-250-130V
A77D(E)-300-130V
A77D(E)-400-130V
A77D(E)-500-130V

6
12
16
20
25
30
35
40
50
60
75
100
6
12
16
20
25
30
35
40
50
60
75
100
6
12
16
20
25
30
35
40
50
75

3 / 2 / 2 (5/5/5)
6 / 3 / 3 (10/5/5)
8 / 4 / 5 (15/10/10)
10 / 5 / 6 (15/10/10)
12 / 6 / 7 (20/10/10)
--------------6 / 3 / 3 (10/5/5)
12 / 6 / 7 (20/10/10)
16 / 8 / 9 (25/15/15)
20 / 10 / 11 (30/15/20)
24 / 12 / 14 (35/20/25)
--------------15 / 7 / 8 (25/10/15)
29 / 15 / 17 (40/25/25)
39 / 20 / 23 (60/30/35)
49 / 24 / 28 (70/35/40)
61 / 31 / 35 (90/50/50)
-------

DC
Amps

130 Volt Systems

48
V Volt Systems

24
V Volt Systems

75
100
125
150
200
250
300
400
50
75
100
125
150
200
250
300
400
25
30
35
40
50
75
100
125
150
200
250
300
400
500
Note: Case size subject to change without notice
*Consult Factory for optional export crating weight

-----

(A)120
----------15 (25)
17 (25)
20 (30)
24 (35)
29 (40)
37 (50)
49 (70)
----------29 (40)
34 (50)
39 (60)
49 (70)
59 (90)
73 (100)
98 (125)
----------73 (100)
85 (125)
98 (150)
-----

(D)208

----------8 (15)
10 (15)
11 (20)
14 (20)
17 (25)
21 (30)
28 (40)
----------17 (25)
20 (30)
23 (35)
28 (40)
34 (50)
42 (60)
56 (90)
----------42 (60)
49 (70)
56 (90)
70 (100)
106 (150)

(B)240
----------7 (15)
9 (15)
10 (15)
12 (20)
15 (20)
18 (30)
24 (35)
----------15 (20)
17 (25)
20 (30)
24 (35)
29 (40)
37 (50)
49 (70)
----------37 (50)
43 (60)
49 (70)
61 (90)
92 (125)

(C)480

----------4 (10)
4 (10)
5 (10)
6 (10)
7 (10)
9 (15)
12 (20)
------5 (10)
6 (10)
7 (10)
9 (15)
10 (15)
12 (20)
15 (20)
18 (25)
24 (35)
4 (10)
7 (10)
10 (15)
12 (20)
15 (20)
18 (25)
21 (30)
24 (35)
31 (50)
46 (70)

Enclosure
(ZD)600
--------------4 (10)
5 (10)
6 (10)
7 (10)
10 (15)
--------5 (10)
6 (10)
7 (10)
8 (15)
10 (15)
12 (20)
15 (20)
20 (30)
3 (5)
6 (10)
8 (15)
10 (15)
12 (20)
15 (20)
17 (25)
20 (30)
24 (35)
37 (50)

Three Phase
AC Input Current Draw Amps @ 100% Load
(Recommended Feeder AC Supply Breaker)

477
477
477
477
477
977
977
10
10
477
477
477
477
477
477
477
977
977
977
477
477
477
477
477
477
977
977
977
72N

Enclosure

(D) 2 0 8

(B) 240

(C ) 4 8 0

(ZD) 600

11 (15)
14 (20)
18 (25)
22 (30)
29 (40)
36 (50)
43 (60)
58 (80)
14 (20)
22 (30)
29 (40)
36 (50)
43 (60)
58 (80)
72 (100)
86 (125)
115 (175)
18 (30)
22 (30)
25 (35)
29 (40)
36 (50)
54 (80)
72 (90)
90 (125)
108 (150)
144 (200)
180 (250)
216 (300)
288 (400)
360 (500)

9 (15)
12 (20)
16 (25)
19 (30)
25 (35)
31 (50)
37 (60)
50 (70)
12 (20)
19 (30)
25 (35)
31 (50)
37 (60)
50 (70)
62 (90)
75 (100)
100 (150)
16 (25)
19 (30)
22 (30)
25 (35)
31 (50)
47 (70)
62 (90)
78 (125)
94 (150)
125 (175)
156 (225)
187 (300)
250 (350)
312 (450)

5 (10)
6 (10)
8 (15)
9 (15)
12 (20)
16 (25)
19 (30)
25 (35)
6 (10)
9 (15)
12 (20)
16 (25)
19 (30)
25 (35)
31 (50)
37 (60)
50 (70)
8 (15)
9 (15)
11 (15)
12 (20)
16 (25)
23 (35)
31 (50)
39 (60)
47 (70)
62 (90)
78 (125)
94 (150)

4 (5)
5 (10)
6 (10)
7 (15)
10 (15)
12 (20)
15 (25)
20 (30)
5 (10)
7 (15)
10 (15)
12 (20)
15 (25)
20 (30)
25 (35)
30 (50)
40 (60)
6 (10)
7 (15)
9 (15)
10 (15)
12 (20)
19 (30)
25 (35)
31 (50)
37 (60)
50 (70)
62 (90)
75 (100)
100 (150)
125 (175)

125 (175)
156 (225)

10
10
10
10
10

977
977
72N
72N
72N
46N
46N
47N
977
977
977
72N
72N
46N
46N
47N
47N
977
977
977
977
977
72N
72N
46N
46N
46N
47N
47N
57
57

Shipping
Weight*

(Approximate)

lbs

kgs

71
92
98
100
104
147
150
174
185
208
350
385
84
108
146
158
170
190
196
240
236
300
350
460
147
185
212
235
255
300
432
422
480
735

32
42
45
46
48
67
69
79
84
95
159
175
38
49
66
72
73
86
89
109
107
137
159
209
67
84
96
107
116
137
196
192
218
334

Shipping
Weight*

(Approximate)

lbs

kgs

330
475
530
600
675
800
875
1050
317
374
600
680
700
755
800
900
1200
305
315
330
335
410
660
750
850
1067
1800
2000
2028
2500
3645

150
215
240
272
306
363
398
477
144
170
272
308
318
342
363
408
544
138
143
150
161
186
299
340
385
484
816
907
920
1134
1653

A77 Charger Chart


Three Phase

DC
Amps

Model Number

260 Volt
Systems

AC Input Current Draw Amps @ 100% Load


(Recommended Feeder AC Supply Breaker)

A77D(E)-25-260V
A77D(E)-50-260V
A77D(E)-75-260V
A77D(E)-100-260V
A77D(E)-150-260V
A77D(E)-200-260V

(D)208

25
50
75
100
150
200

(B)240

36
72
108
144
216
288

Enclosure

(Approximate)

(ZD)600

(C)480

31
62
94
125
187
250

Shipping
Weight*

16
31
47
62
94
125

72N
72N
46N
47N
47N
57

13
26
39
52
78
104

lbs

kgs

600
700
900
1800
2200
3000

272
317
408
816
998
1360

Note: Case size subject to change without notice


*Consult Factory for optional export crating weight

Enclosure Specifications
Overall Dimensions
Enclosure

Width

Depth

Cable Entry

Height

Optional
Mounting
Kits

Standard
Mounting

in

mm

in

mm

in

mm

10

19

483

15.1

384

12.3

310

RIGHT TOP / BOTTOM LEFT TOP / BOTTOM

WALL

19 / 23

477

19

483

15.1

384

24

610

RIGHT TOP / BOTTOM

WALL

19 / 23

977

20.8

585

15.7

399

37.9

963

RIGHT TOP / BOTTOM LEFT TOP / BOTTOM

FLOOR

23

72N

27

686

23.5

597

44.5

1130

BOTTOM RIGHT

BOTTOM LEFT

FLOOR

---

---

1676

TOP / BOTTOM

TOP / BOTTOM

FLOOR

---

---

AC Input

DC Input

Rack

LEFT TOP / BOTTOM

Floor

STD

46N

30

762

20

508

66

47N

38

986

39.4

1001

70

1778

TOP / BOTTOM

TOP / BOTTOM

FLOOR

---

---

57

60

1524

36

915

80

2032

TOP / BOTTOM

TOP / BOTTOM

FLOOR

---

---

Model Number Nomenclature


A77D (E) - 25 - 130V - ( ) 1 - ( ) - (

Model Number

Factory Assigned
Accessory Code

Battery Eliminator

Battery Cell Type


Code

DC Amps

AC Phase Code

DC Volts

AC Voltage Code

AC Voltage Codes

AC Phase Codes

ABD - 120/240/208
A - 120
D - 208
Q - 230
BL - 240/220
B - 240
G - 380
ZA - 400
J - 415
K - 440
C - 480

1 - Single Phase
3 - Three Phase

Ordering Information

When ordering, please specify:


- La Marche Model Number A77D/A77DE
- DC Amps
- DC Volts
- Special Frequency, When Required
- AC Voltage Code
- AC Phase Code
- Battery Cell Type Code
- Optional Accessories (Option Code)

Battery Cell Type Code


11L
57L
17N
83N

12L 13L 22L 23L 24L 25L 26L 53L 54L 55L 56L
58L 59L 60L 61L 62L 110L 115L 116L 120L
18N 19N 20N 33N 34N 35N 36N 37N 38N 39N
84N 85N 86N 87N 88N 89N 90N 91N 92N 93N
L = Lead Acid
N = Nickel Cadmium
LR = VRLA

Battery Charger Sizing Guidelines


- Required Battery Backup Time (Hours)
- DC Output Voltage
- Ampere Hour Capacity of Battery
- Allowable Recharge Time From Full Discharge
(Hours), Where Applicable
- Continuous and Intermittent DC Loads and
Duration (Amps)