Electrical Maintenance
Electrical Maintenance
Electrical Maintenance
Section 26 29 90
Low Voltage Power
System Maintenance
2008-06-02
Use this Section to specify maintenance requirements for Low Voltage Power Systems (under 750
Volts), including inspection and report requirements.
Repair or replacement services are not included in this Section.
This Master Specification Section contains:
.1
Cover Sheet
.2
General
Intent
Related Work Not Provided Under This Contract
Regulatory Requirements
Appended Documents
Reference Documents
Safety Procedures
Contractors Qualifications
Inspection and Testing Reports
Inquiries
2.
Products
(Not used)
3.
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
Execution
General Cleaning Requirements
Power Transformers, Dry Type
Maintenance of Switchgear Enclosures
Maintenance of Low Voltage Air Circuit Breakers
Fused or Unfused LB and NLB Disconnect Switchgear
Maintenance of Protective Relays
Maintenance of Overhead Radial Power Lines
Surge Arrestors
Deficiency List and Cost Estimate
PMSMS
Alberta Infrastructure
Master Specification System
Page 0
2008-06-02
.3
Appended Section 26 29 90A - Low Voltage Power System Maintenance Inspection Reports:
.1
.2
.3
.4
.5
.6
.7
.8
.9
.10
.11
.12
.13
.4
Appended Section 26 29 90B - Low Voltage Power System Maintenance Equipment Schedule.
PMSMS
Alberta Infrastructure
Master Specification System
Page 01
Section 26 29 90
Low Voltage Power
System Maintenance
.2
Obtain electrical single line control diagram, if required, providing reference to project plan
number and drawing number, from:
Office of the Tender Administrator
Main Floor, 6950 - 113 Street
Edmonton, Alberta T6H 5V7
Telephone (780) 427-3962
.3
Complete all portions of Section 26 29 90B - Low Voltage System Maintenance Power
Equipment Schedule.
The need for repair or replacement of faulty or non-operating components and devices will
normally be identified in the Inspection Report submitted by Contractor performing work of this
Section.
.4
PMSMS
Alberta Infrastructure
Master Specification System
Page 02
2008-06-02
This Equipment Schedule is provided as an example only. Refer to Section 26 29 90B and Section
Cover Sheet for details.
Equipment
Make
Model
Quantity
PMSMS
Alberta Infrastructure
Master Specification System
Page 03
Alberta Infrastructure
1.
GENERAL
1.1
INTENT
Section 26 29 90
Low Voltage Power System Maintenance
Equipment Schedule
Page 1
.1
This Section specifies maintenance service requirements for low voltage power systems.
.2
Provide labour and equipment for testing of existing low voltage power systems.
.3
1.2
1.3
.1
Comply with Electrical Protection Act of Alberta and rules and regulations made pursuant
thereto, including the Canadian Electrical Code.
.2
.3
Electrical products shall be approved by Canadian Standards Associations (CSA) and bear
CSA label. Alternatively, where a product does not bear a CSA label, it shall be approved
in writing by authority having jurisdiction.
.4
Submit to authority having jurisdiction and utility company, necessary number of drawings
and specifications for examination and approval prior to commencement of work. Pay
associated fees.
Alberta Infrastructure
1.4
Section 26 29 90
Low Voltage Power System Maintenance
Equipment Schedule
Page 2
APPENDED DOCUMENTS
.1
.2
.3
1.5
REFERENCE DOCUMENTS
.1
.2
.3
.4
.5
Section 26 29 90
Low Voltage Power System Maintenance
Equipment Schedule
Page 3
Alberta Infrastructure
1.6
SAFETY PROCEDURES
.1
1.7
.2
.3
At point of isolation, rack out and tag, or lock off and tag switches or breakers.
Place tag and safety lock at points of isolation.
.4
.5
On completion of the Work and prior to return of system to normal, remove safety
grounds and signify:
.1
.2
CONTRACTOR QUALIFICATIONS
.1
.2
Foreman employed for this project shall be a licensed journeymen electrician holding
current journeyman's certificate in the Province of Alberta.
.3
1.8
Record inspection and test results on appropriate forms included in Section 26 29 90A Low Voltage System Maintenance Inspection Report, appended to this Section.
.2
.3
Record comparisons of test data with previous records, with comments on deviations and
observed trends.
.4
Upon completion of inspections and tests, assemble three copies of reports and submit to
Minister.
Section 26 29 90
Low Voltage Power System Maintenance
Equipment Schedule
Page 4
Alberta Infrastructure
2.
PRODUCTS
(Not Used)
3.
EXECUTION
3.1
.2
.3
Where applicable, use only clean lint free cloth and clean brushes.
3.2
Strictly adhere to required procedures for system switching operations. Switching, deenergizing and energizing shall be performed by authorized personnel only.
.2
.3
General:
.1
The following tests and procedures shall apply to dry type distribution
transformers:
.1
.2
.3
.4
.5
.4
.2
.3
Check tap changer for connection and proper mechanical and electrical operation,
if applicable.
.4
.5
Section 26 29 90
Low Voltage Power System Maintenance
Equipment Schedule
Page 5
Alberta Infrastructure
.6
.7
Cleaning:
.8
.5
.1
.2
.3
Clean lead or cable supports, tap changers, bushings and other insulating
surfaces using brush or wiping with lint free cloth.
Check connections (including ground and tap changer links) for tightness. Torque
to proper value in accordance with manufacturer's recommendations.
.2
.6
.7
Ratio Test:
.1
Carry out ratio test of windings in all tap positions to ensure accuracy to within
0.001 percent.
.2
Insulation Resistance:
.1
.2
.8
Compare test results to factory test data and to previous maintenance test results.
Alberta Infrastructure
3.3
Section 26 29 90
Low Voltage Power System Maintenance
Equipment Schedule
Page 6
.2
Megger test using 250 volt megger (or size recommended by manufacturer)
between core and ground to ensure no other grounds exist between core and
ground.
.3
Compare values to factory test values and to previous maintenance test results.
.4
Strictly adhere to required procedures for system switching operations. Switching, deenergizing and energizing shall be performed by authorized personnel only.
.2
Completely isolate switchgear enclosure to be tested and inspected from sources of power.
.3
.4
.5
.6
Mechanical Inspection:
.1
.2
.3
.4
Check disconnects, starters, and circuit breakers in accordance with inspection and
test reports and procedures.
.5
.6
Inspect insulators and insulating surfaces for cleanliness, cracks, chips, tracking.
.7
.8
.9
.10
Perform
Alberta Infrastructure
.11
.7
.8
Section 26 29 90
Low Voltage Power System Maintenance
Equipment Schedule
Page 7
Cleaning:
.1
Check for accumulations of dirt especially on insulating surfaces and clean interiors
of compartments thoroughly using a vacuum or blower.
.2
.3
.4
.5
Electrical Testing:
.1
.2
.3
Megger test bussing phase to ground, and phase to phase, using a 1000 volt
megger.
.4
Test contact resistance across bolted sections of buss bars. Record results and
compare test values to previous acceptance and maintenance results and comment
on trends observed.
.9
.10
3.4
Strictly adhere to required procedures for system switching operations. Switching, deenergizing and energizing shall be performed by authorized personnel only.
.2
.3
.4
Alberta Infrastructure
Section 26 29 90
Low Voltage Power System Maintenance
Equipment Schedule
Page 8
.5
Record manufacturer, serial number, type and function of breaker, reading of operations
counter, date of inspection, and signature of person responsible for inspection on report
sheet.
.6
.7
.1
.2
.3
.4
.5
.6
.7
.8
.9
.10
damage to or excessive wear on operating linkage, ensure all clevis pins are
securely retained in position.
.11
.12
Cleaning:
.1
Remove accumulations of dirt from insides of cubicles with vacuum cleaner and/or
blower.
.2
Clean insulating surfaces using brush or wiping with lint free cloth.
.8
.9
'Dress' pitting on contact surfaces, using a burnishing tool. 'Dress' major arcing on
contacts to smooth condition. Remove filings before switchgear is re-energized. Report
unsafe conditions resulting from severe arcing or burning of contacts.
Section 26 29 90
Low Voltage Power System Maintenance
Equipment Schedule
Page 9
Alberta Infrastructure
.10
On completion of foregoing tasks, lightly lubricate bearing points in operating linkage with
manufacturer's specified lubricant. Operate breaker several times to ensure smoothness of
mechanical operation.
.11
.12
.13
On first inspection, record data to auxiliary equipment, i.e. primary fuses, potential
transformer, potential fuses, and current transformers. Record serial numbers, catalogue
numbers, sizes, ratios.
.14
.15
3.5
General:
.1
Test contact resistance across closed line-load contacts, and line and load
circuit breaker plug-in clusters. Record results. Clean contacts using
appropriate tools to get lowest contact resistance reading possible.
.2
.3
.1
Strictly adhere to required procedures for system switching operations. Switching, deenergizing and energizing shall be performed by authorized personnel only.
.2
.3
.4
.5
.6
Alberta Infrastructure
.7
.8
.9
Section 26 29 90
Low Voltage Power System Maintenance
Equipment Schedule
Page 10
.2
.3
.4
.5
.6
fixing bolts being fully tightened where bolted-on shields are fitted.
.7
.8
.9
.10
damage to or excessive wear on operating linkage. Check that all clevis pins are
securely retained in position.
.11
.12
.13
.14
Cleaning:
.1
.2
Clean insulating surfaces using brush or wiping with lint free cloth.
.3
.4
.5
Torque to
Alberta Infrastructure
.10
.11
3.6
Section 26 29 90
Low Voltage Power System Maintenance
Equipment Schedule
Page 11
.2
.3
.4
.5
.1
Strictly adhere to required procedures for system switching operations. Switching, deenergizing and energizing shall be performed by authorized personnel only.
.2
Completely isolate protective relays to be tested and inspected from sources of power.
.3
Set and test protective relays to "as found" settings or to new settings provided by
Minister prior to maintenance commissioning.
.4
.5
Carefully remove cover from relay case. Inspect cover gasket. Check glass for
tightness and cracks.
.2
.3
Ensure disc has proper clearance and freedom of movement between magnet
poles.
.4
.5
Manually operate disc to check for freedom of movement. Allow spring to return
disc to check proper operation.
Alberta Infrastructure
.6
.7
.8
Section 26 29 90
Low Voltage Power System Maintenance
Equipment Schedule
Page 12
.6
.7
Cleaning:
.1
.2
.3
Remove dust and foreign materials from interior of relay using small brush or low
pressure (7 lbs.) blower of nitrogen.
.4
Remove rust or metal particles from disc or magnet poles with magnet cleaner or
brush.
.5
.6
Clean pitted or burned relay contacts with burnishing tool or non-residue contact
cleaner.
Zero check.
.2
.3
Time-current characteristics.
.4
.5
Instantaneous pickup.
.6
.7
Proof test each relay in its control circuit by simulated trip tests to ensure total and
proper operation of breaker and relay trip circuit by injection of the relay circuit to
test the trip operation.
Inspect and test in accordance with manufacturer's most recent installation and
maintenance brochure.
Alberta Infrastructure
.9
3.7
Section 26 29 90
Low Voltage Power System Maintenance
Equipment Schedule
Page 13
.2
Perform tests using manufacturer's relay test unit as applicable, with corresponding
test instructions.
.3
If the manufacturer's tester is not available, use a relay tester unit approved by
relay manufacturer, with proper test data and test accessories.
.4
Proof test each relay in its control circuit by simulated trip tests to ensure total and
proper operation of breaker and relay trip circuit by injection of relay circuit to test
trip operation.
.5
.1
Strictly adhere to required procedures for system switching operations. Switching, deenergizing and energizing shall be performed by authorized personnel only.
.2
Completely isolate overhead radial power lines to be tested and inspected from sources of
power.
.3
.4
Inspect insulators and insulating surfaces for cleanliness, cracks, chips, tracking, and clean
insulators thoroughly.
.5
Check cable connections to insulators and check cable sag between poles.
discovered unsafe conditions.
.6
Visually check wooden poles and sound test with 18 oz. wooden mallet.
.7
Visually inspect metal line structures for rust, deterioration, metal fatigue, and report
discovered unsafe conditions.
.8
Inspect crossarms, bolts, rack assemblies, guys, guy wires, and dead ends.
discovered unsafe conditions.
.9
.10
Report
Report
Alberta Infrastructure
3.8
Section 26 29 90
Low Voltage Power System Maintenance
Equipment Schedule
Page 14
SURGE ARRESTORS
.1
Strictly adhere to required procedures for system switching operations. Switching, deenergizing and energizing shall be performed by authorized personnel only.
.2
Completely isolate surge arrestors to be tested and inspected from sources of power.
.3
.4
Inspect surge arrestors for cleanliness, cracks, chips, tracking and clean thoroughly.
.5
.6
.7
3.9
.2
Provide cost estimates for replacements and repairs of deficiencies for each building.
Include breakdown showing cost for each type of device.
END OF SECTION