Honey Well Smart Temp Transmitter Spec

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

STT 3000 EN0I-5222

December 2008
Smart Temperature Transmitter
Specification and
Model STT350 Model Selection
Guide
Introduction
Honeywell’s microprocessor based STT350
Smart Temperature Transmitter converts a
primary sensor input into an output signal for
a conventional 4 to 20mA, two wire loop.

This universal temperature input model


readily accepts signals from a wide variety of
industry standard thermocouples or
resistance temperature detectors (RTDs) as
well as a straight millivolt or Ohms sensor. Its
output signal is either proportional to the
measured variable or linearized to
temperature, and is transmitted in either an
analog 4-20mA format or a digital DE protocol
format for direct digital integration to the
TPS® control system. You easily select the
analog or digital format for the output signal
transmission through the Smart Field
Communicator® (SFC) which is the common
hand-held operator interface for our
Smartline™ Transmitters. All configuration,
operation and communication functions are
under the control of the STT350’s Figure 1 – STT350 Transmitter in Field Mount Housing.
microprocessors and are implemented
through the SFC.

Features
• Single model accepts input signals from a • Suitable for DIN rail mounting or • Write protect link included to
choice of primary sensors to satisfy varying remote field mounting in a safeguard configuration settings.
applications requirements with minimum flameproof housing. • Designed to be in compliance with
transmitter inventory. • Smart transmitter personality with EMC requirements and is CE-
• Standard digital cold-junction compensation local or remote interfacing means Marked.
function provides accurate and reliable significant manpower efficiency • Includes sensor break detection
temperature measurement over a wide improvements in commissioning, on all input wires.
ambient operating range. start-up, and ongoing • Post read validation of the
• Direct digital integration with TPS system maintenance functions. measured signal before providing
provides local measurement accuracy to the • Automatically provides true differ- fresh output.
system level without adding typical A/D and ential temperature measurement • Supports dual thermocouple
D/A converter inaccuracies. of thermocouple or RTD inputs by sensor inputs for redundant
• Added Smart features include reading of the individual linearization of each sensor operation.
highest and lowest inputs, external cold sensor reading and then • Integral analog or digital indicating
junction compensation temperature at an computing the difference. meter option
isothermal block and engineering units • Suitable for true 4-wire Pt100 • Surge/lightning protection options
displayed in degrees C, F, K, or R plus measurement (or 3- or 2-wire). can be installed internally in
millivolt and Ohms. • FISCO approved housing or externally in conduit.
EN0I-5222
Page 2
Description

The STT350 transmitter is suitable as a


direct replacement for any conventional
temperature transmitter in use today. Its
memory contains the characteristics of
most commonly used temperature
sensors. This means that you can use
the SFC to configure the transmitter for
any of these sensors and it will
automatically correct for their
associated non-linearities. You make all
transmitter adjustments and diagnostic
checks through an SFC connected
anywhere across the 4-20mA wire
route. This lets you initiate configuration
and maintenance functions at locations
remote from the transmitter itself. The
SFC is also fully compatible with all
other Honeywell Smartline
Transmitters. The transmitter module
can also be installed on a standard DIN
rail (to EN50022) or remotely mounted
in a flameproof housing designed for
either surface or two-inch pipe-stand
mounting. Transmitters can be pre-
configured at the factory to your exact
specifications or they will be shipped
with factory default configuration— Figure 2—Block Diagram
ready to accept your own configuration.

Performance Under Rated Conditions


nput Type Digital Maximum Range Limits Digital Normal Range Limits Standards
Accuracy Accuracy for
for Maxi- Normal Range
mum Range Limits
Limits
% of Max. °C °F °C °F °C °F
Span
RTD
Pt 100 0,01 -200 to 850 -328 to 1562 0,1 0,18 -200 to 450 -328 to 842 IEC 751:1986
(a=0.00385)
Pt 200 0,01 -200 to 850 -328 to 1562 0,1 0,18 -200 to 450 -328 to 842 IEC 751:1986
(a=0.00385)
Pt 500 0,02 -200 to 850 -328 to 1562 0,1 0,18 -200 to 450 -328 to 842 IEC 751:1986
(a=0.00385)
Pt 100J 0,01 -200 to 640 -328 to 1184 0,1 0,18 -200 to 450 -328 to 842 JISC 1604-81
(a=0.00392)
Ni 50 0,04 -80 to 150 -112 to 302 0,1 0,18 -50 to 150 -58 to 302 Honeywell Type A
Cu 10 0,37 -20 to 250 -4 to 482 1,0 1,8 -20 to 250 -4 to 482 General Electric
Cu 25 0,19 -20 to 250 -4 to 482 0,5 0,9 -20 to 250 -4 to 482 General Electric
T/C:
B 0,14 200 to 1820 392 to 3308 1,0 1,8 550 to 1820 1022 to 3308 IEC 584-1 (ITS-90)
C 0,03 0 to 2300 32 to 4172 0,6 1,08 0 to 1650 32 to 3002 IPTS 68
D 0,03 0 to 2300 32 to 4172 0,6 1,08 330 to 1370 626 to 2498 IPTS 68
E 0,04 -200 to 1000 -328 to 1832 0,2 0,36 0 to 1000 32 to 1832 IEC 584-1 (ITS-90)
J 0,04 -200 to 1200 -328 to 2192 0,2 0,36 0 – 800 32 to 1472 IEC 584-1 (ITS-90)
K 0,04 -200 to 1370 -328 to 2498 0,3 0,54 -120 to 1370 -191 to 2498 IEC 584-1 (ITS-90)
N 0,06 -200 to 1300 -328 to 2372 0,3 0,54 0 to 1300 32 to 2372 IEC 584-1 (ITS-90)
R 0,09 -50 to 1760 -58 to 3200 0,5 0,9 500 to 1760 932 to 3200 IEC 584-1 (ITS-90)
S 0,08 -50 to 1760 -58 to 3200 0,5 0,9 500 to 1760 932 to 3200 IEC 584-1 (ITS-90)
T 0,14 -250 to 400 -418 to 752 0,2 0,36 -100 to 400 -148 to 752 IEC 584-1 (ITS-90)
NiNiMoly 0,03 0 to 1300 32 to 2372 0,3 0,54 780 to 1300 1436 to 2372 G.E. (IPTS – 68)
Radiamatic 0,6 420 to 1800 788 to 3272 0,7 1,26 780 to 1800 1436 to 2372 Honeywell (RH)
Millivolts 0,01 -20 to 120 mV 8µV -10 to 45 mV
Ohms 0,01 0 to 2000 Ω 0,15Ω 0 to 2000 Ω
EN0I-5222
Page 3
Note that the Page 2 Accuracy values are available merely by selecting the sensor type and range (i.e. without user
calibration). Improvements of up to 2 times can be obtained for the accuracy by calibrating to the required LRV/URV
values. All STT350 units pass through 20 hours of Environmental Stress Screening (ESS) by fast cycling between -
40 and +85°C to ensure maximum product reliability. During this ESS process, the ambient temperature
compensation coefficients are determined for individual units and burned in transmitter memory to provide maximum
performance over a wide range of operating conditions.

SPECIFICATIONS
Operating Conditions
Parameter Reference conditions Rated Condition Operative Limits Transportation and
Storage

Ambient Temperature 23°C ± 2 -40 to 85 -40 to 85 * -50 to 100


73°F ± 4 -40 to 185 -40 to 185 -58 to 212
Humidity
Rack Mounting %RH 10 to 55 5 to 95 5 to 100 5 to 100
Mounted in EP %RH 10 to 55 5 to 100 5 to 100 5 to 100
Housing
Supply Voltage, Current Voltage Range : 10.8 to 42.4 Vdc at the transmitter terminals
and Load Resistance Current Range : 3.6 to 21.8 mA
Load Resistance : 0 to 1450 Ohms (as shown in Fig 3)
Vibration Maximum of 4g over 15 to 200Hz. (restricted to 3g with indication meter)
Shock Maximum of 40g
Output D/A Accuracy ±0.025% of span
Cold Junction Accuracy ± 0.25°C
Total Reference Accuracy In Analog Mode= Digital Accuracy of input + Output D/A Accuracy + CJ Accuracy (T/Cs only)
In Digital Mode = Digital Accuracy of input + CJ Accuracy (T/Cs only)
(example: transmitter operating in Analog Mode with Pt100 sensor and 0 to
200°C
Total Reference Accuracy = 0.1 + ((200/100) x 0.025) = 0.15°C
100
Digital Ambient Temperature Effect RTDs or Ohms : 0.029% of reading
(per 10°C change from 20°C reference) T/Cs or mV : 0.042% of reading
Cold Junction Rejection Effect 60:1 for changes from 23°C ambient
Output D/A Ambient Temperature Effect 0.045% of span per 10°C change
Total Output Ambient Temperature Effect (ATE)
In Analog Mode = Digital ATE + Output D/A ATE + CJ ATE (T/Cs only)
In Digital Mode = Digital ATE + CJ ATE (T/Cs only)
Power Supply Voltage Effect 0.005% of span per Volt
Parameter Description
Adjustment Range No limits to adjustments within the Maximum range except minimum span limit of 1 engineering unit
e.g. 1°C
Output (2 Wire) 4-20mA or Honeywell DE digital protocol
Extended range: 3.8-20.8mA. Fail safe modes <3.8mA or 21.8mA
Damping Time Constant Adjustable from 0 to 102 seconds digital damping

Thermocouple Burnout Burnout detection is user selectable


Upscale or downscale with critical status message
Input to Output Galvanic Meets dielectric strength test of 1400Vac rms (50/60Hz) 2000Vdc for 1 minute
Isolation
Series Mode Rejection 40dB (100 to 1) for 50 or 60Hz ±0.5Hz (with internal software filter set to local power line frequency)
EMC Compliance In compliance with 89/336/EEC, Electromagnetic Compatibility (EMC) Directive
RFI Rejection ±0.1% of span at 30V/m over 20 to 1,000MHz in explosion-proof housing with shielded cables
Update Rate 2 to 5 measurements per second depending on input variation
Response Time 1.5 seconds to 90% of final step value
Stability/Time Drift 0.05% of maximum span per year. Auto calibration against internal reference every second.

Short term Operative Limit of –50°C (-58°F)


EN0I-5222
Page 4

Physical Mounting, Construction and Approvals


Parameter Description
Mounting DIN rail (top hat or G rail)
Field Mount Housing with surface mounting or 2-inch pipe mounting (IP 66/NEMA 4X Rating)
Field Mount Housing meets the applicable requirements of NEMA 7 and 9
Wiring Screw Terminals - M3.5x6.7mm nickel coated brass Accepts up to 12AWG, 16AWG recommended
Net Weight Transmitter for DIN rail mount - 0.5kg (1.1 pounds)
Transmitter in EP or XC housing - 1.6kg (3.6 pounds)
Transmitter + indicator in housing - 2.4kg (5.2 pounds)
Materials of construction Transmitter module - Aluminum housing with baked on Polyester paint cover - Noryl terminal block.
EP housing - Aluminum housing with baked on epoxy-polyester hybrid paint cover (beige)
XC housing - Aluminum housing with baked on 2 coats epoxy resin cover (beige)
ST02 housing - Aluminum housing with baked on 2 coats epoxy resin cover (red)
Dimensions See Fig 4
Sensor/Cable Entry (EP, 1/2 inch NPT electrical connection with optional adapters for M20x1.5, or 3/4 inch NPT
XC or ST02 Housing)
Safety Approvals STT350 Module CENELEC Intrinsically Safe Ex ia IIC T4/T5/T6 with
30V/100mA/1.2W barrier
(T4/T5/T6 = -20 to +80/+50/+40 °C
ambient)
CSA Intrinsically Safe Class I, Div.1, Groups A
to D
FM Intrinsically Safe Class I, II, III, Div. 1,
Groups A to G
Non-incendive Class I, Div. 2, Groups A
to D
Suitable for Class II, III, Div. 2, Groups F
and G
Russian Certificate of pattern Approval
No 332 of 18/10/94 IEC 68 and IEC 801
Additional Approvals with EP, XC or With or Without Integral Meter
ST02 Housings Zone 2: T6, 28V/22mA
Cenelec Flame Proof Ex d IIC T6
CSA Explosion Proof Class I, II, III, Div. 1, Groups B to G
FM Explosion Proof Class I, II, III, Div. 1, Groups B to G
Without Integral Meter
FM Explosion Proof Class I, II, III, Div. 1, Groups A to G
Surge/Lightning Internal SP Selection 10 kA peak current (8/ 20 µs waveform), 10kV peak
Voltage (10/50 µs waveform)
Protection Options External LP Selection 10 kA peak current (10/ 20 µs waveform), 500A peak
Current (10/1000 µs waveform)
Thermowell & Probe STT350 can be supplied integrally mounted with any of the previously listed standard resistance
Availability temperature devices (RTDs) and thermocouple (T/Cs) elements.
Probe Types:
• 1/4" Rigid or spring loaded RTDs or T/Cs in Inconel or Stainless Steel sheaths in standard lengths
from 3" to 24" (other lengths by request).
• Standard or heavy duty service.
• Locally mounted to the STT350 housing or remotely mounted into explosion-proof mounting heads.
• With (or without) probe lag hardware : Hex nipple, Straight nipple or Double lag and Union
connections.
• Single or dual element availability; grounded or ungrounded T/Cs
Additionally, the following types of Thermowells can also be provided as an integral thermal solution :
Thermowell Materials:
Carbon Steel, 304SS, 316SS, 316L SS, 446SS, Hastelloy B, Hastelloy C, Monel, Inconel 600 (other
materials by request).
Thermowell Types:
Threaded well, Flanged well, or Socket well, (with or without thermowell lag extensions).
Flange Types:
Raised Face, Flat Faced and Ring Type Joint flange availability in 1", 1.5", 2" or 3" sizes.
Flange Ratings:
ANSI 150#, 300#, 600# and 1500# ratings.
EN0I-5222
Page 5

NOTE: A minimum of 250 Ohms of


loop resistance is required to support
communications. Loop resistance is
the total of loop wiring resistance,
safety barrier and receiving device
input developing resistor.

The triangle outlined by the heavy


lines alongside shows the operating
area for field wiring and barrier
resistance beyond the 250 Ohms
necessary for communications.

If a Smart Meter is included in the


loop, allow an additional 2.25 Volts for
meter power.

If surge lightning protection is included


this adds 44 Ohms to the loop
resistance; i.e., allow 1 Volt additional
supply or reduced loop wiring power. Figure 3—Supply Voltage versus Load Resistance

Figure 4—STT350 Transmitter and Optional Flameproof Housing Dimensions –reference only – mm (inches)
EN0I-5222
Page 6

Model Selection Guide (34-44-16-02)


EN0I-5222
Page 7
EN0I-5222
Page 8
EN0I-5222
Page 9

This page has been intentionally left blank


EN0I-5222
Page 10

Warranty/Remedy

Honeywell warrants goods of its manufacture as being free of defective materials and faulty
workmanship. Contact your local sales office for warranty information.
If warranted goods are returned to Honeywell during the period of coverage, Honeywell will
repair or replace without charge those items it finds defective. The foregoing is Buyer's sole
remedy and is in lieu of all other warranties, expressed or implied, including those of
merchantability and fitness for a particular purpose.
Specifications may change without notice. The information we supply is believed to be
accurate and reliable as of this printing. However, we assume no responsibility for its use.

While we provide application assistance personally, through our literature and the Honeywell
web site, it is up to the customer to determine the suitability of the product in the application.

Honeywell Process Solutions


2500 W. Union Hills Dr.
Phoenix, AZ 85027
EN0I-5222
Tel: 877.466.3993 or 602.313.6665
December 2008
www.honeywell.com/ps © 2006-08 Honeywell International Inc.

You might also like