ATS22C41Q: Product Data Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

Product data sheet

Characteristics

ATS22C41Q

soft starter-ATS22-control 220V-power


230V(110kW)/400...440V(220kW)

Range of product

Altistart 22

Product or component
type

Soft starter

Product destination

Asynchronous motors

Product specific application

Severe and standard applications

Component name

ATS22

Network number of
phases

3 phases

Power supply voltage

230...440 V (- 15...10 %)

Motor power kW

220 kW at 440 V
220 kW at 400 V
110 kW at 230 V

Factory setting current

388 A

Power dissipation in W

177 W for standard applications

Utilisation category

AC-53A

Type of start

Start with torque control (current limited to 3.5 In)

Icl nominal current

410 A (connection in the motor supply line) for standard applications

IP degree of protection

IP00

Complementary
Assembly style

With heat sink

Function available

Internal bypass

Power supply voltage limits

195...484 V

Power supply frequency

50...60 Hz (- 10...10 %)

Network frequency

45...66 Hz

Device connection

In the motor supply line


To the motor delta terminals

Control circuit voltage

220...230 V -15...10 % at 50/60 Hz

Control circuit consumption

20 W

Discrete output number

Discrete output type

(R2)Relay outputs 230 V running, alarm, trip, stopped, not stopped, starting,
ready, C/O
(R1)Relay outputs 230 V running, alarm, trip, stopped, not stopped, starting,
ready, C/O

Minimum switching current

Relay outputs 100 mA at 12 V, DC

Maximum switching current

Relay outputs 2 A at 30 V, DC inductive load, L/R = 7 ms


Relay outputs 2 A at 250 V, AC inductive load, cos phi = 0.4, L/R = 20 ms
Relay outputs 5 A at 30 V, DC resistive load, cos phi = 1
Relay outputs 5 A at 250 V, AC resistive load, cos phi = 1

Discrete input number

Discrete input type

(LI1, LI2, LI3)logic 5 mA 4.3 kOhm

Discrete input voltage

24 V (<= 30 V)

Discrete input logic

(LI1, LI2, LI3)positive logic state 0 < 5 V and < 2 mA state 1 > 11 V and > 5 mA

Output current

0.4...1 Icl adjustable

PTC probe input

750 Ohm

Communication port protocol

Modbus

Connector type

1 RJ45

Communication data link

Serial

Physical interface

RS485 multidrop

Jan 23, 2015

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.

Main

Transmission rate

4800, 9600 or 19200 bps

Max nodes number

31

Protection type

Thermal protection on starter


Thermal protection on motor
Phase failure on line

Marking

CE

Type of cooling

Forced convection

Operating position

Vertical +/- 10 degree

Height

425 mm

Width

206 mm

Depth

299 mm

Product weight

33 kg

Environment
Electromagnetic compatibility

Voltage/Current impulse conforming to IEC 61000-4-5 level 3


Immunity to radiated radio-electrical interference conforming to IEC 61000-4-3
level 3
Immunity to electrical transients conforming to IEC 61000-4-4 level 4
Electrostatic discharge conforming to IEC 61000-4-2 level 3
Damped oscillating waves conforming to IEC 61000-4-12 level 3
Conducted and radiated emissions conforming to IEC 60947-4-2 level A

Standards

EN/IEC 60947-4-2

Product certifications

CCC
CSA
C-Tick
GOST
UL

Vibration resistance

1.5 mm (f = 2...13 Hz) conforming to EN/IEC 60068-2-6


1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-6

Shock resistance

15 gn for 11 ms conforming to EN/IEC 60068-2-27

Noise level

56 dB

Pollution degree

Level 2 conforming to IEC 60664-1

Relative humidity

<= 95 % without condensation or dripping water conforming to EN/IEC 60068-2-3

Ambient air temperature for operation

> 40...< 60 C with current derating 2.2 % per C


-10...40 C without derating

Ambient air temperature for storage

-25...70 C

Operating altitude

> 1000...< 2000 m with current derating of 2.2 % per additional 100 m
<= 1000 m without derating

Offer Sustainability
Sustainable offer status
RoHS

Not Green Premium product


Compliant - since 0939 -

Schneider Electric declaration of conformity

Product environmental profile

Available

Download Product Environmental

Product end of life instructions

Available

Download End Of Life Manual

Product data sheet


Dimensions Drawings

ATS22C41Q

Frame Size D
Dimensions

Product data sheet


Mounting and Clearance

ATS22C41Q

Precautions
Standards
The Altistart 22 soft starter is compliant with pollution Degree 2 as defined in NEMA ICS1-1 or IEC 60664-1.
For environment pollution degree 3, install the Altistart 22 soft starter inside a cabinet type 12 or IP54.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
ATS22 soft starters are open devices and must be mounted in a suitable enclosure.
Failure to follow these instructions will result in death or serious injury.

Air Circulation
Leave sufficient free space to help the air required for cooling purposes to circulate from the bottom to the top of the unit.

Overheating
To avoid the soft starter to overheat, respect the following recommendations:
Mount the Altistart 22 Soft Starter within 10 of vertical.
Do not locate the Altistart 22 Soft Starter near heat radiating elements.
Electrical current through the Altistart 22 Soft Starter will result in heat losses that must be dissipated into the ambient air immediately
surrounding the soft starter. To help prevent a thermal fault, provide sufficient enclosure cooling and/or ventilation to limit the ambient
temperature around the soft starter.
If several soft starters are installed in a control panel, arrange them in a row. Do not stack soft starters. Heat generated from the
bottom soft starter can adversely affect the ambient temperature around the top soft starter.

Wall mounted or Floor-standing Enclosure with IP 23 Degree of protection


Introduction
To help proper air circulation in the soft starter, grilles and forced ventilation can be installed.

Ventilation Grilles

Forced Ventilation Unit

ATS22C41Q

Product data sheet

Connections and Schema

Power Terminal
Bar Style

Power supply and output to motor

Bar

5 mm (0.2 in)

Bolt

M12 (0.47 in)

Cable and protective cover

Size

Gauge

2X250 MCM

Protective cover

LA9F703

Tightening torque

57 N.m

2X150 mm

498.75 lb.in

Power connections, minimum required wiring section


IEC cable

UL cable

mm (Cu 70C/158F) (1)

AWG (Cu 75C/167F) (1)

2 X 150

2 X 250 MCM

230 Vac control, logic Inputs (LI) 24 Vdc, 3-wire control


With Line Contactor, Freewheel or Controlled Stop

230 Vac control, logic Inputs (LI) 24 Vdc, 2-wire control,freewheel stop
6

30 mm (1.18 in)

Connection in the motor delta winding in series with each winding


Wiring
ATS22 soft starters connected to motors with the delta connections can be inserted in series in the motor windings.
The following wiring requieres particular attention. It is documented in the Altistart 22 Soft start - soft stop unit user manual. Please contact
Schneider Electric commercial organisation for further informations.

Example
A 400 V - 110 kW motor with a line current of 195 A (nominal current for the delta connection). The current in each winding is equal to
195/1.5 or 130 A. The rating is determined by selecting the soft starter with a permanent nominal current (ICL) just above this current.

Product data sheet


Performance Curves

ATS22C41Q

Motor Thermal Protection - Cold Curves


Curves

A
B
C

Class 10
Class 20
Class 30

Trip time for a Standard Application (Class 10)


3.5 ln
32 s

Trip time for a Severe Application (Class 20)


3.5 ln
63 s

Trip time for a Severe Application (Class 30)


3.5 ln
95 s

Motor Thermal Protection - Warm Curves


Curves

A
B
C

Class 10
Class 20
Class 30

Trip time for a Standard Application (Class 10)


3.5 ln
16 s

Trip time for a Severe Application (Class 20)


3.5 ln
32 s

Trip time for a Severe Application (Class 30)


3.5 ln
48 s