ATS22C41Q: Product Data Sheet
ATS22C41Q: Product Data Sheet
ATS22C41Q: Product Data Sheet
Characteristics
ATS22C41Q
Range of product
Altistart 22
Product or component
type
Soft starter
Product destination
Asynchronous motors
Component name
ATS22
Network number of
phases
3 phases
230...440 V (- 15...10 %)
Motor power kW
220 kW at 440 V
220 kW at 400 V
110 kW at 230 V
388 A
Power dissipation in W
Utilisation category
AC-53A
Type of start
IP degree of protection
IP00
Complementary
Assembly style
Function available
Internal bypass
195...484 V
50...60 Hz (- 10...10 %)
Network frequency
45...66 Hz
Device connection
20 W
(R2)Relay outputs 230 V running, alarm, trip, stopped, not stopped, starting,
ready, C/O
(R1)Relay outputs 230 V running, alarm, trip, stopped, not stopped, starting,
ready, C/O
24 V (<= 30 V)
(LI1, LI2, LI3)positive logic state 0 < 5 V and < 2 mA state 1 > 11 V and > 5 mA
Output current
750 Ohm
Modbus
Connector type
1 RJ45
Serial
Physical interface
RS485 multidrop
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Transmission rate
31
Protection type
Marking
CE
Type of cooling
Forced convection
Operating position
Height
425 mm
Width
206 mm
Depth
299 mm
Product weight
33 kg
Environment
Electromagnetic compatibility
Standards
EN/IEC 60947-4-2
Product certifications
CCC
CSA
C-Tick
GOST
UL
Vibration resistance
Shock resistance
Noise level
56 dB
Pollution degree
Relative humidity
-25...70 C
Operating altitude
> 1000...< 2000 m with current derating of 2.2 % per additional 100 m
<= 1000 m without derating
Offer Sustainability
Sustainable offer status
RoHS
Available
Available
ATS22C41Q
Frame Size D
Dimensions
ATS22C41Q
Precautions
Standards
The Altistart 22 soft starter is compliant with pollution Degree 2 as defined in NEMA ICS1-1 or IEC 60664-1.
For environment pollution degree 3, install the Altistart 22 soft starter inside a cabinet type 12 or IP54.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
ATS22 soft starters are open devices and must be mounted in a suitable enclosure.
Failure to follow these instructions will result in death or serious injury.
Air Circulation
Leave sufficient free space to help the air required for cooling purposes to circulate from the bottom to the top of the unit.
Overheating
To avoid the soft starter to overheat, respect the following recommendations:
Mount the Altistart 22 Soft Starter within 10 of vertical.
Do not locate the Altistart 22 Soft Starter near heat radiating elements.
Electrical current through the Altistart 22 Soft Starter will result in heat losses that must be dissipated into the ambient air immediately
surrounding the soft starter. To help prevent a thermal fault, provide sufficient enclosure cooling and/or ventilation to limit the ambient
temperature around the soft starter.
If several soft starters are installed in a control panel, arrange them in a row. Do not stack soft starters. Heat generated from the
bottom soft starter can adversely affect the ambient temperature around the top soft starter.
Ventilation Grilles
ATS22C41Q
Power Terminal
Bar Style
Bar
5 mm (0.2 in)
Bolt
Size
Gauge
2X250 MCM
Protective cover
LA9F703
Tightening torque
57 N.m
2X150 mm
498.75 lb.in
UL cable
2 X 150
2 X 250 MCM
230 Vac control, logic Inputs (LI) 24 Vdc, 2-wire control,freewheel stop
6
30 mm (1.18 in)
Example
A 400 V - 110 kW motor with a line current of 195 A (nominal current for the delta connection). The current in each winding is equal to
195/1.5 or 130 A. The rating is determined by selecting the soft starter with a permanent nominal current (ICL) just above this current.
ATS22C41Q
A
B
C
Class 10
Class 20
Class 30
A
B
C
Class 10
Class 20
Class 30