YIA Millennium
SINGLE-STAGE
STEAM or WATER
ABSORPTION LIQUID
CHILLER
COOLING CAPACITIES
Steam: 420 to 4850 kW
Hot Water: 420 to 4850 kW
Warm Water: 200 to 4000kW
TM
YPC-ST Millennium
TWO-STAGE STEAM
ABSORPTION LIQUID
CHILLER
YIA
COOLING CAPACITIES
Steam: 1050 to 2370 kW
TM
YPC-FS Millennium
TWO-STAGE
DIRECT-FIRED
ABSORPTION LIQUID
CHILLER/HEATER
COOLING CAPACITIES
YPC
700 to 2370 kW
HEATING CAPACITIES
565 to 1970 kW
York Absorption chillers use the earths most
environment friendly refrigerant WATER
which is totally free of ozone depletion and
global warming effects. By using waste heat
or clean burning natural gas these machines
are responsible for far less carbon dioxide
production and acid rain producing
emissions per kW of cooling than electrically
driven machines.
In contrast to many absorption chillers using
chromates or arsenates as corrosion
inhibitors York absorption chillers use
molybdate inhibitors which are not classified
as a hazardous waste.
CONTENTS
Features
Specification
Operating Limitations
YIA Technical Data
YPC-ST Technical Data
YPC-FS Technical Data
YPC-ST
Cooling
kW
420
550
600
720
830
960
1090
1170
1280
1440
1570
1820
1990
2170
2480
2790
3190
3380
4040
4340
4840
YPC-FS
Model
Cooling
kW
Heating
kW
12SC
13SC
703
809
563
675
1055
14SC
1055
844
16SL
17S
1547
1705
15SL
16S
16SL
17S
1231
1407
1547
1705
1013
1125
1268
1407
18S
19S
2039
2373
18S
19S
2039
2373
1688
1969
Model
14SC
Cooling
kW
TABLE 1
Page F.9
Doc. No. PC121/10.03/GB
FEATURES
YIA
YPC-ST
Single-stage
Two-stage operation, making for low Two-stage operation, making for low
Water is used as the refrigerant and Water is used as the refrigerant and
including
economical
operation mode with warm water at 80 C.
Refrigerant: water, absorbent: lithium
bromide,
non-acidic,
non-toxic,
non-flammable,
odourless
with
ADVAGuard 750 added as corrosion
inhibitor.
Safe
programming
and
servicing
capabilities through Millennium control
panel.
Microprocessor control board with
alphanumeric text display and memory for
display and storage of operating and fault
information.
High reliability and long operation life.
Hermetic pumps with 55,000 hour service
inspection interval.
Suction and discharge isolation valves on
the hermetic pumps for quick and easy
pump servicing without draining, or loss of
vacuum.
Fully automatic operation.
Continuously operating purge system.
Automatic protection against excessive
concentration.
Automatic decrystallisation.
Continuous operation due to stabiliser
and unloader controls.
Electrical
equipment
CE
certified
according to EN 292-2, EN 60204-1, EN
50081-2 and EN 50082-2.
Compact and sturdy.
Small footprint due to arrangement of both
shells on top of each other.
Easy transport, installation and operation.
YPC-FS
energy costs.
energy costs.
SPECIFICATION
GENERAL
YIA
Page F.10
Doc. No. PC121/10.03/GB
SPECIFICATION
Chilled Water Flow Switch with paddle. Main Control Panel for single-point wiring
English
Language
Installation, connection, voltage 380/400-3-50 + NE +
Commissioning,
Operation
and PE, with controllers and safety units for the
internal pumps. Unit capacity is modulated
Maintenance manual.
between 100 % and 20 % by the steam valve
YIA Optional Equipment:
in keeping with the chilled water leaving
Special tubes for the heat exchangers
temperature.
Marine water boxes
Hermetic Solution and Refrigerant
High pressure water flanges
Pumps, self-lubricating. The ports are
Two optional printed circuit boards for welded into the piping. Isolating valves at the
remote reset of chilled leaving water inlet and outlet to facilitate maintenance.
temperature and remote steam/hot water
YPC-ST Optional Equipment:
limit using 4 - 20 mA or 0 - 10 Vdc signals
Two part shipment on units YIA 1A1 to YIA Heat exchanger with special tubing.
10E3
Marine water boxes.
Water boxes for elevated working
YPC-ST
pressures.
Main shell, with vertically arranged tube
heat exchangers, absorber, evaporator, Optional board for remote resetting of
leaving chilled water temperature or
second-stage generator and condenser
steam input limitation using a 4 - 20 mA or
housed in 2 separate sections. Optimal
0 - 10 Vdc signal.
geometrical enhancement of the heat
exchanger surface in the absorber and YPC-FS
evaporator by virtue of atomised distribution
Main Shell, with vertically arranged tube
via stainless steel spray nozzles. There are
heat exchangers, absorber, evaporator,
finned eliminator baffles between each
second-stage generator and condenser
evaporator/absorber pair and between the
housed in 2 separate sections. Optimal
second-stage generator and the condenser.
geometrical enhancement of the heat
The heat exchanger tubing in the absorber,
exchanger surface in the absorber and
evaporator, second-stage generator and
evaporator by virtue of atomised distribution
condenser is made of copper and,
via stainless steel spray nozzles. There are
depending on the application, features a
finned eliminator baffles between each
smooth or enhanced surface. Each tube is
evaporator/absorber pair and between the
roller-expanded into rugged tube sheets.
second-stage generator and the condenser.
Operating pressure: water side 10 bars, unit
The heat exchanger tubing in the absorber,
side 0.95 bars.
evaporator, second-stage generator and
First-Stage Generator positioned next to condenser is made of copper and,
the shell assembly. The unit features a depending on the application, features a
welded design with U-shaped Cu/Ni 70/30 smooth or enhanced surface. Each tube is
piping. It comes equipped with a condensate roller-expanded into rugged tube sheets.
Operating pressure: water side 10 bars, unit
drain cooler.
side 0.95 bars.
Control Centre for precision system control
and monitoring. All messages are displayed First-Stage Generator positioned next to
in plain text on the 40-character the shell assembly. It features a welded
alphanumeric display. Memory for 4 cycling design with vertical carbon steel boiler
or safety shutdowns. Remote unit start/stop, tubes, the tubes possessing an enhanced
remote reset of chilled water leaving surface in part.
temperature and/or steam limiting signal
upon
startup.
YORK
ISN
Energy
Management Interface (also optionally
available for "non-ISN" building automation
systems).
Additional
OPERATING LIMITS
YIA
YPC-ST
YPC-FS
Chilled water leaving temperature min. 4.4 C, minimum cooling water entering temperature with steam 7.2 C,
or with hot water 20 C, steam input pressure 0.2 to 1.0 barg, hot water temperature 80 C to 128 C.
Chilled water leaving temperature min. 5.6 C (special design temperature down to 5.0 C possible),
cooling tower entering temperature 20 C, design for steam pressure 3 barg to 9 barg possible.
Chilled water leaving temperature min. 5.6 C (special design temperature down to 5.0 C possible),
cooling tower water entering temperature min. 20 C, 20 mbar gas pressure for models 12SC to 16 S,
50 mbar for models 16SL to 19S, (design for lower gas pressures available on request).
Page F.11
Doc. No. PC121/10.03/GB
A
B
Model
1A1
1A2
2A3
2A4
2B1
3B2
3B3
4B4
4C1
5C2
5C3
6C4
7D1
7D2
8D3
8E1
9E2
10E3
12F1
13F2
14F3
Nominal
Capacity1
kW
420
550
600
720
830
960
1090
1170
1280
1440
1570
1820
1990
2170
2480
2790
3190
3380
4040
4340
4840
Pump
Shaft
kW
A3
Total
Solution
mm
mm
mm
kg
kg
kg
kg
2.6
2.8
3.0
3.5
3.6
3.8
4.3
4.5
4.5
5.0
5.5
5.9
5.5
6.0
6.2
6.2
7.4
8.6
8.3
8.7
9.2
3720
4330
4940
5550
4940
5550
6160
6770
5550
6160
6770
7530
6160
6770
7530
6870
7630
8390
7630
8390
9150
1760
1420
1420
1420
1580
1580
1580
1580
1770
1770
1770
1770
2110
2110
2110
2290
2290
2290
2480
2480
2480
2320
2320
2320
2320
2640
2640
2640
2640
3020
302
302
302
3540
3540
3540
3840
3840
3840
4240
4240
4240
4040
4450
4910
5310
6090
6720
7360
7990
8400
9170
9900
10670
13030
14620
16210
17710
19710
22020
25020
27110
28920
710
840
970
1100
1220
1420
1550
1740
1800
2130
2320
2640
2640
2960
3280
4050
4570
5020
5790
6500
7140
4950
5500
6130
6590
7900
8540
9490
10490
11400
12260
13620
14760
17890
19840
21800
24110
26830
29790
35550
39050
41140
6920
8860
8920
9770
11730
12890
14440
15980
17450
19270
21080
23110
28650
31770
35290
38760
43320
48170
56100
61910
66250
Dimensions
Transport Weight
Operating Emergency
2
4
Weight
Weight
1 The values given are for a chilled leaving water temperature 12.6/6.7C, cooling water temperature 29.4/39.4C, steam 0.8 g dry/saturated or hot
water 115/109C, fouling factor 0.044mK/kW (ARI 560-92).
2 Measurements and weights are approximate values.
3 A space of the same length as the length of the unit should be kept for maintenance and tube extraction at one end of the unit. This space can be
secured by doors or other openings.
4 The emergency weight is the maximum weight, caused by the failure of a heat exchanger tube (through external reasons) which results in the
complete filling of the entire unit by a connected water circuit.
Page F.12
Doc. No. PC121/10.03/GB
Dimensions
B
Model
A
mm
mm
mm
kg
kg
kg
kg
14SC
16SL
17S
18S
19S
5110
5970
5970
6960
7980
1880
2270
2270
2290
2290
2240
2620
2620
2770
2770
10210
15490
15860
18870
22500
9480
13700
14060
16740
20190
11030
17150
17510
20780
24190
15600
25800
26300
31200
37400
Steam
Inlet
Cond.
Outlet
DN
65
100
100
100
DN
20
20
20
20
100
20
Insulation Areas
Cold
Hot
2
m2
m
11
24
16
37
16
37
19
44
22
Electrical
Power
47
kW
7.5
16.2
16.2
16.2
21.2
1 A clearance equal to the length of the unit is to be maintained at one end of the unit for maintenance and tube withdrawal. This clearance can also be present by virtue of doors or
1 other openings. The tube withdrawal clearance for the first stage generator may be located across from the steam inlet only.
2 Unit supplied with charge filling.
3 Option: unit supplied without charge filling. Filling supplied separately in drums.
4 The emergency weight is the maximum weight which results when an externally induced rupture of a heat exchanger tube causes the content of a connected water circuit
4 to completely fill the unit.
Cooling
Model Capacity
kW
1055
14SC
1547
16SL
1705
17S
2039
18S
2373
19S
Steam
Input
kW
Flow
l/s
1334
1956
2156
2579
3000
45.3
66.5
73.3
87.7
102.0
Condenser
No. of
Pressure
Passes Drop (kPa)
2
2
2
2
2
36
40
39
63
94
Absorber/Evaporator
Flow
No. of
Pressure
l/s
Passes
Drop (kPa)
84.6
124.1
136.8
163.6
190.3
1
2
2
2
2
68
64
70
96
127
Page F.13
Doc. No. PC121/10.03/GB
Dimensions 1
B3
B2
Gas
Transport Transport Operating Emergency
Weight 8 Connection 7
Weight 4,6 Weight 5,6 Weight 6
Exhaust
Flange
Model
A
mm
mm
mm
mm
kg
kg
kg
kg
DN
W/H mm
m2
m2
kW
12SC
13SC
14SC
15SL
16S
16SL
17S
18S
19S
3970
3990
4950
5000
5000
5960
5960
6960
7980
1850
1850
1890
2260
2260
2300
2300
2360
2360
1940
1970
1940
2450
2450
2600
2600
2670
2670
2280
2280
2300
2730
2730
2810
2810
2990
2990
8990
9990
11450
16270
16500
19810
20180
23500
27760
7900
8770
9990
14600
14800
17760
18120
21020
24880
9490
10830
12130
17360
17580
21180
21580
25190
29720
13290
14880
16980
24300
24700
29700
30300
35300
41600
65
65
80
100
125
125
65
80
80
470/520
470/520
475/525
590/590
590/590
740/740
740/740
775/775
775/775
8
8
11
13
13
16
16
19
22
16
18
24
33
33
37
37
44
47
9
9.8
9.8
14.6
14.6
19.6
19.6
19.6
30.2
1 A clearance equal to the length of the unit is to be maintained at one end of the unit for maintenance and tube withdrawal. This clearance can also be present by virtue of doors or other openings.
2 Width of standard unit, without optional hot water heat exchanger.
3 Width including optional hot water heat exchanger.
4 Unit supplied with charge filling.
5 Option: unit supplied without charge filling. Filling supplied separately in drums.
6 The weights indicated here increase by 450 kg when including the optional hot water heat exchanger.
7 Required gas pressure for up to YPC-F 16 SL: minimum 20 mbars. All larger units with 50 mbars. DN for other gas pressures available on request.
8 The emergency weight is the maximum weight which results when an externally induced rupture of a heat exchanger tube causes the content of a connected water circuit to completely fill the unit.
Model
12SC
13SC
14SC
15SL
16S
16SL
17S
18S
19S
Model
12SC
13SC
14SC
15SL
16S
16SL
17S
18S
19S
Cooling
Capacity
kW
Power
Input
kW
Flow
l/s
703
809
1055
1231
1407
1547
1705
2039
2373
629
736
944
1130
1292
1421
1566
1873
2180
30.2
34.8
45.4
52.9
60.5
66.5
73.3
87.7
102.0
Heating
Capacity
kW
Power
Input
kW
Flow
l/s
563
675
844
1013
1125
1268
1407
1688
1969
625
750
938
1125
1250
1407
1563
1875
2188
30.5
36.9
46.1
55.3
61.5
69.2
76.8
92.2
107.6
COOLING
Condenser
No. of
Pressure
Passes Drop (kPa)
3
3
2
3
3
2
2
2
2
44
57
36
67
70
40
39
63
94
HEATING
Condenser
No. of
Pressure
Passes Drop (kPa)
3
3
2
3
3
2
2
2
2
48
67
40
78
78
46
46
74
112
Absorber/Evaporator
Flow
No. of
Pressure
l/s
Passes
Drop (kPa)
55.4
64.9
84.6
98.6
112.8
124.1
136.8
163.6
190.3
Flow
l/s
12.4
14.9
18.6
22.3
24.8
27.9
31.0
37.1
43.3
2
1
1
2
2
2
2
2
2
39
38
68
39
49
63
70
96
127
HT - HZW - WT
No. of
Pressure
Passes
Drop (kPa)
3
3
3
3
3
3
3
3
3
20
18
20
15
18
41
50
43
57
Capacity data at 12.2/6.7 C chilled water, 29.4/35 C cooling water, 55/60 C hot water when heating in the evaporator and
68.3/79.4 C when heating in a high temperature hot water heat exchanger.
Fouling factor 0.044 m C/kW. Design specifications for other temperatures and fouling factors available on request.
Page F.14
Doc. No. PC121/10.03/GB