Mom690 CB Analyzer

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

MOM690

Microhmmeter

A Megger Group Company

M O M 690

MOM690

Microhmmeter
Measuring resistance is an important part of maintaining high-voltage breakers and disconnecting switches.
Instruments that measure the resistance of high-current contacts and other transmission elements have been
included in the Programma line of products for many years.
MOM690 supplements our family of microhmmeters. In addition to high current capacity, MOM690 features
microprocessor-based measurement, storage and reporting. The built-in software enables you to carry out an
individual test or an entire series of tests and store the results.
With the optional MOMWin software you can also export the test results to a PC for further analysis and
reporting. Ranges are set automatically, resistances are measured continually and test results can be automatically
captured at a preset test current. What could be simpler?
After testing a breaker with a CT mounted in its current circuit, e.g. dead tank and GIS breakers, some standards
recommended that the CT is demagnetized. This troublesome task can be accomplished quickly and easily thanks to
the MOM690's AC output. The AC output can also be used as a general multi-purpose current source in different
applications.

Optional accessories

IMPORTANT!

PC Software MOMWin

Read the Users manual before using the instrument.

Measuring the resistance of a breaker


1. Make certain the line is de-energized on both sides of the
breaker.
2. Ground the breaker on one side and make certain it is closed.
3. Ground the microhmmeter.
4. Make certain the microhmmeter's ON/OFF switch is OFF while
making connections.
5. Connect the current cables to the DC+ and COM terminals and
the sensing cables to the sensing inputs to both sides of the
breaker, making sure that the polarities match properly.
IMPORTANT: The sensing cables must be connected inside the
current cables. Otherwise the test data will be incorrect. See Fig.

An optional Windows program named MOMWin is available for


MOM690. It can be used to control measurement, analyse the results
and report the results from a PC. It also enables you to retrieve test
results stored previously in MOM690.
All readings are saved in ASCII-format and can be easily exported to
your favourite spreadsheet program. Results can be presented in table
or diagram form in MOMWin.
The program runs in Windows 95, 98, NT, 2000 or XP. Minimum
requirement is a 486 computer with 8 MB of RAM.
Incl. serial cable for RS-232 port.

Cable set 15 m (49 ft)


2 x 15 m (49 ft), 95 mm2 (current cables).

6. Switch on the MOM690.

2 x 15 m (49 ft), 2.5 mm2 (sensing cables).

7. Select "AUTO" or "MAN" with the <FUNC>-button.

Weight: 29.4 kg (64.8 lbs)

8. Set output current to zero to start the measurement.


9. Increase the current to the desired value (600 A for example).

Cable extension sets

Measuring resistance at busbar joints

Since all current cables have bayonet connectors, standard cables can
be easily prolonged with 5- or 10-metre extension sets if so desired.
In situations requiring high currents and long cable lengths, heavier
cable sets may be necessary however.

1. Make certain the line is de-energized and the test object is


grounded.

Extension cable set No. 1

2. Ground the microhmmeter.

2 x 5 m (16 ft), 50 mm2 (current cables).

3. Make certain the microhmmeter's ON/OFF switch is OFF while


making connections.

2 x 10 m (33 ft), 2.5 mm2 (sensing cables).

4. Connect the microhmmeter's current cables to the test object. Do


not connect the sensing cables. Measurement will be done manually using an external portable voltmeter.

Extension cable set No. 2

10. Read the resistance value.

5. Switch on the MOM690.


6. Select "MAN" with the <FUNC>-button.
7. Set output current to zero to start the measurement.
8. Increase the current to the desired value (100 A for example).
9. Using an external voltmeter, measure the voltage drop across
each contact element within every section of the busbar being
tested. The voltmeter must be set to DC.
10. Calculate the actual resistance.
Example: If the voltage drop is 0.0067 V at a current of 100 A, the
resistance will be 0.0067/100 , i.e. 67 .

Measuring the resistance of a breaker

Weight: 7.5 kg (16.5 lbs)

2 x 10 m (33 ft), 50 mm2 (current cables).


2 x 15 m (49 ft), 2.5 mm2 (sensing cables).
Weight: 15 kg (33 lbs)

Calibration shunt
An optional calibration shunt (600 A/60 mV) can be ordered for
MOM690, that enables you to make certain that the instrument
readings remain correct.

Transport case XL
With space for the standard 5 m cable set + extension cable set No. 1
or No. 2.

Measuring resistance at busbar joints

M O M 690

Application example

M O M 690

Specifications MOM690

Max. load resistance / current, 230 V model

Specifications are valid at nominal input voltage and an ambient


temperature of +25C, (77F). Specifications are subject to change
without notice.

Environment
Application field

Temperature
Operating
Storage & transport
Humidity

The instrument is intended for use in


high-voltage substations and industrial
environments.
0C to +50C (32F to +122F)
-40C to +70C (-40F to +158F)
5% 95% RH, non-condensing
Low Voltage Directive 73/23/ EEC am. by
93/68/EEC
EMC Directive 89/336/EEC am. by
91/263/EEC, 92/31/EEC and 93/68/EEC

EMC

General
Mains voltage
Power consumption
(max)
Protection

115/230 V AC, 50/60 Hz


115 V, 5980 VA (at 600 A output)
230 V, 9660 VA
Miniature circuit breaker, thermal fuse,
software

Measurement section
Ammeter

At 300 A
Max. current

10 m
575 A

Voltage (V)

0
50
100
200
300
400
500
5751)
600
700
8002)

7.3
6.9
6.4
5.5
4.8
3.9
3.0
2.5
2.2
1.5
0.9

Max. load time Input current


(A)

0.8
30 min.
10 min.
10
90 s
19
50 s
30 s
38
15 s
10 s
8s
52
5s

Output AC (CAT I), 115 V model


Current (A)
0
660

Voltage (V)
8.7
3.5

Max. load time Rest time


Cont.

2s
4 min.

Note: The DC and AC outputs must not be loaded at the same time.

Output DC (CAT I), 230 V model


Current (A)
0
50
100
200
300
400
500
600
700
7501)
8002)

Current
(A)
0
660

Voltage (V ) Max. load time Input current


(A)
9.4

0.4
9.0
30 min.
8.6
10 min.
6
8.0
90 s
7.2
50 s
6.4
40 s
5.7
30 s
5.0
15 s
33
4.3
8s
3.8
5s
3.6

42

Voltage
(V AC)
11.2
4.5

Max. load time Rest time


Cont.
2s

Note: The DC and AC outputs must not be loaded at the same time.

Standard 2 x 15 m 95mm
+ Ext. 1
3 m
360 A

Current (A)

Output AC (CAT I), 230 V model

0 200 m, > 200 m not specified


1
100 800 A, 1% of reading + 1 digit
50 99 A, (2% of reading + 2 digits)
0 49 A, not specified
Standard +
Ext. 1
6 m
420 A

480 A

18 m
1.8 m
690 A

Note: The above figures shows maximum load time from cold state 25C. They are not valid
for repeated tests

Max. load resistance / current, 115 V model


Standard

570 A

2 x 15 m 95mm

1) Maximum current with standard cables 2 x 5 m 50 mm


2) At 800 A and above, instant shut off

0 800 A
1A
100 800 A, 1% of reading + 1 digit
50 99 A, (2% of reading + 2 digits)
0 49 A, not specified

Resistance

Cable set

18 m
3.0 m
750 A

Stadard
+ Ext. 1
11 m

Note: The above figures shows maximum load time from cold state 25C. They are not valid
for repeated tests

350 x 270 x 220 mm


(13.8 x 10.6 x 8.7)
Transport case
610 x 290 x 360 mm
(24.0 x 11.4 x 14.2)
Weight, 115 V
24 kg (52.9 lbs)
model
38.9 kg (85.7 lbs) with accessories and
transport case
Weight, 230 V
23.7 kg (52.2 lbs)
model
38.6 kg (85.1 lbs) with accessories and
transport case
Available languages English, French, German, Spanish, Swedish
Current cables
2 x 5 m (16 ft), 50 mm
Sensing cables
2 x 5 m (16 ft), 2.5 mm
Optional current cable sets
Ext.1
Extension 2 x 5 m, 50 mm
Ext.2
Extension 2 x 10 m, 50 mm
2 x 15 m (49.2 ft) 95 mm

Range
Resolution
Inaccuracy

At 300 A
At 600 A
Max. current

Stadard
+ Ext. 1
14 m

1) Maximum current with standard cables 2 x 5 m 50 mm


2) At 800 A and above, instant shut off

Dimensions
Instrument

Range
Resolution
Inaccuracy

Standard

Output DC (CAT I), 115 V model

CE-marking
LVD

Cable set

10 m
540 A

4 min.

Grounding terminal

Connection for mains voltage

Miniature circuit breaker for mains

Switch for mains voltage

Variable transformer
AC current output

Common output terminal

DC current output

Voltage measurement input

Display

Setting selector

Function selector

Interrupts current and toggles the display


between resistance and voltage

RS 232 Serial interface

M O M 690

Information about current generation or memory location.


Value of the generated current.
Indicates whether the current is above (<)
or below (>) a preselected value.
Selected test current for Auto/DC Off.
Scroll using the <>- button.
Selected function. Scroll using the <FUNC>-button.
Shows the measured resistance or voltage value. Toggle by pressing the <>-button.

Ordering information

Art.No.

Complete with:
Cable set standard GA-05055
Ground cable GA-00200
Transport case GD-00182
115 V Mains voltage
230 V Mains voltage

BB-41190
BB-42390

MOM690

Optional accessories

Cable set and current shunt

PC Software MOMWin
Incl. serial cable for RS-232 port
Cable set 15 m (49 ft)
Extension cable set No. 1
Extension cable set No. 2
Calibration shunt
Transport case XL

BB-8010X
GA-09155
GA-05057
GA-05107
BB-90024
GD-00042

NOTICE OF COPYRIGHT & PROPRIETARY RIGHTS


2008, Programma Electric AB. All rights reserved.
The contents of this document are the property of Programma Electric AB. No part of this work may be reproduced or transmitted in any form or by any
means, except as permitted in written license agreement with Programma Electric AB.
Programma Electric AB has made every reasonable attempt to ensure the completeness and accuracy of this document. However, the information
contained in this document is subject to change without notice, and does not represent a commitment on the part of Programma Electric AB.
TRADEMARK NOTICES
Megger and Programma are trademarks registered in the U.S. and other countries.
All other brand and product names mentioned in this document are trademarks or registered trademarks of their respective companies.
Programma Electric AB is certified according to ISO 9001 and 14001.

Programma Electric AB
Eldarvgen 4
Box 2970
SE-187 29 TBY
Sweden

T +46 8 510 195 00


F +46 8 510 195 95
[email protected]
www.programma.se

Subject to change without notice. Art. No. ZI-BB04E Doc. BB0214CE

2008

You might also like