Sineax Ti 816 Passive DC Signal Isolator: Without Power Supply, in Carrying Rail Housing
Sineax Ti 816 Passive DC Signal Isolator: Without Power Supply, in Carrying Rail Housing
Sineax Ti 816 Passive DC Signal Isolator: Without Power Supply, in Carrying Rail Housing
Application
The signal isolator SINEAX TI 816 (Fig. 1) serves to electrically
insulate an analog DC signal in the range 0...20 mA which depending on version is then converted to a current or voltage signal
(020 mA or 010 V). It operates passively and does not require
a separate power supply, but derives the little auxiliary energy it
needs from the DC signal.
Its narrow casing is designed for mounting on different types of
standard rails. A number of signal isolators can be mounted immediately next to each other and where there are many DC signals
to be isolated can form a compact isolator block.
Fig. 1
Features / Benefits
Electrically insulated analog DC signals 020 mA / Prevents the
transfer of interference voltages and currents. Solves grounding
problems in meshed signal networks
Highly accurate / Performs its isolating function with negligible
transmission error
No power supply needed / Saves wiring costs and is easy to install
in existing plants
The device fulfils the protection requirements of the EMC guidelines
(89/336/EWG) / The device bears the CE symbol for EMC. See Table2:
Electromagnetic compatibility
Small and compact / Makes best use of the available space
Z
E
G
+
O
Fig. 2. Schematic diagram.
Camille Bauer
SINEAX TI 816
Passive DC Signal Isolator
Technical data
Mounting:
Snapping
DC current:
020 mA
Max. permissible :
50 mA
or
Voltage limiter:
Mounting position:
Any
Voltage drop:
Electrical connections:
Overshoot:
< 20 A (typical 5 A)
Input signal E
020 mA or 010 V
Limit:
Approx. 30 mA 1
Approx. 15 V 2
Max. burden:
600 1
Internal resistance:
500 2
Residual ripple:
< 20 mV ss
Time constant:
Approx. 5 ms
< 0.1% 1
(reference value 20 mA,
linearity error included)
< 0.2% 2
(reference value 10 V,
linearity error included)
Reference conditions:
Ambient temperature
23 C 1 K
Output burden
100
5 M 2
Additional error:
Burden influence
Temperature coefficient
< 50 ppm/K
Approx. 35 g
Regulations
Accuracy data
Error limits:
Output signal A
DC current or
DC voltage:
Electrical design:
Protection:
Test voltage:
800 V
Ambient conditions
Climatic rating:
Operating temperature:
20 to + 65 C
Storage temperature:
40 to + 85 C
Annual mean
relative humidity:
Seismic test:
Shock test:
50 g
10 shocks in each of 3 directions
Altitude:
Max. 2000 m
Installation data
Mechanical design:
Material of housing:
Camille Bauer
SINEAX TI 816
Passive DC Signal Isolator
Table 1: Versions (stock)
There are two versions of the DC signal isolator SINEAX TI 816 both of which are available ex stock. Quoting the order No. is sufficient when ordering:
Description
Passive DC signal isolator
input signal E: 020 mA,
with 1 isolation and transmission channel,
in carrying rail housing N12
Output signal A
Order Code
Order No.
020 mA
816 - 5110
990 722
010 V
816 - 5111
994 089
EN 55 011
Group 1, Class A
EN 55 011
Group 1, Class A
Electrostatic discharge
IEC 1000-4-2
Direct:
Indirect:
IEC 1000-4-3
IEC 1000-4-4
IEC 1000-4-6
8 kV air
6 kV contact
The device fulfils the protection requirements of the EMC guidelines (89/336/EWG). The device bears the CE symbol for EMC.
Electrical connections
Standard accessories
1 Operating Instruction each in German, French and English
3 4
TI 816
1 2
E
Fig. 3. E = input signal (IN), A = output signal (OUT)
Camille Bauer
SINEAX TI 816
Passive DC Signal Isolator
Dimensional drawings
52
12,5
TI 816
TI 816
75
3 4
75
3 4
1 2
1 2
49,5
12,5