Digital Industrial Controller 1 General Safety Instructions
Digital Industrial Controller 1 General Safety Instructions
Digital Industrial Controller 1 General Safety Instructions
When planning the application of the device, and during its operation, observe
the general technical rules!
Installation and maintenance work should only be carried out by specialist staff
using the correct tools!
Observe the relevant accident prevention and safety regulations for electrical
equipment during the operation and maintenance of the unit!
Always switch off the voltage before carrying out work on the device!
If these instructions are ignored, no liability will be accepted from our side, and
the guarantee on the device and on accessory parts will become invalid!
1110 - 3
english
english
The digital industrial controller is designed as a PID controller for controlling tasks in
the process control technology. It represents a new controller generation based on a
microprocessor.
Either standard current/voltage and frequency-analog signals can be applied to the
scaleable controller inputs or resistance thermometers and thermocouples can be
connected.
Outputs for continuous standard signals or relay outputs can now be used as
controller outputs.
In addition, outputs for error reports and a binary input and output for additional
functions are available.
RS 232 or RS 485 / PROFIBUS serial interfaces are available as connection
options.
The following control tasks can be realised with the controller:
NOTE
4 - 1110
english
english
The controller was conceived for installation in switch panels. On the controller,
first of all remove the retaining elements engaged on both sides by swivelling in
anticlockwise direction. Insert the controller, including the enclosed rubber seal, into
the insertion opening from the front. Then again engage the two retaining elements
in the bolts on the sides of the housing and screw in the threaded pin inside from the
rear.
Switch panel insertion opening (W x H):
Outer controller dimensions (W x H x D):
Controller weight:
Degree of protection:
Operating temperature:
Storage temperature:
ATTENTION!
CONNECTIONS
4.1
Pin assignments
TE connection
(Technical Earth)
Controller input 1
Relay 3
(Alarm)
Position acknowledgement
Controller output
Standard signal
Current
Standard signal
Voltage
Binary
output
Relay 1
(Output)
Relay 2
(Output)
Resistance
thermometer
PT100
Binary
input
Thermo
couples
Power
supply
4.2
Supply voltages
Power supply for the
controller:
Model 1:
Model 2:
Power supply for
transducers:
ATTENTION!
Connect to terminals 14
and 15.
115 / 230V 50 ... 60 Hz
12 / 24V 50 ... 60 Hz
24 V DC
Accessible on terminals 23
and 24.
1110 - 7
english
Relay 3
(Alarm)
english
By means of a jumper inside the unit, the supply voltage can be changed from 230 V
to 115 V, or from 12 V to 24 V respectively. This adaptation must take place before
installing the unit.
Procedure:
Insert all connection and supply lines
Remove the connecting screw for the Technical Earth
Remove the optionally-installed interface card (if present)
Undo the four screws on the rear plate, and remove the rear plate
Pull the unit one third of the way out of the housing
The jumper is easily accessible on the power supply printed-circuit board,
positioned immediately in front of one of the relays and identified by the numbers
1-4 on the board.
At delivery, the connector is positioned between contacts 2 and 4
To change the unit to 115V or 12 V respectively, contacts 1 and 3 must be
bridged with the connector. Proceed identically when changing from 24V to 12V.
Finally, push the unit back into the housing, and screw on the rear plate.
NOTE
If the unit is to be set to the lower voltage, please ensure that the
voltage does not exceed the quoted tolerances, and make a note
on the wiring diagram.
8 - 1110
Supply voltage
16V - 26V DC
Output voltage
Efficiency
> 95%
Switch-on delay
max. 5 secs
Dimensions (WxHxD)
23 x 75 x 110 mm3